Class II, Div. 1 and 2
Groups F, G
Class III
Type: 3RX
APPLICATION and FEATURES:
• U-Line®/Contender® U-Line® receptacles and ECP/NCP
plugs combination are designed for use where power is to be
supplied to portable electric equipment in locations which are
hazardous due to the presence of flammable vapors and gases or
locations where damp or corrosive conditions are encountered.
• These plugs and receptacles are for 15 or 20 ampere use at 125
volts AC and 20 ampere use at 250 volts AC.
• U-Line® receptacles mount on single or double-gang EFD
series boxes. Contender® U-Line® receptacles mount on single
or double-gang EDS series boxes.
• Receptacle is grounded through and extra pole as well as
through the receptacle housing.
INSTALLATION:
ELECTRICAL WARNING
Electrical power supply must be “OFF” before and during
installation and maintenance. Failure to do so may result
in serious or fatal injuries due to electrocution.
Note: Use minimum #12 copper or copper clad building wire
1. Mount receptacle back box in desired location. If receptacle is
already mounted on the box, take out four mounting screws and
remove receptacle. Pull in power source wiring to the box,
making sure wire leads extend out of box far enough for proper
connections to be made (See Figure 2).
2. Strip insulation from power lead ½”. Connect power leads to
receptacle terminals. Wiring must comply with applicable local
codes (See Figure 3).
3. To make connections, loosen wire screws, slide stripped end
of wire into contact and tighten wire screw to 20 in-lb torque (See
Figure 4).
4. Apply a thin film of lubricant (supplied with receptacle) to the
flange. Reinstall receptacle on the flange and tighten four
mounting screws provided to 30 in-lb torque. Receptacle
assembly is now complete and power may now be turned on.
Retain this instruction sheet for future reference.
For Convenience…ECP InterchangerTM Plug fits
ordinary location receptacles (NEMA 5-20 or 15
NEMA 620) and explosion proof U-Line®
Receptacle as well as Killark® “UGR” Series and
Crouse-Hinds® “ENR” Series.
Figure 2
Grounded White Lead
connection for 125V, Black
Lead connection for 250V
Note: For 250V, there are 2 blacks wires, connect
one to black lead and other to indicated white lead
as shown.
Figure 1A
Figure 1B
Figure 3
Black Lead
Connection
ESG Electrical Group • 800-621-1506 • www.appletonelec.com Rev. A 02/18/09 Page 1
The mating flat flange surfaces on both receptacle and
back box are explosion-proof surfaces. Surfaces are not to
be scratched and MUST be clean and flat before assembly.
Gaskets, paint, or any other similar material must NOT be
used in this joint.
OPERATION:
The U-Line®/Contender U-Line® receptacle is dead-front
construction. Electrical connection between it and ECP/NCP plug
is accomplished after plug fully inserts into receptacle and rotate
clockwise.
1. Lift receptacle door and locate polarization on mating plug pin
and receptacle face. Insert plug straight all the way into receptacle
until it can not go further (see figure 5).
2. Rotate plug clockwise limit (37º), this closes internal contacts
and completes circuit. This also mechanically locks plug into
receptacle so it cannot be pulled out.
3. To remove plug, push plug inward and turn to counterclockwise,
pull plug straight out.
MAINTAENANCE:
Electrical and mechanical inspection of all components must be
performed on a regularly scheduled basic, determined by the
environment and frequency of use. It is recommended that
inspection be performed a minimum of once a year.
WARNING
Electrical power supply must be “OFF” before and during
installation and maintenance. Installation and
maintenance procedure must be performed by a trained
and competent electrician.
WARNING
If any parts of the receptacle or plug appear to be missing,
broken, or show signs or damage, DISCONTINUE USE
IMMEDIATELY. Replace with the proper replacement
part(s) before continuing service.
1. Inspect all contact wire terminals for tightness. Discoloration
due to excessive heat is an indicator of a possible problem and
should be thoroughly investigated and repaired as necessary.
2. Inspect contacts for signs of wear and replace if necessary.
3. Clean exterior surfaces making sure nameplates remain legible.
Figure 4 (mounting receptacle onto back box with
hinge in UP position)
Figure 5 - Plug Inserts In Receptacle
Figure 6
Receptacle
Cover
Page 2 330032-1 Rev. A 02/18/09 ESG Electrical Group • 800-621-1506 •ww.appletonelec.com
Dimensions: U-Line® EFS Receptacle and ECP/NCP Plugs
Single Gang Box Double Gang Box
ECP/NCP Plugs
U-Line® EFS Receptacle Catalog Number
Aluminum Receptacle and Malleable Iron Mounting Box ◊Malleable Iron Receptacle and Mounting Box
Class I, Groups C & D, Class II, Group F, G, Class III Class I, Groups C & D, Class II, Groups F, G Class III
Suitable for Group B when external seals are used. Suitable for Group B provided external seals are used.
Single Gang-Factory Seal
Type Hub Size 125V 250V 125V 250V
Class I, Group C and D, Class II, Group F, G, Class III Class I, Group C and D, Class II, Group F, G, Class III
Dead-End ½ EFS250-2023 EFS250-20232 EFS250-2023M EFS250-20232M
¾ EFS275-2023 EFS275-20232 EFS275-2023M EFS275-20232M
1 EFS210-2023 EFS210-20232 EFS210-2023M EFS210-20232M
Feed-Thru ½ EFSC250-2023 EFSC250-20232 EFSC250-2023M EFSC250-20232M
¾ EFSC275-2023 EFSC275-20232 EFSC275-2023M EFSC275-20232M
Malleable Iron Receptacle and Mounting Box With Factory Sealed Chamber
Class I, Groups B, C & D, Class II, Groups F, G Class III
No external seals required.
Single Gang-Factory Seal
Type Hub Size 125V 250V
Dead-End ½ EFSB150-2023M EFSB150-20232M
¾ EFSB175-2023M EFSB175-20232M
Feed-Thru ½ EFSCB150-2023M EFSCB150-20232M
¾ EFSCB175-2023MEFSCB175-20232M
Rating Notes:
1. ◊ Single gang aluminum EFSR receptacle cover and malleable iron EFD box suitable for Class I, Div. 1, Group B when
external seals are used (seals must be placed adjacent to each conduit entrance).
2. Single gang malleable iron EFSR receptacle and mounting EFD box suitable for Group B, no external seals required
when using with sealing chamber.
3. TYPE 3RX when the screw cover is installed and the cover is fully engaged. Apply lubricant provided in the bag on the
cover and all flanges to keep water out.
Ordering Notes:
For aluminum box and receptacle cover, add suff
ix A (For Ex: Cat# EFS150-2023A).
Page 3 330062-1 Rev. A 02/18/09 ESG Electrical Group • 800-621-1506 • ww.appletonelec.com
Class I, Groups C & D, Class II, Group F, G, Class III
Dead-End ½ ENR12201 ENR12202
¾ ENR22201 ENR22202
Feed-Thru
¾ ENRC22201 ENRC22202
Rating Notes:
TYPE 3RX when the screw cover is installed and the cover is fully engaged. Apply lubricant provided in the bag on the
cover and all flanges to keep water out.
Ordering Notes:
Standard U-Line Contender catalog includes aluminum ENR receptacle and malleable iron EDS box. For aluminum box
and receptacle cover, add suffix SA (For Ex: Cat# ENR11201SA)
½ ENRC11201 ENRC11202
1 ENRC31201 ENRC31202
1 ENR32201 ENR32202
½ ENRC12201 ENRC12202
1 ENRC32201 ENRC32202
Retain this instruction sheet for future reference.
Page 4 330062-1 Rev. A 02/18/09 ESG Electrical Group • 800-621-1506 • www.appletonelec.com
U-Line® Intermateability Chart
The Appleton “ECP” Model “D” Plug and “EFS” and “ENR” Receptacles are UL Listed Combinations. The Appleton “ECP” Model “D” Plug with
Killark® UL Listed “UGR” Series Receptacles or with Crouse-Hinds® UL Listed “ENR” Series Receptacles are UL Classified Combinations.
Contender
Appleton Model D U-Line
Plug Appleton Plug Receptacle Receptacle Receptacle Receptacle Receptacle Conduit Size, No. of
Rating Cat. No. Rating Cat. No. Cat. No. Cat. No. Cat. No. Openings In. Gangs