Appleton FSQC Series Receptacles and Powertite Plugs Catalog Page

FSQC 30, 60 and 100 Amp Series Receptacles and Powertite™ Plugs
NEMA 3, 3R, 4 and 4X Rated Interlocked Disconnect Switch
600 Vac Max. 250 Vdc Max.
NEC/CEC:
Class I, Division 1 and 2, Groups B, C, D Class II, Division 1 and 2, Groups F, G Class III NEMA 3, 3R, 4, 4X, 7CD, 9FG
Applications
— Lighting systems — Conveyors — Heaters — Motor-generator sets — Air conditioners — Compressors — Pumps
• Locations where damp or corrosive conditions exist
• Class I: classied locations such as: — Petrochemical plants — Petroleum reneries — Paint and chemical plants — Any location where ignitable vapors or gases are present
• Class II: classied locations such as: — Process industries where there are dust hazards from
handling such products as our, grain and starch or any  location where ignitable amounts of dust are present or  amounts which would adversely affect performance
Features
• Large housing provides ample wiring room.
• Style 2 (shell and extra pole) grounding.
• Spring door keeps dust out of receptacle when plug is not in use.
• Brass contacts exert constant pressure along entire contact surface and provide superior electrical contact.
• Contacts have beryllium copper wire springs.
• Insulators provide superior dielectric and mechanical strength and lowest arc tracking.
• Tapped NPT conduit openings at top and bottom: 30 Amp 3/4”, 60 Amp 1-1/2”, 100 Amp 2”.
Interlocked” Disconnect Switch” provides safe connect and disconnect operation at 30, 60 or 100 Amp, 600 Vac maximum, three pole, non-fused motor circuit switch. FSQC permits safe operation in Class I, Group B as well as Class I, Groups C and D, Class II, Groups F, G, and Class III.
• To operate, insert plug and turn receptacle face to ON” position. To remove plug, turn to OFF position and pull plug out.
• ACP Powertite™ Series plug ts hazardous location FSQC receptacles.
• Both ip and screw covers are provided. 
Standard Materials
• Receptacle and mounting box: copperfree (4/10 of 1% max.) aluminum
• ACP plugs: copperfree (4/10 of 1% max.) aluminum housings
• Insulating blocks: ber glass reinforced polyester
Standard Finishes
• Receptacles, mounting boxes, cord connector housings and caps: epoxy powder coat
30 Amp
Shown with Flip Lid
Cover
60 Amp
Shown with Screw
Cap Cover
Options
• Special Polarization: Prevents plug insertion in a receptacle or connector wired for a different voltage. In installations where there are different line voltages, the special polarization option is desirable. This allows only plugs and receptacles wired for the same line voltage to be mated together. The receptacle or connector interior is positioned 22-1/2°, relative to the polarization rivet, to the right (as specied) of standard, and plug is polarized to correspond. This option can be added to receptacles using the Powertite™ Plug. Add sufx -P4 to receptacle or plug.
• Auxilary contacts 1NO + 1NC. Add sufx -AUX to receptacle.
NEC/CEC Cetifications and Compliances
• UL Standard: UL 1010 (UL 1203), UL 894, UL 1682, UL 1686
• UL Listed: E10784
• CSA Standard: C22.2 No. 25, C22.2 No. 30, C22.2 No. 159
• CSA Certied: 025875
100 Amp
Plugs and RecePtacles: nec/cec HazaRdous location
Shown with Flip Lid
Cover
Receptacle is rated NEMA 4 when mated with a Powertite™ Plug. When not mated, leave the flip cover installed for NEMA 3, 3R rating, or install screw cover
for NEMA 4, 4X rating.
Classified by UL and Certified by CSA for use in specific combinations with Crouse-Hinds Arktite. Arktite is a registered trademark of Cooper Crouse-Hinds.
425
FSQC 30, 60 and 100 Amp Series Receptacles and Powertite™ Plugs
NEMA 3, 3R, 4 and 4X Rated Interlocked Disconnect Switch
600 Vac Max. 250 Vdc Max.
NEC/CEC:
Class I, Division 1 and 2, Groups B, C, D Class II, Division 1 and 2, Groups F, G Class III NEMA 3, 3R, 4, 4X, 7CD, 9FG
Amp
30 3/4 or 1 3W, 4P #10 - #8 FSQC3430 ACP3034BC
60 1-1/2 3W, 4P #6 - #4 FSQC5640 ACP6034BC
100 2 3W, 4P #2 - 1/0 FSQC61040 ACP1034CD
ACP Plugs
Wire/Poles Cable Dia. (Inches) 30 Amp 60 Amp 100 Amp
3W, 4P
Maximum Horsepower Ratings of Switch
Phase Amps 120 Vac 240 Vac 480 Vac 600 Vac
Three
Hub Size
(Inches)
0.500 to 1.250 ACP3034BC ACP6034BC ––
0.875 to 1.906 –– –– ACP1034CD
30 3 7.5 15 20
60 10 25 30
100 10 30 60 75
Wire/Poles
Terminal Block
Wire Range
Receptacle Catalog
Number
Mating Plug Powertite™
ACP Plug Dimensions in Millimeters (Inches)
Max. Amp A B C D
30 152.4 (6.00) 120.6 (4.75) 79.5 (3.13) 47.2 (1.86)
Plugs and RecePtacles: nec/cec HazaRdous location
Receptacle is rated NEMA 4 when mated with a Powertite™ Plug. When not mated, leave the flip cover installed for NEMA 3, 3R rating, or install screw cover
for NEMA 4, 4X rating.
Receptacle insulator and contacts are not serviceable.
60 198.3 (7.81) 125.4 (4.94) 88.9 (3.50) 56.6 (2.23)
100 26.7 (10.50) 168.4 (6.63) 101.6 (4.00) 62.7 (2.47)
426
Loading...
+ 1 hidden pages