Appleton Code•Master™ 2 Emergency PLT Factory Sealed Luminaires Catalog Page

Code•Master™ 2 Emergency PLT Factory Sealed Luminaires
FLUORESCENT/AREA: NEC/CEC EXPLOSIONPROOF
Explosionproof, Dust-Ignitionproof
52 W, 64 W, 84 W Fluorescent. For Use with Threaded Metal Conduit.
NEC:
Class I, Division 1 and 2, Groups C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 4X Marine Type Electric Fixtures
NEC:
Outside Type (Salt Water) Suitable for use in Wet Locations NFPA101, Life Safety Code
Applications
• Ideal for use in chemical and petrochemical plants, such as
manufacturers of plastics, paints and thinners; in reneries; and
• Suitable for use in wet locations.
Features
• Auxiliary (emergency) lighting should be used to provide a lighted means of egress for personnel in walkways, catwalks, stairs, doorways, tunnels, ramps and aisles.
• Auxiliary (emergency) lighting should be used to provide “instant on” illumination during power failures.
• Arrangement of heat-producing components results in more
efcient heat dissipation for cooler xture operation.
• Safe, easy servicing without disconnecting any wiring. Patented
“wireless” design means the threading of the xture unit onto
mounting hood makes electrical connection. This allows for the
xture unit to easily thread off mounting hood for convenient
servicing or for immediate replacement with a “stand-by” unit. Only wiring required is attaching two wires to connection block in mounting hood.
• Connection block is easily wired: (a) loosen two screws; (b) make wire connections; and (c) reposition connection block.
• Acme double-lead threads speed installation and xture
removal from mounting hood – only half as many turns are required as for single-lead threads. The threads do not stick or gall, eliminating the troublesome problems often encountered
with single-lead threads during xture unit removal.
• All threaded joints are ame-tight.
• Factory sealed. External seals not required.
• Fluorescent light source reduces energy costs.
• Fluorescent lamp life of 10,000 hours reduces relamping costs compared to incandescent.
• Strategic location of lamp sockets in combination with the interior prism design of the glass globe provides optimum light distribution and control.
• Superior corrosion resistance with epoxy powder coat nish.
• Choice of mountings: pendant, ceiling, bracket and stanchion.
• Fiberglass-reinforced polyester reectors in standard
dome, deep dome or 30° angle are ideal in installations where luminaire is subject to exceptionally severe corrosive
atmospheres. The high bay aluminum reector is designed for
installations where mounting height work planes range from 6 to 9 m (20 to 30 ft).
• Optional guards protect globes from damage. Guards secure to
xture with three screws.
• Fixture (52, 64 or 84 W) is available for semi-continuous operation (one AC ballast permits two-lamp illumination when power is on and one battery pack permits one-lamp illumination when AC power is interrupted).
• Minimum operating temperature: 0 °C (32 °F).
• Maximum operating temperature: 40 °C (104 °F).
Battery Pack Information
• Long life, high temperature, nickel-cadmium (Ni-Cad) battery.
• Dual voltage (120/277 V, 60 Hz) solid state charger on open circuit board.
• Five-year life expectancy.
• Wiring instructions for “Push-To-Test” button are supplied
with xture.
Illustrated Features
• Remote EEFDB factory sealed “Push-To-Test” station is available to verify emergency operation (order separately).
• Red indicator light is provided with each battery pack to indicate when the battery is charging.
Standard Materials
• Ballast bodies, guards and pendant mounting hoods: copperfree (4/10 of 1% max.) aluminum
• Ceiling, bracket and stanchion mounting hoods: sand-cast copperfree (4/10 of 1% max.) aluminum
• Reectors: aluminum or berglass reinforced polyester
Standard Finishes
• Ballast bodies, guards and mounting hoods: epoxy powder
coat nish, electrostatically applied for complete, uniform
corrosion protection
Options
• Fuse kit CF2 for eld installation.
NEC Certifications and Compliances
• UL Standard: UL 924, UL 844, UL 1598
• UL Listed: E165014
487
Code•Master™ 2 Emergency PLT Factory Sealed Luminaires
FLUORESCENT/AREA: NEC/CEC EXPLOSIONPROOF
Explosionproof, Dust-Ignitionproof
52 W, 64 W, 84 W Fluorescent. For Use with Threaded Metal Conduit.
NEC:
Class I, Division 1 and 2, Groups C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 4X Marine Type Electric Fixtures
Classified Area Suitability of Code•Master 2 Emergency Series (Suitability includes use of reflector)
301-
325
574-
617
Ambient
Temp ˚
°C (°F)
281-
300
538-
572
Lamp
Type
PLT
“T” Numbers Represent the Maximum Surface Temperature for Class I, Division 1 Locations and Maximum Surface Temperature Under Dust Blanket for Class II, Division 1 Locations.
“T”
Number
Temp.
Range
Temp.
Range
351-
(°˚C)
664-
(°F)
Lamps
Watts
52 40 (104)
64 40 (104)
84 40 (104)
T1 350 325 T2 T2A T2B T2C T2D T3 T3A T3B T3C T4 T4A T5 T6
326-
450
350
619-
842
662
NEC:
Outside Type (Salt Water) Suitable for use in Wet Locations NFPA101, Life Safety Code
Class I, Division 1 and 2
With Globe or with Globe and Reflector
UL/NEC Temp. Ident. No.
Nameplate
Marking Groups
T6 C, D T4 E, F, G
T6 C, D T4 E, F, G
T6 C, D T4 E, F, G
261-
280
502-
536
231-
448-
260
500
216-
230
421-
446
201-
215
394-
419
181-
200
358-
392
166-
180
331-
356
With Globe or with Globe and Reflector
Nameplate
Marking Groups
161-
136-
165
160
322-
277-
329
320
Class II, Division 1 and 2
UL/NEC Temp. Ident. No.
121-
101-
120
214-
248
86-100 85
187-
135
250-
275
212
185
Fixture and Accessory Weights in kg (lb)
Fixture Size Fixture Weight Reflector Weight Guard Weight
52 W 20.4 (44.97) 1.4 (3.09) 0.9 (1.98)
64 W 20.4 (44.97) 1.4 (3.09) 0.9 (1.98)
84 W 20.4 (44.97) 1.4 (3.09) 0.9 (1.98)
Mounting Hood Weights kg (lb)
Pendant Ceiling Bracket Stanchion
0.9 (1.98) 1.8 (3.97) 2.7 (5.95) 0.9 (1.98)
Electrical Specification for AC Operation
Fixture
Wattage
52 120 60 PLT Electronic 0.49 52 CMBFS5212
52 277 60 PLT Electronic 0.20 52 CMBFS5227
64 120 60 PLT Electronic 0.57 64 CMBFS6412
64 277 60 PLT Electronic 0.24 64 CMBFS6427
84 120 60 PLT Electronic 0.73 84 CMBFS8412
84 277 60 PLT Electronic 0.31 84 CMBFS8427
Line
Voltage (V)
Frequency
(Hz)
Type of Ballast
Line
Amps (A)
Maximum Wattage
(W/W)
Catalog
Number ˚
For optional fusing, order kit -CF2.
488
Code•Master™ 2 Emergency PLT Factory Sealed Luminaires
FLUORESCENT/AREA: NEC/CEC EXPLOSIONPROOF
Explosionproof, Dust-Ignitionproof
52 W, 64 W, 84 W Fluorescent. For Use with Threaded Metal Conduit.
NEC:
Class I, Division 1 and 2, Groups C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 4X Marine Type Electric Fixtures
Pendant
Ceiling
Bracket
NEC:
Outside Type (Salt Water) Suitable for use in Wet Locations NFPA101, Life Safety Code
Lamp Watts Lamp Type Hub Size (Inches) Catalog Number 
52 PLT
64 PLT
84 PLT
52 PLT
64 PLT
84 PLT
52 PLT
64 PLT
84 PLT
3/4 CFPS5275
1 CFPS5210
3/4 CFPS6475
1 CFPS6410
3/4 CFPS8475
1 CFPS8410
3/4 CFCS5275
1 CFCS5210
3/4 CFCS6475
1 CFCS6410
3/4 CFCS8475
1 CFCS8410
3/4 CFBS5275
1 CFBS5210
3/4 CFBS6475
1 CFBS6410
3/4 CFBS8475
1 CFBS8410
25° Stanchion
52 PLT
64 PLT
84 PLT
Fixture Units
Ballast body with globe. Indicate voltage desired by adding voltage sufx to Fixture Unit catalog number listed below.
Lamp Watts Lamp Type Unit Catalog Number
52 PLT CMBFS52 12 27
64 PLT CMBFS64 12 27
84 PLT CMBFS84 12 27
1-1/2” tapped hub furnished with 1-1/2” to 1-1/4” reducer. To order fixture with guard, add suffix -G before adding voltage suffix. Add voltage suffix -12L for 120 V with lamp; or -27L for 277 V with lamp.
1-1/4 or 1-1/2
1-1/4 or 1-1/2
1-1/4 or 1-1/2
CFSS52150
CFSS64150
CFSS84150
Add Voltage Suffixes
120 V 277 V
489
Code•Master™ 2 Emergency PLT Factory Sealed Luminaires
FLUORESCENT/AREA: NEC/CEC EXPLOSIONPROOF
Explosionproof, Dust-Ignitionproof
52 W, 64 W, 84 W Fluorescent. For Use with Threaded Metal Conduit.
NEC:
Class I, Division 1 and 2, Groups C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 4X Marine Type Electric Fixtures
Mounting Hoods
Pendant
Ceiling
Bracket
25° Stanchion
NEC:
Outside Type (Salt Water) Suitable for use in Wet Locations NFPA101, Life Safety Code
One Hub
Four hubs, Three Close-Up Plugs
Four hubs, Three Close-Up Plugs
Hub Size Inches Catalog Number
3/4 CAP-75
1 CAP-100
3/4 CAC-75
1 CAC-100
3/4 CALB-75
1 CALB-100
Mounting Adapter with Connection Block
One Hub
Permits use of existing A-51 mounting hoods (AAC Ceiling or AALB Bracket) with the new Code•Master 2 Fixture Unit. After removing existing Fixture Unit and adapter, screw in the new CMAD-1 Adapter. Then thread thenew Fixture Unit into the CMAD-1.
1-1/4 or 1-1/2
CAS-150
CMAD-1
1-1/2” tapped hub furnished with 1-1/2” to 1-1/4” reducer.
490
Code•Master™ 2 Emergency PLT Factory Sealed Luminaires
FLUORESCENT/AREA: NEC/CEC EXPLOSIONPROOF
Explosionproof, Dust-Ignitionproof
52 W, 64 W, 84 W Fluorescent. For Use with Threaded Metal Conduit.
NEC:
Class I, Division 1 and 2, Groups C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 4X Marine Type Electric Fixtures
Polyester Reectors
Aluminum High Bay Reectors
Prismatic Glass Globes
NEC:
Outside Type (Salt Water) Suitable for use in Wet Locations NFPA101, Life Safety Code
Description Catalog Number
Standard Dome CMR-4ST
Deep Dome
30˚ Angle CMR-4AN
52, 64, 84 W PLT CGL-400
CMR-4DD
CMR-4HB
Aluminum Guards
Connection Block — For Code•Master 2 PLT Fixtures
52, 64, 84 W PLT CGU4
52 W - 84 W PLT32RS
52 W - 84 W VPT-7
Fixtures when used with Deep Dome Refletors are NOT UL Listed.
491
Code•Master™ 2 Emergency PLT Factory Sealed Luminaires
FLUORESCENT/AREA: NEC/CEC EXPLOSIONPROOF
Explosionproof, Dust-Ignitionproof
52 W, 64 W, 84 W Fluorescent. For Use with Threaded Metal Conduit.
NEC:
Class I, Division 1 and 2, Groups C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 4X Marine Type Electric Fixtures
NEC:
Outside Type (Salt Water) Suitable for use in Wet Locations NFPA101, Life Safety Code
Dimensions in Millimeters (Inches)
Pendant Ceiling Bracket 25° Stanchion
116.3 (4.58)
Dia.
99.3 (3.91)
(9.86)
250.4
101.6 (4.00)
9.9
(.390)
101.6 (4.00)
150.4 (5.92)
23.9
(0.94)
101.6 (4.00)
250.4
(9.86)
125.0
(4.92) Sq.
10.4
(0.41)Dia.
99.6
(3.92)
139.7 (5.50)
250.4
(9.86)
62.5
(2.46)
3.46"/
87.9 mm
31.2
(1.23)
57.9
(2.28)
292.1 (11.5)
349.3
(13.75)
45.5
(1.79)
108.0 (4.25)
60.5
(2.38) Dia.
241.3 (9.5)
154.9
(6.10)
60.5 (4.5) Dia.
Pendant Ceiling Bracket 25° Stanchion
A B C D A B C D A B C D A B C
52-84 W
622.3
(24.50)
596.9
(23.50)
304.8
(12.00)
517.1
(20.36)
618.7
(24.36)
Reflector Dimensions in Millimeters (Inches)
Type Reflector A B C Standard and Deep Dome
Standard Dome
(11.20)
268.2
284.5
Deep Dome
Fixtures when used with Deep Dome Refletors are NOT UL Listed.
(10.56)
149.9 (5.90)
177.8/ (7.00)
475.0
(18.70)
515.6
(20.30)
177.8 (7.00)
593.3
(23.36)
268.2
(10.56)
515.6
(20.30)
304.8
(12.00)
517.1
(20.36)
625.1
(24.61)
599.7
(23.61)
444.5
(17.50)
517.1
(20.36)
563.9
22.20)
30° Angle High Bay
268.2
(10.56)
347.7 (9.75)
410.5
(16.16)
538.5
(21.20)
278.4
(10.96)
528.3
(20.80)
444.5
(17.50)
337.8
(13.30)
492
Code•Master™ 2 Emergency PLT Factory Sealed Luminaires
FLUORESCENT/AREA: NEC/CEC EXPLOSIONPROOF
Explosionproof, Dust-Ignitionproof
* Photometric data is based on a fixture with two 32 W Compact Fluorescent PL-T lamps (2,400 lumens each). For candlepower values of fixtures with two 26 W PL-T lamps (1,800 lumens each), multiply by 0.75. For Candlepower values of fixtures with two 42 W PL-T Lamps. (3,200 lumens each) multiply by 1.34.
NEC:
Class I, Division 1 and 2, Groups C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 4X Marine Type Electric Fixtures
NEC:
Outside Type (Salt Water) Suitable for use in Wet Locations NFPA101, Life Safety Code
Photometric Data
Total Luminaire Efficiency = 79.8%
CIE Type - Semi-Direct
Spacing
Plane
Criteria
0-180 2.88 Coefficients of Utilization - Zonal Cavity Method
90-270 2.88 Effective Floor Cavity Reflectance 0.20
Diagonal 2.82 % Ceiling Rcc 80 70 50 30 10 0
Zone Lumens 0 90 90 90 90 85 85 85 85 76 76 76 68 68 68 60 60 60 57
0-10 17.70 1 76 70 65 60 71 66 61 57 58 54 51 51 48 45 45 42 40 36 10-20 61.05 2 67 58 51 45 63 55 48 42 48 43 38 42 37 34 36 32 29 26 20-30 132.44 3 60 49 41 35 56 46 39 33 40 34 29 35 30 26 30 26 23 20 30-40 236.78 4 54 43 34 28 50 40 32 26 35 28 23 30 25 21 26 21 18 15 40-50 336.66 5 49 37 29 23 46 35 27 22 31 24 19 26 21 17 23 18 15 12 50-60 421.68 6 45 33 25 19 42 31 23 18 27 21 16 23 18 14 20 16 12 10 60-70 485.34 7 41 29 22 16 38 28 20 15 24 18 14 21 16 12 18 14 10 8 70-80 517.29 8 38 26 19 14 36 25 18 13 22 16 12 19 14 10 16 12 9 7 80-90 513.72 9 35 24 17 12 33 23 16 11 20 14 10 17 12 9 15 11 8 9 90-100 468.70 10 33 22 15 11 31 21 14 10 18 13 9 16 11 8 14 10 7 5 100-110 352.77
110-120 200.85
120-130 73.54
130-140 11.28 0-30 211.19 4.4 5.5 90-120 1022.32 21.3 26.7 140-150 1.12 0-40 447.97 9.3 11.7 90-130 1095.85 22.8 28.6 150-160 0.31 0-60 1206.31 25.1 31.5 90-150 1108.26 23.1 28.6 160-170 0.06 0-90 2722.64 56.7 71.1 90-180 1108.63 23.1 28.9 170-180 0.00 0-180 3831.28 79.8 100.0
Total Luminaire Efficiency = 66.5%
CIE Type - Direct
Plane
0-180 1.62 Coefficients of Utilization - Zonal Cavity Method
90-270 1.62 Effective Floor Cavity Reflectance 0.20
Diagonal 1.74 % Ceiling Rcc 80 70 50 30 10 0
Zone Lumens 0 79 79 79 79 77 77 77 77 74 74 74 71 71 71 68 68 68 66
0-10 73.25 1 72 69 66 63 70 67 64 62 64 62 60 62 60 58 59 58 56 55 10-20 220.57 2 65 59 54 50 63 58 53 49 55 52 48 53 50 47 51 48 46 45 20-30 368.60 3 59 51 45 41 57 50 45 40 48 43 40 46 42 39 44 41 38 37 30-40 505.61 4 53 45 38 34 52 44 38 33 42 37 33 40 36 32 39 35 32 30 40-50 603.19 5 49 39 33 28 47 39 33 28 37 32 28 36 31 28 35 31 27 26 50-60 638.42 6 45 35 29 24 43 34 29 24 33 28 24 32 27 24 31 27 23 22 60-70 497.24 7 41 32 25 21 40 31 25 21 30 25 21 29 24 21 28 24 20 19 70-80 226.17 8 38 29 23 19 37 28 22 18 27 22 18 26 22 18 26 21 18 17 80-90 57.98 9 35 26 20 16 34 26 20 16 25 20 16 24 19 16 23 19 16 15 90-100 1.64 10 33 24 18 15 32 24 18 15 23 18 15 22 18 15 22 17 14 13 100-110 0.00
110-120 0.00 Zonal Lumen Summary
120-130 0.00 Zone Lumens % Lamp % Fixture Zone Lumens % Lamp % Fixture 130-140 0.00 0-30 662.42 13.8 20.7 90-120 1.64 0.0 0.1 140-150 0.00 0-40 1168.03 24.3 36.6 90-130 1.64 0.0 0.1 150-160 0.00 0-60 2409.64 50.2 75.5 90-150 1.64 0.0 0.1 160-170 0.00 0-90 3191.04 66.5 99.9 90-180 1.64 0.0 0.1 170-180 0.00 0-180 3192.68 66.5 100.0
Maximum Candela = 493 Located at Horizontal Angle = 0, Vertical Angle = 70 #1 – Vertical Plane through Horizontal Angles (0-180) (Through Max. Cd.) #2 – Horizontal Cone through Vertical Angle (70) (Through Max. Cd.)
Spacing
Criteria
Maximum Candela = 808 Located at Horizontal Angle = 0, Vertical Angle = 35 #1 – Vertical Plane through Horizontal Angles (0-180) (Through Max. Cd.) #2 – Horizontal Cone through Vertical Angle (35) (Through Max. Cd.)
REPORT NUMBER: CMBF64G 64 W (two 32 W lamps) Fluorescent Fixture with Globe only *
% Walls Rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
Zonal Lumen Summary
Zone Lumens % Lamp % Fixture Zone Lumens % Lamp % Fixture
REPORT NUMBER: CMBF64ST 64 W (two 32 W lamps) Fluorescent Fixture with Globe and Standard Dome Reflector *
% Walls Rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
493
Code•Master™ 2 Emergency PLT Factory Sealed Luminaires
FLUORESCENT/AREA: NEC/CEC EXPLOSIONPROOF
Explosionproof, Dust-Ignitionproof
* Photometric data is based on a fixture with two 32 W Compact Fluorescent PL-T lamps (2,400 lumens each). For candlepower values of fixtures with two 26 W PL-T lamps (1,800 lumens each), multiply by 0.75. For Candlepower values of fixtures with two 42 W PL-T Lamps. (3,200 lumens each) multiply by 1.34.
NEC:
Class I, Division 1 and 2, Groups C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 4X Marine Type Electric Fixtures
NEC:
Outside Type (Salt Water) Suitable for use in Wet Locations NFPA101, Life Safety Code
Photometric Data
Total Luminaire Efficiency = 57.4%
CIE Type - Direct
Spacing
Plane
Criteria
0-180 1.52 Coefficients of Utilization - Zonal Cavity Method
90-270 1.70 Effective Floor Cavity Reflectance 0.20
Diagonal 1.62 % Ceiling Rcc 80 70 50 30 10 0
Zone Lumens 0 68 68 68 68 67 67 67 67 64 64 64 61 61 61 58 58 58 57
0-10 62.13 1 61 58 55 52 59 56 54 51 54 51 49 51 49 48 49 48 46 45 10-20 187.93 2 55 49 45 41 53 48 44 40 46 43 39 44 41 39 42 40 38 36 20-30 317.49 3 50 43 37 33 48 42 37 33 40 36 32 38 35 32 37 34 31 30 30-40 428.14 4 45 37 32 28 44 37 31 27 35 31 27 34 30 27 32 29 26 25 40-50 471.22 5 41 33 28 23 40 32 27 23 31 27 23 30 26 23 29 25 22 21 50-60 454.23 6 38 30 24 20 37 29 24 20 28 23 20 27 23 20 26 22 19 18 60-70 384.77 7 35 27 21 18 34 26 21 18 25 21 17 24 20 17 24 20 17 16 70-80 276.31 8 32 24 19 16 32 24 19 15 23 19 15 22 18 15 22 18 15 14 80-90 157.68 9 30 22 17 14 29 22 17 14 21 17 14 20 16 14 20 16 13 12 90-100 13.45 10 28 20 16 12 28 20 15 12 19 15 12 19 15 12 18 15 12 11 100-110 0.00
110-120 0.00 Zonal Lumen Summary
120-130 0.00 Zone Lumens % Lamp % Fixture Zone Lumens % Lamp % Fixture 130-140 0.00 0-30 567.55 11.8 20.6 90-120 13.45 0.3 0.5 140-150 0.00 0-40 995.69 20.7 36.2 90-130 13.45 0.3 0.5 150-160 0.00 0-60 1921.14 40.0 69.8 90-150 13.45 0.3 0.5 160-170 0.00 0-90 2739.90 57.1 99.5 90-180 13.45 0.3 0.5 170-180 0.00 0-180 2753.35 57.4 100.0
Maximum Candela = 731
Horizontal
Located at #1 – Vertical Plane through Horizontal Angles (90-270) (Through Max. Cd.) #2 – Horizontal Cone through Vertical Angle (37.5) (Through Max. Cd.)
Angle = 90, Vertical Angle = 37.5
REPORT NUMBER: CMBF64AN 64 W (two 32 W lamps) Fluorescent Fixture with Globe and 30° Angle Dome Reflector *
% Walls Rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
Total Luminaire Efficiency = 67.2%
CIE Type - Direct
Spacing
Plane
Criteria
0-180 1.44 Coefficients of Utilization - Zonal Cavity Method
90-270 1.44 Effective Floor Cavity Reflectance 0.20
Diagonal 1.60 % Ceiling Rcc 80 70 50 30 10 0
Zone Lumens 0 80 80 80 80 78 78 78 78 75 75 75 71 71 71 69 69 69 67
0-10 88.95 1 73 70 67 65 71 68 66 63 66 63 61 63 61 60 60 59 58 56 10-20 260.61 2 66 61 56 52 65 59 55 52 57 53 50 55 52 49 53 50 48 47 20-30 413.34 3 60 53 47 43 59 52 47 43 50 45 42 48 44 41 46 43 40 39 30-40 539.82 4 55 47 41 36 53 46 40 36 44 39 35 42 38 35 41 37 34 33 40-50 630.36 5 50 41 35 31 49 41 35 30 39 34 30 38 33 30 37 33 29 28 50-60 641.74 6 46 37 31 26 45 36 30 26 35 30 26 34 29 26 33 29 25 24 60-70 436.60 7 43 33 27 23 41 33 27 23 32 27 23 31 26 23 30 26 22 21 70-80 164.84 8 40 30 24 20 38 30 24 20 29 24 20 28 23 20 27 23 20 19 80-90 47.37 9 37 28 22 18 36 27 22 18 26 21 18 26 21 18 25 21 18 16 90-100 1.92 10 34 25 20 16 34 25 20 16 24 19 16 24 19 16 23 19 16 15 100-110 0.00
110-120 0.00 Zonal Lumen Summary
120-130 0.00 Zone Lumens % Lamp % Fixture Zone Lumens % Lamp % Fixture 130-140 0.00 0-30 762.91 15.9 23.7 90-120 1.92 0.0 0.1 140-150 0.00 0-40 1302.73 27.1 40.4 90-130 1.92 0.0 0.1 150-160 0.00 0-60 2574.82 53.6 79.8 90-150 1.92 0.0 0.1 160-170 0.00 0-90 3223.63 67.2 99.9 90-180 1.92 0.0 0.1 170-180 0.00 0-180 3225.55 57.4 100.0
Maximum Candela = 933 Located at Horizontal Angle = 0, Vertical Angle = 7.5 #1 – Vertical Plane through Horizontal Angles (0-180) (Through Max. Cd.) #2 – Horizontal Cone through Vertical Angle (7.5) (Through Max. Cd.)
REPORT NUMBER: CMBF64DD 64 W (two 32 W lamps) Fluorescent Fixture with Globe and Deep Dome Reflector *
% Walls Rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
494
Code•Master™ 2 Emergency PLT Factory Sealed Luminaires
FLUORESCENT/AREA: NEC/CEC EXPLOSIONPROOF
Explosionproof, Dust-Ignitionproof
* Photometric data is based on a fixture with two 32 W Compact Fluorescent PL-T lamps (2,400 lumens each). For candlepower values of fixtures with two 26 W PL-T lamps (1,800 lumens each),
multiply by 0.75. For Candlepower values of fixtures with two 42 W PL-T Lamps. (3,200 lumens each) multiply by 1.34.
NEC:
Class I, Division 1 and 2, Groups C, D Class II, Division 1 and 2, Groups E, F, G Class III NEMA 4X Marine Type Electric Fixtures
NEC:
Outside Type (Salt Water) Suitable for use in Wet Locations NFPA101, Life Safety Code
Photometric Data
Total Luminaire Efficiency = 58.9%
CIE Type - Direct
Spacing
Plane
Criteria
0-180 0.82 Coefficients of Utilization - Zonal Cavity Method
90-270 0.82 Effective Floor Cavity Reflectance 0.20
Diagonal 0.92 % Ceiling Rcc 80 70 50 30 10 0
Zone Lumens 0 70 70 70 70 68 68 68 68 65 65 65 63 63 63 60 60 60 59
0-10 239.15 1 66 64 63 61 65 63 62 60 61 59 58 58 57 57 56 56 55 54
10-20 599.67 2 62 59 56 54 61 58 55 53 56 54 52 54 52 51 52 51 50 49
20-30 645.20 3 58 54 51 48 57 53 50 47 51 49 47 50 48 46 49 47 45 44
30-40 625.54 4 55 50 46 43 54 49 45 43 48 44 42 46 44 42 45 43 41 40
40-50 452.95 5 51 46 42 39 50 45 41 39 44 41 38 43 40 38 42 39 37 36
50-60 185.71 6 48 42 38 35 47 42 38 35 41 37 35 40 37 35 39 36 34 33
60-70 58.40 7 46 39 35 32 45 39 35 32 38 35 32 37 34 32 37 34 32 31
70-80 15.26 8 43 37 33 30 42 36 32 30 36 32 30 35 32 29 34 31 29 28
80-90 4.25 9 41 34 30 28 40 34 30 28 33 30 27 33 30 27 32 29 27 26
90-100 0.69 10 38 32 28 26 38 32 28 26 31 28 26 31 28 25 30 27 25 25
100-110 0.00
110-120 0.00 Zonal Lumen Summary
120-130 0.00 Zone Lumens % Lamp % Fixture Zone Lumens % Lamp % Fixture
130-140 0.00 0-30 1484.03 30.9 52.5 90-120 0.69 0.0 0.0
140-150 0.00 0-40 2109.57 43.9 74.6 90-130 0.69 0.0 0.0
150-160 0.00 0-60 2748.23 57.3 97.2 90-150 0.69 0.0 0.0
160-170 0.00 0-90 2826.12 58.9 100.0 90-180 0.69 0.0 0.0
170-180 0.00 0-180 2628.80 58.9 100.0
Maximum Candela = 2540 Located at Horizontal Angle = 0, Vertical Angle = 5 #1 – Vertical Plane through Horizontal Angles (0-180) (Through Max. Cd.) #2 – Horizontal Cone through Vertical Angle (5) (Through Max. Cd.)
REPORT NUMBER: CMBF64HB 64 W (two 32 W lamps) Fluorescent Fixture with Globe and High Bay Reflector *
% Walls Rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
495