Appleton Code•Master™ Jr. LED Factory Sealed Luminaires Catalog Page

Code•Master™ Jr. LED Factory Sealed Luminaires
LED/AREA: NEC/CEC EXPLOSIONPROOF
© April 2019
Explosionproof, Dust-Ignitionproof
For use with threaded metal conduit.
NEC/CEC:
Class I, Division 1, Groups B, C, D Class II, Division 1, Groups E, F, G Class III Zone 1, Ex db IIB + H2 NEMA 3R, 4X
NEC/CEC:
Suitable for use in Wet Locations Marine Outside Type (Salt Water)
Applications
• For use in chemical and petrochemical plants, such as
manufacturers of plastics, paints and thinners, in reneries,
and in other areas where ignitable vapors, dust, moisture and corrosive elements may be present.
• Suitable for outdoor saltwater locations and for other wet locations.
Features
-40°C to +55°C (-40°F to +131°F) for CJLL1 and CJLL2;
-40°C to +40°C (-40°F to +104°F) for CJLL3.
Nominal Lumens
1,600 100W 50W CJLL1 3,000 300W 70-100W CJLL2 5,150 100-150W CJLL3
• Acme double-lead threads speed installation of xture into the
mounting hood to make electrical connection.
• The only wiring required is attaching two wires to connection
block in mounting hood. Also allows safe, easy servicing without
disconnecting any wires.
• Heat- and impact-resistant globes have smooth dust-resistant exterior.
• Optional guards protect globes from damage. Secured to xture
with three stainless steel screws.
• Choice of mountings: pendant, ceiling, bracket and stanchion.
• Fiberglass-reinforced polyester reectors, in standard dome
or 30° angle styles, are ideal in installations where luminaire is subject to exceptionally severe corrosive atmospheres.
• All threaded joints are ame-tight.
• Universal, high efcient drivers cover voltage requirements for
120-277 Vac 50/60 Hz, 100 – 300 Vdc for CJLL1 and CJLL2; 120-277 Vac 50/60 Hz, 125 – 300 Vdc for CJLL3; 347-480 Vac 50/60 Hz for CJLL3.
Incandescent
Equivalent HID Equivalent Model Number
Options
• Aluminum guard available, purchase separately
Standard Materials
• Fixture housing, mounting hoods and guards: copperfree (4/10 of 1% max.) aluminum
• Globes: prismatic glass
• Reectors: berglass reinforced polyester
Standard Finishes
• Fixture housing, guards and mounting hoods: epoxy power
coat nish, electrostatically applied for complete, uniform
corrosion protection
NEC/CEC Certifications and Compliances
• UL Standard: UL1598 (4th Ed.), UL1598A (1st Ed.), UL8750 (2nd Ed.), UL844 (13th Ed.)
• CSA Standard: CSA C22.2 No. 250.0-08, CSA C22.2 No. 137-18, CSA C22.2 No. 60079-0, and CSA C22.2 No 60079-1
• UL Listed: E10444
Related Products
• CodeMaster LED
• CodeMaster Incandescent
• A-51™ LED
For Group B applications, a Group B rated mounting hood must be used.
1
Code•Master™ Jr. LED Factory Sealed Luminaires
LED/AREA: NEC/CEC EXPLOSIONPROOF
© April 2019
Explosionproof, Dust-Ignitionproof
For use with threaded metal conduit.
NEC/CEC:
Class I, Division 1, Groups B, C, D Class II, Division 1, Groups E, F, G Class III Zone 1, Ex db IIB + H2 NEMA 3R, 4X
Pendant
One Hub 3/4” NPT
CAP75
CAP75B
NEC/CEC:
Suitable for use in Wet Locations Marine Outside Type (Salt Water)
Ceiling
Four Hubs
Three Close-Up Plugs
3/4” NPT
CAC75
CAC75B
Bracket
Four Hubs
Three Close-Up Plugs
3/4” NPT
CALB75
CALB75B
Code•Master Jr. LED Fixture Unit
CJLL
25° Stanchion
One Hub
1-1/4 or 1-1/2” NPT
CAS150
CAS150B
Optional Standard Dome
KR2-ST
Optional Aluminum
For Group B applications, a Group B rated mounting hood must be used.
Guard
CJGU-15
Optional Three Way Exit Sign
CJEXRN
(not UL Listed)
Optional Angle Reflector
KR2-AN
2
Code•Master™ Jr. LED Factory Sealed Luminaires
LED/AREA: NEC/CEC EXPLOSIONPROOF
© April 2019
Explosionproof, Dust-Ignitionproof
For use with threaded metal conduit.
NEC/CEC:
Class I, Division 1, Groups B, C, D Class II, Division 1, Groups E, F, G Class III Zone 1, Ex db IIB + H2 NEMA 3R, 4X
Order using catalog numbering guides below or select catalog number from tables on following pages.
CJL A L1 2 C BU G
Series:
CJL – Code•Master
Jr. LED
Mounting Hood: A – Pendant W – Wall Bracket C – Ceiling S – 25° Stanchion Blank – No Mounting Hood
NEC/CEC Temperature Codes
Model
CJLL1 90 (194)
CJLL2 90 (194)
Use Wire Supply
°C (°F)
NEC/CEC:
Suitable for use in Wet Locations Marine Outside Type (Salt Water)
Lumen Output
(nominal):
L1 – 1600 L2 - 3000 L3 - 5150
2 - 3/4” NPT 3 - 1” NPT 4 - 1-1/4” or 1-1/2” NPT
Blank - No hub size needed if
Hub Size:
stanchion
no mounting hood
Ambient Temperature
°C (°F)
40 (104)
55 (131)
40 (104)
55 (131)
Color
Temperature: C - Cool, 5000K W - Warm, 3000K
BU - 120-277 Vac,
BH - 347-480 Vac,
Class I, Division 1, Groups B, C and D
T6 T6
T6 T6
Options: G – Guard Blank – No Guard
Voltage:
50/60Hz; or 100-300 Vdc
50/60Hz
Class II, Division 1,
Groups E, F and G
CJLL3 90 (194) 40 (104)
“T” Numbers Represent the Maximum External Temperature for Class I, Division 1 Locations and Maximum Surface Temperature Under Dust Blanket for Class II, Division 1 Locations.
“T”
Number
Temp
Range
(°C)
Temp
Range
(°F)
NOTE: The maximum operating temperature of the fixture must not exceed the ignition temperature of the gas, vapor or dust to be encountered per the National
For Group B applications, a Group B rated mounting hood must be used.
Only for L1 and L2 models, 125–300 Vdc for L3 model.
Only for L3 models.
T1 350 325 T2 T2A T2B T2C T2D T3 T3A T3B T3 T4 T4A T5 T6
351-
326-
301-
281-
261-
231-
216-
201-
181-
450
350
325
300
280
664-
619-
574-
538-
842
662
617
Electrical Code and the Canadian Electrical Code.
572
502-
536
260
448-
500
230
421-
446
215
394-
419
200
358-
392
166-
180
331-
356
T6 T6
161-
136-
121-
165
322-
329
160
277-
320
135
250-
275
101-
120
214-
248
86-
100
187-
212
85
185
3
Code•Master™ Jr. LED Factory Sealed Luminaires
LED/AREA: NEC/CEC EXPLOSIONPROOF
© April 2019
Explosionproof, Dust-Ignitionproof
For use with threaded metal conduit.
NEC/CEC:
Class I, Division 1, Groups B, C, D Class II, Division 1, Groups E, F, G Class III Zone 1, Ex db IIB + H2 NEMA 3R, 4X
Electrical Specifications (are within +/-10%)
Model
Number Voltage
120 Vac 13 0.11 >.9 <20%
277 Vac 14 0.05 >.9 <20%
CJLL1
100 Vdc 13 0.13 N/A <20%
300 Vdc 14 0.05 N/A <20%
120 Vac 26 0.22 >.9 <20%
277 Vac 27 0.10 >.9 <20%
CJLL2
100 Vdc 26 0.26 N/A <20%
NEC/CEC:
Suitable for use in Wet Locations Marine Outside Type (Salt Water)
Input Power
(Watts)
Input Current
(Amps)
Power Factor
(PF)
Total Harmonic
Distortion (THD)
CJLL3
300 Vdc 27 0.09 N/A <20%
120 Vac 48 0.40 >.9 <20%
277 Vac 47 0.18 >.9 <20%
125 Vdc 48 0.38 N/A <20%
300 Vdc 47 0.16 N/A <20%
347 Vdc 49 0.15 >.9 <20%
480 Vdc 49 0.11 >.9 <20%
For Group B applications, a Group B rated mounting hood must be used.