Appleton Instruction Sheet: Appleton™ and O-Z/Gedney™ Explosionproof Junction Boxes and Cast Control Centers Field Drilling and Tapping, F6450 Manuals & Guides

F6450
INSTRUCTION SHEET
E85310/E84577
APPLETON™ AND OZ/GEDNEY™ EXPLOSIONPROOF JUNCTION BOXES AND
CAST CONTROL CENTERS FIELD DRILLING AND TAPPING INSTRUCTIONS
• Series JBEW explosionproof junction boxes are used where hazardous materials are handled or stored. These junction boxes may be used for terminals, splicing wires, pull boxes or bus boxes.
• Series CSEW explosionproof cast control centers are used where hazardous materials are handled and stored. Cast control centers allow for auxiliary devices, such as push buttons, switches, pilot devices, etc. to be installed into one enclosure to satisfy a wide range of control applications. The CSEW Series of enclosures have only been investigated and CLASSIFIED by Underwriters Laboratories as to explosion
and re hazards.
• Refer to the product nameplate for important information regarding the hazardous location rating, enclosure environmental rating, agency approval(s), and important safety information. Adhere to all warning and caution statements that may be located on the exterior or interior of the enclosure.
• Class I, Division 1 locations require a conduit seal to be installed in each conduit run within the specied distance noted on the product
nameplate.
• Unused conduit openings shall have a certied close-up plug installed that has the same hazardous location ratings as the enclosure. The close-up plug must engage a minimum of ve full threads.
• Only qualied personnel should install, inspect, and perform regular maintenance on the enclosure.
• Take extreme care not to damage the at-machined ange when opening the enclosure cover. Damaging the ange could affect the enclosure’s
integrity to protect the hazardous area.
• Dirt, grease, and other foreign material must not accumulate on the at-machined ange surface of the body and cover. The cover and body must
fully mate against each other to provide the proper protection to the hazardous area.
• Do not attempt to repair the cover gasket if damaged; contact factory for replacement. Remove damaged gasket and continue to use the
enclosure. The gasket does not affect on the enclosure’s safety for use in hazardous locations. However, the enclosure’s environmental rating(s)
will no longer be valid.
• Install only approved drain and/or breather ttings that have the same hazardous location ratings as the enclosure. Note, if a drain and/or breather tting are installed, care must be taken during hosedown operations. The enclosure may be watertight, but the drain and breather may
not be.
• Always keep the cover bolts tight to prevent ignition of hazardous atmospheres and disconnect circuits before opening cover.
• Perform all machining operations prior to installation of the enclosure.
• The enclosure shall be installed in accordance with all national and local electrical codes, and be acceptable to the Authority Having Jurisdiction.
• Since the conditions of use are outside of our control, the purchaser should determine the suitability of the enclosure for the intended use and
assumes all risk and liability in regards to the specic application.
INSTRUCTIONS TO MAINTAIN THE ENCLOSURE APPROVALS.
RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
MOUNTING INSTALLATION
!
WARNING
1. Enclosure may be furnished with or without drilled and tapped openings. Drilling and tapping of conduit and cover openings are subject to the limitations of maximum size, number of openings, and spacing. Perform all machining operations prior to installing enclosure. Refer to the drilling and tapping sections for additional information.
2. It is the responsibility of the installer to properly install the enclosure using the mounting feet supplied with the enclosure.
3. Mount the enclosure on a at surface capable of supporting the enclosure, controls devices, wiring, etc. For the approximate weight of enclosure,
reference TABLE 1.
4. Attach conduit system with seal tting(s) in accordance with the required distance stated on the product nameplate.
5. Remove cover bolts and set aside. Take extreme care not to damage the at-machined ange of the body and cover.
6. Pull wires into enclosure leaving enough length to make the required electrical connections.
7. To meet the NEC and CEC requirements for grounding of electrical equipment, install the grounding kit supplied with enclosure. Refer to
GROUND LUG INSTALLATION section for information on how to install the grounding kit.
8. Inspect and perform a continuity test for all electrical connections, including an insulation resistance testing for unwanted grounds.
9. Check cover and body at-machined anges for scratches and/or gouges before installing cover. Clean the anges and inspect the cover gasket
for damage.
10. Line up the cover and body bolt holes. Hand start the corner bolts rst, before installing the remaining cover bolts. Tighten cover bolts to the
required torque.
11. Cover must fully seat against the body ange to provide a proper explosion proof joint.
12. Seal conduits entering enclosure per the manufacturer’s installation instructions and the applicable national and local electrical codes.
TO AVOID RISK OF ELECTRICAL SHOCK TURN POWER OFF BEFORE INSTALLATION AND MAINTENANCE
F6450 Rev. 3 02/1/2017 • Page 1 of 4Appleton • 1.800.621.1506 • www.appletonelec.com
TABLE 1
JBEW / CSEW
Enclosures
030303 1-1/2 N/A 2.00 1.50 Short 1 1 1 6 030703 1-1/2 N/A 2.25 5.75 Short 2 1 2 9 031103 1-1/2 N/A 2.25 9.75 Short 3 1 3 11 031503 1-1/2 N/A 2.25 13.75 Short 5 1 5 15 031803 1-1/2 N/A 2.00 16.50 Short 6 1 6 17 032403 1-1/2 N/A 2.25 22.75 Short 9 1 9 22 033003 1-1/2 N/A 2.25 28.33 Short 11 1 11 26 033603 1-1/2 N/A 2.25 34.33 Short 13 1 13 35 040604 1-1/2 M40 2.25 4.25 Short 2 1 2 15 040805 3/4 N/A 3.13 6.50 Short 3 1 3 15 040903 1-1/2 M40 2.62 7.75 Short 3 1 3 21 041604 1-1/2 M40 2.75 14.75 Short 6 1 6 22 050903 1-1/2 M40 4.63 9.13 Short 8 2 4 21 060604 2 N/A 4.25 4.25 Short 2 1 2 20 060804 2 M50 4.25 6.25 Short 6 2 3 20 060806 2 M50 4.25 6.25 Short 6 2 3 20 061004 1-1/2 M40 5.75 10.38 Short 6 2 3 27 061204 2 M50 4.13 10.13 Short 8 2 4 25 061604 1-1/2 M40 5.50 13.06 Short 10 2 5 32 061806 3 N/A 4.50 16.50 Short 14 2 7 35 070804 2 N/A 4.25 5.88 Short 6 2 3 15 071106 2 M50 7.44 10.94 Short 12 3 4 35 080806 2 M50 6.25 6.25 Short 9 3 3 30 081006 2 M50 6.25 8.25 Short 6 2 3 36 081304 2 M50 5.38 10.63 Short 10 2 5 25 081307 2 M50 9.00 14.19 Short 15 3 5 30 091105 2 M50 9.38 11.13 Short 16 4 4 22 091504 2 M50 6.25 12.38 Short 15 3 5 33 101004 2 M50 7.19 7.19 Short 6 2 3 38 101006 4 M75 7.19 7.19 Short 6 2 3 44 101208 4 M75 8.50 10.50 Long 12 3 4 55 101406 4 M75 8.75 12.75 Short 20 4 5 55 101408 4 M75 8.75 12.75 Short 20 4 5 60 102408 4 M75 8.50 21.63 Long 24 3 8 120 111606 2 N/A 8.25 13.25 Short 12 3 4 85 112005 3 M75 8.25 17.13 Long 21 3 7 85 112406 3 M75 7.75 21.38 Long 27 3 9 72 113006 3 M75 7.63 26.25 Long 33 3 11 113 121206 4 M75 9.25 9.25 Short 12 3 4 65 121208 4 M75 9.25 9.25 Short 12 3 4 70 121806 4 M75 9.25 15.25 Short 18 3 6 90 121808 4 M75 9.25 15.25 Short 18 3 6 101 122408 4 M75 10.00 22.00 Long 27 3 9 138 123608 4 M75 9.50 33.25 Long 39 3 13 218 133806 4 M75 10.63 35.13 Long 56 4 14 190 141406 4 M75 11.00 11.00 Short 16 4 4 98 141408 4 M75 11.00 11.00 Short 16 4 4 105 141608 4 M75 11.25 13.25 Short 18 3 6 120 142408 4 M75 11.88 21.25 Long 40 5 8 131 142808 4 M75 11.25 24.81 Long 36 4 9 170 153707 4 M75 15.38 34.00 Long 65 5 13 250 161606 4 M75 13.25 13.25 Long 25 5 5 132 161608 4 M75 13.25 13.25 Long 25 5 5 140 161812 4 M75 14.75 16.75 Long 42 6 7 150 162005 2 M50 12.63 17.25 Short 30 5 6 98 162205 3 M75 13.00 19.00 Long 35 5 7 130 162206 2 M50 13.00 19.00 Long 35 5 7 130 162408 4 M75 13.25 21.25 Long 40 5 8 180 162805 3 M75 13.25 25.25 Long 50 5 10 188
NOTE: JBEW and CSEW catalog numbers may contain the prex “A”, “C” or “N”
Maximum Conduit
Opening Size
NPT Metric Width Length Wide Tall
Flat Machinable Area (in.)
CSEW Cover Openings
Control Operator
Barrel
Max. Number
of Operators
Number of Rows
Weight (lbs.)
Enclosure
Approx.
F6450 Rev. 3 02/1/2017 • Page 2 of 4Appleton • 1.800.621.1506 • www.appletonelec.com
Loading...
+ 2 hidden pages