Appleton CODE•MASTER 2™ FLOOD LUMINAIRE Instruction Sheet

654028-001
INSTRUCTION SHEET
INSTALLATION AND MAINTENANCE INSTRUCTIONS
CODE•MASTER 2™ AND CODE•MASTER 2™ FLOOD LUMINAIRE
Read carefully before attempting to install fi xture.
Class I, Div. 1 and 2, Groups C, D Class II, Div. 1 Groups E,F, G Class II, Div. 2 Groups F, G Class III
UL 1598A, 844 Suitable for Use in Wet Locations
U.S. Pat. 3,170,750 Pat Can 1968
Code•Master 2™ and Code•Master 2™ Flood Factory Sealed Fixtures: Explosion-Proof, Dust-Ignition-Proof; 50W-400W
High Pressure Sodium: High Power Factor (Min.P.F. 90%), Metal Halide and Mercury Vapor: Constant Wattage (Min P.F. 90%), Pulse Start Metal Halide: Super CWA (Min. P.F. 90%).
Applications
• Ideal for use in chemical and petrochemical plants such as manufacturers of plastics, paints and thin­ners in refi neries, and in other process areas where ignitable vapors, dust, moisture and corrosive ele­ments may be present.
• Suitable for use in wet locations.
Features
• Fixtures operate safely in high ambient tempera­tures. For example, in Class I areas the 150W HPS fi xture operates at a maximum temperature of 120˚C in a 65˚C ambient (100˚C temperature in a 40˚C ambient). See page 4 for specifi c ratings.
• Arrangement of heat-producing components results in more effi cient heat dissipation for cooler fi xture operations.
• Patented “wireless” design. Threading of fi xture unit
onto mounting hood makes electrical connection. Only wiring required is attaching two wires to con­nection block in mounting hood.
• Connection block is easily wired: (a) loosen two screws. (b) make wire connections (c) re-position connection block.
• Safe, easy servicing without disconnecting any wir­ing. “Wireless” fi xture unit easily threads off mount- ing hood for convenient servicing or for immediate replacement with a “stand-by” unit.
• Acme double lead threads speed installation and xture removal from mounting hood-only half as many turns are required as for single lead threads.
Rev. E 09/27/04 Page 1
DIMENSIONS:
PENDANT
CEILING
BRACKET
25û STANCHION
Classifi ed Area Suitability of Code•Master 2™ Series HID Fixtures (Suitability includes use of re ector.)
Class I, Div. 1 & 2 With † Class II, Div. 1 & 2 Globe or with Globe & Refl ector With Globe or with UL/NEC Temp. Ident. No. Globe & Refl ector
Nameplate Marking
UL/NEC Temp. Ident. No.
Lamp Lamps Supply Ambient Code•Master Code•Master Nameplate Type Watts Wire ˚C Temp ˚C 2 Flood Groups Marking Groups
50 60 40 T5 T5 C,D T4 E,F,G 50 75 55 T4A C,D — — 50 85 65 T4A C,D —
70 60 40 T5 T5 C,D T4 E,F,G 70 75 55 T4A C,D — — 70 85 65 T4A C,D —
High 100 60 40 T5 T5 C,D T4 E,F,G Pressure 100 75 55 T4A C,D — Sodium 100 85 65 T4A C,D —
150 60 40 T5 T5 C,D T3A E,F 150 75 55 T4A C,D — — 150 85 65 T4A C,D —
250 75 40 T3C T4 C,D — — 250 85 55 T3C C,D — —
400 85 40 T3C T3A C,D — —
175 75 40 T4 T3B C,D T3C E,F,G
Metal Halide 250 75 40 T4 T3B C,D T3A E,F
400 75 40 T3C T3 C,D — —
100 75 40 T3C T3A C,D T3B E,F,G
Mercury Vapor
175 75 40 T3C T3A C,D T3A E,F
250 75 40 T3C T3A C,D T3 E,F
400 85 40 T3A T2D C,D — —
175 75 40 T4 T3B C,D T3C E,F,G
Pulse Start Metal Halide
250 75 40 T4 T3B C,D T3A E,F
320 75 40 T3C T3 C,D —
350 75 40 T3C T3 C,D — —
400 75 40 T3C T3 C,D — —
NOTE: The maximum operating temperature of the fi xture must not exceed the ignition temperature of the gas, vapor or dust to be encountered per NEC 500-2(c). For ignition temperatures, see Cat. Sec. F1.
Applies to Code•Master 2 Only.
“T” Numbers Represent the Maximum Surface Temperature for Class I, Div. 1 Locations and Maximum Surface Temperature Under Dust Blanket for Class II, Div. 1 Locations.
“T” Number
T1 350 325 T2 T2A T2B T2C T2D T3 T3A T3B T3C T4 T4A T5 T6
Temp. Range (˚C) 351-450 326-350 301-325 281-300 261-280 231-260 216-230 201-215 181-200 166-180 161-165 136-160 121-135 101-120 86-100 85
Type Refl ector A B C
Dimensions In Inches
Standard Dome 11.2 5.9 18.7 Deep Dome 10.56 7.0 17.5
Pendant Ceiling Bracket 25° Stanchion
A B C A B C A B C A B C
Dimensions In inches
50-250W* 21.5 20.5 12.0 21.61 20.61 12.0 21.86 20.86 17.5 19.5 18.7 16.0
250-400W 24.5 23.5 12.0 24.36 23.36 12.0 24.61 23.61 17.5 22.2 21.2 17.5
*50, 70, 100 and 150W HPS; 175 and 250W MH; and 100, 175 and 250W MV; 250 and 400W HPS and 400W MH and MV and 175, 250, 320, 350, 400W PSMH.
age 2 654028-001
P
Rev. E 09/27/04
Loading...
+ 2 hidden pages