Cable Gland Accessories and Tools
Hazardous Location Fittings: cabLe gLand accessories and tooLs
© November 2016
For Cable Entries
Entry Thread Seals – Sealing (IP) Washers
• It is essential to maintain the integrity of the degree of IP protection for which explosionproof equipment have been rated. The need for a
sealing washer will depend on the IP rating, code of protection and the type of entry holes available within that equipment (e.g. for Ex e
apparatus or terminal boxes which are permitted to have untapped through clearance holes it is necessary to t a sealing washer to ensure
that the minimum IP54 requirement is met). Other equipment with tapped entry holes may not require a sealing washer to maintain the
rated integrity of the instal lation.
• Entry thread sealing washers are produced in 2mm thick white nylon as standard which are recommended and meet the specied
requirements of Shell’s Offshore operations.
• To verify the effectiveness of the nylon entry sealing washers, independent 3rd party tests to BS EN 60529:1992 have been conducted on
certain cable gland types at IP66, IP67 and IP68 levels of protection. Documentation of these high standard tests is available upon request.
Description Box Quantity
M16 1000 16ETS2 050NPT 100 050NPTETS
M20 1000 20ETS2 075NPT 100 075NPTETS
M25 1000 25ETS2 100NPT 50 100NPTETS
M32 500 32ETS2 125NPT 50 125NPTETS
M40 200 40ETS2 150NPT 10 150NPTETS
M50 200 50ETS2 200NPT 5 200NPTETS
M63 100 63ETS2 250NPT 5 250NPTETS
M75 100 75ETS2 300NPT 1 300NPTETS
M90 10 90ETS2 350NPT 1 350NPTETS
M100 10 100ETS2 — — —
Metric Catalog
Number (White) Description Box Quantity
NPT Catalog
Number (Green)