650432-000 INSTALLATION INSTRUCTIONS
FOR MERCMASTER III LOW PROFILE
WITH QL INDUCTION SYSTEMS
CAUTION : FOR PROPER AND SAFE INSTALLATION OF THIS PRODUCT, READ THE FOLLOWING INSTRUCTIONS.
IMPORTANT :When installing in a Hazardous Location, it is necessary that the Globe be in place, and that the fixture be
tightly closed. Globe and Reflector should be cleaned periodically to maintain lighting efficiency.
CAUTION : This fixture is designed for and should be installed in accordance with the Canadian Electrical Code and
the National Electrical Code and all applicable local codes.
CAUTION : Do not open or remove Fixture with circuit energized.
CAUTION : Do not use Fixture on ungrounded system.
TO FAILURE GROUND THIS FIXTURE CAN RESULT IN AN ELECTRICAL SHOCK WHICH MAY BE
FATA L!
CAUTION
RATINGS : CLASS I, DIVISION 2, GROUPS A,B,C,D
: Do not touch induction generator or mounting plate - VERY HOT!
CLASS I, ZONE 2, AEx nA nR IIC, Ex nA nR IIC
PENDANT HOOD
KPA-75
KPA-100
KPAF-75
KPAF-100
Secure Pendant Hood to the 3/4" or 1" Conduit Stem, and Tighten the Set
Screw inside Hood.
CONE MOUNT
KPCH-75
or
KPCH-100
Secure Cone Hood to the 3/4" or 1" Conduit
Stem, and Tighten the Set Screw.
STANCHION MOUNT
KPST-125
or
KPST-150
NOTE - 5 Full Threads Must Be Engaged.
Secure Stanchion to the 1-1/4" or 1-1/2" Conduit,
Orient and Tighten Set Screw.
Jct Box
Set Screw
Ceiling
Set Screw
Set Screw
CEILING MOUNT
KPC-75 or KPC-100
NOTE - Remove Unused Conduit Plugs, and Re-install with Pipe Sealant
Mount Ceiling Hood Directly to Structural Member,
Conduit, or Flush Mounted Jct Box. Four Drill marks
on 3-1/2" Pitch Dia are Provided for Jct Box Mtg.
Install Gasket Supplied with Jct Box between Box and Hood.
WALL MOUNT
KPWB-75
or
KPWB-100
Fasten junction box to structural member.
Feed supply wire through gasket and wall adapter.
Fasten wall adapter to junction box with screws provided.
Gasket supplied with junction box is required between mounting hood and
junction box.
25o STANCHION MOUNT
KPS-125
or
KPS-150
NOT E - 5 Full Threads Must Be Engaged.
Secure Stanchion to the 1-1/4" or 1-1/2"
Conduit, Orient and Tighten Set Screw.
Jct Box
Gasket
Screw (4)
Set Screw
INDUCTION GENERATOR HOUSING INSTRUCTIONS
1. Mount Hood to Conduit or Structural Member as shown.
2. Feed proper Temperature Supply Wire into Hood (See Nameplate).
3. Hang Ballast Housing on Hinge and Connect the Power to Proper
QL Unduction generator lead.
(See Wiring Diagrams.)
4. Connect Supply and Housing Bonding Leads to Green Bonding Lead
in Mtg Hood.
5. Fold All Excess Supply Leads and Fasten in Hood with Bundling Tie
Provided to Avoid Pinching Wires.
6. Swing Induction Generator Housing Up and Secure with Hex Nut and
Washer Combination and Tighten Securely.
7. Install Optional Reflector and/or Guard per Fixture Fitting Label in
Induction Generator Housing. (See Accessory Tree.)
EGS Electrical Group · 800-261-1506 · www.appletonelec.com Rev. B 06/15/11 Page 1
Hinge
Hinge Pin
Induction
Generator Hsg
Bundling Tie
Hood
Ceiling
Grd Wires
Gasket
Latch
Hex Nut &
Washer
Combination

FOR ALL QL INDUCTION FIXTURES
GLASS GLOBE
VPGL4HR (85W QL)
55W QL Induction System
85W QL Induction System
GLASS GLOBE
VPGL3HR (55W QL)
GLOBE GUARD
KPGU400
EGS Electrical Group
·
800-621-1506
·
www.appletonelec.com 650432-000 Rev. B 06/15/11 Page 2