APG LFE-11P-0A, LFE-11P-0B, LFE-11P-1A, LFE-11R-0B, LFE-11R-1A LFE Manual

...
Page 1
AUTOMATION
Operator’s Manual
PRODUCTS
GROUP, INC.
Industrial OEM Low Cost
Liquid Level Switches
Doc #9004721; Part #200430
Rev. A2, 11/19
Automation Products Group, Inc.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • E-mail: sales@apgsensors.com
Page 2
LFE Series Rev. A2, 11/19
Table of Contents
Warranty ..................................................................................3
Introduction ............................................................................. 4
Specication ............................................................................4
Installation Location ...............................................................6
Wiring .......................................................................................7
Automation Products Group, Inc.
2
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 3
Rev. A2, 11/19 LFE Series
Warranty and Warranty Restrictions
This product is covered by APG’s warranty to be free from defects in material and workmanship under normal use and service of the product for 24 months. For a full explanation of our Warranty, please visit https://www.apgsensors.com/about-us/terms-conditions. Contact Technical Support to receive a Return Material Authorization before shipping your product back.
Scan the QR code below to read the full explanation of our Warranty on your tablet or smartphone.
Automation Products Group, Inc.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
3
Page 4
LFE Series Rev. A2, 11/19
• Introduction
The miniature magnetic level sensors are used for liquid level detection. They have been designed for reliable operation in small tanks and containers. Their rugged design and careful engineering make them the optimum solution for OEM and large volume applications.
• Specications
Operational Versions
LFE-11P-0A ...............................for water - PP, 10 VA, NC
LFE-11P-0B ...............................for water - PP, 10 VA, NO
LFE-11P-1A ...............................for water - PP, 50 VA, NC
LFE-11R-0B ...............................for oil - Buna, 10 VA, NO
LFE-11R-1A ...............................for oil - Buna, 50 VA, NC
LFE-12P-0A ................................for water - PP, 10 VA, NC
LFE-12R-0A ................................for oil - Buna, 10 VA, NC
LFE-12R-0B ................................for oil - Buna, 10 VA, NO
Automation Products Group, Inc.
4
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 5
Rev. A2, 11/19 LFE Series
• Specications(continued)
Characteristics
Switch Rating (resistive load) (50 VA):
Max contact rating .......................50 VA AC; 50 W DC
Max current .................................0.5 A AC; 0.5 A DC
Max voltage .................................300 V AC; 300 V DC
Life expectancy ...........................107 operations (at 12 VDC, 5 mA)
Switch Rating (resistive load) (10 VA):
Max contact rating .......................10 VA AC; 10 W DC
Max current .................................0.2 A AC; 0.2 A DC
Max voltage .................................100 V AC; 100 V DC
Life expectancy ...........................107 operations (at 12 VDC, 5 mA)
Max temperature range ................-14 to 194°F (-10 to 90°C)
Max pressure ...............................Polypropylene oat: 145 psi (10 bar)
Buna oat: 145 psi (10 bar)
Min SG ........................................Polypropylene oat: 0.9
Buna oat: 0.7
Max viscosity ..............................0.5 Pa s
Max humidity ..............................95% RH
Max impact ..................................10 G
Automation Products Group, Inc.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
5
Page 6
LFE Series Rev. A2, 11/19
• Installation Location
Locate the LFE where the change in liquid level will actuate the switch. DO
NOT locate near liquid inlets/outlets. If there is turbulence, use a time delay relay to dampen the switch action.
Figure A Figure B
LFE-XXX-XA (Switch closes as level falls), see Figure A
LFE-11R LFE-12R LFE-11P LFE-12P
Close as level falls 18 28 15 25
Open as level rises 16.5 26.5 13.5 23.5
LFE-XXX-XB (Switch closes as level rises), see Figure B
LFE-11R LFE-12R LFE-11P LFE-12P
Close as level rises 17 26 14 23
Open as level falls 18.5 27.5 15.5 24.5
Automation Products Group, Inc.
6
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 7
Rev. A2, 11/19 LFE Series
• Wiring
Wiring shall be in accordance with all local codes. Lead wires are #22 AWG,
UL listed (UL1430). APG recommends the use of solderless lugs for connection.
Black
Switch Rating (Resistive)
• Max capacity 50 VA, 50 W
• Max current 0.5 A AC, 0.5 A DC
Black
Yellow
• Max voltage 300 VAC, 300 VDC
Switch Rating (Resistive)
• Max capacity 10 VA, 10 W
• Max current 0.2 A AC, 0.2 A DC
Yellow
• Max voltage 100 VAC, 100 VDC
Note: Max pull-load of the lead wire is 19.6 N. Excessive pulling or kinking
of the lead wire may break the switch.
Caution!
Protection for electrical surges:
Overvoltage
Reed switches are not designed for the direct starting of inductive loads such as motors, contactors, solenoid valves, and so on. They are susceptible to damage from overvoltages. DO NOT EXCEED THE CONTACT RATINGS. Contact should be wired to miniature relays, suppressors or similar devices.
Overcurrent
Momentary surge current may be produced by switching lamps or stray capacity from long cable length, consequently welding the reed switch. Contact should be wired to a relay unit, coils in series, or suppressors.
Automation Products Group, Inc.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
7
Page 8
AUTOMATION
PRODUCTS
GROUP, INC.
Automation Products Group, Inc.
Tel: 1/888/525-7300 1/435/753-7300 Fax: 1/435/753-7490
e-mail: sales@apgsensors.com
www.apgsensors.com
Automation Products Group, Inc.
1025 W. 1700 N.
Logan, UT 84321