Appleton ATX™ MS Series Motor Starters Catalog Page

ATX™ MS Series Motor Starters
CONTROLS: ATEX/IECEx FLAMEPROOF MOTOR STARTERS
© June 2017
Flameproof
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK10
• These motor starters are used in areas where hazardous material are handled or stored. These units provide:
— Disconnecting means — Undervoltage protection — Circuit protection — Motor running protection — Thermal time delay overload protection
Features
• Magnetic circuit breaker protects equipment and personnel and eliminates replacement of fuses.
• Three pole contactor.
• Thermal overload relay with manual reset push button.
• Green pilot light ”Running/ON”.
• Rated voltage 400/415 Vac 50/60 Hz AC-3 category.
• Control circuit supplied via a transformer fed between phases.
• Direct entries or indirect entries with Ex e box allows use of cable gland with elastomer seal.
• Type 2 coordinated protection (IEC 60947-4-1) has the following
benets:
— Safety - limiting the energy delivered to the short circuit
ensures the safest applications for personnel, facilities and equipment.
— Reduced costs - preventing short circuit damage to
components minimizes labor and replacement costs.
— Increased productivity - as component replacement due to
short circuits is minimized, so are interruptions to production.
• Direct ammeter for 0.37 kW to 2.2 kW versions. Ammeter with current transformer for 3 kW to 75 kW versions.
Standard Materials
• Body and cover:
— Gray painted marine grade aluminum alloy (RAL 7038) — Cover bolts: stainless steel — Hinges: stainless steel
• Ex e box for indirect entries:
— Gray (RAL 7038) painted aluminum alloy (size 2 and 6) or
stainless steel (size 8 and 11)
— Cover bolts: stainless steel
Standard Finish
• Corrosion resistant gray powder coat epoxy
Options
• Available up to 300 kW - contact your local representative.
ATEX/IECEx Certifications and Compliances
• Certication Type CF
— Gas: Zone 1 and 2
– Conforming to ATEX 94/9/CE: II 2 G – Type of Protection: Ex d IIB – Temperature Class: T6
— Dust: Zone 21 and 22
– Conforming to ATEX 94/9/CE: II2 D – Type of Protection: Ex tD A21 – Surface Temperature: T80 °C (T176) – Ambient Temperature: CF 60: -50 °C to +55 °C
( -58 °F to +131 °F); CF 20, 40, 50: -40 °C to +55 °C ( -40 °F to +131 °F); CF 30: -20 °C to +55 °C ( -4 °F to +131 °F)
Ex d Version
Ex de Version
• CE Declaration of Conformity: 50229
• ATEX Certicate: LCIE 02 ATEX 6057X
• IECEx Certicate: IECEx LCI 08.0023X
• Index of Protection according EN/IEC 60529: IP66
• Impact Resistance (shock): IK10
• Internal Volume: > 2 dm
3
(122 in³) - 2 liters
EURASEC Certification
• EURASEC RU C-FR. ГБ05.B.00911
338
ATX™ MS Series Motor Starters
CONTROLS: ATEX/IECEX FLAMEPROOF MOTOR STARTERS
© June 2017
Flameproof
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 - IK10
Catalog Numbering Guide
MS B 003 D 4 2 A
Series:
MS - Motor Starters
Zone 1
ATEX/IECEx Certified
Classification: B - Ex d IIB H - Ex d IIB + H
2
Power kW:
003 - 0.37 005 - 0.55 007 - 0.75 011 - 1.1 015 - 1.5 022 - 2.2 030 - 3 040 - 4 055 - 5.5 075 - 7.5
D - D.O.L. Direct On Line
Type:
090 - 9 110 - 11 150 - 15 185 - 18.5 220 - 22 300 - 30 370 - 37 450 - 45 550 - 55 750 - 75
Control Circuit Voltage: 2 - 230 Vac 50/60 Hz via
Rated Voltage:
4 - 400/415 V 50/60 Hz
Transformer
Options: A - Ammeter B - Indirect entries with
Ex e Box E - Local emergency Stop H - Anti-condensation
(Heater, Thermostat,
Blue pilot light) S - Selector switch
Hand/Off/Auto T - Fault trip signal with
yellow pilot light F - Full Options
(A,B,E,H,S,T)
339
Loading...