650483-000 INSTRUCTION SHEET
Installation Instructions for N2LED Series Emergency Luminaire
Product Safety
FOR PROPER AND SAFE INSTALLATION OF THIS PRODUCT, PLEASE READ THE FOLLOWING INSTRUCTIONS.
Signal Words Defined
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a hazardous
situation which, if not avoided, could result in death or serious injury. CAUTION indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury. NOTICE is used to address practices not related to physical injury.
Safety Instructions
WARNING:
• Before installation, ensure that the unit complies with the hazardous area classication. Failure to do so may result in bodily injury
and/or property damage. Refer to the xture nameplate for suitability in specic hazardous locations.
• To prevent ignition of hazardous atmospheres, the area must be free of hazardous vapors before opening the enclosure or servicing
the xture. To reduce the possibility of static sparking, do not attach metallic parts to the outside of the unit (e.g. metallic screws,
tags, decals, etc).
• Do not mount the unit near gas or electric heaters.
• De-energize the unit before opening.
• To reduce the risk of electric shock, disconnect AC power before servicing. To prevent arcing, avoid shorting the battery terminals.
CAUTION:
• Servicing of this equipment should be performed by qualied service personnel.
• Do not attempt to service the battery. The unit uses a sealed, NiCD battery which requires no maintenance. For replacement,
contact the factory.
NOTICE:
• Do not use this equipment for anything other than its intended use.
• The use of accessory equipment is not recommended and may cause an unsafe condition.
• Wiring and installation should be performed in accordance with the National Electrical Code® (NEC®) and other applicable
local code requirements.
Agency Ratings
• Class I, Division 2, Groups A, B, C, D
• Class
• Type 4X
• IP66
• Marine Outside Type (Salt Water)
I, Zone 2, Group IIC
Appleton • 1.800.621.1506 • www.appletonelec.com 650483-000 Rev. B 07/15 • Page 1 of 10

Product Description
N2LED2T1 Master Unit
EMERGENCY LAMPS
UNIT MOUNTED
CONDUIT
HUB
9.80 in. [248.9 mm]
7.87 in. [200 mm]
LIGHT HEAD
SET SCREWS
LIGHT HEAD
GROUND WIRE
GROUND PLATE
GROUND WIRE
TERMINAL
BLOCK
5.75 in. [146 mm]
COVER SCREW INSERT
(FOUR [4] PLACES)
EIGHT (8) AVAILABLE FOR MAXIMUM
LIGHT HEAD CONTACT
FOUR (4) LIGHT HEADS
FRONT VIEW—COVER REMOVED
7.44 in. [189 mm]
8.46 in. [215 mm]
9.00 in. [228.6 mm]
LIGHT HEAD
SET SCREWS
LIGHT HEAD
GROUND WIRE
GROUND PLATE
PUSH TO TEST SWITCH
INTEGRAL PILOT LIGHT
5.20 in. [132.1 mm]
UNIT MOUNTING HOLES
(FOUR [4] PLACES)
BATTERY
INSTALLER CONNECTS
BATTERY TO PCA CONNECTOR
Figure 1: Description & Dimensions for N2LED2T1 Master Unit
Appleton • 1.800.621.1506 • www.appletonelec.com 650483-000 Rev. B 07/15 • Page 2 of 10

N2LED0T1 Master Unit
8.70 in. [221.0 mm]
7.87 in. [200 mm]
5.75 in. [146 mm]
GROUND PLATE
GROUND WIRE
TERMINAL
BLOCK
CONDUIT
HUB
GROUND PLATE
PUSH TO TEST SWITCH
INTEGRAL PILOT LIGHT
5.20 in. [132.1 mm]
COVER SCREW INSERT
(FOUR [4] PLACES)
EIGHT (8) AVAILABLE FOR MAXIMUM
LIGHT HEAD CONTACT
FOUR (4) LIGHT HEADS
FRONT VIEW—COVER REMOVED
Figure 2: Description & Dimensions for N2LED0T1 Master Unit
7.44 in. [189 mm]
8.46 in. [215 mm]
9.00 in. [228.6 mm]
UNIT MOUNTING HOLES
(FOUR [4] PLACES)
BATTERY
INSTALLER CONNECTS
BATTERY TO PCA CONNECTOR
Appleton • 1.800.621.1506 • www.appletonelec.com 650483-000 Rev. B 07/15 • Page 3 of 10