300880-4
INSTRUCTION SHEET
U.S. Patent No. 3,735,078
DBR Receptacles with Disconnect Switch:
30, 60, and 100 Amp.; Dust-lgnition-Proof.
Weatherproof Spring Cover, 600V A.C. Max.
Grounding thru Extra Pole and Shell
Class II, Div. 1 and 2
Groups F*, G
Class III
NEMA 3, 3R, 4X, 9F*G
DBR Enclosure has O-Ring
Gasket for Dust-Tight,
Rain-Tight Fit.
I. TO DISASSEMBLE RECEPTACLE INTERIOR
1. Remove polarizing screw and washer.
2. Rotate terminal holder counter-clockwise.
II. TO CONNECT CONDUCTORS TO RECEPTACLE
INTERIOR
1. Strip insulation from ends of individual conductors.
2. Loosen screws in pressure connectors and slide
prepared ends of conductors into the connectors,
observing proper polarity. Tighten screws.
III. TO REASSEMBLE RECEPTACLE INTERIOR
1.Insert Terminal Holder and turn clockwise until front end
is approximately 1/4” inside of casting surface.
Recessed radial depression in Terminal Holder must
be lined up with polarizing washer/locator. Replace
screw through the ground strip.
IV. POLARITY AND PHASE ROTATION
1. ACP CPH Plugs and EBRH Receptacle are polarized
so that the plug will enter the receptacle only one way.
2. Special Polarization: suffix – P4 added to catalog
number of the receptacle. Prevents plug insertion in a
receptacle wired for a different voltage.
V. Wiring
1. Conductors rom Receptacles are connected to the
Disconnect Switch as shown.
TERMINAL
HOLDER
Solderless lugs are provided for line connections and receptacle is prewired to the
load side of disconnect switch. Cover-mounted components leave entire enclosure
space free for pulling of line conductors and wiring.
POLARIZED SCREW
AND WASHER
PRESSURE
CONNECTORS
SCREW
DBR
1-1/2” threaded conduit
openings- one in top
and two in bottom
Plug is mechanically locked in receptacle when
switch is ON. Design provides interlocked connect
and disconnect operation.
Switch operating handle can be padlocked in
either “ON” or “OFF” position.
Dimensions of DBR Receptacles
CONDUIT OPENINGS
TAPPED 1-1/2”
C/L OF
CONDUIT OPENINGS
2.75”
7.0 CM
30 Amp 60 Amp 100 Amp 30 Amp 60 Amp 100 Amp
A 14.81" 14.81" 15.25" B 15.5" 17.06" 17.75"
(37.6cm) (37.6cm) (38.72cm) (39.4cm) (43.3cm) (45.1cm)
MOUNTING HOLES
FOR 3/8” DIA. BOLTS
1 1/2 - 11 1/2 NPT
TOP VIEW CONDUIT OPENING
BOTTOM VIEW
CONDUIT OPENING
1.75”
45 CM
3/4 - 14
NPT
3/4 - 14
NPT
TWO
THREADED
1 1/2 CONDUIT
OPENINGS
IN BOTTOM
3.00”
7.6 CM
A
C/L OF
CONDUIT OPENINGS
7.44”
18.9 CM
9.06”
23 CM
3.0”
76 CM
14.06”
35.7 CM
B
16.69”
42.4 CM
15.13”
38.4 CM
2.63”
6.7 CM
3.81”
9.7 CM
2.00”
5.1 CM
4.50”
11.4 CM
9.00”
22.9 CM
2.63”
8.7 CM
2.00”
5.1 CM
3.81”
9.7 CM
Dimensions Of Plugs in Inches
ACP Plugs for DBR Receptacles
No. Poles A B C D
30 Amp 2, 3, 4 6.00 4.75 3.13 1.86
60 Amp 2, 3 7 81 4.94 3.50 2.23
60 Amp 4 7.81 4.94 3.81 2.55
100 Amp 2, 3 10.50 6.63 4.00 2.47
100 Amp 4 10.50 6.63 4.25 2.72
CPH Plugs for DBR Receptacles
Max.
Amps. Wire/Pole A B C D E
30 2W, 3P; 3W, 4P 6.13 2.38 1.86 1.81 4.44
60 2W, 3P 8.44 3.06 2.23 3.31 5.69
60 3W, 4P 8.44 3.06 2.55 3.31 5.69
C
D
A
B
D C
B
E
A
CPH 30 Amp. Plug
CPH 60 Amp. Plug
CAUTION: To prevent Ignition
of hazardous atmospheres
do not use in Class II Group
F locations that contain elec-
trically conductive dusts.
Most coal dusts are not elec-
trically conductive.