Appleton FV Series Nonmetallic Fluorescent Luminaires, 650416001 Instruction Sheet

650416-001
INSTALLATION INSTRUCTIONS FOR
FV SERIES FLUORESCENT FIXTURES
INSTALLATION INSTRUCTIONS FOR FV SERIES FLUORESCENT FIXTURES
IMPORTANT: this xture is designed for permanent installation in Class I, Div. 2, Groups A, B, C & D, Class I, Zone 2, Group
IIC, Class II, Group F & G, Marine Outside Type (Salt Water), Type 4X and Wet locations in accordance with the National Electric Code and all applicable local codes. Marine Outside (Salt Water) Rating is not applicable for fi xtures that include fusing.
DO NOT OPEN OR REMOVE FIXTURE WHILE IT IS ENERGIZED. DO NOT USE FIXTURE ON UNGROUNDED CIRCUITS. Failure to ground this xture can result in electrical shock which
may be fatal. DO NOT use in areas of limited ventilation or in high ambient areas (above 55°C for FVR 240 models or 40°C for all other models).
• Lens should be cleaned periodically for maximum light output.
SURFACE MOUNT - FVSM.
1. Attach the mounting brackets to the back of the housing using
2. Mount the fi xture, with mounting brackets installed, directly to the ceiling or to any structural support member that can handle the weight of the fi xture in accordance with local building code and all applicable local codes.
3. Once the fi xture is securely mounted in place, open the fi xture lens by rotating actuator counter-clockwise to release the fi xture lens from the locking mechanism. Refer to wiring page 2.
4. Hinge the refl ector to one side by pulling down on the refl ector on the side where the two red tabs call be seen that hold the refl ector in position. Refer to wiring page 2.
CHAIN MOUNT - FVCM
1. Attach the chain mounting brackets by threading them into
the holes on the back of the fi xture. Tighten against the back of the fi xture housing but, make sure not to over-tighten as dam- age to the fi xture housing may occur.
2. Attach chain (not supplied) to chain mounting brackets.
3. Attach chain to structural support member in area to be
installed.
4. Once the fi xture is securely mounted in place, open the fi xture lens by rotating the actuator counter-clockwise to release the xture lens from the locking mechanism.
5. Hinge the refl ector to one side by pulling down on the refl ector on the side where the two red tabs call be seen that hold the refl ector in position. Refer to wiring page 2.
FVSM
Actuator
SEE BRACKET DIMENSIONS ON PAGE 2
FVCM
Actuator
FVWFM
45 ° FIXED WALL MOUNT FVWFM
1. Attach the 45° wall mounting brackets to the back of the hous-
ing using hardware supplied as shown in Figure 1, NOTE: Use screws supplied with fi xture.
2. Mount the fi xture with mounting brackets installed directly to the wall or to any structural support member that can handle the weight of the fi xture in accordance with all applicable local codes.
3. Once the fi xture is securely mounted in place, open the fi xture lens by rotating the actuator counter-clockwise to release the xture lens from the locking mechanism.
4. Hinge the refl ector to one side by pulling down on the refl ector on the side where the two red tabs call be seen that hold the refl ector in position, Refer to wiring page 2.
EGS Electrical Group • 800-621-1506 • www.appletonelec.com Rev. D 03/20/2012 Page 1
FIGURE 1
SCREW AND
WASHER
Actuator
ADJUSTABLE WALL MOUNT - FVWAM
1. Attach the adjustable wall mounting brackets to the back of the
housing, Using hardware supplied, as shown in Figure 2.
2. Mount the fi xture, with mounting brackets installed, directly to the wall or to any structural support member that can handle the weight of the fi xture in accordance with local building code and all applicable local codes.
3. Once the fi xture is securely mounted in place, open the fi xture lens by rotating the actuator counter-clockwise to release the xture lens from the locking mechanism.
4. Hinge the refl ector to one side by pulling down on the refl ec- tor on the side where the two red tabs can be seen that hold the refl ector in position. Refer to wiring.
FVWAM
FIGURE 3
FIGURE 2
ACTUATOR
WIRING AND RELAMPING
TO OPEN FIXTURE
1. Once the xture is securely mounted in place, open the x-
ture lens by rotating the actuator counter-clockwise to release the fi xture lens from the locking mechanism.
2. Hinge the refl ector to one side by pulling down on the refl ec- tor on the side where the two red tabs can be seen that hold the refl ector in position. (See illustration below and at right ).
WIRING OF FIXTURE
1. Pull supply wires through conduit system and into the lighting
xture. Use supply wire rated at least 75° C.
2. Ground wire, if present should be secured inside the cup washer with the ground screw located on the hub plate. Refer to Figure 4.
3. Connect the black and white leads from the conduit to proper ballast leads.
4. If fi xture contains an optional terminal block, connect the black, white and ground leads from the conduit to the proper terminals on the terminal block. Likewise, similar connections are to be made for fi xtures that contain optional fusing.
5. Close the refl ector by pushing it back up into place until it snaps over the posts on the lampholder bracket locking it in place.
6. Install lamps, checking both lamp type and wattage for proper lamp. Make sure to secure the opposite ends of the lamps in place in the lamp clips (FVP only) attached to the fixture reflector, as shown in figure 6.
7. Secure the lens by swinging it back up into place until the lens gasket touches the fi xture lousing. Then rotate the actuator clock- wise to secure lens in the closed position.
8. Power can now be applied to the fi xture. Note that the fi xture lamps will only light when the fi xture lens is secured in the "closed" position.
A B
MIN 7.5" MAX 9.50"
Disassemble bracket assembly to attach hinge bracket to fi xture then reassemble and hang fi xture.
2. Hinge refl ector to one side by pressing refl ector release tabs with a small screw driver to release refl ector .
FIGURE 4
FIGURE 5
NOTE: Terminal block positions
are labeled.
M8 Screw supplied with Fixture
Page 2 Rev. D 650416-001 03/20/2012 EGS Electrical Group • 800-621-1506 • www.appletonelec.com
RELAMPING
RELAMPING INSTRUCTIONS FOR 40 WATT PL-L LAMPS: FIGURE 6
1. Rotate the actuator counter-clockwise to release the xture
lens from the locking Mechanism. NOTE: The power will be disconnected from The lampholders once the fi xture lens is open.
2. Remove lamps from the fi xture by carefully pulling down on lamps from the end to free from lamp clips; lamps can now be removed by pulling outward away from lampholder.
3. Install new lamps by inserting lamp pins into lampholder fi rst then carefully pushing lamp end into lamp clip.
4. Secure the lens by swinging it back up into place until the lens gasket touches the fixture housing then, rotate the actuator clockwise to secure lens in the closed position.
5.Power can now be applied to the xture. NOTE: The xture lamps will only light when the xture lens is
secured in the ÒclosedÒ position.
RELAMPING INSTRUCTIONS FOR FOUR FOOT (HO) T8 & T12 LAMPS:
1. Rotate the actuator counter-clockwise to release the xture
lens from the locking mechanism. NOTE: The power will be dis­connected from the lampholders once the fi xture lens is open.
2. Remove lamps from the fi xture by pushing inward (toward) spring-loaded lampholder and then remove lamp end from rigid socket at opposite end of fi xture.
3. Replace lamp with lamp of proper wattage and size.
4. Reassemble lamps by following steps 1 through 3 in reverse
order.
5. To secure lens and apply power follow steps 4 & 5 from PL-L relamping instructions.
FIGURE 6
BRACKET MOUNTING DIMENSIONS
FIGURE 7
5/16” DIA.
13/64” DIA.
15/16”
2-3/8”
8-1/4”
5/16” DIA.
13/64” DIA.
5
/16” DIA.
4-1/8”
1
Fixed Surface Mount FVSM
14 GA.Stainless Steel
9-1/2”
FIGURE 8
45° Fixed Wall Mount Bracket for Fixture FVWFM
11 GA. (1/8") Stainless Steel
FIGURE 9
Chain Ring Bolts for Fixture FVCM
Set of 2 Zinc Plated M8 Steel Ring Bolts for suspended Units Internal Dia. 20mm
EGS Electrical Group • 800-621-1506 • www.appletonelec.com Rev. D 650416-001 03/20/2012 Page 3
SINGLE BALLAST LAYOUT (2 FT., 2 LAMP PL-L LAMPS)
TERMINAL BLOCK (OPTIONAL)
SAFETY SWITCH
RED SAFETY LOCK TAB
DOUBLE BALLAST LAYOUT (4 LAMP PL-L LAMPS)
TERMINAL BLOCK (OPTIONAL)
NOTE: Terminal block positions are labeled. (SEE PAGE 2)
SAFETY SWITCH
RED SAFETY LOCK TAB
FUSE BLOCK
(OPTIONAL)
FUSE BLOCK
(OPTIONAL)
BALLAST (SINGLE)
RED REFLECTOR SAFETY LOCK TAB
TWO BALLAST
RED REFLECTOR SAFETY LOCK TAB
DIMENSIONS
0.6"
5.7"
8.6"
Standard Materials
Housing: Fiberglass reinforced polyester.
• Lens: Polycarbonate.
• Gasket: Elastomer.
Hubs: Stainless Steel (3/4" NPT). One on each side
of fi xture.
• Lampholders: Polycarbonate.
• Internal Refl ectors Highly Refl ective White Polycarbonate.
Standard Finishes
Housing: White color fi nish.
HOUSING
LENS
TWO FOOT FIXTURE 15.8" 30.7" FOUR FOOT FIXTURE 27.6" 54.7"
A B
Compliances:
• FV Series: Class I, Div. 2,Groups A,B,C,D.
• Class II, Div. 2, Groups F & G.
• Class 1 Zone 2, Group IIC.
• Wet Locations.
• Type 4X.
• UL844
• UL1598 and 1598A
• Marine Outdoor Type (Salt Water). Except fi xtures containing fusing.
Page 4 Rev. D 650416-001 03/20/2012 EGS Electrical Group • 800-621-1506 • www.appletonelec.com