ATX™ HBE Series Round Bulkhead Luminaires
INCANDESCENT/AREA: ATEX INCREASED SAFETY
© May 2016
Increased Safety. Incandescent
ATEX:
Zone 1 and 2 - 21 and 22
II 2 GD
IP65
Applications
• Suitable for use in:
— Stairways
— Small areas
— Emergency exit
Features
• For incandescent lamps 60 W to 150 W maximum, mixed lamp
100 W maximum. Lamps not supplied.
• E27 lampholder.
• Screw locking mechanism.
• Operates in all positions.
• Connection to lampholder via two 2 x 2.5 mm2
(0.003 x 0.004 in2) terminals.
• Internal earth two terminals 2 x 2.5 mm
External earth 1 x 4 mm2 (0.002 x 0.006 in2).
• Three M20 entries in “T” formation. Supplied with one M20
cable gland [6.5 to 14.5 mm (0.26 to 0.57 in) diameter] and two
M20 blanking plugs.
Standard Materials
• Body: gray painted aluminum alloy
• Diffuser: glass
• Sealing gasket: silicone
• Guard: zinc plated steel
• Cable gland and blanking plug: polyamide
ATEX Certifications and Compliances
• Certication Type: HBe150
— Gas: Zones 1 and 2
– Conforming to ATEX 94/9/CE: II 2 G
– Type of Protection: Ex e II
– Temperature Class: See T Rating (Gas) and Surface
Temperature (Dust) Table
— Dust: Zones 21 and 22
– Conforming to ATEX 94/9/CE: II2 D
– Type of Protection: Ex tD A21
– Surface Temperature: T102 °C to T137 °C (T216 °F to T279 °F)
• Ambient Temperature: -40 °C to +50 °C (-40 °F to +122 °F)
• CE Declaration of Conformity: 50244
• ATEX Certicate: LCIE 02 ATEX 6228X
• Index of Protection according EN/IEC 60529: IP65
EURASEC Certification
• EURASEC N° TC RU C-FR.ГБ05.B.00912
Other Certification
• INMETRO Certicate: BVC 11.0494-X
2
(0.003 x 0.004 in2).
HBERI15 and HBEPGZ
Inmetro certication available on special request only. Contact your local sales representative for more information.
ATX™ HBE Series Round Bulkhead Luminaires
INCANDESCENT/AREA: ATEX INCREASED SAFETY
© May 2016
Increased Safety. Incandescent
ATEX:
Zone 1 and 2 - 21 and 22
II 2 GD
IP65
Weight kg (lb) Volume dm3 (in3) Catalog Number
3 (6.61) 15 (915.36) HBERI15
Accessories
Catalog Number
Protective Guard HBEPGZ
Spare Lamp Glass HBEGD
T Rating (Gas) and Surface Temperature (Dust) Table
Lamp Type and Wattage
Wattage Type
Operating
Positions
For Ta = +40° C (+104° F) +50° C (+122° F)
T° at
Cable Entry T Rating
Gas Dust
T° at
Cable Entry
Surface T° for
Ta =
+50° C (+122° F)T Rating
60 Incandescent
75 Incandescent
100 Mercury
100 Incandescent
150 Mixed
Any Position T2
T3
T4
Any Position T2
T3
T4
Any Position T2
T3
T3
Any Position T1
T3
T3
Any Position T2
T3
+90 °C
(+194 °F)
+90 °C
(+194 °F)
+82 °C
(+ 180°F)
+82 °C
(+ 180°F)
T2
T3
T4
T2
T3
T4
T2
T3
T3
T1
T2
T3
T2
T3
+83 °C
(+181°F)
+83 °C
(+181°F)
+100 °C
(+212 °F)
+100 °C
(+212 °F)
+92 °C
(198 °F)
+92 °C
(198 °F)
+102 °C
(+216°F)
+107 °C
(+225°F)
+117 °C
(+243°F)
+137 °C
(+279°F)
+130 °C
(+266°F)
T3
Not Applicable, no need for high temperature cable for cable entry temperature less than +80 ºC (+176 ºF).
T3