Appleton Instruction Sheet: Appleton JBR Series 30 and 60 Amp Switched Receptacles, 330112 Manuals & Guides

INSTRUCTION SHEET
INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE OF
"JBR" RECEPTACLE: 30 & 60 AMPERE
330112
"JBR" SERIES:
Receptacle Interlocked with switch for use in hazardous locations.
Compliances:
U.L. Standards 1010, 1682, 1686 CSA Standard C22.2
Electrical Ratings
Maximum voltage: 600 VAC at 50-400 Hz Continuous current: 30 or 60 amperes
APPLICATION:
Designed to supply power to portable or fi xed electri-
cal equipment such as motor generator units, welders, pumps, compressors and similar apparatus.
Ideal for use on shipping docks, ports, and other "Ship to
Shore" applications.
Suitable for use in locations where a weatherproof
enclosure is required.
Interlocked receptacle design to provide for use in
hazardous locations.
Rough usage construction.
FEATURES: A. Rugged and weatherproof boxes or covers sealed with gasket. B. Grounding style. Style 2 receptacles ground through
shell and extra pole.
C. Insulating blocks. Provide high mechanical and dielec-
tric strength, low "arc tracking".
D. Arcing confi ned. Interlocked receptacle design means
that all electrical switching is done with internal switch. Plug can not be engaged or disengaged with receptacle when switch is "ON".
E. Positive contact. Brass contacts have integral springs for
positive, maintained electrical contact.
F. Receptacle face enables the engagement of plugs for a
weatherproof union.
G. Positive ground. Grounding terminal for style 2 recep-
tacle "makes fi rst, breaks last."
H. Receptacle is designed so that it can only be turned
to the "ON" position when the proper mating plug is engaged with it, providing a totally "dead-front" receptacle. See "Table B" for a list of the mating plugs.
I. Receptacles come with both a fl ip cover and a screw
cover for protection against environmental conditions. See page 9 of this instruction sheet for ratings.
J. P4 option. Special polarization prevents plug insertion
into a receptacle wired for a different voltage.
Read instructions carefully and with full under­standing for safe installation and operation
TOP CONDUIT
ENTRY
30 AMP / 60 AMP
ACP PLUG
JBR WITH
SCREW COVER
ASSEMBLY
OPENED JBR SHOWING
BOTTOM CONDUIT ENTRY
Style 2 Interlocked receptacle is equipped with contacts designed to provide a safety polarization means called "controlled length" contacts. This fea­ture will not allow the plug grounding contact (style
2) to touch an energized receptacle "line" contact in the event the plug becomes damaged and/or loses its primary polarization means and/or is rotated into the incorrect position.
Retain this instruction sheet for future reference.
EGS Electrical Group • 800-621-1506 • www.appletonelec.com
Rev. D 05/31/06 Page 1
Except as expressly provided by Appleton Electric, LLC (Appleton), Appleton products are intended for ultimate purchase by industrial users and for opera­tion by persons trained and experienced in the use and maintenance of this equipment and not for consumers or consumer use. Appleton warranties DO NOT extend to, and no reseller is authorized to extend Appleton's warranties to, any consumer.
MODIFICATION WARNING
DO NOT modify these devices in anyway. Replace any missing or broken parts with proper replacement parts from Appleton Electric, LLC. Modifi cation of these devices or substitution of parts with non-standard parts may result in serious/fatal person injury from electrocution.
MODIFICATION WARNING
Use only copper cable or wire per the National Electric Code (NEC) for given amp rating of the receptacle. Tighten terminal block lug screws to the torques given in "Table A" for the listed wire ranges. Failure to do so may result in over stressed wire termina­tions which could cause the conductors to pull out of the terminal block and cause serious/fatal injuries due to electrocution.
WIRING WARNING
A wire scheme must be followed so that the same color wire is always put into the same numbered contact open­ing in all plugs, connectors and receptacles in the system. This will help to insure the correct polarity for the system and helps to eliminate possibilities for equipment damage and/or personal injuries due to electrocution.
DAMAGE WARNING
If any part of the receptacle appear to be missing, broken or shown sign of damage:
DISCONTINUE USE IMMEDIATELY!
This condition could cause serious/fatal personal injury due to electrocution and/or equipment damage. Repair with the proper replacement part(s) before continuing service.
ELECTRICAL WARNING
Electrical power must be turned "OFF" before and during installation and maintenance. Failure to do so may result in serious or fatal injuries due to electrocution.
TABLE B:
ACP & CPH PLUGS FOR JBR RECEPTACLE
CABLE PLUG CATALOG NUMBER DIAMETER 30 AMP 60 AMP
ACP
(INCHES) 2W, 3P 3W, 4P 2W, 3P 3W, 4P
.390 - 1.375 ACP3023BC ACP3034BC ACP6023BC ACP6034BC .500 - .875 CPH3023B CPH3034B ---- ---- .390 - 1.375 ---- ---- CPH6023BC CPH6034BC
CPH
CAUTION
To prevent ignition of hazardous atmospheres do not use in Class I, Group F locations that contain electrically con­ductive dusts.
TABLE A: Tightening torque terminal block lug screws
WIRE
TERMINAL BLOCK
LUG SCREW
WIRE TIGHTENING RANGE TORQUE (AWG) (IN-LBS)
2/0-6 120
SCREWDRIVER
8 40 10 - 14 35
SUPPLEMENT 1
INTERMATEABILITY CHART
APPLETON APPLETON APPLETON APPLETON CROUSE-HINDS RECEPTACLE RECEPTACLE PLUG PLUG PLUG RATING CAT. NO. RATING CAT. NO. CAT. NO.
600 VAC, 30 A 10 HP JBR3023-150 600 VAC, 30 A, 10 HP ACP3023BC APJ3385 600 VAC, 60 A, 20 HP JBR6023-150 600 VAC, 60 A 20 HP ACP6023BC APJ6385 600 VAC, 30 A, 20 HP JBR3034-150 600 VAC, 30 A, 20 HP ACP3034BC APJ3485 600 VAC, 60 A, 30 HP JBR6034-150 600 VAC, 60 A, 30 HP ACP6034BC APJ6485
Note:
The Appleton "JBR" receptacles and "ACP" plugs are UL listed combinations. The Appleton "JBR" receptacle with Crouse-Hinds UL listed "APJ" series plugs are UL Classifi ed combinations. "JBR" receptacle and "APJ" plugs are Classifi ed for Class I, Div. 1, Groups B, C and D. Receptacles with the P4 option have the interior rotated 22 1/2° for special polarization applications. They are compatible only with Appleton plugs with the P4 option, or Crouse-Hinds plugs with the S4 option.
Page 2 330112 Rev. D 05/31/06
EGS Electrical Group • 800-621-1506 • www.appletonelec.com
FIGURE A — JBR RECEPTACLE
DIMENSIONS: JBR RECEPTACLE WITH COVER OPEN
CONDUIT ENTRY
CATALOG "A" CONDUIT NUMBER ENTRY SIZE
JBR3023-150 1-1/2 — 11-1/2 NPT JBR3034-150 OR JBR6023-150 1-1/4 — 11-1/2 NPT JBR6034-150 (WITH PROVIDED REDUCER
NOTE:
JBR RECEPTACLE WITH SCREW COVER NOT SHOWN
FIGURE B
LOCKOUT HOLE
TERMINAL BLOCK
10.18"
(4) KEY-HOLE SLOTS
FOR 3/8 BOLTS
3.75"
9.5 CM
DRILLING PLANS FOR MOUNTING BOLTS
25.9 CM
FIGURE C — JBR INTERLOCKED RECEPTACLE
(4) KEY-HOLE SLOTS
FOR 3/8" BOLTS
(8) BOLDS ARE
SUPPLIED
3.53"
9.0 CM
13.27"
33.7 CM
2.22"
5.8 CM
11.75"
29.8 CM
CONDUIT SIZE
LOCATED IN CENTER
OF BOX (SEE TABLE C)
14.04"
35.66 CM
WIRE MARKER
TERMINAL LUG
#8 WIRE FROM DISCONNECT SWITCH
11.75"
129.8 CM
2.22"
5.8 CM
CONDUIT SIZE "A"
LOCATED IN CENTER
OF BOX (SEE TABLE C)
3.53"
9.0 CM
10.9 CM
EGS Electrical Group • 800-621-1506 • www.appletonelec.com
4.25"
10.28"
26.1 CM
8.25"
21.0 CM
8.70"
22.1 CM
330112 Rev. D 05/31/06 Page 3