Appleton Instruction Sheet: Industrial Contender LED Series Luminaires, 650583-001 | Appleton Manuals & Guides

650583-001 INSTRUCTION SHEET
Installation Instructions for Appleton™ Industrial Contender™ LED Luminaire
FOR PROPER AND SAFE INSTALLATION OF THIS PRODUCT, PLEASE READ THE FOLLOWING INSTRUCTIONS.
Product Safety
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICE is used to address practices not related to physical injury.
Safety Instructions
WARNING
• Do not open or remove the luminaire with the circuit energized.
• Do not use this luminaire on ungrounded systems. Failure to ground the luminaire can result in an electric shock, which may be fatal.
CAUTION:
• Risk of re.
• Do not look directly at the LEDs when energized.
• It is necessary that the globe and all conduit plugs are tightly secured and all luminaire ttings (mounting hood and optic) are tightly secured to the LED housing to prevent water and dust entry. The optic should be cleaned periodically to maintain lighting efciency.
NOTICE:
• Do not touch the LEDs; touching could leave oily deposits, causing hot spots and potential premature failure.
• This luminaire is designed for and should be installed in accordance with the National Electrical Code®/Canadian Electrical Code and all applicable local codes.
• This product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the product and hazards involved.
• Do not use this equipment for anything other than its intended use.
Applications/Intended Use
• Marine and wet locations
• Non-hazardous locations where severe weather conditions, excessive moisture, dirt, dust, corrosive atmospheres, and high ambient temperatures are encountered.
• Areas of low clearance, low ceiling heights, or where luminaire weights must be minimized.
Agency Ratings
• Type 3R, 4, 4X • IP66/67
• Suitable for use in Wet Locations • Marine Outside Type (Salt Water) for USA only j
• Refer to product nameplate for details.
NOTES:
j To be installed in accordance with CG-259 of American Bureau of Shipping and Coast Guard.
Appleton • 1.800.621.1506 • www.appletonelec.com 650583-001 Rev. C 02/25/19 • Page 1 of 8
Luminaire Dimensions
FIGURE 1: CONTENDER LED LUMINAIRE
650583-001 Rev. C 02/25/19 • Page 2 of 8Appleton • 1.800.621.1506 • www.appletonelec.com
LED Housing Installation
Canadian Electrical Code (Rule 30-500 and Section 10). Verify that ground continuity has been established by using an Ohm meter or other suitable test equipment before energizing the luminaire. Failure to properly ground the luminaire will create an electric shock hazard, which can cause serious injury or death.
This product is intended to be used with Eaton Crouse-Hinds Champ series mounting hoods. It is up to the installer to ensure that the Crouse-Hinds mounting hood that this product is being installed on is in good condition and will mate with the luminaire properly. Installer must ensure that the gasket is compressed properly against the Crouse-Hinds hood all the way around the luminaire.
Once this product is installed to a compatible Crouse-Hinds mounting hood it may not be removed from the hood as this is a non-serviceable joint. To service the xture the three captive bolts from the top side of the xture may be removed to access the electronic driver.
WARNING: The luminaire must be grounded as required by the National Electrical Code (Paragraph 410-21 and Article 250) or
FIGURE 2: WIRING COMPARTMENT
1. Disconnect facility power to the electric power supply leads.
2. Hang the LED housing on the hinge as shown in the gure above.
3. Connect the electric power supply leads to the cord either by wire nuts or on SKUs ending with “T” it will be terminated using the
provided terminal block. For wire nut versions approximately 12" of wire is provided from the top of the xture with stripped leads. If less cord is desired the installed may cut the wires shorter and re-strip the leads.
4. Make sure hood is grounded to the luminaire by attaching ground wire to the cord provided.
5. Once wired, swing luminaire into position and tighten the captive bolt into the Crouse-Hinds hoods until the luminaire and mounting
hood bottoms out.
650583-001 Rev. C 02/25/19 • Page 3 of 8Appleton • 1.800.621.1506 • www.appletonelec.com