Appleton Instruction Sheet: Appleton EBR Series, 300880-1 Manuals & Guides

Class I, Div. 1 and 2 Groups C, D Class II, Div. 1 and 2 Groups F, G Class III Type 3, 3R, 4, 4X NEMA 7CD, 9F*G
300880-1
INSTRUCTION SHEET
U.S. Patent No. 3,735,078
EBR Receptacles with Interlocked Circuit Breaker:
Explosion-Proof, Dust-lgnition-Proof.
Weatherproof Spring Cover—30, 60, 100 and 150 Amps at 600V A.C. Max.
Interlocked Circuit Breaker Safety Construction. Grounding thru Extra Pole and Shell
I. TO DISASSEMBLE RECEPTACLE INTERIOR
1. Remove polarizing screw and washer.
2. Rotate terminal holder counter-clockwise.
II. TO CONNECT CONDUCTORS TO RECEPTACLE INTERIOR
1. Strip insulation from ends of individual conductors.
2. Loosen screws in pressure connectors and slide prepared ends of conductors into the connectors, observing proper polarity. Tighten screws.
III. TO REASSEMBLE RECEPTACLE INTERIOR
1.Insert Terminal Holder and turn clockwise until front end is approximately 1/4” inside of casting surface. Recessed radial depression in Terminal Holder must be lined up with polarizing washer/locator. Replace screw through the ground strip.
IV. POLARITY AND PHASE ROTATION
1. ACP, CPH Plugs and EBR Receptacle are polarized so that the plug will enter the
1-1/2” threaded conduit
openings- one in top and
two in bottom
receptacle only one way.
2. Special Polarization: sufx - P4 added to catalog number of the receptacle. Prevents plug insertion in a receptacle wired for a different voltage (doesn’t apply for 150 Amp).
Solderless lugs are provided for line connections and receptacle is prewired to the load side of breaker. Cover-mounted components leave entire enclosure space free for pulling of line conductors and wiring.
POLARIZED SCREW AND WASHER
PRESSURE
CONNECTORS
SCREW
TERMINAL
HOLDER
Flip cover suitable for Type 3 and 3R only. Select screw cover for
Type 4 and 4X. Both covers are included with product. Type 4 rating maintained with Appleton Type 4 plug installed.
Plug is mechanically locked in receptacle when circuit breaker is ON. Design provides interlocked connect and disconnect operation as well as short circuit and thermal time delay overload protection. Breaker operating handle can be padlocked in either “ON” or “OFF” position and is trip-free.
Enclosure has 3/4” threaded openings top and bottom for installation of UL Listed drain and breather. Reducers are suitable for Class I, Groups B, C and D; Class II, Groups F and G when installed such that at least ve full threads are engaged. Unused openings must be plugged with fac­tory supplied plugs.
EGS Electrical Group • 800-621-1506 • www.appletonelec.com Rev. E 01/15/2009 Page 1
Dimensions of EBR Inter-Interlock Circuit Breaker Receptacles
C/L OF CONDUIT OPENINGS
7.44”
CONDUIT OPENINGS
TAPPED 1-1/2”
16.69”
42.4 CM
15.13”
38.4 CM
18.9 CM
14.06”
35.7 CM
B
TOP VIEW CONDUIT OPENING
1 1/2 - 11 1/2 NPT
2.63”
6.7 CM
3/4 - 14
NPT
4.50”
11.4 CM
9.00”
22.9 CM
2.00”5.1 CM
3.81”
9.7 CM
3.81”
9.7 CM
2.00”
5.1 CM
1.75”
45 CM
3.00”
7.6 CM
2.63”
8.7 CM
TWO THREADED 1 1/2
CONDUIT OPENINGS IN BOTTOM
BOTTOM VIEW
CONDUIT OPENING
2.75”
7.0 CM
A
C/L OF CONDUIT OPENINGS
3.0”
76 CM
9.06”
23.0 CM
3/4 - 14
NPT
MOUNTING HOLES
FOR 3/8” DIA. BOLTS
30 Amp 60 Amp 100/150 Amp 30 Amp 60 Amp 100/150 Amp
A 14.25” 14.25” 14.69” B 16.13” 17.69” 18.38” (36.2cm) (36.2cm) (37.3cm) (41.0cm) (44.9cm) (46.7cm)
Dimensions in Inches
A
ACP Plugs for EBR Receptacles
Amp No. Poles A B C D 30 Amp 2, 3, 4 6.00 4.75 3.13 1.86
D
C
60 Amp 2, 3 7.81 4.94 3.50 2.23 60 Amp 4 7.81 4.94 3.81 2.55
B
100 Amp 2, 3 10.50 6.63 4.00 2.47 100 & 150(CD) Amp 4 10.50 6.63 4.25 2.72 150(DE) 4 13.40 9.63 4.25 2.72
CPH Plugs for EBR Receptacles
D
C
B
Max. Amps. Wire/Pole A B C D E
E
A
30 2W, 3P; 3W, 4P 6.13 2.38 1.86 1.81 4.44 60 2W, 3P 8.44 3.06 2.23 3.31 5.69 60 W, 4P 8.44 3.06 2.55 3.31 5.69
ACP PLUG
CPH PLUG
ACP Plugs for EBR Receptacles
Cable Dia. (In.) 30 Amp 60 Amp 100 Amp 150 Amp
2W, 3P 3W, 4P 2W, 3P 3W, 4P 2W, 3P 3W, 4P 3W, 4P
.390 to 1.375 ACP3023BC ACP3034BC ACP6023BC ACP6034BC --------- --------- ---------
.875 to 1.906 --------- --------- --------- --------- ACP1023CD ACP1034CD ACP15034CD
1.25 to 2.19 --------- --------- --------- --------- --------- --------- ACP15034DE
CPH Plugs for EBR Receptacles
Cable Dia., 30 Amp 60 Amp
Inches 2W, 3P 3W, 4P 2W, 3P 3W, 4P
.500 to .875 CPH3023B CPH3034B --------- ---------
.390 to 1.375 --------- --------- CPH6023BC CPH6034BC
EGS Electrical Group • 800-621-1506 • www.appletonelec.comPage 2 300880-1 Rev. E 01/15/2009