AEXMS Series Manual Motor Starters
CONTROLS: NEC/CEC EXPLOSIONPROOF MOTOR STARTERS
Explosionproof, Dust-Ignitionproof, Watertight
NEC:
Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 3R, 4, 4X, 7CD, 9EFG
Applications
• Explosionproof across the line manual motor starters for
starting polyphase Vac motors.
Features
• Rugged, compact enclosures supplied with Square D or
Cutler-Hammer ✢ manual motor starters using three overloads.
• Mating surfaces are precision milled to exceed explosionproof
specications. Covers secure with stainless steel (300 Series)
hex head bolts.
• O-ring gasket provides NEMA Type 4 rating.
• Four cast on mounting feet allow easy rack or individual
mounting.
Enclosures have standard conduit openings at top and bottom.
• Operating levers are positive operating and can be locked in the
ON or OFF position.
Standard Materials
• Enclosure and handle: cast copperfree (4/10 of 1%) aluminum
• Shaft, bushing and cover bolts: stainless steel (300 Series)
• Mounting hardware: stainless steel
Standard Finishes
• Housing: two coat epoxy powder coat
NEC Certifications and Compliances
• UL Standards: UL 508, UL 698, UL 1203
• UL Listed: E76550
Catalog Number
AEXMS-A 0 2 Square D 2510 TB01
AEXMS-F 0 2 Cutler-Hammer B100 M0B
AEXMS-D 0 3 Square D 2510 TB02
AEXMS-J 0 3 Cutler-Hammer B100 M0C
AEXMS-B 1 2 Square D 2510 TC01
AEXMS-G 1 2 Cutler-Hammer B100 M1B
AEXMS-E 1 3 Square D 2510 TC03
AEXMS-K 1 3 Cutler-Hammer B100 M1C
AEXMS-C 1-1/2 2 Square D 2510 TC02
AEXMS-H 1-1/2 2 Cutler-Hammer B100 MDB
Horsepower Ratings
Starter Size Poles Phase
1-1/2 2 1 3 5 — — —
▲ Add suffix for heater. See table on next page.
Square D is a registered trademark of Schneider Electric.
✢ Cutler-Hammer is a registered trademark of Eaton Corporation.
▲
0 3 3 2 3 5 — —
1 3 3 3 7-1/2 10 — —
0 2 1 1 2 — 1 1-1/2
1 2 1 2 3 — 1-1/2 2
NEMA Size Number of Poles Motor Starter Series Motor Starter Model Number
Max. Horsepower Ratings
Volts AC Volts DC
120 208/240 480/600 120 230
315
AEXMS Series AC Manual Motor Starter Heater
CONTROLS: NEC/CEC EXPLOSIONPROOF MOTOR STARTERS
Explosionproof, Dust-Ignitionproof, Watertight
NEC:
Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 3R, 4, 4X, 7CD, 9EFG
Select heater elements based on motor nameplate listed Full Load
Amps (FLA). Trip rating of elements is 125% of motor minimum
FLA listed for the elements. Three heaters required per starter.
Heater Table
Motor Full Load Amps
at +40 °C (+104 °F)
0.28 - 0.29 -B44 0.25 - 0.26 -FH03
0.30 - 0.33 -B51 0.27 - 0.29 -FH04
0.34 - 0.36 -B57 0.30 - 0.32 -FH05
0.37 - 0.44 -B63 0.33 - 0.35 -FH06
0.45 - 0.52 -B71 0.36 - 0.39 -FH07
0.53 - 0.59 -B81 0.40 - 0.44 -FH08
0.60 - 0.64 -B92 0.45 - 0.49 -FH09
0.65 - 0.71 -B103 0.50 - 0.55 -FH10
0.72 - 0.80 -B116 0.56 - 0.61 -FH11
0.81 - 0.90 -B130 0.62 - 0.68 -FH12
0.91 - 1.03 -B145 0.69 - 0.75 -FH13
1.04 - 1.14 -B167 0.76 - 0.83 -FH14
1.15 - 1.27 -B188 0.84 - 0.91 -FH15
1.28 - 1.44 -B210 0.92 - 1.00 -FH16
1.45 - 1.63 -B240 1.01 - 1.10 -FH17
1.64 - 1.79 -B265 1.11 - 1.22 -FH18
1.80 - 2.01 -B300 1.23 - 1.35 -FH19
2.02 - 2.19 -B330 1.36 - 1.50 -FH20
2.20 - 2.52 -B370 1.51 - 1.66 -FH21
2.53 - 2.95 -B415 1.67 - 1.84 -FH22
2.96 - 3.17 -B485 1.85 - 2.03 -FH23
3.18 - 3.50 -B550 2.04 - 2.23 -FH24
3.51 - 3.73 -B625 2.24 - 2.45 -FH25
3.74 - 4.22 -B690 2.46 - 2.69 -FH26
4.23 - 4.68 -B770 2.70 - 2.95 -FH27
4.69 - 4.98 -B820 2.96 - 3.23 -FH28
4.99 - 5.59 -B910 3.24 - 3.53 -FH29
5.60 - 6.43 -B102 3.54 - 3.85 -FH30
6.44 - 7.41 -B115 3.87 - 4.22 -FH31
7.42 - 8.02 -B128 4.23 - 4.61 -FH32
8.03 - 8.59 -B140 4.62 - 5.03 -FH33
8.60 - 9.52 -B155 5.04 - 5.49 -FH34
9.53 - 10.5 -B175 5.50 - 5.99 -FH35
10.6 - 11.2 -B195 6.00 - 6.53 -FH36
11.3 - 12.7 -B220 6.54 - 7.11 -FH37
12.8 - 14.3 -B250 7.12 - 7.73 -FH38
14.4 - 16.1 -B280 7.74 - 8.40 -FH39
16.2 - 17.8 -B320 8.41 - 9.12 -FH40
17.9 - 20.1 -B360 9.13 - 9.89 -FH41
20.2 - 22.6 -B400 9.90 - 1.70 -FH42
22.7 - 25.5 -B450 10.8 - 11.8 -FH43
25.6 - 26.0 -B500 11.9 - 13.0 -FH44
Square D
Add
Suffix
Cutler-Hammer
Motor Full Load Amps
at +40 °C (+104 °F)
13.1 - 14.0 -FH45
14.1 - 15.0 -FH46
15.1 - 16.1 -FH47
16.2 - 17.3 -FH48
17.4 - 18.6 -FH49
18.7 - 20.0 -FH50
20.1 - 21.5 -FH51
21.6 - 23.2 -FH52
23.3 - 25.0 -FH53
25.1 - 26.8 -FH54
Dimensions in Millimeters (Inches)
✢
Add
Suffix
Side View
Cover View
Bottom View
Square D is a registered trademark of Schneider Electric.