Appleton Instruction Sheet: Industrial Baymaster LED Luminaire (No Mount), 650548-001 | Appleton Manuals & Guides

650548-001 INSTRUCTION SHEET
Installation Instructions for Appleton™ Industrial Baymaster™ LED Luminaire - No Mount
FOR PROPER AND SAFE INSTALLATION OF THIS PRODUCT, PLEASE READ THE FOLLOWING INSTRUCTIONS.
Product Safety
Signal Words Defined
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a hazardous
Safety Instructions
WARNING:
• Do not open or remove luminaire with the circuit energized.
• Do not remove or replace fuse when luminaire is energized.
• Do not use this luminaire on ungrounded systems. Failure to ground this luminaire can result in an electric shock, which may be fatal.
• Do not use on ungrounded 480 Volt circuits.
CAUTION:
• Do not look directly at the LEDs when energized.
• Risk of re.
NOTICE:
• Do not touch the LEDs; touching could leave oily deposits, causing hot spots and potential premature failure.
• This product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the product and the hazards involved.
• This luminaire is designed for and should be installed in accordance with the National Electrical Code®/Canadian Electrical Code and all applicable local codes.
Marine Locations
CAUTION/ATTENTION:
• Make sure to tighten unused close-up plug to 400 in.-lb. after applying TLNC4 grease. TLNC4 grease shall be applied in 3 lines, spaced approximately 120 degrees apart, perpendicular to the threads.
• Where exible cord is used, it should be approved for extra hard, wet location usage and shall have a separate ground conductor.
Agency Ratings
• Wet Locations
• Marine Outside Type (Salt Water) (For installation in USA only)
• Type 3R, 4, & 4X
• IP66 & IP67
Appleton • 1.800.621.1506 • www.appletonelec.com 650548-001 Rev. A 06/26/17 • Page 1 of 10
Dimensions
Figure 1: LED Luminaire
Appleton • 1.800.621.1506 • www.appletonelec.com 650548-001 Rev. A 06/26/17• Page 2 of 10
Wiring
WARNING: The luminaire must be grounded as required by the National Electrical Code (Paragraph 410-21 and Article 250) or
Canadian Electrical Code (Rule 30-500 and Section 10). Verify that ground continuity has been established by using an Ohm meter or other suitable testing equipment before energizing the luminaire. Failure to properly ground the luminaire will create an electric shock hazard, which can cause serious injury or death.
Wiring the Baymaster LED Luminaire
1. Open the luminaire wiring compartment by loosening the four captive screws. Allow the cover to swing open, exposing the wiring compartment.
2. Insert the cable/conduit through the conduit entry (with appropriate tting attached) to the luminaire wiring compartment.
3. Strip the individual conductors to bare wire and insert them into the proper terminal block connectors. The connection points
are identied on the terminal block as: “L” = Line, “N” = Neutral and “G” = Ground. Tighten down the terminal block screws onto the wire.
4. Once the terminal block is wired to incoming power, close the luminaire wiring compartment cover.
5. Tighten the four captive screws by applying a minimum of 14 in.-lb using an (x) pattern.
6. Close all unused conduit entries with close-up plugs (provided). Make sure to tighten unused close-up plugs to 400 in.-lb
after applying TLNC4 grease. TLNC4 grease shall be applied in 3 lines, spaced approximately 120 degrees apart, perpendicular to the threads.
7. Power can now be applied to the luminaire.
Figure 2: (x) Pattern
Appleton • 1.800.621.1506 • www.appletonelec.com 650548-001 Rev. A 06/26/17• Page 3 of 10