Appleton Instruction Sheet: Industrial Rigmaster LED Series Luminaires, Class I, Division 2, 650609-001 | Appleton Manuals & Guides

650609-001 INSTRUCTION SHEET
Installation Instructions for the Appleton™ Rigmaster™ Industrial LED Luminaire
FOR PROPER AND SAFE INSTALLATION OF THIS PRODUCT, PLEASE READ THE FOLLOWING INSTRUCTIONS.
Product Safety
Signal Words Defined
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a hazardous situation
Safety Instructions for Luminaire
WARNING:
• Do not open or remove luminaire when supply is ON.
• Do not use luminaire on ungrounded systems. Failure to ground this luminaire can result in an electric shock, which may be fatal.
• Disconnect the luminaire from the supply circuit before opening to reduce the risk of ignition. Keep tightly closed when in operation.
• Do not mount near gas or electric heaters.
• De-energize the unit ve (5) minutes before opening.
• Use two safety cables for installations experiencing high vibrations.
• Do not use on ungrounded 480-volt circuits.
• Supply wires to be rated for minimum 90°C.
CAUTION:
• Do not look directly at the LEDs when energized.
• Lens cleaning instructions: Wipe/clean from the outside only with a moist cloth. (Beware of electrostatic charges.)
• When installing, it is necessary that the reector, lens, and all certied conduit plugs be in place and tightened securely to the housing.
NOTICE:
• Do not touch the LEDs; touching could leave oily deposits, causing hot spots and potential premature failure.
• The LED lens should be cleaned periodically from the outside only with a moist cloth to maintain lighting efciency.
• This luminaire is designed for and should be installed with wiring method required in accordance with the National Electrical Code®/ Canadian Electrical Code and all applicable local codes.
• This product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the product and hazards involved.
Applications/Intended Use
• Marine and wet locations; apply a corrosion-inhibiting grease, such as petroleum or soap thickened mineral oils, in 3 lines, spaced approximately 120 degrees apart, perpendicular to the threads. Tighten all unused close-up plugs.
• Areas of low clearance, low ceiling heights, or where luminaire weights must be minimized.
• Non-hazardous locations where severe weather conditions, excessive moisture, dirt, dust, corrosive atmospheres, and high ambient temperatures are encountered.
• Where exible cord is used, it should be approved for extra hard, wet location usage and shall have a separate ground conductor.
Appleton • 1.800.621.1506 • www.appletonelec.com 650609-001 Rev. 00 20/03/19 • Page 1 of 24
Agency Ratings : (NEC/CEC)
• Wet Locations
• Type 3R, 4 & 4X
• IP66
• Marine Outside Type (Salt Water) (For installations in USA only)
NOTES:
Refer to the product nameplate, located on the housing body, for details.
Dimensions/Details
LUMINAIRE DIMENSIONS
FIGURE 1: RIGMASTER 2 FT. LUMINAIRE
FIGURE 2: RIGMASTER 4 FT. LUMINAIRE
650609-001 Rev. 00 20/03/19 • Page 2 of 24Appleton • 1.800.621.1506 • www.appletonelec.com
Mounting Instructions
1. Make sure power is disconnected before installing the luminaire.
2. Determine appropriate mounting distance between mounting holes for your application.
3. Use bolts (not supplied) appropriate for the structural support member.
4. Secure luminaire to structural support element having through holes that can handle the weight of the luminaire in accordance with
local building code and all other code requirements.
5. Tighten the bolts to secure the luminaire in place.
Mounting Brackets
SMALL SWIVEL BRACKET (RMSSB)
1. Make sure power is disconnected before installing the luminaire.
2. Mount the luminaire with bracket to a at surface using user-supplied hardware. See Figure 3 for mounting hole locations.
3. Slightly loosen the locking screw, mounting screw and tilt the luminaire to the desired position with your free hand. See Figure 3.
4. Retighten the screws to secure the luminaire in place with a torque of 15 N.m (133 Lb.in).
FIGURE 3: MOUNTING OPTIONS – RMSSB BRACKET
650609-001 Rev. 00 20/03/19 • Page 3 of 24Appleton • 1.800.621.1506 • www.appletonelec.com
LARGE SWIVEL BRACKET (RMLSB)
1. Make sure power is disconnected before installing the luminaire.
2. Mount the luminaire with bracket to a at surface using user-supplied hardware. See Figure 4 for mounting hole locations.
3. Slightly loosen the locking screw, mounting screw and tilt the luminaire to the desired position with your free hand. See Figure 4.
4. Retighten the screws to secure the luminaire in place with a torque of 15 N.m (133 Lb.in).
FIGURE 4: MOUNTING OPTIONS – RMLSB BRACKET
650609-001 Rev. 00 20/03/19 • Page 4 of 24Appleton • 1.800.621.1506 • www.appletonelec.com
LOW PROFILE BRACKET (RMLPB)
1. Make sure power is disconnected before installing the luminaire.
2. Mount the luminaire with bracket to a at surface using user-supplied hardware. See Figure 5 for mounting hole locations.
3. Tighten the screws to secure the luminaire in place with a torque of 15 N.m (133 Lb.in). Locking screws should be applied such
that they are diagonally opposite to each other on either side. See Figure 5.
FIGURE 5: MOUNTING OPTIONS – RMLPB BRACKET
TABLE 1: MOUNTING BRACKET COMPATIBILITY CHART FOR RETROFIT INSTALLATIONS
Appleton Part Number
Manufacturer Part Number
Crouse Hinds DP1057MTK X X
LTXW4 X X
Dialight
LTXW4LP X X
AZZ™ Rigalite 53050 X X
Appleton™ Viamaster™ GRFC75A X
RMSSB
Small Swivel Bracket
RMLSB
Large Swivel Bracket
650609-001 Rev. 00 20/03/19 • Page 5 of 24Appleton • 1.800.621.1506 • www.appletonelec.com
RMLPB
Low Profile Bracket
Wiring
WARNING: The luminaire must be grounded as required by the National Electrical Code (Paragraph 410.21 and Article 250) or
Canadian Electrical Code (Rule 30-500 and Section 10). Verify that ground continuity has been established by using an Ohm meter or other suitable testing equipment before energizing the luminaire. Failure to properly ground the luminaire will create an electric shock hazard, which can cause serious injury or death.
Please use supply wires with temperature rating 90°C or above
Wiring the Rigmaster™ LED Luminaire For Luminaire Series with Wire Nut Option
1. Make sure power is disconnected before wiring the luminaire.
2. A. Wiring with Cable: Strip the cable outer jacket as required. Strip the insulation of individual wire by approximately
10 mm (0.4 in)
B. Wiring with Individual Wires: Strip the insulation of individual wire by approximately 10 mm (0.4 in)
3. For standard Wiring: Connect electrical power supply leads to the 3 wire conductors coming out of wiring compartment with
the help of wire nuts supplied with luminaire: see Figure 6. After completing the wiring insert wire nuts in wiring compartment through the Conduit / Cable entry hole. For Wiring diagram refer to Figures 7 and 8.
For through feed Wiring:
4. A. Open the luminaire wiring compartment by loosening the four captive screws. Allow the cover to swing open,
enabling access to the wiring compartment. See Figure 6. Pull the wires through the cable entry hole on the other side of the box. Connect electrical power supply leads to the respective wires with the help of wire nuts supplied with luminaire. After completing the wiring insert wire nuts in wiring compartment through the Conduit / Cable entry hole. For Wiring diagram refer to Figures 7 and 8.
B. Check all connections for continuity and ground integrity and close the luminaire wiring compartment cover.
C. Tighten the four captive screws by applying a torque of 2.25 N.m (20 Lb.in) using the sequence shown as in
Figure 9. Make sure wires do not pinch between cover and wiring compartment when closing.
5. Apply TLNC4 grease on plugs (three supplied) in 3 lines, spaced approximately 120 degrees apart, perpendicular to the
threads. After applying TLNC4 grease close all unused conduit entries with plugs. Apply torque of 45 N.m (400 Lb.in.) for 3/4" NPT plug, 28 N.m (250 Lb.in.) for 1/2" NPT plug and 25 N.m (225 Lb. in.) for M20 plug.
6. For continuous row mounting below mentioned number of luminaires are connected.
Maximum 28 luminaires of 2 FT. connected in series Maximum 15 luminaires of 4 FT. connected in series
7. Power can now be applied to the luminaire
FIGURE 6: RIGMASTER LUMINAIRE WITH WIRE NUT OPTION
650609-001 Rev. 00 20/03/19 • Page 6 of 24Appleton • 1.800.621.1506 • www.appletonelec.com
Wiring Diagrams
FIGURE 7: FOR RIGMASTER 4000 LUMEN WITH WIRE NUTS FOR CUSTOMER WIRING
FIGURE 8: FOR RIGMASTER 8000 LUMEN WITH WIRE NUTS FOR CUSTOMER WIRING
FIGURE 9: SCREW TIGHTENING SEQUENCE
650609-001 Rev. 00 20/03/19 • Page 7 of 24Appleton • 1.800.621.1506 • www.appletonelec.com
For Luminaire Series with Fixed Screw Terminal Option
1. Make sure power is disconnected before wiring the luminaire.
2. Open the luminaire wiring compartment by loosening the four captive screws. Allow the cover to swing open, enabling
access to the wiring compartment. see gure 10.
3. A. Wiring with Cable
1. Strip the cable outer jacket as required.
2. Insert the cable through the conduit entry (with appropriate tting attached) to the luminaire wiring compartment.
B. Wiring with Individual Wires
1. Run conductors down through the conduit to the luminaire wiring compartment.
NOTE: See the product nameplate for supply wire requirements. The terminal block can accept 12-20 AWG wire. Use the appropriate wire gauge based on the application.
4. Strip the individual wires by approximately 5 mm (0.2 in) and insert them into the proper terminal block connections. The
connection points are identied on the terminal block as: “L” = Line, “N” = Neutral, and “PE” = Ground. Tighten down the terminal block screws onto the wire with torque of 0.75 N.m (6.5 Lb.in) See Figure 10.
5. Check all connections for continuity and ground integrity.
6. Once the terminal block is wired to incoming power, close the luminaire wiring compartment cover.
7. Tighten the four captive screws by applying a torque of 2.25 N.m (20 Lb.in) using the sequence shown as in Figure 9. Make
sure wires do not pinch between cover and wiring compartment when closing.
8. Apply TLNC4 grease on plugs (three supplied) in 3 lines, spaced approximately 120 degrees apart, perpendicular to the
threads. After applying TLNC4 grease close all unused conduit entries with plugs. Apply torque of 45 N.m (400 Lb.in.) for 3/4" NPT plug, 28 N.m (250 Lb.in.) for 1/2" NPT plug and 25 N.m (225 Lb. in.) for M20 plug.
9. For continuous row mounting below mentioned number of luminaires are connected.
Maximum 28 luminaires of 2 FT. connected in series Maximum 15 luminaires of 4 FT. connected in series
10. Power can now be applied to the luminaire.
FIGURE 10: RIGMASTER LUMINAIRE WITH SCREW TERMINAL OPTION
650609-001 Rev. 00 20/03/19 • Page 8 of 24Appleton • 1.800.621.1506 • www.appletonelec.com
Loading...
+ 16 hidden pages