Apollo America MSR-50R Installation Manual

PRODUCT DESCRIPTION
The MSR Series remote accessories offer the most comprehensive set of features, functionality and ease of installation ever available in a duct smoke detector remote accessory. They are compatible with the range of duct smoke detectors as described herein. All MSR-Series remote accessories are compatible with standard Decora style cover plates (base color choice plate included).
The MSR-50 Series
MSR-50RM
The MSR-50RM provides a hidden magnet test switch and a pushbutton reset. The indicator/control assembly provides:
• Tri-color visual indication of detector Pilot, Trouble and Alarm conditions
• Magnet operated detector Test function
• Pushbutton operated detector Reset function
• Lever-operated quick connect “No-Tools” four-position terminal block
• Port for plugging in Audio/Visual assembly
To put the detector in alarm, place a magnet over the RESET button on the faceplate of the accessory. The detector will stay in Alarm until the RESET pushbutton is pressed. Also the RESET button can be used to reset a detector-initiated alarm.
MSR-50RK
The MSR-50RK indicator/control assembly provides:
• Tri-color visual indication of detector Pilot, Trouble and Alarm conditions
• Key-operated detector Test and Reset function
• Lever-operated quick connect “No-Tools” four-position terminal block
• Port for plugging in Audio/Visual assembly
MSR- Series Audible and Visible Alarm Indicators
The MSR-AV, MSR-A and MSR-V are designed to provide and/or augment the Audible and Visual Alarm indications of the MSR-50RM, MSR-50RK and MSR-100R Remote Accessories.They will fit in a second-gang configuration and require no additional wiring, other than to plug into the main control.
MSR-AV – Remote Alarm Module Combination Sounder (Audible) and Strobe (Visual) MSR-A – Remote Alarm Sounder Module (Audible) MSR-V – Remote Alarm Sub-Assembly Strobe (Visual) for use with MSR-50A Remote Alarm Sounder Module
Note: The MSR-AV, MSR-A and MSR-V are intended for Private Mode Audible and Visual notification only. They are not intended for Public Mode Audible
and Visual evacuation and relocation signaling. Note: An MSR-V combined with an MSR-A will provide the same functionality as an MSR-AV. All “V” code units come with Strobe Lens decals for optional use. “SMOKE” in blue lettering and “FIRE” in red lettering, 2 each in both vertical and horizontal orientations. All units require one gang of space in a standard deep gang box – not supplied.
Installation
To install an MSR-A or MSR-AV Module to a Controller (MSR-50RM, MSR-50RK or MSR-100R), simply plug the provided polarized connector into the Controller’s pins which are indicated as “STROBE” on the back of those units.
To install an MSR-V Sub-Assembly to an MSR-A Module simply position the three link pins on the MSR-V Sub-Assembly over the three provided plug holes in the MSR-A Module’s front cover and push firmly until the pins are seated and the four snap-in legs on the MSR-V Sub-Assembly completely snap-in and latch to the mating surfaces provided on the MSR-A Module. It should be noted that when connecting the MSR-AV or MSR-A to an MSR-100R, a louder yet redundant Audible Alarm signal will be obtained compared to the built-in Alarm / Trouble buzzer in the MSR-100R.
You
in Control
AND
AIR PRODUCTS
AIR PRODUCTS
CONTROLS
AIR PRODUCTS AND CONTROLS INC.
INSTALLATION GUIDE FOR MSR- SERIES REMOTE ACCESSORIES
MSR-50 Series
INST APD0397 B110223
MAGNET
PLACEMENT
MSR-50RM
MSR-50RM
MSR-50RK
MSR-50A
MSR-50SA
AND
CONTROLS
You
in Control
US Toll Free 888.332.2241 • Phone 248.332.3900 • Fax 248.332.8807 • www.ap-c.com
25 Corporate DriveAuburn Hills, MI 48326 USA
PACKAGE CONTENTS AND STROBE CONSTRUCTION
Remote accessories that include the indicator/control unit are shipped with the following parts:
• Installation Instructions
• Indicator/Control Unit with back box mounting screws (back box not supplied)
• Keys for Test/Reset function (MSR-50RK) OR Magnet for magnet test function (MSR-50RM)
• Decora Style Cover Plate with mounting screws (single gang)
Remote accessories that include the indicator/control unit and sounder module are shipped with the following parts:
• Indicator/Control Unit package
• Sounder Module with back box mounting screws (back box not supplied)
• Decora Style Cover Plate with mounting screws (double gang)
Remote accessories that include the indicator/control unit, sounder module and strobe assembly are shipped with the following parts:
• Indicator/Control Unit package
• Sounder Module package
• Strobe Assembly
• Strobe Lens Decals for optional use: “SMOKE”, “FIRE”
(1 of each version in horizontal orientation plus 1 each vertically set)
Strobe Assembly Units may be ordered seperately but are only functional when paired with the MSR-50A Sounder Module. Strobe Assemblies are shipped with:
• Installation Instructions
• Strobe Assembly
• Strobe Lens Decals for optional use: “SMOKE”, “FIRE”
(1 of each version in horizontal orientation plus 1 each vertically set)
INST APD0397 B110223
2
Decora Cover
Plate
Sounder Module
(MSR-50A)
Strobe Assembly
(MSR-50V)
STROBE CONSTRUCTION
MSR-AV and MSR-A Module Audible Sounder Output Configurations
The sound output level is selectable at either 83 db (low) or 87 db (high). The unit is shipped pre-set to the higher level. To change the selection to the lower tone simply remove the pre-installed jumper plug where shown (at right).
The sound output format on these units is selectable for Steady Tone or Temporal (Code 3) Pattern. The unit is shipped with the output format programmed for Temporal (Code 3). Simply remove the pre-installed jumper plug where shown (at right) for Steady Tone.
Note: As with all final completed installations, equipment should be completely tested to insure proper functionality.
MECHNICAL SPECIFICATIONS
Power Requirements:
MSR-50RM MSR-50RK
Standby: 06mA Standby: 06mA Detector Alarm: 22mA Alarm: 22mA Remote Alarm Test: 37mA Alarm w/Sounder: 138mA Detector Alarm w/Sounder: 57mA Alarm w/Sounder & Strobe: 92mA Detector Alarm w/Sounder & Strobe: 92mA Remote Alarm w/Sounder: 72mA Remote Alarm w/Sounder & Strobe: 107mA
MSR-50AV MSR-50A MSR-50V
Standby current: 0.0 mA 0.0 mA 0.0 mA Alarm current: 70.0 mA 35.0 mA 70.0 mA Alarm db: 68 db @10 ft (high); 53 db @ 10 ft (low) 69 db @10 ft (high); 54 db @ 10ft (low) N/A Alarm candela: 2.0 on axis N/A 2.0 on axis Temperature: 0
o
C to 49oC (32oF to 120oF) 0oC to 49oC (32oF to 120oF) 0oC to 49oC (32oF to 120oF)
Dimensions: Single Gang Plate: 4½” (114.3mm)H x 2¾” (69.85mm)W
Double Gang Plate: 4½” (114.3mm)H x 4½” (114.3mm)W
Wiring: 14-28AWG, Solid or Stranded Approvals: UL Listed for use with Air Products and Controls duct smoke detectors referenced herein including all RW- Series, SM- Series
and SL- Series duct smoke detectors. Listings and Approvals shown are for MSR-50RK and MSR-50RM Series ONLY
UL URRQ.S7425 • CSFM 7300-1004:107 • MEA 73-92-E Vol.31
Pre-installed Jumpers
set output to High Level Sound, Temporal Pattern. Take off the jumper(s) for alternate settings.