ATX™ FELED Series Nonmetallic LED Luminaires
LED/AREA: ATEX/IECEX ENCLOSED AND GASKETED/INCREASED SAFETY
© May 2019
Standard and Emergency Battery Back-Up, Increased Safety
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 – IK10
Applications
• For use in locations where:
— Hazardous areas are designated as Zone 1 and 2 – 21 and 22
— A high degree of corrosion resistance is required
— Protection against dirt, water and moisture is necessary
• Typical applications include:
— Oil reneries
— Petrochemical facilities
— Food processing plants
— Waste and water treatment plants
— Underground tunnels
— General manufacturing facilities
Features
• Available in 5000K or 4000K Color Temperatures.
• Meets photobiological requirement for Risk Group 0 (RG0).
• Easy to retrot in same mounting footprint as Appleton’s FE
series nonmetallic uorescent luminaires.
• Full range of lumen outputs, with light distribution equivalent to
Appleton’s FE series uorescent luminaires.
• Corrosion-resistant berglass reinforced polyester body and
hinged polycarbonate lens.
• High impact resistance housing (20 Joules – IK10) from
-30 °C to +55 °C (-22 °F to +131 °F) ambient temperature
and wind prole for use in extreme offshore and onshore
environments.
• 60,000+ hour LED life for years of maintenance free operation.
• Lightweight design, hinged cover with captive screws, and
terminal block wiring for easy installation and maintenance.
• Contemporary, low prole design suitable for tight spaces.
• Standard screw-type terminal block can accept 1.5 to 6 mm2
wire.
• Field replaceable LED driver.
• Industry-leading thermal management for safe, reliable
operation over wide temperature range.
• Universal, high efciency, drivers cover voltage requirements for
120-277 Vac, 170-300 Vdc, 50/60 Hz +/- 10%.
• High power factor electronic driver (>0.95).
• Standard 6KV surge suppression.
• M20 plug or M25 plug provided.
• Latch assembly and elastomer gasket seals against water and
dust ingress, IP66.
• Easily accessed for maintenance using Allen key or straight
blade screwdriver.
• Central opening with unique patented release system to prevent
damage.
• Can be horizontally or vertically mounted.
• Available in 3 hour emergency version, including built-in monthly
self- test. Test results through multi-colored LED.
• Positive safety switch disconnects power to LED’s and driver to
allow maintenance in hazardous locations (emergency version).
• Ex e battery with plug-in connector.
Options
• 3 Hours Emergency/Battery Back-Up available ;
— Add sufx -E to the end of the catalog number.
Example: FELED5CBDSADE
Standard Materials
• Housing: berglass reinforced polyester
• Lens: polycarbonate
• Diffuser: polycarbonate
• Gasket: elastomer
• Internal reector: highly reective white polycarbonate (standard
versions) or powder coated aluminum (emergency versions)
• Mounting accessories available in different materials such as
gray painted aluminum, zinc plated steel, galvanized steel or
316 stainless steel
ATEX/IECEx Certifications and Compliances
• Certication Type: FELED30
— Gas: Zones 1 and 2
– Conforming to ATEX 2014/34/EU: II 2 G
– Type of Protection: Ex eb mb op is IIC Gb
– Temperature Class: T4
— Dust: Zones 21 and 22
– Conforming to ATEX 2014/34/EU: II 2 D
– Type of Protection: Ex op is tb IIIC Db
– Surface Temperature: +60 °C to +75 °C (+140 °F to +167 °F)
• Ambient Temperature: -30 °C up to +55 °C
(-22 °F up to +131 °F)
• EU Declaration of Conformity: 50318
• ATEX Certicate: INERIS 18 ATEX 0042X
• IECEx Certicate: IECEx INE 18.0039X
• Certication Type: FELED (emergency)
— Gas: Zones 1 and 2
– Conforming to ATEX 2014/34/EU: II 2 G
– Type of Protection: Ex db eb mb IIC Gb
– Temperature Class: T6
— Dust: Zones 21 and 22
– Conforming to ATEX 2014/34/EU: II 2 D
– Type of Protection: Ex tb IIIC Db
– Surface Temperature: +63 °C to +73 °C (+145 °F to +163 °F)
• Ambient Temperature: -20°C up to +50 °C (-4 °F up to 122 °F)
• EU Declaration of Conformity: 50317
• ATEX Certicate: LCIE 16 ATEX 3048X
• IECEx Certicate: IECEx LCIE 16.0038X
• Standard and Emergency:
— Index of Protection according EN/IEC 60529: IP66
— Impact Resistance (shock): IK10
— Photobiological Safety, IEC 62778 and IEC 62471: RG0 at
0.25m mounting height
Available for 5K lumen models only.
1

ATX™ FELED Series Nonmetallic LED Luminaires
Standard and Emergency Battery Back-Up, Increased Safety
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 – IK10
Order using catalog numbering guide below or select catalog number from tables on following pages.
FELED 3 C BU S A D
Series:
FELED - Zone 1, 2,
21, 22 ATEX/
IECEx
Certified
Blank - Direct (with diffuser)
I - Indirect (without diffuser)
LED/AREA: NEC/CEC EXPLOSIONPROOF/ATEX/IECEx FLAMEPROOF/INCREASED SAFETY
LED Position:
Lumen
Output :
3 - 3K
4 - 4K
5 - 5K
7 - 7K
Color Temperature:
C - 5000K (Cool)
N - 4000K (Neutral)
Voltage:
BU - 120-277Vac,
170-300Vdc,
50/60 Hz
BD - 100 to 240 Vac,
50/60 Hz
Mounting Version :
S - Surface/Suspension Mount
Standard Wiring (single
phase)
L - Surface/Suspension Mount
Dual Loop In/Out Through
Wiring (single phase)
Cable Entry:
A - Armored
M20
N - Unarmored
M25
Options:
D - Diffused
E - 3H Emergency
(combined)
All values displayed reflect typical values.
Standard and Loop In/Out cable entries provide 3 entries; 1 at one and 2 at the other end of the housing.
BD voltage for emergency model only
Must order armored cable glands separately. M20 entries are with brass earth continuity plate for armored cable.
Cable glands provided in luminaires with unarmored hub entries.
Diffuser required for direct, not included with indirect.
Available for 5K lumen model only.
2

ATX™ FELED Series Nonmetallic LED Luminaires
3 entries, 1 at one end and 2 at the other
Version : S
Standard
L
N
PE
PE
L
N
PE
L’
L
L
N
N
PE
L’
Version : L
Dual Loop In/Out - Through Wiring (Single Phase) (Single Phase)
3 entries, 1 at one end and 2 at the other 3 entries, 1 at one end and 2 at the other
Version : S
Standard
L’
L’
L
PE
N
PE
N
PE
N
L
L
L’
PE
L’
L
L
N
N
PE
L’
Version : S
Standard
LED/AREA: ATEX/IECEX ENCLOSED AND GASKETED/INCREASED SAFETY
© May 2019
Standard and Emergency Battery Back-Up, Increased Safety
ATEX/IECEx:
Zone 1 and 2 - 21 and 22
II 2 GD
IP66 – IK10
Wiring Diagrams
Standard
Emergency
Version : L
Dual Loop In/Out - Through Wiring (Single Phase)
3 entries, 1 at one end and 2 at the other
N
L
N
N
L
PE
PE
L
PE
Version : S
Standard
(Single Phase)
3 entries, 1 at one end and 2 at the other
L
N
N
L
PE
PE
5