Appleton Appleton and O-Z/Gedney Explosionproof Junction Boxes and Cast Control Centers Field Drilling and Tapping, F6450 Instruction Sheet

F6450
INSTRUCTION SHEET
E85310/E84577
APPLETON™ AND OZ/GEDNEY™ EXPLOSIONPROOF JUNCTION BOXES AND
CAST CONTROL CENTERS FIELD DRILLING AND TAPPING INSTRUCTIONS
• Series JBEW explosionproof junction boxes are used where hazardous materials are handled or stored. These junction boxes may be used for terminals, splicing wires, pull boxes or bus boxes.
• Series CSEW explosionproof cast control centers are used where hazardous materials are handled and stored. Cast control centers allow for auxiliary devices, such as push buttons, switches, pilot devices, etc. to be installed into one enclosure to satisfy a wide range of control applications. The CSEW Series of enclosures have only been investigated and CLASSIFIED by Underwriters Laboratories as to explosion
and re hazards.
• Refer to the product nameplate for important information regarding the hazardous location rating, enclosure environmental rating, agency approval(s), and important safety information. Adhere to all warning and caution statements that may be located on the exterior or interior of the enclosure.
• Class I, Division 1 locations require a conduit seal to be installed in each conduit run within the specied distance noted on the product
nameplate.
• Unused conduit openings shall have a certied close-up plug installed that has the same hazardous location ratings as the enclosure. The close-up plug must engage a minimum of ve full threads.
• Only qualied personnel should install, inspect, and perform regular maintenance on the enclosure.
• Take extreme care not to damage the at-machined ange when opening the enclosure cover. Damaging the ange could affect the enclosure’s
integrity to protect the hazardous area.
• Dirt, grease, and other foreign material must not accumulate on the at-machined ange surface of the body and cover. The cover and body must
fully mate against each other to provide the proper protection to the hazardous area.
• Do not attempt to repair the cover gasket if damaged; contact factory for replacement. Remove damaged gasket and continue to use the
enclosure. The gasket does not affect on the enclosure’s safety for use in hazardous locations. However, the enclosure’s environmental rating(s)
will no longer be valid.
• Install only approved drain and/or breather ttings that have the same hazardous location ratings as the enclosure. Note, if a drain and/or breather tting are installed, care must be taken during hosedown operations. The enclosure may be watertight, but the drain and breather may
not be.
• Always keep the cover bolts tight to prevent ignition of hazardous atmospheres and disconnect circuits before opening cover.
• Perform all machining operations prior to installation of the enclosure.
• The enclosure shall be installed in accordance with all national and local electrical codes, and be acceptable to the Authority Having Jurisdiction.
• Since the conditions of use are outside of our control, the purchaser should determine the suitability of the enclosure for the intended use and
assumes all risk and liability in regards to the specic application.
INSTRUCTIONS TO MAINTAIN THE ENCLOSURE APPROVALS.
RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
MOUNTING INSTALLATION
!
WARNING
1. Enclosure may be furnished with or without drilled and tapped openings. Drilling and tapping of conduit and cover openings are subject to the limitations of maximum size, number of openings, and spacing. Perform all machining operations prior to installing enclosure. Refer to the drilling and tapping sections for additional information.
2. It is the responsibility of the installer to properly install the enclosure using the mounting feet supplied with the enclosure.
3. Mount the enclosure on a at surface capable of supporting the enclosure, controls devices, wiring, etc. For the approximate weight of enclosure,
reference TABLE 1.
4. Attach conduit system with seal tting(s) in accordance with the required distance stated on the product nameplate.
5. Remove cover bolts and set aside. Take extreme care not to damage the at-machined ange of the body and cover.
6. Pull wires into enclosure leaving enough length to make the required electrical connections.
7. To meet the NEC and CEC requirements for grounding of electrical equipment, install the grounding kit supplied with enclosure. Refer to
GROUND LUG INSTALLATION section for information on how to install the grounding kit.
8. Inspect and perform a continuity test for all electrical connections, including an insulation resistance testing for unwanted grounds.
9. Check cover and body at-machined anges for scratches and/or gouges before installing cover. Clean the anges and inspect the cover gasket
for damage.
10. Line up the cover and body bolt holes. Hand start the corner bolts rst, before installing the remaining cover bolts. Tighten cover bolts to the
required torque.
11. Cover must fully seat against the body ange to provide a proper explosion proof joint.
12. Seal conduits entering enclosure per the manufacturer’s installation instructions and the applicable national and local electrical codes.
TO AVOID RISK OF ELECTRICAL SHOCK TURN POWER OFF BEFORE INSTALLATION AND MAINTENANCE
F6450 Rev. 3 02/1/2017 • Page 1 of 4Appleton • 1.800.621.1506 • www.appletonelec.com
TABLE 1
JBEW / CSEW
Enclosures
030303 1-1/2 N/A 2.00 1.50 Short 1 1 1 6 030703 1-1/2 N/A 2.25 5.75 Short 2 1 2 9 031103 1-1/2 N/A 2.25 9.75 Short 3 1 3 11 031503 1-1/2 N/A 2.25 13.75 Short 5 1 5 15 031803 1-1/2 N/A 2.00 16.50 Short 6 1 6 17 032403 1-1/2 N/A 2.25 22.75 Short 9 1 9 22 033003 1-1/2 N/A 2.25 28.33 Short 11 1 11 26 033603 1-1/2 N/A 2.25 34.33 Short 13 1 13 35 040604 1-1/2 M40 2.25 4.25 Short 2 1 2 15 040805 3/4 N/A 3.13 6.50 Short 3 1 3 15 040903 1-1/2 M40 2.62 7.75 Short 3 1 3 21 041604 1-1/2 M40 2.75 14.75 Short 6 1 6 22 050903 1-1/2 M40 4.63 9.13 Short 8 2 4 21 060604 2 N/A 4.25 4.25 Short 2 1 2 20 060804 2 M50 4.25 6.25 Short 6 2 3 20 060806 2 M50 4.25 6.25 Short 6 2 3 20 061004 1-1/2 M40 5.75 10.38 Short 6 2 3 27 061204 2 M50 4.13 10.13 Short 8 2 4 25 061604 1-1/2 M40 5.50 13.06 Short 10 2 5 32 061806 3 N/A 4.50 16.50 Short 14 2 7 35 070804 2 N/A 4.25 5.88 Short 6 2 3 15 071106 2 M50 7.44 10.94 Short 12 3 4 35 080806 2 M50 6.25 6.25 Short 9 3 3 30 081006 2 M50 6.25 8.25 Short 6 2 3 36 081304 2 M50 5.38 10.63 Short 10 2 5 25 081307 2 M50 9.00 14.19 Short 15 3 5 30 091105 2 M50 9.38 11.13 Short 16 4 4 22 091504 2 M50 6.25 12.38 Short 15 3 5 33 101004 2 M50 7.19 7.19 Short 6 2 3 38 101006 4 M75 7.19 7.19 Short 6 2 3 44 101208 4 M75 8.50 10.50 Long 12 3 4 55 101406 4 M75 8.75 12.75 Short 20 4 5 55 101408 4 M75 8.75 12.75 Short 20 4 5 60 102408 4 M75 8.50 21.63 Long 24 3 8 120 111606 2 N/A 8.25 13.25 Short 12 3 4 85 112005 3 M75 8.25 17.13 Long 21 3 7 85 112406 3 M75 7.75 21.38 Long 27 3 9 72 113006 3 M75 7.63 26.25 Long 33 3 11 113 121206 4 M75 9.25 9.25 Short 12 3 4 65 121208 4 M75 9.25 9.25 Short 12 3 4 70 121806 4 M75 9.25 15.25 Short 18 3 6 90 121808 4 M75 9.25 15.25 Short 18 3 6 101 122408 4 M75 10.00 22.00 Long 27 3 9 138 123608 4 M75 9.50 33.25 Long 39 3 13 218 133806 4 M75 10.63 35.13 Long 56 4 14 190 141406 4 M75 11.00 11.00 Short 16 4 4 98 141408 4 M75 11.00 11.00 Short 16 4 4 105 141608 4 M75 11.25 13.25 Short 18 3 6 120 142408 4 M75 11.88 21.25 Long 40 5 8 131 142808 4 M75 11.25 24.81 Long 36 4 9 170 153707 4 M75 15.38 34.00 Long 65 5 13 250 161606 4 M75 13.25 13.25 Long 25 5 5 132 161608 4 M75 13.25 13.25 Long 25 5 5 140 161812 4 M75 14.75 16.75 Long 42 6 7 150 162005 2 M50 12.63 17.25 Short 30 5 6 98 162205 3 M75 13.00 19.00 Long 35 5 7 130 162206 2 M50 13.00 19.00 Long 35 5 7 130 162408 4 M75 13.25 21.25 Long 40 5 8 180 162805 3 M75 13.25 25.25 Long 50 5 10 188
NOTE: JBEW and CSEW catalog numbers may contain the prex “A”, “C” or “N”
Maximum Conduit
Opening Size
NPT Metric Width Length Wide Tall
Flat Machinable Area (in.)
CSEW Cover Openings
Control Operator
Barrel
Max. Number
of Operators
Number of Rows
Weight (lbs.)
Enclosure
Approx.
F6450 Rev. 3 02/1/2017 • Page 2 of 4Appleton • 1.800.621.1506 • www.appletonelec.com
TABLE 1 (continued)
PERATORS2
.
5
3
/
414NPSM
JBEW / CSEW
Enclosures
Maximum Conduit
Opening Size
Flat Machinable Area (in.)
NPT Metric Width Length Wide Tall
CSEW Cover Openings
Control Operator
Barrel
Max. Number
of Operators
Number of Rows
Weight (lbs.)
162806 4 M75 13.25 25.25 Long 50 5 10 150 164208 4 M75 12.25 38.13 Long 40 4 10 180 181806 4 M75 15.25 15.25 Long 36 6 6 188 181808 4 M75 15.25 15.25 Long 36 6 6 198 182408 4 M75 15.25 21.25 Long 48 6 8 224 182410 4 M75 15.25 21.25 Long 48 6 8 235 183008 4 M75 15.25 27.25 Long 66 6 11 265 183608 4 M75 14.50 33.50 Long 78 6 13 250 183610 4 M75 14.50 33.50 Long 78 6 13 270 184207 4 M75 15.63 39.25 Long 90 6 15 310 184806 3 M75 14.25 44.25 Long 85 5 7 350 206008 4 M75 16.00 56.00 Long 132 6 22 521 242408 4 M75 21.25 21.25 Long 64 8 8 225 242410 4 M75 21.25 21.25 Long 64 8 8 240 242416 4 M75 21.25 21.25 Long 64 8 8 280 243008 4 M75 19.88 25.88 Long 80 8 10 420 243608 4 M75 21.00 33.25 Long 104 8 13 420 243610 4 M75 21.00 33.25 Long 104 8 13 450 303808 4 M75 31.88 39.88 Long 130 10 13 600 303816 4 M75 31.88 39.88 Long 130 10 13 800 303817 4 M75 26.00 34.00 Long 130 10 13 840
NOTE: JBEW and CSEW catalog numbers may contain the prex “A”, “C” or “N”
Enclosure
Approx.
GROUND LUG INSTALLATION
!
CAUTION
1. To meet the NEC® and CEC requirements for grounding of electrical equipment, the ground lug must be installed.
Contact the factory if a grounding kit was not supplied with the enclosure.
2. If the enclosure was ordered with a mounting pan, install the ground lug in the tapped hole provided using a 1/4-20
screw.
3. If the enclosure does not have a mounting pan, install the ground lug in one of the tapped mounting bosses (stand-offs).
4. Peel off and place the ground symbol sticker next to the ground lug.
5. If the ground conductor is larger than a #2 AWG, contact the factory for an additional lug (Grounding Kit CGL-500).
DO NOT TERMINATE COPPER AND ALUMINUM CONDUCTORS ON THE SAME LUG
CSEW COVER OPENINGS
!
CAUTION
1. Cover openings for control operators shall be 3/4-14 NPSM with a minimum of seven threads of engagement for Class I, Group B hazardous locations; ve threads of engagement for Class I, Group C & D.
2. Only use approved open type auxiliary devices that are suitable for the same hazardous locations marked on the enclosure nameplate.
3. Control operators can be placed anywhere in the at machinable area on the cover. Cover openings may not be located outside the indicated at machinable area. Reference FIGURE 1.
4. To determine the maximum number of cover operators permissible in the at machinable area, refer to TABLE 1.
If enclosure has window(s) consult factory for maximum number of operators permissible.
5. Openings must be at least 0.125 inch from the edge of the at machining area.
6. Openings shall not be less than 2.5-inches center-to-center vertically and horizontally, reference FIGURE 2.
7. Mark the hole location on the at machinable area.
8. Drill a 0.938 inch diameter hole in the cover perpendicular to the surface.
9. Tap the hole using a 3/4-NPS tap. Only use machining oil suitable for aluminum.
10. Enclosure covers having a thickness greater than 0.88 inches require a control operator with a long barrel. Reference TABLE 1.
11. Install the approved auxiliary device per the manufacturer’s installation instructions and the applicable national and local
electrical codes.
12. Cover openings must be properly closed with an approved auxiliary device or 3/4-NPSM plug.
COVER OPENINGS SHALL BE 3/4-14 NPSM AND NOT LESS THAN 2.5 INCHES CENTER-TO-CENTER
GROUND SYMBOL
FIGURE 1
W
L
FLAT MACHINABLE AREA -
FIGURE 2
3/4"-14 NPSM
OPERATORS 2.5”
O
OPERATORS 2.5"
CENTERS, MIN.
CENTERS, MIN.
F6450 Rev. 3 02/1/2017 • Page 3 of 4Appleton • 1.800.621.1506 • www.appletonelec.com
JBEW AND CSEW CONDUIT OPENINGS
INSIDE RADIUS
1.5"
0.75"
BOTTOM WALL
SIDEWALL
Conduit opening without conduit stop
THREADED RIGID CONDUIT
ROUNDED
!
IMPORTANT
ALL CONDUIT OPENINGS MUST MEET THE FOLLOWING REQUIREMENTS
1. Use TABLE 3 to determine the maximum number of conduit openings permissible to be drilled and tapped on each side of the enclosure. Openings must be at least 1.5 inches from the inside adjacent sidewall and 0.75 inches from the inside bottom wall. See FIGURE 3 and 4 for additional information.
2. Consult factory if eld drilling of enclosure back is necessary.
3. For the maximum conduit opening size permissible to be drilled and tapped into the side of the enclosure, reference TABLE 1. Minimum allowable conduit opening that may be drilled and tapped is 1/2 inch.
4. NPT conduit openings must have at least ve full threads of engagement between the conduit and enclosure body. ISO-Metric conduit openings must have at least seven full threads of engagement between the conduit and enclosure body. To determine the minimum wall thickness to engage ve full NPT threads into the conduit opening without a conduit stop, see TABLE 2.
5. For the minimum center-to-center spacing of any two conduit opening sizes, reference TABLE 3. Example: Minimum spacing between a 1.0 inch NPT opening (rst column) and 3.0 inch NPT opening (rst row) is 4.13 inches.
6. Conduit openings shall be a modied National Standard Pipe Taper (NPT) thread, 3/4 inch per foot per ANSI/ASME B1.20.1 or ISO-Metric thread with a 6H/g tolerance t per the Standard for General Purpose
Metric Screw Threads, ISO 965 Part 1 and 3.
7. NPT conduit openings shall gauge from +1/2 to +3-1/2 turns beyond the L-1 gauging notch in lieu of the
−1 to +1 turns described in ANSI/ASME B1.20.1.
8. Conduit must be able to reach wrench tight without bottoming out on the unthreaded portion of the conduit. Do not over tap conduit opening, reference TABLE 2 for maximum number of threads.
9. All conduit openings without a conduit stop shall have a smooth and well-rounded inner end as shown in
FIGURE 5.
10. To install a conduit stop, use an approved reducer bushing having the same hazardous location ratings,
Class and Groups as the enclosure. For UL Listed Outlet Boxes and Classied Enclosures use a UL Listed reducer bushing. CSA International Certied Enclosures use a CSA Certied reducer bushing. To install the reducer bushing, drill and tap to the next larger NPT size opening using the minimum center­to-center spacing requirements in TABLE 3.
11. To install a conduit bushing, counter bore a 1/8-inch (maximum) larger hole than the outer diameter of the conduit to a depth that will still allow for a minimum of ve full threads of engagement, reference TABLE 2. NPT conduit openings from 2.5 -to- 4 inches may have the conduit bushing applied to the
exposed end of the conduit without counter boring.
FIGURE 3
FIGURE 4
FIGURE 5
TABLE 2
Conduit Size,
NPT
1/2 -to- 3/4 14 0.375 in. 7
1 -to- 2 11-1/2 0.428 in. 8
2-1/2 -to- 4 8 0.625 in. 9
TABLE 3: CONDUIT OPENING MINIMUM CENTER-TO-CENTER SPACING, INCHES
Conduit Size 1/2 (M20) 3/4 (M25) 1 (M32) 1-1/4 (M40) 1-1/2 (M50) 2-1/2 (M75) 2-1/2 (M75) 3 3-1/2 4
1/2 (M20) 3/4 (M25)
1 (M32) 1-1/4 (M40) 1-1/2 (M50)
2 (M63) 2-1/2 (M75)
3
3-1/2
4
All technical information and recommendations contained in this instruction sheet are based on industry practices and standards we believe to be reliable and accurate. It is the responsibility of the user to ensure the product is installed and used in safe manner that comply with all local and national electrical codes acceptable to the Authority Having Jurisdiction.
Except as expressly provided by Appleton Grp, LLC (Appleton), Appleton products are intended for ultimate purchase by industrial users and for operation by persons trained and experienced in the use and maintenance of this equipment
and not for consumers or consumer use. Appleton warranties DO NOT extend to, and no reseller is authorized to extend Appleton’s warranties to any consumer.
While every precaution has been taken to ensure accuracy and completeness in this manual, Appleton Grp, LLC. assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or
omissions. Specications are subject to change without notice. The Appleton and Emerson logos are registered in the U.S. Patent and Trademark Ofce. All other product or service names are the property of their registered owners.
©2017 Appleton Grp, LLC. All rights reserved.
No. of Threads
per Inch
Min. Wall Thickness for
5 Thread Engagement
Max. No.
of Threads
2.13 2.13 2.25 2.63 2.81 3.13 3.63 4 4.25 4.5
2.13 2.13 2.25 2.63 2.81 3.13 3.63 4 4.25 4.5
2.25 2.25 2.38 2.81 3 3.25 3.75 4.13 4.5 4.88
2.63 2.63 2.81 3.13 3.31 3.63 4.13 4.5 4.75 5
2.81 2.81 3 3.31 3.5 3.81 4.31 4.63 4.94 5.25
3.13 3.13 3.25 3.63 3.81 4.13 4.63 5 5.38 5.75
3.63 3.63 3.75 4.13 4.31 4.63 5.13 5.31 5.75 6.13
4 4 4.13 4.5 4.63 5 5.31 5.75 6 6.25
4.25 4.25 4.5 4.75 4.94 5.38 5.75 6 6.25 6.5
4.5 4.5 4.88 5 5.25 5.75 6.13 6.25 6.5 6.75
F6450 Rev. 3 01/23/2017 • Page 4 of 4
Loading...