650481-000 INSTRUCTION SHEET
Installation Instructions for Viamaster™ LED Luminaire Fittings for NEC and CEC Governed Locations
FOR PROPER AND SAFE INSTALLATION OF THIS PRODUCT, PLEASE READ THE FOLLOWING INSTRUCTIONS.
Product Safety
Signal Words Defined
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a hazardous situation
Safety Instructions for Complete Luminaire
WARNING:
• Before installation, ensure that the unit complies with the hazardous area classication. Refer to luminaire nameplate, located on the exterior of the housing body, for suitability in specic hazardous locations.
• Do not open or remove luminaire when AC supply is on.
• Do not use luminaire on ungrounded systems. Failure to ground this luminaire can result in an electric shock, which may be fatal.
• Disconnect the luminaire from the supply circuit before opening to reduce the risk of ignition in hazardous atmospheres. Keep tightly closed when in operation.
• De-energize ve (5) minutes before opening.
CAUTION:
• Do not look directly at the LEDs when energized.
• Lens cleaning instructions: Wipe/clean from the outside only with a moist cloth. (Beware of electrostatic charges.)
• When installing in a hazardous location, it is necessary that the reector, lens, and all certied conduit plugs be in place and tightened securely to the housing.
NOTICE:
• Do not touch the LEDs; touching could leave oily deposits, causing hot spots and potential premature failure.
• The LED lens should be cleaned periodically from the outside only with a moist cloth to maintain lighting efciency.
• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
• This luminaire is designed for and should be installed by a qualied electrician in accordance with the National Electrical Code®/ Canadian Electrical Code and all applicable local codes under the direction of the Authority Having Jurisdiction (AHJ).
Applications/Intended Use
• For marine and wet locations, apply a corrosion-inhibiting grease, such as petroleum or soap-thickened mineral oils, in 3 lines, spaced approximately 120 degrees apart, perpendicular to the threads. Tighten all unused close-up plugs.
• Areas where ammable gases and vapors are present under conditions dened by the ratings below.
• Areas of low clearance, low ceiling heights, or where luminaire weights must be minimized.
• Non-hazardous locations where severe weather conditions, excessive moisture, dirt, dust, corrosive atmospheres, and high ambient temperaures are encountered.
Appleton • 1.800.621.1506 • www.appletonelec.com 650481-000 Rev. P 7/16 • Page 1 of 10
Agency Ratings
HINGE THIS SIDE
HINGE THIS SIDE
• Class I, Division 2, Groups A, B, C, D • Marine Outside Type
j
k
• Class 1, Zone 2, Group IIC • IP66/IP67
• Class II, Division 2, Groups F, G • -40° C to +65° C (select luminaires)
• Class III
• Type 3R, 4 & 4X
NOTES:
j Refer product nameplate, located on the housing body, for details.
k To be installed in accordance with CG-259 of American Bureau of Shipping and Coast Guard.
Dimensions/Details
LUMINAIRE HOUSING (LLEDA12LU2, LLEDA15LU2, LLEDA17LU2, LLEDA12BH2, LLEDA15BH2, LLEDA17BH2)
LUMINAIRE DIMENSIONS
HINGE THIS SIDE
HINGE THIS SIDE
LUMINAIRE INTERNAL LAYOUT – LLEDA12 AND LLEDA15 PICTURED WITH OPTIONAL FUSE
HINGE THIS SIDE
HINGE THIS SIDE
LUMINAIRE INTERNAL LAYOUT – LLEDA17 PICTURED WITH OPTIONAL FUSE
650481-000 Rev. P 7/16 • Page 2 of 10Appleton • 1.800.621.1506 • www.appletonelec.com
Optic Installation
LENSES (LLEDCPL, LLEDDPL)
1. Before installation: (Beware of electrostatic charges)
a. Ensure that the sealing surface on the reector is clean and no dirt or foreign particles are present. b. Ensure that the lens is free from dirt or any other foreign particles. c. Use only a moist cloth to clean lens if necessary.
2. Align the holes of the lens with the reector and use M4 screws to secure in place. Screws require a torque of 0.75 Nm (6.64 lbf-in.)
LENS SCREW TIGHTENING PATTERN
Mounting Instructions
1. Make sure power is disconnected before installing the luminaire.
2. Determine appropriate mounting distance between mounting holes on top of luminaire housing for your application. Note that
distance can be 15.75 in. [400 mm] or 20.87 in. [530 mm].
3. Use 5/16 in. (M8) bolts (not supplied) appropriate for the structural support member.
4. Secure luminaire to structural support member having through holes (such as a unistrut or grated walkway) that can handle the
weight of the luminaire in accordance with local building code and all other code applications.
5. Tighten 5/16 in. (M8) bolts to secure the luminaire in place.
Mounting Brackets (Optional Accessories)
Note: Zinc plated steel mounting brackets are not for use where Marine Listing is required.
FIXED 45° WALL MOUNT (FVWFM)
1. Make sure power is disconnected before installing the luminaire.
2. Determine appropriate mounting distance between brackets for your application. Note that distance between brackets can be
15.75 in. [400 mm] or 20.87 in. [530 mm].
3. Mark and drill holes for mounting brackets. Use 5/16 in. (M8) bolts and anchors (not supplied) appropriate for the
mounting surface.
4. Attach two (2) supplied 45° wall mounting brackets to desired M8 - 1.25 x 13 mm threaded mounting holes on back of luminaire
housing using supplied hardware.
5. Secure luminaire with mounting brackets installed directly to the wall or any structural support member that can handle the weight
of the xture in accordance with local building code and all other code applications.
6. Tighten wall mount screws to secure the luminaire in place.