504851-000 INSTRUCTION SHEET
Appleton™ ALPN/ALPF/APPN/APPF Explosion-Proof Panelboard
Instruction Manual
RETAIN THIS INSTRUCTION SHEET FOR FUTURE REFERENCE. For safe installation and
operation, please read these instructions carefully and with full understanding.
Signal Words Defined
DANGER indicates a hazardous situation which, if not avoided, will result in death or
serious injury. WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury. CAUTION indicates a hazardous situation which, if not
avoided, could result in minor or moderate injury. NOTICE is used to address practices
not related to physical injury.
1.0 SCOPE
• This manual contains general information with regards to description, installation and
maintenance of EGS ALPN/ALPF Series Explosion Proof Panelboards, for up to fortytwo branch circuit breakers. It does not cover special modications, additions
or deletions, other than those listed in the catalogue.
• More specic information, if required, can be obtained by contacting the EGS Sales
representative in your area.
2.0 INSTALLATION
2.1 Mounting
The ALPN/ALPF Series panelboard is intended to be mounted vertically. Provided for this
purpose are four mounting feet with keyhole slots, sized to accommodate 3/8” bolts. For
mounting centers, see Section 6.1.
2.2 Wiring
Wire after mounting.
Open cover by loosening all cover bolts; do not remove bolts as they are captive to the cover. Supply circuit is wired into the main
panel lugs or main circuit breaker. A main ground lug is provided for system ground. For panelboards that are prewired (ALPF or
APPF), supply circuit connections are made in the top/bottom box main terminals.
2.2.1 Standard Breaker
Load circuit line goes to breaker, load circuit neutral to panel neutral bar, load circuit ground to ground bar.
2.2.2 GFI Breaker
Load circuit line and neutral go to breaker, load circuit ground to ground bar, breaker neutral to panel neutral bar. (See gure 6.4)
2.2.3 GFI Breaker with Alarm Contact
Load circuit line and neutral go to breaker, load circuit ground to ground bar, breaker neutral to panel neutral bar, alarm contact
leads to external enunciator. (See gure 6.4)
504851-000 Rev. A 02/07/19 • Page 1 of 6
3.0 MAINTENANCE
3.1 Flange/Cover Closure
After each opening and before each closure of the cover, the anges of both box and cover must be wiped clean of any dust, dirt or
metal particles which may prevent complete and tight closure of the unit. Enclosure ange should be oiled or greased. Failure to do so
may result in an explosion hazard. During normal operation, ensure that all cover screws are installed and kept tight. Failure to do so
may result in an explosion hazard.
3.2 GFI Breaker Testing
Each GFI breaker in the panel must be tested monthly to ensure maximum protection against electrical shock hazard. The date of
this test should be recorded on an appropriate record sheet, posted in a conspicuous place on or adjacent to the panel. Test record
stickers are supplied with the panel.
3.3 Parts Replacement
Before replacing any parts of the panel, which may require opening of the cover, ensure that the power to the panel mains
is locked off.
3.3.1 Standard Breaker
Disconnect the load circuit line from the breaker; replace with appropriate breaker supplied by EGS or Cutler Hammer. Reconnect
as per Section 3.2.1.
3.3.2 GFI Breaker
Disconnect the load circuit line and neutral line from the breaker and breaker neutral from the panel neutral bar; replace with
appropriate breaker supplied by EGS or Cutler Hammer.
Reconnect as per Section 3.2.2.
3.3.3 GFI Breaker with Alarm Contact
Disconnect the load circuit line and neutral line from the breaker, breaker neutral from the panel neutral bar and alarm contact
leads from the external enunciator leads; replace with appropriate breaker supplied by EGS or Cutler Hammer. Reconnect as per
Section 3.2.3.
3.4 Cleaning
The exterior of the panel may be washed with water and mild soap solution. Avoid abrasives which may damage the nish, especially
on the Lexan circuit directory card shields or Lamacoid operator cover or legend plates.
4.0 OPERATION
4.1 Breaker
The status of the breaker is determined by the position of the knob as indicated by the label at the top of the column of operators.
Operation is as simple as twisting the knob to the desired position. (See g. 6.2)
NOTE: After closing panel door, whether during initial installation or after maintenance be sure to TWIST or PULL and TWIST (for
APPN/F) exterior actuator to ensure proper mechanical interface between exterior actuator and internal breaker toggle. See Panel
Board Actuator Instruction Sheet.
CAUTION: Never try to defeat a LOCKED OUT breaker.
4.2 GFI Test Button
The GFI breaker test is performed by depressing the test button adjacent to the GFI breaker. A positive test will put the breaker in
tripped condition. Reset the breaker to resume normal operation.
4.3 Resetting Tripped Breakers
Resetting is accomplished by rst turning the breaker OFF, and then ON again. A tripped breaker cannot be turned ON before it
is RESET. If it cannot be turned ON, it is either not RESET, or it is being subjected to conditions which cause an immediate trip.
Investigate Circuit.
4.4 Heater
The heater is factory pre-wired to the panel interior main and neutral lugs. It sometimes can be wired through a fuse. Heater operation
is automatic.
504851-000 Rev. A 02/07/19 • Page 2 of 6