Apollo America SM-501-N, SM-501-P Installation Manual

INST AP-191 B060405
You
You
in Control
in Control
AND
AIR PRODUCTS
AIR PRODUCTS
CONTROLS
CONTROLS
SM-501-N 4-Wire, Ionization Type SM-501-P 4-Wire, Photoelectric Type
AIR PRODUCTS AND CONTROLS INC. INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR SM-501 SERIES DUCT SMOKE DETECTORS
PRODUCT OVERVIEW
PRODUCT APPLICATION
SM-501 Series duct smoke detectors provide early detection of smoke and products of combustion present in air moving through an HVAC duct supply, return, or both in commercial, industrial, and res­idential applications. These devices are designed to prevent the recirculation of smoke in areas by the air handling system’s fans, and blowers. Complete systems may be shut down in the event of smoke detection.
**
NOTE: For the correct installation of a duct smoke unit, please
refer to the NFPA 72 (National Fire Alarm Code), NFPA 90A (Standard for Installation of Air Conditioning and Ventilation Systems),NFPA 92A (Recommended Practice for Smoke Control Systems.), NFPA 5000 (Building Construction and Safety Code), IMC (International Mechanical Code), and IFC (International Fire Code).
This detector is not intended for open area protection nor should it be used for early warning detection or replace a regular fire detection system.
PRODUCT DESCRIPTION
The SM-501 Series smoke detector is fitted with a mounting base that will accept an ionization smoke detector head model 55000-225APO (or 55000-250APO) or photoelectric smoke detector head model 55000-328APO (or 55000-350APO). The duct unit supports two sets of form “C” alarm contacts and one form “C” trouble contact. The trou­ble contact supervises the presence of the input power and removal of the detector head.
**
THE TROUBLE CONTACTS (TERMINALS 13-14-15) ARE
SHOWN IN THE NON-ENERGIZED CONDITION. IN NORMAL OPERATION, CONTACTS WILL BE REVERSED.
The trouble contacts will not
operate in the event of a smoke alarm. The SM-501 Series duct detector will operate from various input voltage sources; namely 24VAC, 24VDC, 115VAC and 230VAC.
SAMPLING TUBES
The operating principle of a duct detector is based on the Venturi effect. Two tubes extend into the HVAC duct. Air flowing through the duct is forced into the air intake (inlet) tube via the air intake holes, (facing the airflow) and passes over the detector head. The air will be drawn out via the exhaust tube back into the HVAC duct. (A 7” exhaust tube is provided in the installation kit.) When the concentra­tion of smoke particles suspended in the air stream reach the alarm threshold of the detector head, the unit will go into alarm.
The duct smoke detector units are designed to operate in duct widths from 6” to 10’ wide with an air velocity between 500 to 4,000 feet per minute. To verify correct installation, the pressure differential between
the sampling (high side) and exhaust (low side) tubes should be measured using a Magnehelic pressure gauge or equivalent. An acceptable reading is between 0.01 and 1.2 inches of water.
To minimize the impact of air turbulence and stratification on per­formance, a duct smoke detector should be located as far as pos­sible downstream from any obstruction (i.e. deflector plates, elbows, dampers, etc.). In all situations, confirmation of velocity and pres­sure differential within specifications is required.
REMOTE ACCESSORIES
Audible and visual alarm indicators, remote status indicators, and remote reset/test switches can be accommodated by the SM-501 Series duct units by connecting to DC voltage output terminals 16 through 21. These terminals are not supervised and the voltage/current will only be present when the detector unit is in alarm. The remote pilot (green) LED will be permanently illuminat­ed when connected to the output terminals as long as input power and detector head are present.
SM-501 AT-A-GLANCE
MODEL NUMBER:
SM-501-N 4-Wire Ionization Duct Smoke Detector SM-501-P 4-Wire Photoelectric Duct Smoke Detector
DETECTOR HEAD MODEL NUMBER:
Ionization Detector Head: 55000-225APO Photoelectric Detector Head: 55000-328APO
PO
WER REQUIREMENTS:
STANDBY CURRENT ALARM CURRENT
24VAC 35.0mA 24VAC 74.0mA 24VDC 15.0mA 24VDC 56.0mA 115VAC 25.0mA 115VAC 32.0mA 230VAC 12.0mA 230VAC 16.0mA
RELAY CONTACT RATINGS:
Alarm contacts: 2 Sets form “C” rated at 10A @ 115VAC resistive Trouble contacts: 1 Set form “C” rated at 10A @ 115VAC resistive Air velocity: 500 to 4,000ft/min. Ambient temperature:SM-501-N: 32°F to 158°F (0°C to 70°C)
SM-501-P: 32°F to 140°F (0°C to 60°C) Humidity: 10% to 85% RH Non-Condensing/Non-Freezing Material: 18GA steel back box, clear plastic cover
(Makrolon 94V-0) Finish: Gray paint on black box Dimensions: 9 1/8” L X 7 1/4” W X 2 1/4” H Max. net wt.: 3 1/2 lbs. Radioactive element: SM-501-N (Ionization) - Americium 241,
0.9 micro curie.
Do not expose to corrosive atmospheres.
1
INST AP-191 B060405
LOCA
TION PREREQUISITES
This guideline contains general information on duct smoke detec­tor installation, but does not preclude the NFPA and/or ICC docu­ments listed. Air Products and Controls assumes no responsibility for improperly installed duct detectors. To determine the correct installation position for an SM-501 Series duct smoke detector, the following factors must be considered.
1) A uniform non-turbulent (laminar) airflow between 500 ft/min. to 4,000 ft/min. must be present in the HVAC duct. To determine duct velocities, examine the engineering specifications that define the expected velocities or use an Alnor model 6000AP velocity meter (or equivalent).
2) To minimize the impact of air turbulence and stratification on performance, a duct smoke detector should be located as far as possible downstream from any obstruction (i.e. deflector plates, elbows, dampers, etc.). In all situations, confirmation of velocity and pressure differential within specifications is required.
The pressure differential between the input sampling (high pressure) tube and exhaust (low pressure) tube for the SM-501 Series smoke duct detector should be greater than 0.01 inches of water and less than 1.2 inches of water.
3) Identify a code compliant location (supply or return side, or both) for the installation of the duct unit that will permit easy access for viewing and serviceability.
4) When installing on the return side, install duct units prior to the air being exhausted from the building or diluted with outside “fresh” air.
5) When installing duct smoke units downstream of filters, fires occurring in the filters will be detected, but if the filters become blocked, insufficient air flow through the duct unit will prevent the correct operation of the duct detector. Duct units installed in the supply air side may monitor upstream equipment and/or filters.
6) Where possible, install duct detectors upstream of air humidifiers and downstream of dehumidifiers.
7) To prevent false alarms, the duct detector should not be mounted in areas of extreme high or low temperatures, in areas where high humidity exists, or in areas where the duct may contain gases or excessive dust.
SAMPLING TUBE ASSEMBLY
Sampling tubes are to be ordered separately in one of four stan­dard lengths.
STS-1.0 For duct widths of 6” TO 1.0’
STS-2.5 For duct widths of 1.0’ TO 2.5’
STS-5.0 For duct widths of 2.5’ TO 5.0’
STS-10.0 For duct widths of 5.0’ TO 10.0’
Standard sampling tubes are steel tubes with air intake holes drilled the entire length of the tube. These tubes must be cut to length and should span the entire width of the duct. Sampling tubes over 3.0’ must be supported on the opposite side of the duct.
MECHANICAL INSTALLATION
To ensure the correct operation of the sensing tube, the red end cap (red stopper in installation kit) must be inserted in the end of the air intake sampling tube. For custom duct widths, always use the next longest standard size and cut down to the exact requirement.
Once the airflow direction has been determined, insert the inlet and exhaust tubes into the sampling tube connectors fitted to the back of the duct smoke detector which are equipped with set screws. These connectors will allow the tubes to be correctly ori­entated and secured by tightening the set screw. Ensure air intake sampling tube is positioned so that the inlet holes are directly facing the airflow.
DUCT PREPARATION
Remove mounting template from the installation kit. Remove paper backing from the mounting template and affix it to the duct at the desired location. Using the template as a guide, drill (4) mounting holes (3/32” diam.) for the # 12 X 1/2” sheet metal screws packaged in the installation kit. Drill or punch (2) 1 3/8” holes for inlet sampling and exhaust tubes, using the template as a guide. Clean all holes.
MOUNTING
After securing the sampling and exhaust tubes to the duct smoke unit, (or initially placing the tubes through the 1 3/8” holes drilled or punched in the HVAC duct to accept the inlet sampling and exhaust tubes and then attaching them to the duct unit), hold the duct unit assembly in position and use (4) # 12 X 1/2” sheet metal screws (packaged in the installation kit) to secure the duct smoke detector to the HVAC duct sheet metal.
AIR SAMPLING VERIFICATION
To ensure correct operation of the duct unit use a Magnehelic dif­ferential pressure gauge, Dwyer 2000 or 4000 Series (or equiv­alent) to determine the differential pressure between the inlet (high side) and exhaust (low side) tubes. The differential pres­sure between the two tubes should be greater than 0.01 inches of water and less than 1.2 inches of water.
2
Loading...
+ 4 hidden pages