Appleton ATX™ UPR Series 32 Amp Plugs and Sockets Catalog Page

ATX™ UPR Series 32 Amp Plugs and Sockets
Increased Safety
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
IP66 - IK09
Applications
• Plugs and sockets are used with portable or stationery
electrical equipment such as:
— Lighting systems — Conveyors — Heaters — Motor generators
— Air conditioning equipment
— Compressors — Pumps
• For use in corrosive atmospheres and installations in Zone 1 and 2 and 21 and 22 of the oil and gas industry, such as:
   — Reneries
— Chemical and petrochemical plants — Pipelines — Loading docks — Onshore and offshore drilling platforms
Features
• Plug and socket system is designed with a mechanical interlock to insure disengagement cannot occur while energized.
Large ON/OFF actuator on the receptacle gives clear, visible
indication of the receptacle status for maximum hazardous
location protection.
Low Voltage receptacle can be locked in 0 (Off) and 1 (On) positions.
Different voltages are color coded for easy identication.
• The receptacles are keyed to accept UPR plugs of the proper
PLUGS AND RECEPTACLES: ATEX/IECEX FLAMEPROOF
voltage.
• Receptacle explosionproof switch.
• UPR plugs can be used in non-hazardous IEC 60309-2 sockets.
• Operating temperature of -20 °C to +55 °C (-4 °F to +131 °F)
Standard Materials
• Wall Socket: polyamide
• Plug: polyamide
ATEX/IECEx Certifications and Compliances
• Certication Type UPR — Gas: Zones 1 and 2
– Conforming to ATEX 94/9/CE:  II 2 G – Type of Protection: Ex db eb IIB – Temperature Class: T6 for Ta  +40 °C (+104 °F)
and T5 for +55 °C (+131 °F)
— Dust: Zones 21 and 22
– Conforming to ATEX 94/9/CE:  II 2 D – Type of Protection: Ex tb IIIB – Surface Temperature: T79 °C [Ta +40 °C (+104 °F)];
T94 °C [(Ta +55 °C (+131 °F)]
• Ambient Temperature: -20 °C  Ta  +55 °C (-4 °F  Ta  +131 °F)
• Index of Protection according EN/IEC 60529: IP66
• Impact Resistance (shock): IK09
• CE Declaration of Conformity: 50311
• ATEX Certicate: LCIE 15 ATEX 3054X
• IECEx Certicate: IECEx LCIE 15.0044X
Plug Wall Mounting Socket
Technical Data
Breaking Capacity
AC3 32 Amp 690 Vac
AC22 32 Amp 690 Vac
Short Circuit Withstand (ICC) : 10kA
566
ATX™ UPR Series 32 Amp Plugs and Sockets
Increased Safety
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
IP66 - IK09
Wall Mounting Socket Plug
• Two M32 threaded entries on the bottom or top upon request.
• Supplied with one M32 cable gland – Ø 10 to Ø 25 mm (0.39 to 0.98 in) and one M32 blanking plugs.
• Terminal capacity 2 x 6 to 10 mm² (#10 to #8 AWG). Can be through-wired up to 6mm² (#10 AWG).
• Fitted with two linked earth terminals.
• One integrated cable clamp – Ø 14.1 to Ø 29.1 mm (0.55 to 0.98 in) for 3P+N+E versions.
• Terminal capacity 6 to 10 mm
2
(#10 to #8 AWG).
PLUGS AND RECEPTACLES: ATEX/IECEX FLAMEPROOF
LV - Low Voltage
Yellow Blue Red Black
100/130 Vac 200/250 Vac 380/415 Vac 480/500 Vac
600/690 Vac
567
Loading...
+ 2 hidden pages