Appleton Appleton Code•Master 2 Emergency PLT Factory Sealed Luminaires, 650441001 Instruction Sheet

INSTALLATION AND MAINTENANCE INSTRUCTIONS
CODE•MASTER 2™ EMERGENCY PLT LUMINAIRE
Class I, Div. 1 and 2, Groups C, D Class II, Div 1 and 2, Groups E, F, G
Class III UL 1598A, 844, 924
Suitable for Use in Wet Locations
Code•Master 2™ Factory Sealed Fixtures: Explosion-Proof, Dust-Ignition-Proof; 52, 64 and 84 Watt PLT Compact Fluorescent Emergency.
650441-001
INSTRUCTION SHEET
DO NOT ATTEMPT INSTALLATION UNTIL YOU ARE FAMILIAR WITH ALL PRECAUTIONS AND PROCEDURES OUTLINED WITHIN
THIS INSTRUCTION SHEET
WARNING
THE FIXTURE MUST BE GROUNDED AS REQUIRED BY THE
NATIONAL ELECTRICAL CODE (PARAGRAPH 410-21 AND ARTICLE 250) OR CANADA ELECTRIC CODE (RULE 30-500 AND
SECTION 10). FAILURE TO PROPERLY GROUND THE FIXTURE WILL CREATE AN ELECTRIC SHOCK HAZARD WHICH CAN
CAUSE SERIOUS INJURY OR DEATH.
INSTALLATION PRECAUTIONS
• All National and Local Codes MUST be followed in the instal­lation of the xture. For code interpretation, consult local authority.
• Consult xture nameplate for suitability in specic location.
• Consult xture nameplate for minimum required supply wire rat­ing.
• Verify that supply voltage agrees with xture rating as indi­cated on nameplate. Verify that the maximum ambient tem­perature of environment in which xture is to be installed does not exceed xture rating as indicated on nameplate.
• Verify that there is ground continuity in the electrical system.
FLUORESCENT EMERGENCY BALLAST SAFEGUARDS AND INSTRUCTIONS
• To prevent high voltage from being present on output leads (yellow and red), Do not join inverter connectors until AC power is supplied to the emergency ballasts.
• To reduce the risk of electrical shock, disconnect the AC input and inverter connectors before servicing.
• The emergency ballast must be connected to an unswitched AC power source.
• When AC power is applied, the charging indicator lights are illuminated, indicating that the batteries are being charged. When power fails, the emergency ballasts automatically pro­vide at least 90 minutes of emergency lighting.
• The batteries must be charged for at least 24 hours before conducting a long-term test.
• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
• Contact the manufacturer for information on replacement parts.
APPLICATIONS
• Ideal for use in chemical and petrochemical plants such as manufacturers of plastics, paints and thinners in reneries, and in other process areas where ignitable vapors, dust, moisture and corrosive elements may be present.
• Suitable for use in wet locations.
FEATURES
• Fixtures operate safely in high ambient temperatures. For example, in Class I areas the 84W PLT xture operates at a maximum temperature of 85˚C in a 40˚C ambient. See chart on page 2 for specic ratings.
• Arrangement of heat-producing components results in more efcient heat dissipation for cooler xture operations.
• Patented “wireless” design. Threading of xture unit onto mounting hood makes electrical connection. Only wir­ing required is attaching two wires to connection block in mounting hood.
• Connection block is easily wired: (a) loosen two screws. (b) make wire connections (c) re-position connection block.
• Safe, easy servicing without disconnecting any wiring. “Wireless” xture unit easily threads off mounting hood for convenient servicing or for immediate replacement with a “stand-by” unit.
• Acme double lead threads speed installation and xture removal from mounting hood-only half as many turns are required as for single lead threads.
CAUTION
VERIFY THAT GROUND CONTINUITY HAS BEEN
ESTABLISHED BY USING AN OHMMETER OR OTHER SUITABLE TESTING EQUIPMENT BEFORE ENERGIZING THE
FIXTURE. FAILURE T0 PROPERLY GROUND THE FIXTURE
WILL CREATE AN ELECTRICAL SHOCK HAZARD WHICH CAN
CAUSE SERIOUS INJURY OR DEATH.
EGS Electrical Group • 800-621-1506 • www.appletonelec.com Rev. E 06/27/11 Page 1
Classied Area Suitability of Code•Master 2™ Series Emergency PLT Fixtures
(Suitability includes use of reector.)
Lamp
Type
PLT
(4-pin)
PLT
(4-pin)
PLT
(4-pin)
Lamp Watts
52
(2x 26)
64
(2x 32)
84
(2x 42)
Class I, Div. 1 & 2 with Globe or
with Globe & Reector
UL/NEC Temp. Ident. No.
Supply
Wire °C
Ambient Temp °C
Nameplate
Marking
Groups
75 40 T6 (85 °C) C,D T4 (135 °C) E,F,G
75 40 T6 (85 °C) C,D T4 (135 °C) E,F,G
75 40 T6 (85 °C) C,D T4 (135 °C) E,F,G
Class II, Div. 1 & 2 with
Globe and Reector
UL/NEC Temp. Ident. No.
Nameplate
Marking
“T” Numbers Represent the Maximum Surface Temperature for Class I, Div. 1 & 2 and the Maximum Surface Temperature for Class II, Div. 1 & 2 Locations Under a Dust Blanket
“T”
Number
Temp.
Range
(˚C)
T1 350 325 T2 T2A T2B T2C T2D T3 T3A T3B T3C T4 T4A T5 T6
351-450 326-350 301-325 281-300 261-280 231-260 216-230 201-215 181-200 166-180 161-165 136-160 121-135 101-120 86-100 85
Dimensions
Groups
Dim. in Inches
52, 64, 84
Watt
Dimensions In Inches
Standard Dome
A B C A B C A B C A B C
24.5 23.5 12 24.36 23.36 12 24.61 23.61 17.5 22.2 21.2 17.5
Type Reector A B C
Deep Dome
PENDANT
Pendant Ceiling Bracket 25° Stanchion
11.2 5.9 18.7
10.56 7.0 20.3
BRACKET
CEILING
25° STANCHION
Cat. No. CMR-4HBCat. No. CMR-4ANCat. No. CMR-4ST
Page 2
650441-001 Rev. E 06/27/11
EGS Electrical Group • 800-621-1506 • www.appletonelec.com
INSTALLATION AND MAINTENANCE INSTRUCTIONS CODE•MASTER 2™ EMERGENCY PLT LUMINAIRE
Read carefully before attempting to install xture
VERIFY that the supply line voltage and xture nameplate voltage are compatible.
VERIFY that the xture operating temperature marked on nameplate complies with temperature restrictions of hazardous area.
USE supply wire rated for ambient temperature to be encountered. See nameplate.
INSTALLATION OF MOUNTING ACCESSORIES: PENDANT HOOD
Remove connection block from hood by loosening two mounting screws. Thread hood onto conduit and tighten locking set screw. Connect the ground wire to the green screw provided in hood. Connect supply wires to connection block. Replace connection block into mounting hood and tighten securely.
STANCHION ARM
Remove connection block. Thread stanchion onto conduit and tighten locking set screw. Connect electrically as described under pendant hood.
WALL BRACKET AND CEILING BOX
Install wall bracket or ceiling box on support surface with four bolts through four external mounting holes. Remove connection block and connect electrically as described under pendant hood.
INSTALLATION OF FIXTURE
Fixtures are completely wired, needing no additional eld wiring.
REMOVING GLOBE-RING ASSEMBLY
Loosen round head locking screw in globe ring until screw clears pry bars in ballast housing. Unthread globe-ring assembly (Do not hold glass globe to unthread globe-ring assembly as this might loosen globe locking ring. Should the globe locking ring be accidentally loosened it must be retightened. Loosen set screw in globe locking ring and tighten the locking ring, then retighten the set screw.) A screwdriver inserted through slot in ring and operated against pry bars in housing will assist in removing globe-ring assembly.
WIRING BALLAST
Loosen the two screws securing the socket support plate, remove plate and set aside (enough slack in the wires is provided). Locate xture lead marked “Line” and connect to ballast voltage lead corresponding to supply voltage. Replace socket support plate and tighten the two screws to secure into the xture.
INSTALLATION REMOTE TEST SWITCH
This unit MUST BE installed with a test switch as required by U.L. -924 “Emergency Lighting and Power Equipment” regulation. The test switch and switch enclosure must comply with the standards and ratings as listed on the ballast housing nameplate. Use appropriate conduit and ttings in accordance with the National Electrical Code. The test switch should be connected to the xture circuit as shown in the wiring diagram on page 4 and the device being connected.
PENDANT HOOD
LOCKING SET SCREWS
CONNECTION
BLOCK
WALL BRACKET
LOCKING
SET SCREW
GLOBE RING
SET SCREW
LOCKING RING
ROUND HEAD
SCREW
HOUSING
GLOBE
SCREWS FOR
REFLECTOR AND GUARD
CEILING BOX
LOCKING SET SCREWS
STANCHION
ARM
LOCKING SET SCREWS
ROUND HEAD
SCREW
SCREWS FOR REFLECTOR AND GUARD
SET
SCREW
LOCKING
RING
GLOBE
EGS Electrical Group • 800-621-1506 • www.appletonelec.com
650441-001 Rev. E 06/27/11 Page 3
INSTALLING LAMPS AND CLOSING FIXTURE
Check lamp type and wattage against xture nameplate, then install lamps. Rethread globe-ring assembly into housing until hand tight and lock in place by driving locking screw to engage pry bar.
GLOBE-RING ASSEMBLY TIGHTENING INSTRUCTIONS
The globe-ring assembly must be tightened to compress gasket to insure watertightness. Thread globe-ring assem­bly by hand until gasket makes contact with housing, then rotate additionally past three notches or for 2 inches of travel. To assist in rotating globe-ring assembly, use two screwdrivers inserted through slots on opposite sides of ring and operated against pry bars in housing.
INSTALLING FIXTURE ON MOUNTING ACCESSORY
Install assembled xture by threading into mounting acces­sory, the electrical contacts will automatically engage. Insure that xture is tightly threaded, then tighten locking set screw in bottom of mounting accessory.
INSTALLATION OF REFLECTOR AND GUARD
Reectors and guards are provided with keyhole slots. To install, loosen three screws in the globe ring and assemble reectors or guards. Tighten the three screws. When an angle reector is used, orient reector to direct the main light beam near desired direction. Fine tune by rotating globe ring assembly after loosening round head locking screw. Retighten locking screw.
RELAMPING CAUTION: DISCONNECT THE FIXTURE FROM SUP­PLY CIRCUIT BEFORE OPENING TO SERVICE. KEEP TIGHTLY CLOSED WHEN IN OPERATION.
To relamp, after disconnecting power, open xture as described under “Removing globe-ring assembly.” Remove old lamp and install new as described under “Installing lamp and Closing Fixture.”
HOUSING
GASKET SILICONE RUBBER
GLOBE RING
LOCKING RING
GLOBE
GLOBE-RING ASSEMBLY
Rotate additionally past three notches or for 2 inches of travel
WIRING DIAGRAMS
SEMI-CONTINUOUS OPERATION: 1-LAMP WIRING WITH EMERGENCY BALLAST FOR 26W, 32W & 42W LAMPS
UNSWITCHED LINE
BLK
WHT
GRD
2-LAMP
NCU
BLST
BLUE
BLUE
YEL
YEL
RED
RED
BLU
BLU/WHT
BROWN BROWN
YEL YEL
RED/WHT
RED
I42L
EMER
BLST
VIOLET
2
1 SELECT PROPER VOLTAGE LEAD & CAP UNUSED LEAD.
2 FOR 26W, 32W AND 42W APPLICATIONS, CAP OFF THE
INDIVIDUAL VIOLET LEADS.
3 DO NOT MATE CONNECTOR UNTIL INSTALLATION IS COMPLETE
VIOLET
WHT/BLK
WHT
BLK (120V)
ORG (277V)
BLK/ORG OR BLK/BRN
BLK/ORG OR BLK/BRN
RED OR RED/BLK
WHT/RED
WHT/BLK
BATTERY CONNECTOR SWITCH
3
1
INDICATOR LIGHT
Page 4
650441-001 Rev. E 06/27/11