INSTALLATION INSTRUCTIONS
MERCMASTER II FAMILY OF ENCLOSED AND GASKETED
FIXTURES FOR HAZARDOUS AND WET LOCATIONS
EGS Electrical Group • 800-621-1506 • www.appletonelec.com Rev. C 03/03/04 Page 1
IMPORTANT
When installing in a hazardous location it is necessary that the optic be in place and that the unit be tightly closed.
This fixture is designed for permanent installation in Class I, Div. 2, Class II, Div. 1 or marine locations in accordance with the
• DO NOT OPEN OR REMOVE FIXTURE WHILE IT IS ENERGIZED.
• DO NOT USE FIXTURE ON UN-GROUNDED CIRCUITS. Failure to ground this fixture can result in an electrical shock which
may be fatal.
Optic and reflector should be cleaned periodically to maintain lighting efficiency.
Orient hinges and latches 90° from the aiming direction desired for the angle reflector. This applies to ceiling, wall and
stanchion mounting hoods.
All unused conduit plugs and conduit runs must have a pipe sealant applied to the threads. This will prevent water entry into
the fixture through the pipe threads.
WARNING: FAILURE TO GROUND THIS FIXTURE CAN RESULT IN AN ELECTRICAL SHOCK WHICH MAY BE FATAL. CAUTION: Fixture with optional photocontrol or quartz auxiliary lamp does not comply with UL requirements for use in
hazardous locations.
WIRING AND BALLAST HOUSING INSTRUCTIONS
1. Mount hood to conduit or structural members as shown.
2. Feed proper temperature supply wire into hood. (See Name Plate)
3. Hang ballast housing on hinge and connect the power to proper ballast lead.
Be sure to leave all unused ballast leads capped. (See wiring diagrams)
4. Connect supply ground and housing ground leads to green ground screw on
mounting hood.
5. Fold all excess supply leads and fasten in hood with wire tie provided.
6. Swing ballast housing up and secure with hex latch knob. Tighten securely.
7. Install lamp, checking both lamp type and wattage for proper lamp. Tighten lamp
securely.
8. Install globe or refractor and optional reflector and/or guard as per fixture
fitting label in ballast housing. See accessory list inside this instruction sheet.
INSTALLATION OF FUSE KIT
1. Attach line and ballast leads to fuse holder per
diagram.
2. Assemble fuse holder and insulation to boss with
thread forming screw furnished.
3. Complete wire connections with supplied connectors.
INSTALLING PHOTOCONTROL KIT
1. Remove knockout in top of hood by inserting tip of a
chisel or screwdriver into the knockout groove. Strike with a hammer, then pry out slug.
2. Install photocontrol in knockout hole, placing gaskets
provided between photocontrol and hood and between tightening nut and top of hood. Tighten nut.
3. Thread shading cup over exposed threads/orient
open angle end toward north.
Non-Hazardous Photocontrol
Photocontrol for automatic dusk-to-dawn 'ON-OFF' control fits all Mercmaster mounting hoods (except ceiling).
Not for use in hazardous locations.
FUSE
HINGE
GASKET
BALLAST
SOCKET
GLOBE
SNAP-ON
GUARD
CAPACITOR
GROUND SCREW
SET SCREW
GUARD AND REFLECTOR MTG. SCREWS (3)
THREE PHASE
SYSTEM
SINGLE
PHASE
SYSTEM
INSULATOR
1
2
3
LINE LEAD FROM HOOD
PHASE 1 LINE LEAD FROM HOOD
PHASE 2 LINE LEAD FROM HOOD
LINE LEAD
FROM BALLAST
COMMON LEAD
FROM BALLA
ST
LINE LEAD
FROM BALLAST
LINE
COMMON
Pendant Ceiling Wall Mount 25° Stanchion
One Hub Five Hubs Five Hubs One Hub
3/4" LPA -75 3/4" LPC-75 3/4" LPWB-75 1-1/4" LPS-125
1" LPA-100 1" LPC-100 1" LPWB-100 1-1/2" LPS-150
Prismatic Glass Globe
Heat Resistant VPGL-2HR
Amber VPGL-2AM
Blue VPGL-2BL
Green VPGL-2GR
Red VPGL-2RE
Tuff Skin™ Coated VPGL-2HRT
Polycarbonate Globe(100W Max)
Clear VPGL-2PL
Amber VPGL-2AMPL
Green VPGL-2GRPL
Red VPGL-2REPL
Closed Prismatic
Refractor
8” GLASS
NEMA I LPG-R1
NEMA III LPG-R3
NEMA V LPG-R5
8” Steel Guard
LPRG-2
12" Closed Prismatic Refractors
GLASS POLYCARBONATE
(50-100W)
NEMA II LPRF-2CG LPRF-2CP
NEMA III —— LPRF-3CP
NEMA IV —— LPRF-4CP
NEMA V LPRF-5CG LPRF-5CP
LPB Series
50-150W HPS
100-250W MV
100W MH
Mogul Base
LPB Series
50-150W HPS
100-250W MV
100W MH
Mogul Base
MERCMASTER II LIGHTING FIXTURE
FAMILY TREE
MOUNTING HOODS
Aluminum Guard
Snap-On VPGU2
Snap-On Porcelain Steel Reflector
Standard Dome LPR-25ST / 30° Angle LPR-25AN
12" Steel Guard
LPBG-12
Aluminum Guard
KGU2
Polyester Reflector
Standard Dome KR2-ST / 30° Angle KR2-AN
Mounting Adapter
Use with MM II to
V 51 Mounting
LPAD-1
Mounting Adapter
LPAD-1
Factory wired.
Enables the use of Mercmaster
II pendant hood on existing V-51
and Mercmaster I mounting units.
Pendant - One Hub.
3/4" LPA-75 - 1" LPA-100
Screw Pendant Hood onto
the conduit and tighten the set
screw (inside hood).
Brace required on conduit
stems longer than 12" (N.E.C.
required).
Ceiling - Five Hubs.
3/4" LPC-75 - 1" LPC-100
Ceiling Hood may be mounted
directly to a structural member
conduit or flush mounted junc-
tion box.
Four drill Holes are provided
on 3-1/2 inch centers for
exact positioning of junction box.
Gasket supplied with junction
box required between mounting
hood and junction box.
Fasten junction box to struc-
tural member. Feed supply
wire through gasket and wall
adapter into hood.
Fasten adapter to junction box.
Gasket supplied with junction
box is required between mount-
ing hood and junction box.
25° Stanchion - One Hub.
1-1/4" LPS-125 -
1-1/2" LPS-150
Install 25° Stanchion on the 1-
1/4" or 1-1/2" conduit. Five
full threads must be
engaged.
Orient fixture and tighten
set screw.
SET SCREW
IMPORTANT:
Remove all
unused conduit
plugs and reinstall
with pipe sealant.
EGS Electrical Group • 800-621-1506 • www.appletonelec.com 654008-001 Rev. C 03/03/04 Page 2