American Power Conversion PD80KL6FK1-M, PD80KF6FK1-M, PD80KG6FK1-M User Manual

80kW InfraStruXure PDU
PD80KF6FK1-M
PD80KG6FK1-M
PD80KL6FK1-M
Operation and Configuration
208/480/600V Input
About This Manual
This manual is intended for end-users of an 80kW InfraStruXure PDU. It covers the operation,
customization, and quick configuration of the InfraStruXure PDU. It also includes basic
InfraStruXure system operation.

Companion manuals

For additional information about the InfraStruXure system, see the following manuals that were
included with the PDU:
InfraStruXure 80kW Installation and Start-Up (990-1467B) covers the installation and start-up
of InfraStruXure UPS power distribution to the rack and power distribution within the rack.
Certified Electrician’s Instructions (990-1469A) provides specific instructions for the
electrician connecting utility conductors to the InfraStruXure PDU.
For information about specific components in your InfraStruXure system, see the documentation
included with each component. Before installing or operating any component, refer to the safety
instructions in the component’s manual.
The illustrations of products in this manual may vary slightly from the products in your InfraStruXure
system.

How to find updates to this manual

The content in this manual is based upon the latest available information. You can check for updates
to this manual by clicking on the User Manuals link on the Support page of the APC Web site
(www.apc.com). In the list of InfraStruXure manuals, look for the latest letter revision (A, B, etc.) of
the part number on this manual.
80kW InfraStruXure PDU—Operation and Configuration i
Contents
Safety ......................................................................1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Save these instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety symbols used in this manual . . . . . . . . . . . . . . . . . . . 1
Cross-reference symbols used in this manual . . . . . . . . . . . . . 1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation/Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Maintenance performed while the PDU is receiving input power
Total Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
DANGER—Risk of Electric Shock! . . . . . . . . . . . . . . . . . . . . . 3
Emergency Power Off (EPO) . . . . . . . . . . . . . . . . . . . . . . . . 3
EMI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . 2
Overview .................................................................5
InfraStruXure PDU Components. . . . . . . . . . . . . . . . . . . . . . . . . 5
PDU front view (exterior) . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Front view (interior) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Front view (door open) . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Rear view (interior) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
PDU monitoring unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
User connection plate . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
PDU Display Interface.............................................13
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Top-level status screens . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Top-level menu screen . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Navigating through screens . . . . . . . . . . . . . . . . . . . . . . . 14
Password-protected screens . . . . . . . . . . . . . . . . . . . . . . . 15
Load-Meter Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Volt-Meter Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
80kW InfraStruXure PDU—Operation and Configuration iii
Contacts Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Breakers Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Alarms Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
View Active Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Alarm/Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Alarm Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Alarm Beeper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
PDU Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Panel Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Branch Ckt Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Branch Ckt Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Panel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Global Panel Config . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Config Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
System/Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Electrical Config . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Manufacturer Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
System ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Factory Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Firmware Updates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
System Operation .................................................. 31
How to Transfer the UPS into Maintenance Bypass Operation . 31
How to Return from Maintenance Bypass Operation . . . . . . . . 34
How to Ensure Total Power Off . . . . . . . . . . . . . . . . . . . . . . . 37
How to Apply Power to the System . . . . . . . . . . . . . . . . . . . . . 39
Communication Configuration ............................... 43
InfraStruXure PDU Management Options . . . . . . . . . . . . . . . . . 43
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
InfraStruXure Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Network management interfaces . . . . . . . . . . . . . . . . . . . . 43
Configuring the InfraStruXure Manager . . . . . . . . . . . . . . . . . . 44
iv 80kW InfraStruXure PDU—Operation and Configuration
Configuring the Network Management Interface . . . . . . . . . . . 45
Connect the InfraStruXure PDU to your network . . . . . . . . . 45
Configuration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . 45
TCP/IP configuration methods . . . . . . . . . . . . . . . . . . . . . . 46
Device IP Configuration Wizard . . . . . . . . . . . . . . . . . . . . . . 46
BOOTP & DHCP configuration . . . . . . . . . . . . . . . . . . . . . . 47
Local access to the control console . . . . . . . . . . . . . . . . . . . 49
Remote access to the control console . . . . . . . . . . . . . . . . . 49
Control console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
How to Access a Network Management
Interface on a Configured InfraStruXure PDU. . . . . . . . . . . . . . 51
Web interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Telnet and SSH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
FTP and SCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
How to Recover From a Lost
Network Management Interface Password. . . . . . . . . . . . . . . . 54
Customizing and Updating the PDU .......................55
Important Safety Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . 55
PDU Orderable Part List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
How to Add Circuit Breakers and Power Cables . . . . . . . . . . . . 58
Add a circuit breaker on the PDU . . . . . . . . . . . . . . . . . . . . 58
Add a power cable to the PDU or RDP . . . . . . . . . . . . . . . . 58
How to Test the EPO Switch . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Testing the EPO wiring and switches . . . . . . . . . . . . . . . . . 60
Safety warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
How to Connect User Input Contacts and
Relay Outputs to the PDU User Connection Plate . . . . . . . . . . . 63
How to Download Firmware Up grades . . . . . . . . . . . . . . . . . . . 65
Specifications .........................................................67
80kW InfraStruXure PDU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
80kW InfraStruXure PDU—Operation and Configuration v
Product Information .............................................. 71
InfraStruXure Standard Warranty . . . . . . . . . . . . . . . . . . . . . . . 71
Life-Support Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
How to Obtain Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Appendix .............................................................. 75
Changes in This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
vi 80kW InfraStruXure PDU—Operation and Configuration

Safety

d
o

Overview

Save these instructions

This manual contains important instructions that must be followed during installation, operation, and
maintenance of the PDU.

Safety symbols used in this manual

Indicates an electrical hazard, which, if not avoided, could result in injury or
Electrical
Hazar
Warning
death.
Indicates a hazard, which, if not avoided, could result in personal injury or
damage to product or other property.
Indicates a potential hazard which could result in damage to product or other property.
Caution
Indicates important information.
Note
Indicates a heavy load that should not be lifted without assistance.
Heavy
Indicates a standby state. When in standby, the unit is not operating, but it may still
contain hazardous voltage. It is not safe to service until the equipment is
disconnected from all sources of electrical power.

Cross-reference symbols used in this manual

Indicates that more information is available on the same subject in a different section
of this manual.
Indicates that more information is available on the same subject in a different manual.
See als
80kW InfraStruXure PDU—Operation and Configuration 1

Warnings

Installation/Maintenance

Only a certified electrician can perform these tasks:
• Connect the InfraStruXure PDU to utility power
• Connect the cross tie output breaker to another InfraStruXure PDU
• Connect a switch to the EPO interface on the InfraStruXure PDU
Only a certified electrician or an APC Field Service Engineer can perform these tasks:
• Connect the PDU to the Symmetra PX UPS
• Perform maintenance of the PDU
When you connect the PDU to utility power, you must install a circuit breaker to protect the PDU
against over-current. Determine the type of circuit breaker that you need to install:
Input Voltage Circuit Breaker Size
208V 350A
480V 150A
600V 125A

Maintenance performed while the PDU is receiving input power

APC does not recommend that you perform maintenance of the PDU while it is receiving input
power. However, due to the critical nature of data center loads, this may occur. If you must perform
maintenance while the PDU is receiving input power, observe the following precautions to reduce the
risk of electric shock:
1. Never work alone.
2. Perform the maintenance only if you are a certified electrician who is trained in the hazards of
live electrical installation.
3. Know the procedure for disconnecting electricity to the PDU and the data center in case of an
emergency.
4. Wear appropriate personal protective equipment.
5. Use double-insulated tools.
6. Always follow local and site regulations when working on the PDU.
2 80kW InfraStruXure PDU—Operation and Configuration

Total Power Off

d
1. Set the Symmetra PX UPS System Enable switch to Off.
2. Set the DC Disconnect breaker of each Battery Enclosure to Off.
3. Set the PDU Main Input (A) switch to Off.
4. If applicable, set the PDU Bypass Input (B) switch to Off
5. If applicable, set the PDU Cross Tie Output (X) breaker to Off.
6. Set the upstream utility power circuit breaker(s) to Off.
7. Disconnect the batteries in the Battery Enclosure by pulling them out to the red disconnect line.

DANGER—Risk of Electric Shock!

Hazardous, live parts may exist inside the PDU because of the Symmetra PX UPS
inverter even when the AC power is disconnected. Test any electrical parts before
Electrical
Hazar
touching them.
Safety

Emergency Power Off (EPO)

Hazardous voltage from the branch circuit must be isolated from the 24VAC, 24VDC, and contact
closure. 24VAC and 24VDC are considered Class 2 circuits as defined in Article 725 of the National
Electrical Code (NFPA 70) and Section 16 of the Canadian Electrical Code (C22.1).
A Class 2 circuit is a source having limited voltage and energy capacity as follows:
a. If an Inherently Limited Power Source, voltage and energy are limited to less than 30VAC,
less than 30VDC, and 8A.
b. If not an Inherently Limited Power Source, voltage and energy are limited to less than
30VAC, less than 60VDC, 250VA, and the current is limited to 1000/Vmax. The fuse is
limited to 5A if less than 20VAC or 20VDC, or 100/V maximum if less than 30VAC or
60VDC.
If you choose to use a 24VAC, 24VDC, or contact closure connection to the EPO, use one of the
following UL-listed wire types:
• CL2 Class 2 cable for general purpose use
• CL2P Plenum cable for use in ducts, plenums, and other space used for environmental air
• CL2R Riser cable for use in a vertical run shaft from floor to floor
• CL2X Limited Use cable for use in dwellings and for use in a raceway
• For installation in Canada, the cable should be CSA Certified, type ELC (extra-low-voltage
control cable).
If you do not use a CL2 cable, route the EPO wiring in conduit that does not contain any branch
circuit wiring.
80kW InfraStruXure PDU—Operation and Configuration 3
Safety
EMI
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with this user manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference. The user will
bear sole responsibility for correcting such interference.
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numerique de le class A est conforme a la norme NMB-003 du Canada.
4 80kW InfraStruXure PDU—Operation and Configuration

Overview

InfraStruXure PDU Components

The APC 80kW InfraStruXure PDU provides distribution and management of electrical power. The
InfraStruXure PDU has the capacity of 80kW, accepts 208, 480, or 600V, 3-phase input, and
distributes 208V, 3-phase power to equipment racks and Rack Distribution Panels (RDPs). The RDPs
sit in the top 10U of specially-designed NetShelter VX enclosures and distribute power to equipment
racks. The InfraStruXure PDU is housed in a specially-designed 23-inch NetShelter VX wide
enclosure. Each 80kW InfraStruXure PDU has thirty pole positions available for feeding equipment
racks and four, three-pole positions available for feeding RDPs. Each RDP has thirty-nine pole
positions available for feeding equipment racks and one, three-pole position that back-feeds the RDP.
Rack Distribution Panel (RDP)
39 pole positions available
One, 3-pole breaker back-feeding the RDP
NetShelter VX Enclosure
InfraStruXure PDU
Four circuit breakers sub-feeding the RDPs
30 pole positions available
Power cables feeding equipment racks
42-position circuit breaker panel
80kW InfraStruXure PDU—Operation and Configuration 5
Sub-feed power cable feeding the RDP
Overview

PDU front view (exterior)

PDU wide shielding
troughs—The PDU shielding
troughs accommodate the
power cables exiting the roof of
the PDU.
Power Cables—These power
cables feed equipment racks;
they are fed through knockout
panels on the top (or bottom) of
the PDU. The power cables
consist of five wires: three
phases, one neutral, and one
ground. The number of power
cables installed in the PDU
depends on your system
configuration. Each power
cable has a NEMA L21-20
outlet, which accepts a variety
of APC InfraStruXure
accessories, including Rack
PDUs and the Rack ATS.
Sub-feed power cables—These power cables are an option for feeding RDPs; they are fed
through knockout panels on the top (or bottom) of the PDU. The power cables consist of five
wires: three phases, one neutral, and one ground. You can have up to four sub-feed power
cables. If you ordered this option, each power cable has an IEC 309 outlet, which connects to
another sub-feed power cable fed from the RDP with an IEC 309 plug.
Display interface—The display interface is attached to the name plate on the front door of the
enclosure. It has an LCD, five-button interface, basic status lights, and a beeper.
Lock-out bracket—The bracket allows for a padlock to be applied to the door to lock access
to the PDU switches and breakers.
Cable access holes—Both side panels on the PDU have cable access holes for Symmetra PX
UPS input and output wiring. During installation, the APC Field Service Engineer exchanges
side panels between the PDU and the Symmetra PX UPS so that the adjacent sides of the two
units have panels with cable access holes.
Leveling feet—The feet adjust for leveling the enclosure. All enclosures must be level before
installation of the system begins.
6 80kW InfraStruXure PDU—Operation and Configuration

Front view (interior)

 
Ground lugs— Ground lugs
are provided for the Main
Input switch, Bypass Input
switch, and Cross Tie Output
breaker. The main input lug
has two holes: one for a main
ground and one for the GEC.
See the instruction sheet,
Certified Electrician’s
Instructions for more
information.
Main Input switch (A)—
The main power source
connects to your system at
the Main Input switch. See
the instruction sheet,
Certified Electrician’s
Instructions for more
information.
Overview
Optional Bypass Input switch (B)— If you ordered a PDU that accepts input power from two
different sources, your secondary power source connects to your system at the Bypass Input switch
(Q10). The switch requires 208V input and 4-wire input conductors. The secondary source must
have its phases in sync with the main input source (A). See the instruction sheet, Certified
Electrician’s Instructions for more information.
Optional Cross Tie Output circuit breaker (X) or MCCB subfeed— You have the option of
selecting ether a cross tie or MCCB subfeed breaker. The cross tie is a 4-pole circuit breaker that
outputs 208V, 320 A to a bypass input switch on a different system. The MCCB subfeed outputs
208V, 150A or 208V 225A to a bypass input switch on a different system. Either circuit breaker
allows systems to be cascaded. See “Site Planning” in the InfraStruXure 80kW Installation and
Start-Up and the instruction sheet, Certified Electrician’s Instructions for more information.
PDU monitoring unit circuit breakers—Power supplied to the PDU monitoring unit is controlled
through these two circuit breakers.
Fuses—These fuses protect the silicon-controlled rectifiers in the UPS bypass static switch. The
fuses are present only on dual-fed PDUs and single-fed PDUs without a transformer.
Optional bottom feed—If you ordered main input wiring to be routed under the floor, these
terminal blocks are your connection to the Main Input switch, Bypass Input switch, and Cross Tie
Output breaker.
80kW InfraStruXure PDU—Operation and Configuration 7
Overview

Front view (door open)

Wraparound
maintenance bypass
panel—The
maintenance bypass
panel has three
circuit breakers that
allow the UPS to be
electrically isolated
from the main power
source, while
maintaining the
power panels. The
input circuit breaker
is labeled Q1, the
output circuit breaker
is labeled Q2, and the
maintenance bypass
circuit breaker is
labeled Q3. The label
on the maintenance
bypass panel of the
PDU illustrates the
power flow, and the
H2 and H3 LEDs
indicate when it is
safe to operate the Q2
and Q3 circuit
breakers.
Optional bottom-feed cable access—These knockouts are for bottom-feed power cables and
RDP cables. If you ordered a PDU to accommodate under-floor wiring, your power cables for
equipment racks and RDPs will exit the PDU from these cable access holes.
UPS input and output cables—The cables that connect the PDU to the UPS are shipped coiled
on the floor of the PDU. The input cables consist of 5 wires: 3 phases, 1 neutral, and one ground.
The output cable consist of 4 wires: 3 phases and 1 neutral. The bypass cables consist of 4-wires:
3 phases and one neutral. Each wire is labeled and corresponds to a lug on the Symmetra PX UPS
bus bars. During installation, the Field Service Engineer will connect the PDU to the UPS.
User connection plate—The user connection plate is connected to the PDU monitoring unit, and
provides easy access to the input contacts, relay outputs, network, and EPO connections. Make
connections from inside the enclosure, and route wires through the knockout provided on the
plate. See “User connection plate” on page 11 for a more detailed description.
8 80kW InfraStruXure PDU—Operation and Configuration

Rear view (interior)

42-position circuit breaker
panel—Each PDU has a
circuit breaker panel with 42
pole positions. Each pole
provides power at 120 volts
L-N or 208 volts L-L. The
amperage each position
provides depends on the size
of the circuit breaker used.
Panel current sensors
Wires that feed the
distribution panel pass
through these current sensors,
providing data to the PDU
monitoring unit.
Overview
PDU monitoring unit—The PDU monitoring unit receives signals from several current and
voltage monitoring boards that report to a central board assembly located in the PDU
monitoring unit. The monitoring unit has one 10Base-T (Cat-5) connection to the Information
Controller Hub (or switch), four (4) relay output connections, four (4) input contact
connections, and one (1) EPO input connection. Make these connections at the user connection
plate located on the roof of the PDU. See “PDU monitoring unit” on page 10 for a more
detailed description.
Input transformer— The delta-wye transformer installed in your PDU is based on your input
voltage (208V, 480V, or 600V input). The output of the transformer feeds the input circuit
breaker of the maintenance bypass panel. (APC also offers a 208V PDU without a transformer.)
Load test ports—The load test ports are an available option on the PDU. The load test bank
connector allows a UPS system to be load-tested to ensure that the system will operate
according to specifications if a power outage occurs.
80kW InfraStruXure PDU—Operation and Configuration 9
Overview

PDU monitoring unit

This connection provides the input power for the PDU monitoring
unit. The power is supplied by the monitoring unit circuit breaker on the front of the PDU. If the panel is on, and the monitoring unit circuit breaker is closed, the monitoring unit is powered.
Connects to sensors monitoring values such as voltage, current, and
power.
Digital input sensing for monitoring such as circuit breaker status,
transformer temperature, fans, etc.
The Display port (RJ-45) connects the PDU monitoring unit to the
PDU display interface.
885-2288
The Power LED indicates wether the monitoring unit is receiving
power from the AC output of the UPS. If the UPS is powered off, the LED remains lit—the EPO function is still available, however the monitoring unit is not powered.
Use the Console port (DB-9) to connect a laptop computer to the
monitoring unit using an appropriate communication cable (APC part number 940-0103). This port is used to configure items relating to servicing the PDU.
EPO DIP switches configure the EPO input for the type of EPO
switch that is connected—Normally Open (NO) or Normally Closed (NC).
When the EPO Arm/Test rocker is in the Tes t position, engaging
the EPO switch will not cause the load to be powered off. When the rocker is in the Armed position, engaging the EPO switch will cause the PDU’s Main Input switch and the Symmetra PX UPS to be switched OFF. See “Testing the EPO wiring and switches” on page 60 for more information on testing the EPO switch.
The EPO Armed LED is green when the rocker is in the Armed
position. The LED is dark when the rocker is in the Te st position.
The EPO Tripped LED is red when the EPO switch is engaged
(the EPO button is pressed), regardless of the state of the EPO Arm/Test rocker.
  
NETWORK
RESET
EPO
USER / EPO CONTACTS
TO U PS
LINK RX/TX
STATUS
TRIPPED
ARMED
TEST
NC
NO
12345678910111213
25 24 23 22 21 20 19 18 17 16 15 14
10= GRN
100=ORN
DISPLAY
POW ER
RS-232
9600-8-N-1
CONSOLE PORT
The Reset button resets the network processor; it does not reset the PDU or the PDU monitoring unit.
Connect to the InfraStruXure Manager through the network port.
The To UP S port connects the PDU monitoring unit to the Maintenance Bypass/PCB board and the EPO board
inside the Symmetra PX UPS. This port is connected to wire harnesses secured inside the PDU that are connected to the Symmetra PX UPS during installation of the system.
The optional User/EPO Contacts port is connected to wire harnesses that connect to the User Connection Plate
in the roof (or floor) of the PDU. The port allows for relay outputs (4), input contacts (4), and an EPO input (1). See “How to connect contacts to the PDU monitoring unit” on page 20 and “Testing the EPO wiring and switches” on page 60 for more information.
The branch current monitoring boards connect to the Branch Current Monitor ports (RJ-11). These ports are on the top side of the PDU monitoring unit, and are labeled on the face of the unit. Each port corresponds to a section of circuit breakers on the PDU distribution circuit breaker panel:
Note
10 80kW InfraStruXure PDU—Operation and Configuration
upper left=[01..41]; upper right= [02..42]; lower left=[43..83]; lower right= [44..84].

User connection plate

For a description and location of the user connection plate, see () on page 8. For clarity, the user
connection plate is shown in the following illustration in greater detail.
\
!
!
USER INTERFACE
© 2001 APC
MADE IN USA
1 234
Contact Inputs
Contact Outputs
ATS 0
!
+
EPO 24V
EPO
ATS 1
ATS 2
AC/DC
Contact
ATS EN
Overview
Connect the InfraStruXure PDU to the network of the InfraStruXure Manager
through the ethernet port.
The user connection plate has four input contact connections for monitoring
Normally Open (NO) or Normally Closed (NC) dry contacts. See page 20 and
page 64 for more information.
The user connection plate has four relay output connections for connection
of Normally Open (NO) or Normally Closed (NC) dry contacts. See page 20
and page 64 for more information.
Connect an Emergency Power Off (EPO) switch at one of three choices of
EPO connections (24VDC, 24VAC, or contact closure). See page 60 for
more information.
80kW InfraStruXure PDU—Operation and Configuration 11

PDU Display Interface

Overview

You can use the display interface to configure settings, set alarm thresholds, and provide audible and
visual alarms.
Load Powered
Check Log
Bypass
Alarm
ESC
?

Load On LED When green, all output phases are within the limits
specified by the output alarm limit thresholds.
Check Log LED When yellow, at least one new alarm condition has been
detected.
Bypass LED When yellow, power to the load is being supplied directly
by the utility power source—the UPS has been removed from the circuit for maintenance or replacement. Bypass breakers on the PDU function as input breakers to protect the load equipment.
Alarm LED When red, an alarm condition exists.
LCD View alarms, status data, instructional help, and
configuration items.
Up and Down
navigation keys
ENTER key Opens menu items and inputs changes to system
Selects menu items and accesses information.
parameters.
HELP key Launches context-sensitive help. Press the HELP key for
information about each item on the screen and for instructions on how to perform certain tasks (i.e. placing the UPS into Maintenance Bypass operation).
ESC key Returns to previous screen displayed.
80kW InfraStruXure PDU—Operation and Configuration 13
PDU Display Interface

Top-level status screens

After system start-up, the display interface displays a brief start-up screen and then scrolls
automatically and continuously through four screens of basic status information. Press the Up and
Down arrow keys to interrupt the automatic scrolling if you wish to view a specific status screen.
Volts In
L1-2: 000 L2-3: 000 L3-1: 000
Total Output Loading
kW:
000
kVA:
000
Freq:
00.0
Volts Out
L1: 000 L2: 000 L3: 000
PF:
000
%LD:
000
Load Current
L1: 000 L2: 000 L3: 000
Active Alarm: 01of11
Input Transformer
Temperature Too High
Neut:
Gnd: 000

Top-level menu screen

On any top-level status screen, press the ENTER key to open the top-level menu screen.
Load-Meter Volt-Meter Contacts Breakers
Alarms Panel Config Help
If the display interface is inactive for the time specified as the Time-out setting, the
interface reverts to the initial basic monitoring screens.
Note
000
For descriptions of the top-level menu choices, see the individual sections starting on
page 16.

Navigating through screens

To open any screen, press the Up and Down arrow keys until the selector arrow ( rests next to your
desired selection. Press the
When configuring settings, press the Up and Down arrow keys
until the selector arrow (
change, and press the
an input arrow (
will appear next to the setting. Press the Up and

Down arrow keys until your desired change is listed. Press the
ENTER key to select the setting.
ENTER key to view the selected screen.
Load-Meter Volt-Meter Contacts Breakers
Alarms Panel Config Help
Contacts In: 02of04 Name: User Switch #2 Normal: Open Status: Open
rests next to the setting you want to

ENTER key. If the setting is a list of choices,
Contacts In: 02of04 Name: User Switch #2 Normal: Open Status: Open
14 80kW InfraStruXure PDU—Operation and Configuration
PDU Display Interface
On some screens, continue arrows ( indicate that there
are additional screens to view in the category. Press the Up
or Down arrow key to view the additional screens.
System/Network Electrical Configuration Panel Configuration Manufacturer Data
Product Data Factory Defaults Firmware Updates

Password-protected screens

When configuring or changing settings, you will be prompted for your password. To enter your
password:
1. Press the Up or Down arrow key until the correct letter is
displayed, and then press the
ENTER key.
Enter Password:
*******
After you press the ENTER key, the character you
entered is displayed as an asterisk and the input
Note
arrow moves to the next space for you to select
the next password character.
2. Press the
ENTER key twice after you enter your password.
See “System Password” on page 28 to change your password.
80kW InfraStruXure PDU—Operation and Configuration 15

Load-Meter Screen

From the Load-Meter screen, you can select the following items:
Total Load by Phase The load supported by each phase in kVA, in
and as a percentage of the maximum allowable load (%LD).
Total Load Summary For the total load supported:
kW: The power provided, in kilowatts.
kVA: The actual power drawn by the load, in kilovolt-amperes.
Freq: Frequency.
PF: The power factor, which affects the power available to the
load.
%LD: The load as a percentage of the maximum allowable
load.
Power Factor For each phase:
kVA: The actual power drawn by the load, in kilovolt-amperes.
kW: The power, in kilowatts provided by the phase.
PF: The power factor (kW/kVA), which affects the power
available to the load.
RMS current (Irms),
16 80kW InfraStruXure PDU—Operation and Configuration

Volt-Meter Screen

From the Volt-Meter screen, you can select the following items:
Output Voltage Displays each phase-to-phase output voltage (e.g., L1-2 for phase L1 to
phase L2) and each phase-to-neutral output voltage (e.g., L1 for phase L1
to neutral).
Input Voltage Displays each phase-to-phase input voltage (e.g., L1-2 for phase L1 to L2),
or, if your service transformer is a Wye transformer, each phase-to-neutral
input voltage (e.g., L1 for phase L1 to neutral).
Bypass Voltage Displays each phase-to-phase bypass (dual-feed input) voltage (e.g., L1-2
for phase L1to phase L2) and each phase-to-neutral bypass voltage (e.g.,
L1 for phase L1 to neutral). Appears only on PDUs that have a bypass
input switch.
80kW InfraStruXure PDU—Operation and Configuration 17

Contacts Screen

Overview

The PDU can monitor external contact closure events. Possible applications include the following:
• Magnetic contact switches
• Window foil
• Tamper switches
• Heat detectors
• Water sensors
• Pressure sensors
• Building smoke and fire detection systems
You can set input contacts to cause alarm conditions based on their current state and a user-defined
normal state. Relay outputs can map internal alarms and events to outside devices. Use the Contacts
screen to display and configure information about input contacts and relay outputs.
Input Contacts Scroll through the list to display information about each of the
installed input contacts. For example 02of04 displays
information about the second of four installed input contacts.
Name—The name of this input contact (Maximum: 14
alphanumeric characters).
Normal—The normal position of this input contact, either
Open or Closed.
Status—The position of this input contact. If the position is
not the normal position, an alarm condition occurs.
Relay Outputs Scroll through the list to display information about each of the
installed relay outputs. For example 04of04 displays information
about the fourth of four available relay outputs.
Name—The name of this relay output (Maximum: 14
alphanumeric characters).
Normal—The normal position of this relay output, either
Open or Closed.
Status—The position of this relay output.
See “Relay Outputs” on page 68 for relay output specifications.
18 80kW InfraStruXure PDU—Operation and Configuration
PDU Display Interface
Alarm Relay Map Configure the relay outputs,
using the Alarm Relay Map.
Each Alarm Map corresponds
to an output relay. For
example, Alarm Map 01of04 corresponds to the first of four
relay outputs. The second line, in brackets [ ], lists the items that
you have selected to map to the selected relay. The third line
allows you to select the alarms to which you want to map the
relay:
Any Load (L)—Maps to over- or under-current alarms for
circuit breaker panels and branch circuits.
Overload (O)—Maps to over-current alarms for circuit
breaker panels, branch circuits, and SYSGND.
Input Voltage (Vi)—Maps to any input voltage alarm.
Output Voltage (Vo)—Maps to any output voltage alarm.
PDU in Bypass (By)—Mapping this option will cause the
output relay to actuate when the Q3 breaker is closed.
Any Breaker (Br)—Mapping this option will cause the
output relay to actuate when the input, bypass input (Q10),
or cross-tie output breaker is not in its normal state.
Contacts 1–4 (C1, C2, C3, C4)—Maps to the input contact
alarms.
Alarm Map: 01 of 04 [Vo, By, C4] Map: Input Voltage Apply Now
Before exiting the screen, to save your changes, select the Apply
Now option on the bottom line of the screen.
.
80kW InfraStruXure PDU—Operation and Configuration 19
PDU Display Interface

How to connect contacts to the PDU monitoring unit

1. Choose one or more contact number on the User/EPO contacts port on the user connection
plate to which you will connect the contacts. The user connection plate is connected to the PDU
monitoring unit.
2. From the PDU display interface:
a. Press the
b. Select Contacts on the top-level menu screen, and press the
c. Select Contact Inputs (or Relay Outputs) and press
ESC or ENTER key to go to the top-level menu screen.
Load-Meter Volt-Meter Contacts Breakers
Alarms Panel Config Help
ENTER to display the contact inputs (or
ENTER key.
relay outputs) screen.
>Contact Inputs >Relay Outputs
>Alarm Relay Map
d. Select Contact In and press the
ENTER key to select the number of the contact you are
connecting. The continue arrow will appear next to the contact number.
Contact In:01of04 Name:User Contact 1 Normal: Open Status: Closed
e. Press the Up or Down arrow key to select the appropriate contact number, and press the
ENTER key.
f. Press the Down arrow key to enter a unique Name for the contact and to configure the
Normal state of the contact (Open or Closed). The default Normal state is Open. Press the
ENTER key to select the item to configure.
You will be prompted for your password to configure these items.
Note
3. Connect contact wires (300V-rated cabling required) to the User Contacts terminal block on the
user connection plate. You will need a 2.5-mm standard screwdriver.
4. Run the wires from the terminal block out the roof or under the floor of the PDU to your
contact’s location.
Ensure that wires are properly retained and away from high voltage lines and breakers.
Warning
20 80kW InfraStruXure PDU—Operation and Configuration

Breakers Screen

Use the Breakers screen to view the status of the system and PDU circuit breakers.
UPS & System Bypass Reports the operation mode of the UPS and the state of the Q1,
Q2, and Q3 circuit breakers on the PDU.
Main Input Reports status of PDU Main Input Circuit Breaker (Open or
Closed). Under normal operation, this circuit breaker is Closed.
Bypass Input Reports status of the PDU Bypass Input switch (Open or
Closed). Under normal operation, this circuit breaker is Closed.
Cross Tie Reports status of the Cross Tie Output circuit breaker (Open or
Closed). Under normal operation, this circuit breaker is Closed.
80kW InfraStruXure PDU—Operation and Configuration 21

Alarms Screen

View Active Alarms

Use this option of the Alarms screen to display active alarms (alarms that have not been resolved).
Scroll through the list to view each active alarm.

Alarm/Event Log

Use this selection of the Alarms screen to access the following options:
New Logged Items Display a description and the date and time of each alarm that
occurred since the last time this option was used. The date/time
format is mm/dd/yyyy hh:mm:ss.
• The most recent alarm is displayed initially.
• If the log contains no alarms, the screen displays
Empty
Entire Log Display a description and the date and time of each alarm in the
alarm log. The date/time format is mm/dd/yyyy hh:mm:ss.
.
Alarm Log
• The most recent alarm is displayed initially. To move to the
previous alarm press the Down arrow
more recent alarm, press the Up arrow key.
• If the log contains no alarms, the screen displays
Empty
Clear Log Delete the contents of the alarm log. You will be asked to confirm
this deletion.
.
key. To move to the next
Alarm Log
22 80kW InfraStruXure PDU—Operation and Configuration

Alarm Setup

Use this option of the Alarms screen to access the following options:
Loading Limits Configure the following in amps and as a percentage of full load:
Out High: The upper limit for output current
Out Low: The lower limit for output current
Out Neut: The upper limit for current on the neutral wire for
the output phases
Voltag e Limi t s Configure the following as a percentage under or over the rated
voltage:
Input: The allowed range for input voltage
Output: The allowed range for output voltage
Bypass: The allowed range for bypass input voltage (only on
PDUs with dual-fed input)
PDU Display Interface
Other Limits Configure these limits:
Frequency: The frequency variation, in hertz, that is acceptable
for the output current.
Global Alarm Config
Set all the loading limits or all the voltage limits simultaneously as a
percentage of full load:
Load Limits: Set the same percentage for the upper limit for
output current, the lower limit for output current, and the upper
limit for current on the neutral wire for the output phases. (Use
the Loading Limits option to set these thresholds individually).
Volt L imit s : Set the same percentage for the high and low
thresholds for input and output voltage. (Use the Volt age
Limits option to set these thresholds individually).
Select Apply Now and then YES to implement your changes.

Alarm Beeper

Use this option of the Alarms screen to turn the alarm beeper ON or OFF.
80kW InfraStruXure PDU—Operation and Configuration 23
PDU Display Interface

PDU Alarms

This table lists all alarms that can be generated by the InfraStruXure PDU, as displayed by the All Possible
Alarms option, with numeric variables between the < > characters. Logged alarms will display specific
numbers instead.
Alarm Condition Explanation
Input V <Ln-N> =<Value> Voltage Under Limit
Input V <Ln-N> =<Value> Voltage Over Limit
Output V <Ln-N> =<Value> Voltage Under Limit
Output V <Ln-N>=<Value> Voltage Over Limit
Output I L<n>=<Value> Current Over Limit
Output I L<n>= <Value> Current Under Limit
Output Neut=<Value> Current Over Limit
Output FDev=<Value> Freq Out of Range
Input Transformer Temperature Too High
Input voltage of the phase indicated has dropped below the configured lower limit.
Input voltage of the phase indicated exceeded the configured upper limit.
Phase-to-neutral output voltage for phase <L-N> dropped below the configured limit.
Phase-to-neutral output voltage for phase <L-N> exceeded the configured limit.
Current of output phase <n> exceeded the configured limit.
Current of output phase <n> dropped below the configured limit.
Current on the neutral wire for the output phases exceeded the configured limit.
Frequency of the output current is above or below the range that is configured as acceptable.
The temperature of the PDU transformer exceeded the normal limit, if applicable.
Message When
Condition Cleared.
Input Voltage V <Ln-N> Back In Range
Output Voltage V <L-N> Back In Range
Output Phase <N> Current Within Limit
Output Neutral Current Within Limit
Output Frequency Back In Range
Input Transformer Temp. Back to Normal
Main Breaker Open Alarm Active
<User Contact Name> Alarm Active
No UPS Input Breaker Q1 Open
No Panel Feed Breakers Q2&Q3 Open
Atypical Bypass Mode Alarm Active
Branch Ckt Pos: <nn> Current Over Limit
Branch Ckt Pos: <nn> Current Under Limit
Fan Rotation Failure Alarm <Active
The Main input switch is Off. Main Circuit Breaker
Has Been Closed
A user-configured contact connected to the PDU monitoring unit is reporting an alarm condition.
The Q1 circuit breaker is open, and the PDU is not receiving power from the UPS.
The Q2 & Q3 circuit breakers are open, and the PDU is not supporting connected equipment.
The system state as set by the Q1, Q2, & Q3 breakers is in a bypass mode.
Current on one of the poles of branch circuit breaker nn exceeded the configured limit.
Current on one of the poles of branch circuit breaker nn dropped below the configured limit.
There is a failure in one of the fans. The fan needs to be replaced.
Alarm Cleared
None
None
None
Branch Ckt Pos: <nn> Current Within Limit
None
24 80kW InfraStruXure PDU—Operation and Configuration

Panel Screen

Branch Ckt Loading

You can display Branch Ckt Loading (Branch Circuit Loading) status if the option to measure
current at the distribution breakers is installed.
You can view data for each individual panel position on the distribution panel. To view status of a
panel position, select the range that includes the position:
Branch Ckt Loading Select Range: [01..41] [02..42]
The panel position numbers on the screen correspond to the numbers on the distribution panel. (Odd
numbers are on the left; even numbers are on the right.)
After you have selected the correct range, press the Up and Down arrow keys to scroll through the list
of breakers in the selected range. Poles that are tied together will be shown on the same screen.
Ckt: 03of21 Irms %LD 05: 20A
11.3 56.5
In the example above, the screen shows the third breaker of 21 breakers in the selected range. This is
a single-pole breaker, occupying panel position 05. The breaker is rated at 20 amps. The following
data are displayed for each pole:
Irms: Measured root mean square (
RMS) current of the pole position.
%LD: Present load as a percentage of rated load of the panel position.

Branch Ckt Limits

Available only if the option to measure individual currents is installed, Branch Ckt Limits (Branch
Circuit Limits) accesses a scrollable list of the breakers in the panel. For each breaker, the screen
displays, in the Loading column, the current on each panel position as a percentage of the rated
current. In the Load Alarm column, you can configure the high and low thresholds for the breaker as
a percentage of its rated current. For example, if you set 80% as the high threshold for a single-pole
20-amp breaker, an alarm condition occurs if the current reaches 16 amps.
80kW InfraStruXure PDU—Operation and Configuration 25
PDU Display Interface

Panel Configuration

Configure the branch metering settings for each breaker on the
distribution panel. The panel position numbers on the screen
correspond to the numbers on the distribution panel. (Odd
Panel Configuration Select Range: [01..41] [02..42]
numbers are on the left; even numbers are on the right.) Once you
have selected the correct range, configure the settings for each breaker in the range:
Pos: The panel positions in the selected range.
Breaker: Two configurable items:
• The breaker rating, in amps.
• The breaker tie indicator—define the number of panel positions tied (i.e., associated). You can
associate positions with breakers, which enables you to view status about each breaker and
receive alarm notification when any of a breaker’s poles are above or below the configured
branch circuit limit. You can also tie together panel positions that are logically associated. For
example, you can tie together panel positions for three separate breakers that are connected to
the same PDU power cord and that feed power to the same equipment enclosure.
To configure the values on this screen:
1. From the first column, use the arrow keys to scroll up or down to the pole position you want to
configure.
2. Press the
ENTER key to move to the item you want to configure in the third column (the breaker
rating or the breaker tie indicator).
3. Scroll again to select the value you want for the breaker rating or the breaker tie indicator. To
associate one panel position with the next position in the list, choose the + character as the tie
indicator immediately following the breaker rating. To indicate that the position is not tied to
(associated with) the next panel position in the list, choose the
immediately following the breaker rating. When you change the
breaker rating in one row, the
+ or [ character before the breaker rating in the next row also
] character as the tie indicator
+ or ] character that follows the
changes to indicate the changed association between the panel positions.
For example, this screen shows three, single-pole, 20A, tied
breakers occupying positions 08, 10, and 12 on the top right
distribution panel.
Pos 08 10 12
Breaker [ 20A + + 20A +
+ 20A ]
Circuit breakers with ratings above 60A are considered sub-feeds. To configure a
subfeed circuit breaker, select a value above 60A. The interface will display “SUB”
Note
after the rating you have selected. Only the bottom 12 positions on the distribution
panel can be configured as sub-feeds.
26 80kW InfraStruXure PDU—Operation and Configuration
PDU Display Interface

Global Panel Config

Configures the same number of poles or breaker ratings for all circuit breakers simultaneously. For
example, if your system uses only 3-pole, 20-amp breakers, choose this option, scroll to the value 3
for Poles and 020 for Amp Rating, and then select Apply Now and YES to implement your changes.
80kW InfraStruXure PDU—Operation and Configuration 27

Config Screen

System/Network

Use this option of the Config screen to access these options:
System Password • Password: Change the system password required to access
protected screens and fields in the display interface. Enter a
string of up to eight alphanumeric characters, followed by the
underline character (
default password is APC.
Time-out: Set the time that the display interface waits for user
input before it reverts to the initial scrolling of status screens.
Select 1, 2, 5, 10 (the default), or 30 minutes; or 1, 2, or 4 hours,
or Forever.
Invalidate NOW: Re-enter the system password for viewing
password-protected screens.
_) to indicate the end of the string. The
Date/Time Date: Set in the following format: dd-mmm yyyy.
Time: Set in the following format: hh:mm:ss.
Local Interface Contrast: Set the screen contrast for the LCD. Select from 1
(high contrast) to 8 (low contrast).
Key Click: Choose On for an audible click whenever you press
a navigation key. Choose Off to disable the key click.
Beeper: Select High, Medium, Low, or Off to adjust the
loudness of the audible beeper and the key click.
Network Address The following values are set by the InfraStruXure Manager during
initial configuration:
IP: The System IP address, which the domain name server
translates into a domain name.
Mask: The subnet mask, which identifies the subnetwork on
which the InfraStruXure PDU operates.
GW: The Gateway address. This is the physical address of the
InfraStruXure PDU, expressed as a 48-bit hexadecimal number.
28 80kW InfraStruXure PDU—Operation and Configuration
PDU Display Interface

Electrical Config

This option of the Config screen displays information about the electrical service that provides input
to the InfraStruXure PDU. All of the values displayed on this screen are set at the factory. Use this
information when viewing and setting alarms.
Input Config Configure the following items:
Main Input: The voltage from the building’s electrical
service coming into the PDU Main Input switch.
• 3W: 3-phase Delta, measured line-to-line
• 4W: 3-phase wye, measured line-to-neutral
Tran sformer: Indicates whether the InfraStruXure PDU has
a transformer.
Bypass Input: Indicates whether the PDU has a Bypass Input
switch (B).
Fuse: Indicates whether the PDU has fuses protecting the
SCRs in the UPS. The fuses are present only on dual-fed
PDUs and single-fed PDUs without a transformer.
Output Config Configure the following items:
Panel Voltage: The nominal voltage of the distribution panel
supplying power to the load equipment. (This is measured
line-to-neutral.)
Panel Breaker: The rating, in amps, of the breaker feeding
the distribution panel.
Load Test Port: Indicates whether the InfraStruXure PDU
has a Load Test Port.
Frequency: The frequency, in hertz, of the output.
Cross Tie Out: Indicates whether the PDU has a Cross Tie
Output breaker.
Other Config Items Configure the following items:
Load Test Port: Indicates whether the PDU has a load test
port installed.
Max Power: Maximum power of your InfraStruXure PDU
(40kW or 80kW).
Subfeed Port: Indicates the port at which the subfeed resides
(port 3).
80kW InfraStruXure PDU—Operation and Configuration 29
PDU Display Interface

Manufacturer Data

Use this option of the Config screen to display a scrollable list containing information about the
InfraStruXure PDU. This information is useful when requesting service or product updates. The
following information is displayed:
• Manufacturer Name
• Date of Manufacture
• Date of Calibration
• Hardware Revision
• Firmware Revision (for PDU monitoring and metering)
• Serial Number
•Model Number

System ID

Use this option of the Config screen to identify your InfraStruXure PDU. The following fields can be
configured:
Device Name Set a unique name for your InfraStruXure PDU.
Product Location Name the physical location of the product in your data center.
Product Contact Identify the person to notify concerning questions or problems with regard
to the product.

Factory Defaults

Use this option of the Config screen to reset all InfraStruXure PDU settings to their factory default
values.

Firmware Updates

Use this option of the Config screen to download updated firmware to the InfraStruXure PDU.
30 80kW InfraStruXure PDU—Operation and Configuration

System Operation

How to Transfer the UPS into Maintenance Bypass Operation

Select Help from the top-level menu screen of the PDU display interface and select
the first help topic, Putting the PDU into Maintenance Bypass, or follow the
Note
When servicing the UPS, transfer the UPS into maintenance bypass operation. When the UPS is
operating in maintenance bypass, input power flows directly to the PDU and out to the load
equipment.
1. Command the UPS into static bypass operation through the UPS display interface:
procedure below.
E
SC
a. Press the
key at the top-level status screen to
open the top-level menu.
b. Select Control on the top-level menu, and press
E
NTER
the
key.
Top-Level Menu
Control Status Setup Accessories
Control Menu
UPS Into Bypass Do Self Test
c. Select UPS Into Bypass on the Control menu
and, press the
E
NTER
key.
Simulate Power Fail Graceful Reboot
Graceful Turn Off Start Runtime Cal Turn Load On
Confirmation Screen
d. Confirm the selection on the next screen: select
E
NTER
Yes, UPS into Bypass and press the
key.
Confirm Yes, UPS into Bypass No, Abort
The UPS Bypass LED illuminates and the following screens appear:
Logging Display Diags Help
UPS has been
commanded to go
into Bypass...
UPS load is in Bypass
Press any key...
80kW InfraStruXure PDU—Operation and Configuration 31
System Operation
Note
2. Close (turn ON) the Q3 circuit breaker on the PDU.
If you have a dual-fed system, check to ensure that
power is available before operating the Q3 circuit
breaker.
Note
The H3 LED above the Q3 circuit breaker illuminates, indicating that it is safe to
operate the Q3 circuit breaker.
The H2 LED above the Q2 circuit breaker illuminates, indicating that it is safe to
operate the Q2 circuit breaker.
3. Open (turn OFF) the Q2 circuit breaker on the PDU.
4. Open (turn OFF) the UPS System Enable switch.
32 80kW InfraStruXure PDU—Operation and Configuration
5. Open (turn OFF) the XR Battery Enclosure DC
Disconnect circuit breaker.
6. Open (turn OFF) the Q1 circuit breaker on the
PDU.
System Operation
7. If applicable, open (turn OFF) the PDU Q10
Bypass Input (B) switch.
The UPS is now in maintenance bypass operation.
80kW InfraStruXure PDU—Operation and Configuration 33

How to Return from Maintenance Bypass Operation

Select Help from the top-level menu screen on the PDU display interface and select the
second help topic, Returning from PDU Maintenance Bypass, or follow the
Note
1. Close (turn ON) the Q1 circuit breaker on the
procedure below:
PDU.
2. If applicable, close (turn ON) the PDU Q10
Bypass Input (B) switch.
3. Close (turn ON) the XR Battery Enclosure DC
Disconnect circuit breaker.
34 80kW InfraStruXure PDU—Operation and Configuration
4. Close (turn ON) the UPS System Enable switch.
The UPS will show a Forced Bypass message on
the display interface, and the Fault LED will be
red.
5. Command the UPS to apply power to the load:
System Operation
E
SC
a. Press the
key at the top-level status screen to
open the top-level menu and have access to eight
submenus.
b. Select Control, and press the
E
NTER
key.
Top-Level Menu
Control Status Setup Accessories
Control Menu
UPS Into Bypass
c. Select Tu rn Lo a d On from the Control menu, and
press the
E
NTER
key.
Do Self Test Simulate Power Fail Graceful Reboot
Graceful Turn Off Start Runtime Cal Turn Load On
Confirmation Screen
d. On the next screen: select Yes, UPS Load ON, and
press the
E
NTER
key.
Confirm Yes, UPS Load ON No, Abort
The Load On LED illuminates and the interface displays the following two screens:
Logging Display Diags Help
UPS has been
commanded to turn
load power on...
UPS load is on
Press any key...
6. Command the UPS into static bypass operation through the UPS display interface:
E
SC
a. Press the
key at the top-level status screen to
open the top-level menu.
b. Select Control on the top-level menu, and press the
E
NTER
key.
80kW InfraStruXure PDU—Operation and Configuration 35
Top-Level Menu
Control Status Setup Accessories
Logging Display Diags Help
System Operation
c. Select UPS Into Bypass on the Control menu, and
E
NTER
press the
key.
d. Confirm the selection on the next screen: select Yes,
UPS into Bypass, and press the
E
NTER
key.
The H2 LED above the Q2 circuit breaker illuminates, indicating that it is
safe to operate the Q2 circuit breaker.
Note
7. Close (turn ON) the Q2 circuit breaker on the PDU.
Control Menu
UPS Into Bypass Do Self Test Simulate Power Fail Graceful Reboot
Graceful Turn Off Start Runtime Cal Turn Load On
Confirmation Screen
Confirm Yes, UPS into Bypass No, Abort
The H3 LED above the Q3 circuit breaker illuminates, indicating that it is safe to
operate the Q3 circuit breaker
Note
8. Open (turn OFF) the Q3 circuit breaker on the PDU.
The UPS automatically comes out of Static Bypass
operation.
36 80kW InfraStruXure PDU—Operation and Configuration

How to Ensure Total Power Off

1. Command the UPS to turn off power to the load:
E
SC
a. Press the
key at the top-level status
screen to open the top-level menu and have
access to eight submenus.
b. Select Control, and press the
E
NTER
key.
Top-Level Menu
Control Status Setup Accessories
Logging Display Diags Help
Control Menu
UPS Into Bypass
c. Select Tu rn Lo a d Off from the Control
menu, and press the
E
NTER
key.
Do Self Test Simulate Power Fail Graceful Reboot
Graceful Turn Off Start Runtime Cal Turn Load Off
Confirmation Screen
d. On the next screen: select Yes, UPS Load
E
NTER
OFF, and press the
key.
Confirm Yes, UPS Load OFF No, Abort
The Load On LED turns off and the interface displays the following two screens:
2. Set the UPS System Enable switch to the OFF
position.
UPS has been
commanded to turn load power off...
UPS load is off
Press any key...
80kW InfraStruXure PDU—Operation and Configuration 37
System Operation
3. Set the XR Battery Enclosure DC Disconnect
circuit breaker to the OFF position.
4. Pull out all battery units in the XR Battery
Enclosures to the red battery disconnect line.
5. Set the Main Input switch (A), and, if
applicable, the Q10 Bypass Input switch (B),
and Cross Tie Output or MCCB Subfeed
circuit breaker (X) on the PDU to the OFF
position.
6. Set the Q1, Q2, and Q3 circuit breakers on the
PDU to the OFF position.
7. Set the upstream main input, and, if applicable,
the bypass input and utility circuit breaker to the
OFF or Locked Out position.
A
38 80kW InfraStruXure PDU—Operation and Configuration
B

How to Apply Power to the System

This procedure instructs on how to apply power to a system that has already been installed. For initial
start-up instructions, see the InfraStruXure 80kW Installation and Start-Up manual.
1. Set the upstream utility, and, if applicable, the
bypass input and utility circuit breaker to ON.
1. Set the Main Input (A) switch on the
PDU to ON.
2. Set the Q1 circuit breaker on the
PDU to ON to apply power to the UPS.
A
B
3. If applicable, set the Q10 Bypass
Input (B) switch on the PDU to ON.
80kW InfraStruXure PDU—Operation and Configuration 39
System Operation
4. Ensure that all battery units are pushed all the way into the XR Battery Enclosures and locked
into position.
5. Set the XR Battery Enclosure DC Disconnect
circuit breaker to ON.
6. Set the UPS System Enable switch to ON
When the System Enable switch is placed in the ON position, the Startup screen appears on the
display interface of the Symmetra PX UPS.
PowerView RM
Rev: 000 English
Please wait...
The top-level status screen appears on the display interface. This may take up to 30 seconds.
Fuel% Load% In 208V out000V 60Hz Runtime:
|||||||||||| |||
1hr 2m
40 80kW InfraStruXure PDU—Operation and Configuration
7. Read the messages displayed on the UPS display interface:
System Operation
a. Note any alarms, and verify that they are appropriate
for start-up conditions.
b. Verify that the UPS accepts the input.
8. Command the UPS to apply power to the load:
E
SC
a. Press the
key at the top-level status screen to open
the top-level menu and have access to eight submenus.
E
NTER
b. Select Control, and press the
key.
c. Select Tu rn Lo a d On from the Control menu, and
press the
E
NTER
key.
Top-Level Status Screen
Fuel% Load% In 208V out000V 60Hz Runtime:
|||||||||||| |||
1hr 2m
Top-Level Menu
Control Status Setup Accessories
Logging Display Diags Help
Control Menu
UPS Into Bypass Do Self Test Simulate Power Fail Graceful Reboot
Graceful Turn Off Start Runtime Cal Turn Load On
d. On the next screen: select Yes, UPS Load ON, and
E
NTER
press the
key.
Confirmation Screen
Confirm Yes, UPS Load ON No, Abort
The Load On LED illuminates, and the interface displays the following two screens:
UPS has been
commanded to turn
load power on...
UPS load is on
Press any key...
80kW InfraStruXure PDU—Operation and Configuration 41
System Operation
9. To apply power to the PDU distribution panel,
close (turn ON) the Q2 circuit breaker on the PDU.
10. To apply power to the PDU power cords and
connected equipment, close (turn ON) the
distribution panel breakers.
11. If applicable, close (turn ON) the Cross Tie
Output or MCCB Subfeed (X) circuit breaker.
42 80kW InfraStruXure PDU—Operation and Configuration

Communication Configuration

o
o
o

InfraStruXure PDU Management Options

Overview

You have two management options for the InfraStruXure PDU. You can manage the InfraStruXure
PDU along with the rest of your InfraStruXure equipment through the InfraStruXure Manager (APC
LAN), or you can manage your InfraStruXure PDU through APC’s network management interfaces
(User LAN).

InfraStruXure Manager

The InfraStruXure Manager is a rack-mount management device that coordinates the management
functions of APC InfraStruXure-Certified devices installed in your data center. It provides one single
interface to view and configure all APC InfraStruXure-Certified devices. See “Configuring the
InfraStruXure Manager” on page 44 for configuration instructions.
For more information about the InfraStruXure Manager, see the Installation and
Configuration manual included with the InfraStruXure Manager.
See als

Network management interfaces

The control console and Web interfaces provide menus with options that allow you to manage the
UPS. See “Configuring the Network Management Interface” on page 45 for configuration
instructions.
For more information about the internal user interfaces, see the InfraStruXure PDU
online Network Management User’s Guide.
See als
®
The SNMP interface allows you to use an SNMP browser with the PowerNet
Information Base (MIB) to manage the UPS. See “Configuring the Network Management Interface”
on page 45 for configuration instructions.
To use the PowerNet MIB with an SNMP browser, see the PowerNet® SNMP
Management Information Base (MIB) Reference Guide, which is provided on the
See als
InfraStruXure PDU Utility CD.
Management
80kW InfraStruXure PDU—Operation and Configuration 43

Configuring the InfraStruXure Manager

o

Connect the InfraStruXure PDU to the InfraStruXure Manager

1. Connect a Cat-5 network cable to the surge-protected ethernet port on the PDU user connection
plate.
You can make connections from
inside the enclosure, or you can
remove the user connection plate
and make your connections.
Remove the plate using a Phillips
or standard screwdriver to loosen
the two captive screws. Use the
knockout in the plate to route
cables to and from the user
connections on the plate. If you
remove the plate, make sure that
you do not disturb the existing connections.
2. Run the connected Cat-5 network cable through the knockout in the user connection plate to the
InfraStruXure Manager Hub.
3. Once all APC InfraStruXure-Certified equipment is installed, the network cables are connected
to the InfraStruXure Manager Hub, and start-up of the system is complete, configure the
InfraStruXure Manager.
For detailed configuration instructions, see the InfraStruXure Manager Installation and
See als
Quick-Start manual included with your InfraStruXure Manager.
44 80kW InfraStruXure PDU—Operation and Configuration

Configuring the Network Management Interface

Connect the InfraStruXure PDU to your network

1. Connect a Cat-5 network cable to the surge-protected ethernet port on the PDU user connection
plate.
You can make connections from
inside the enclosure, or you can
remove the user connection plate
and make your connections.
Remove the plate using a Phillips
or standard screwdriver to loosen
the two captive screws. Use the
knockout in the plate to route
cables to and from the user
connections on the plate. If you
remove the plate, make sure that you do not disturb the existing connections.
2. Run the connected Cat-5 network cable through the knockout in the user connection plate to
your network connection.
3. Configure the TCP/IP settings of the InfraStruXure PDU. See “Configuration Overview” on
this page for further instructions.

Configuration Overview

You must configure the following TCP/IP settings before the InfraStruXure PDU can operate on a
network:
• IP address of the InfraStruXure PDU
• Subnet mask
• Default gateway
If a default gateway is unavailable, use the IP address of a computer that is located on the same subnet as the InfraStruXure PDU and that is usually running. The
Note
InfraStruXure PDU uses the default gateway to test the network when traffic is very light. See “Watchdog Features” in the “Introduction” of the InfraStruXure Power Distribution Unit’s online Network Management User’s Guide for more information about the watchdog role of the default gateway.
80kW InfraStruXure PDU—Operation and Configuration 45
Communication Configuration
o

TCP/IP configuration methods

Use one of the following methods to define the TCP/IP settings needed by the InfraStruXure PDU:
• Device IP Configuration Wizard (See “Device IP Configuration Wizard” on this page.)
• BOOTP or DHCP server (See “BOOTP & DHCP configuration” on page 47.)
• Local computer (See “Local access to the control console” on page 49.)
• Networked computer (See “Remote access to the control console” on page 49.)

Device IP Configuration Wizard

You can use the Device IP Configuration Wizard on a Windows NT® 4.0, Windows 2000, or
Windows XP computer to discover unconfigured InfraStruXure PDUs and configure their basic
TCP/IP settings.
To configure one or more InfraStruXure PDUs by exporting configuration settings from
a configured PDU, see “How to Export Configuration Settings” in the online Network
See als
Management User’s Guide on the Utility CD.
1. Insert the InfraStruXure PDU Utility CD into a computer on your network.
2. Launch the Wizard, when prompted, or, if prompted to restart the computer, access the Wizard
from the Start menu after the computer has restarted.
3. Wait for the Wizard to discover the first unconfigured InfraStruXure PDU, then follow the on-
screen instructions.
If you leave the Start a Web browser when finished option enabled, you can use apc
for both the User Name and Password to access the InfraStruXure PDU through your
Note
browser.
46 80kW InfraStruXure PDU—Operation and Configuration
Communication Configuration
o

BOOTP & DHCP configuration

The Boot Mode Setting, a TCP/IP option in the InfraStruXure PDU’s Network menu, identifies how
the TCP/IP settings will be defined. The possible settings are Manual, DHCP only, BOOTP only,
and DHCP & BOOTP (the default setting).
The DHCP & BOOTP setting assumes that a properly configured DHCP or BOOTP
server is available to provide TCP/IP settings to InfraStruXure PDUs. If these servers
Note
are unavailable, see “Device IP Configuration Wizard” on page 46, “Local access to the
control console” on page 49, or “Remote access to the control console” on page 49 to
configure the needed TCP/IP settings.
With Boot Mode set to DHCP & BOOTP, the InfraStruXure PDU attempts to discover a properly
configured server. It first searches for a BOOTP server, then a DHCP server, and repeats this pattern
until it discovers a BOOTP or DHCP server.
For more information, see “BOOTP” on this page or “DHCP” on page 48.
Note
BOOTP. You can use an RFC951-compliant BOOTP server to configure the TCP/IP settings for the
InfraStruXure PDU.
The BOOTP setting assumes that a properly configured BOOTP server is available to
provide TCP/IP settings to APC InfraStruXure PDUs. If a BOOTP server is unavailable,
Note
see “Device IP Configuration Wizard” on page 46, “Local access to the control console”
on page 49, or “Remote access to the control console” on page 49 to configure the
TCP/IP settings.
1. Make sure that the BOOTP setting, a TCP/IP option in the InfraStruXure PDU’s Network
menu, is enabled.
2. Enter the InfraStruXure PDU’s MAC and IP addresses, the subnet mask and default gateway
settings, and an optional Bootup file name in the BOOTPTAB file of the BOOTP server.
For the MAC address, look on the Quality Assurance slip included with the
InfraStruXure PDU.
See als
80kW InfraStruXure PDU—Operation and Configuration 47
Communication Configuration
o
o
3. When the InfraStruXure PDU reboots, the BOOTP server provides it with the TCP/IP settings.
– If you specified a bootup file name, the InfraStruXure PDU attempts to transfer that file from
the BOOTP server using TFTP or FTP. The InfraStruXure PDU assumes all settings
specified in the bootup file.
– If you did not specify a bootup file name, the InfraStruXure PDU can be configured remotely
by using Telnet or by using the Web interface: User Name and Password are both apc, by
default.
To create the bootup file, see your BOOTP server documentation.
See als
DHCP. You can use a RFC2131/RFC2132-compliant DHCP server to configure the TCP/IP settings
for the InfraStruXure PDU.
This section briefly summarizes the InfraStruXure PDU communication with a DHCP
server. For more detail about how a DHCP server is used to configure the network
See als
settings for a InfraStruXure PDU, see “DHCP Configuration” in the InfraStruXure
PDU’s online Network Management User’s Guide.
1. A InfraStruXure PDU sends out a DHCP request that uses the following to identify itself:
– A Vendor Class Identifier (APC by default)
– A Client Identifier (by default, the InfraStruXure PDU’s MAC address value)
– A User Class Identifier (by default, the identification of the InfraStruXure PDU’s application
firmware)
2. A properly configured DHCP server responds with a DHCP offer that includes all of the
settings that the InfraStruXure PDU needs for network communication. The DHCP offer also
includes the Vendor Specific Information option (DHCP option 43). By default, the
InfraStruXure PDU will ignore DHCP offers that do not encapsulate the APC cookie in the
Vendor Specific Information option using the following hexidecimal format:
Option 43 = 01 04 31 41 50 43
where
– the first byte (
– the second byte (
– the remaining bytes (
01) is the code
04) is the length
31 41 50 43) are the APC cookies
See your DHCP server documentation to add code to the Vendor Specific Information
option. To disable the APC cookie requirement, see “Local access to the control
console” on page 49.
To change the control console’s DHCP Cookie Is setting, use the Advanced option in
the TCP/IP menu. See “Remote access to the control console” on page 49.
48 80kW InfraStruXure PDU—Operation and Configuration
Communication Configuration
o

Local access to the control console

You can use a local computer that connects to the InfraStruXure PDU through the console port on the
InfraStruXure PDU monitoring unit to access the control console.
1. Select a serial port at the local computer, and disable any service that uses that port.
2. Use the configuration cable (APC part number 940-0103) to connect the selected port to the
console port on the InfraStruXure PDU monitoring unit.
3. Run a terminal program (such as HyperTerminal
®
) on your computer and configure the selected
port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control, and save the changes.
4. Press E
NTER to display the User Name prompt.
5. Use apc for the User Name and Password.
6. See “Control console” on page 50 to finish the configuration.

Remote access to the control console

From any computer on the same subnet as the InfraStruXure PDU, you can use ARP and Ping to
assign an IP address to an InfraStruXure PDU, and then use Telnet to access that InfraStruXure
PDU’s control console and configure the needed TCP/IP settings.
After an InfraStruXure PDU has its IP address configured, you can use Telnet, without
first using ARP and Ping, to access that InfraStruXure PDU.
Note
1. Use ARP to define an IP address for the InfraStruXure PDU, and use the InfraStruXure PDU’s
MAC address in the ARP command. For example, to define an IP address of 156.205.14.141 for
an InfraStruXure PDU that has a MAC address of 00 c0 b7 63 9f 67, use one of the following
commands:
– Windows command format:
arp -s 156.205.14.141 00-c0-b7-63-9f-67
– LINUX command format:
arp -s 156.205.14.141 00:c0:b7:63:9f:67
For the MAC address, look on the Quality Assurance slip included with the
InfraStruXure PDU.
See als
80kW InfraStruXure PDU—Operation and Configuration 49
Communication Configuration
2. Use Ping with a size of 113 bytes to assign the IP address defined by the ARP command. For the
IP address defined in step 1, use one of the following Ping commands:
– Windows command format:
ping 156.205.14.141 -l 113
– LINUX command format:
ping 156.205.14.141 -s 113
3. Use Telnet to access the InfraStruXure PDU at its newly assigned IP address. For example:
telnet 156.205.14.141
4. Use apc for both User Name and Password.
5. See “Control console” on this page to finish the configuration.

Control console

After you log on at the control console, as described in “Local access to the control console” on
page 49 or “Remote access to the control console” on page 49:
1. Choose Network from the Control Console menu.
2. Choose TCP/IP
from the Network menu.
3. If you are not using a BOOTP or DHCP server to configure the
TCP/IP settings, select the Boot Mode menu. Select Manual boot mode, and then press
return to the TCP/IP menu. (Changes will take effect when you log out.)
4. Set the System
5. Press
CTRL-C to exit to the Control Console menu.
IP, Subnet Mask, and Default Gateway address values.
6. Log out (option 4 in the Control Console menu).
If you disconnected a cable during the procedure described in “Local access to the
control console” on page 49, reconnect that cable and restart the associated service.
Note
ESC to
50 80kW InfraStruXure PDU—Operation and Configuration
How to Access a Network Management
o
Interface on a Configured InfraStruXure PDU
Disregard the procedures in this section if you have the APC InfraStruXure
Manager as part of your system. See the InfraStruXure Manager’s Installation
Note

Web interface

As your browser, you can use Microsoft® Internet Explorer 5.0 (and higher) or Netscape® 4.0.8 (and
higher, except Netscape 6.x) to access the InfraStruXure PDU through its Web interface. Other
commonly available browsers also may work but have not been fully tested by APC.
To use the Web browser to configure InfraStruXure PDU options or to view the event log, you can
use either of the following:
• The HTTP protocol (enabled by default), which provides authentication by user name and
and Quick-Start manual for access information.
password but no encryption.
• The more secure HTTPS protocol, which provides extra security through Secure Socket Layer
(SSL) and encrypts user names, passwords, and data being transmitted. It also provides
authentication of Network Management Cards by means of digital certificates.
To access the Web interface and configure the security of your device on the network:
1. Address the InfraStruXure PDU by its IP address or DNS name (if configured).
2. Enter the user name and password (by default, apc and apc for an Administrator, or device and apc for a Device Manager).
3. Select and configure the type of security you want. (This option is available only for Administrators.)
See the chapter entitled “Security” in the InfraStruXure PDU’s online Network
Management User’s Guide for information on choosing and setting up your
See als
network security. Use the Web/SSL option of the Network menu to enable or
disable the HTTP or HTTPS protocols.

Teln et an d SSH

You can access the control console through Telnet or Secure SHell (SSH), depending on which is
enabled. (An Administrator can enable these access methods through the Telnet/SSH option of the
Network menu.) By default, Telnet is enabled. Enabling SSH automatically disables Telnet.
80kW InfraStruXure PDU—Operation and Configuration 51
Communication Configuration
o
Telnet for basic access. Telnet provides the basic security of authentication by user name and
password, but not the high-security benefits of encryption. To use Telnet to access an InfraStruXure
PDU’s control console from any computer on the same subnet:
1. At a command prompt, use the following command line, and press
telnet address
ENTER:
As address, use the InfraStruXure PDU’s IP address or DNS name (if configured).
2. Enter the user name and password (by default, apc and apc for an Administrator, or device and
apc for a Device Manager).
SSH for high-security access. If you use the high security of SSL for the Web interface, use
Secure SHell (SSH) for access to the control console. SSH encrypts user names, passwords, and
transmitted data.
The interface, user accounts, and user access rights are the same whether you access the control
console through SSH or Telnet, but to use SSH, you must first configure SSH and have an SSH client
program installed on your computer.
See the InfraStruXure PDU’s online Network Management User’s Guide for more information on configuring and using SSH.
See als

SNMP

After you add the PowerNet MIB to a standard SNMP MIB browser, you can use that browser for
SNMP access to the InfraStruXure PDU. The default read community name is public; the default
read/write community name is private.
If you enable SSL and SSH for their high-security authentication and encryption,
disable SNMP. Allowing SNMP access to the InfraStruXure PDU compromises the
Note
high security you implement by choosing SSL and SSH. To disable SNMP, you must be
an Administrator; use the SNMP option of the Network menu.
52 80kW InfraStruXure PDU—Operation and Configuration
Communication Configuration
o

FTP an d SCP

You can use FTP (enabled by default) or Secure CoPy (SCP) to transfer new firmware to the
InfraStruXure PDU, or to access a copy of the InfraStruXure PDU’s event logs. SCP provides the
higher security of encrypted data transmission and is enabled automatically when you enable SSH.
If you enable SSL and SSH for their high-security authentication and encryption, disable FTP. Allowing file transfer to the InfraStruXure PDU through FTP
Note
compromises the high security you implement by choosing SSL and SSH. To disable FTP, you must be an Administrator; use the FTP Server option of the Network menu.
To access the InfraStruXure PDU through FTP or SCP, the default user name and password are apc and apc for an Administrator, or device and apc for a Device Manager. In the command line, use the IP address of the unit.
See the InfraStruXure PDU’s online Network Management User’s Guide to use FTP or SCP to retrieve log files from the InfraStruXure PDU or to transfer firmware files to the
See als
InfraStruXure PDU.
80kW InfraStruXure PDU—Operation and Configuration 53

How to Recover From a Lost Network Management Interface Password

Disregard the procedures in this section if you have the APC InfraStruXure
Manager as part of your system. See the InfraStruXure Manager’s Installation
Note
1. Select a serial port at the local computer, and disable any service that uses that port.
2. Connect the serial cable (APC part number 940-0103) to the selected port on the computer and
3. Run a terminal program (such as HyperTerminal®) on your computer and configure the selected
and Quick-Start manual for information on recovering from a lost password.
to the console port on the
port as follows:
– 9600 bps
– 8 data bits
–no parity
InfraStruXure PDU monitoring unit.
– 1 stop bit
– no flow control
4. Press
5. Press the Reset button on the InfraStruXure PDU monitoring unit. The Status LED will flash
6. Press
7. From the Control Console menu, select System, then User Manager.
ENTER, repeatedly if necessary, to display the User Name prompt. If you are unable to
display the User Name prompt, verify the following:
– The serial port is not in use by another application.
– The terminal settings are correct as specified in step 3.
– The correct cable is being used as specified in step 2.
alternately orange and green. Press the Reset button on the InfraStruXure PDU monitoring unit
a second time immediately while the LED is flashing to reset the user name and password to
their defaults temporarily.
ENTER as many times as necessary to redisplay the User Name prompt, then use the
default, apc, for the user name and password. (If you take longer than 30 seconds to log on after
the User Name prompt is redisplayed, you must repeat step 5 and log on again.)
8. Select Administrator, and change the User Name and Password settings, both of which are
now defined as apc.
9. Press
54 80kW InfraStruXure PDU—Operation and Configuration
CTRL-C, log off, reconnect any serial cable you disconnected, and restart any service you
disabled.

Customizing and Updating the PDU

Important Safety Instructions

APC does not recommend that you perform maintenance of the PDU while it is
Electrical
Hazard
receiving input power. However, due to the critical nature of data center loads, this
may occur. If you must perform maintenance while the PDU is receiving input
power, observe the following precautions to reduce the risk of electric shock:
1. Never work alone.
2. Perform the maintenance only if you are a certified electrician who is trained
in the hazards of live electrical installation.
3. Know the procedure for disconnecting electricity to the PDU and the data
center in case of an emergency.
4. Wear appropriate personal protective equipment.
5. Use double-insulated tools.
6. Always follow local and site regulations when working on the PDU.
80kW InfraStruXure PDU—Operation and Configuration 55

PDU Orderable Part List

Circuit Breakers
PD1P20ABBSD single-pole, 20-amp breaker PD3P20ABBSD three-pole, 20-amp breaker
PD1P50ABBSD single-pole, 50-amp breaker PD3P80ABBSD three-pole, 80-amp breaker
PD2P20ABBSD two-pole, 20-amp breaker PD3P100ABBSD three-pole, 100-amp breaker
PD2P30ABBSD two-pole, 30-amp breaker PD3P150ABBSD three-pole, 15-amp breaker
Power Cables
20A, 3-wire power cables
PDW5L21-20R 5-foot power cable PDW35L21-20R 35-foot power cable
PDW7L21-20R 7-foot power cable PDW37L21-20R 37-foot power cable
PDW9L21-20R 9-foot power cable PDW39L21-20R 39-foot power cable
PDW11L21-20R 11-foot power cable PDW41L21-20R 41-foot power cable
PDW13L21-20R 13-foot power cable PDW43L21-20R 43-foot power cable
PDW15L21-20R 15-foot power cable PDW45L21-20R 45-foot power cable
PDW17L21-20R 17-foot power cable PDW47L21-20R 47-foot power cable
PDW19L21-20R 19-foot power cable PDW49L21-20R 49-foot power cable
PDW21L21-20R 21-foot power cable PDW51L21-20R 51-foot power cable
PDW23L21-20R 23-foot power cable PDW53L21-20R 53-foot power cable
PDW25L21-20R 25-foot power cable PDW55L21-20R 55-foot power cable
PDW27L21-20R 27-foot power cable PDW57L21-20R 57-foot power cable
PDW29L21-20R 29-foot power cable PDW59L21-20R 59-foot power cable
PDW31L21-20R 31-foot power cable PDW61L21-20R 61-foot power cable
PDW33L21-20R 33-foot power cable PDW63L21-20R 63-foot power cable
56 80kW InfraStruXure PDU—Operation and Configuration
Customizing and Updating the PDU
Power Cables
30A, 3-wire power cables
PDW7L6-30C 7-foot power cable PDW43L6-30C 43-foot power cable
PDW9L6-30C 9-foot power cable PDW45L6-30C 45-foot power cable
PDW11L6-30C 11-foot power cable PDW47L6-30C 47-foot power cable
PDW13L6-30C 13-foot power cable PDW49L6-30C 49-foot power cable
PDW15L6-30C 15-foot power cable PDW51L6-30C 51-foot power cable
PDW17L6-30C 17-foot power cable PDW53L6-30C 53-foot power cable
PDW19L6-30C 19-foot power cable PDW55L6-30C 55-foot power cable
PDW21L6-30C 21-foot power cable PDW57L6-30C 57-foot power cable
PDW23L6-30C 23-foot power cable PDW59L6-30C 59-foot power cable
PDW25L6-30C 25-foot power cable PDW61L6-30C 61-foot power cable
PDW27L6-30C 27-foot power cable PDW63L6-30C 63-foot power cable
PDW29L6-30C 29-foot power cable PDW65L6-30C 65-foot power cable
PDW31L6-30C 31-foot power cable PDW67L6-30C 67-foot power cable
PDW33L6-30C 33-foot power cable PDW69L6-30C 69-foot power cable
PDW35L6-30C 35-foot power cable PDW71L6-30C 71-foot power cable
PDW37L6-30C 37-foot power cable PDW73L-30C 73-foot power cable
PDW39L6-30C 39-foot power cable PDW75L6-30C 75-foot power cable
PDW41L6-30C 41-foot power cable
80kW InfraStruXure PDU—Operation and Configuration 57

How to Add Circuit Breakers and Power Cables

Add a circuit breaker on the PDU

1. Snap and bolt the new circuit breaker
into a position on the panel.
2. Remove the corresponding plastic
blanking plate on the front panel of the
PDU.

Add a power cable to the PDU or RDP

Before adding a power cable, add a circuit breaker.
1. Install a strain-relief connector in
any available knockout on the roof
of the PDU.
2. Slide enough of the power cable
through the strain-relief connector
to reach the new circuit breaker.
3. Tighten the strain-relief connector.
If you are installing 20A or 30A power cables in a knockout designed for 50 A
power cables, you must use reducing washers (provided) to adjust the size of the
Note
knockout.
58 80kW InfraStruXure PDU—Operation and Configuration
Customizing and Updating the PDU
4. At the front of the PDU, connect the power cord’s individual wires:
a. If you have branch current monitoring installed, route the phase conductor through a current
sensor. If it is a three-phase cable, route the L1, L2, and L3 wires through a current sensor.
b. Connect the L1, L2, and L3 wires to the circuit breaker(s). The illustration below shows
single pole circuit breakers; however, you can also connect three-pole breakers.
c. Connect the neutral wire to the closest open termination point on the Neutral Bar (N).
d. Connect the ground wire to the closest open termination point on the Ground Bar (G).
N
G
80kW InfraStruXure PDU—Operation and Configuration 59

How to Test the EPO Switch

Overview

APC offers an optional InfraStruXure EPO System (EPW9). Contact your APC sales
representative, or visit the APC Web site (www.apc.com) for more information.
Note
After a certified electrician has connected an EPO switch to the PDU
monitoring unit by way of the user connection plate, you can easily test
the switch to make sure it is wired and working properly. The
illustration below shows the EPO functions on the PDU monitoring unit.
EPO DIP switches configure the EPO input for the type of EPO
switch that is connected—Normally Open (NO) or Normally
Closed (NC).
When the EPO Arm/Test rocker is in the Test position, engaging the EPO switch will not
cause the load to be powered off. When the rocker is in the Armed position, engaging the
EPO switch will cause the PDU’s main input switch and the Symmetra PX UPS to be
switched OFF. The EPO Armed LED is green when the rocker is in the Armed position. The led is dark
when the rocker is in the Test position. The EPO Tripped LED is red when the EPO switch is engaged (the EPO button is pressed),
regardless of the state of the EPO Arm/Test rocker.
 
ARMED
EPO
TRIPPED
TEST
NC
NO

Testing the EPO wiring and switches

1. Place the Arm/Test rocker switch in the Te st position. The EPO state LEDs will be dark and
the PDU display interface will show the following alarm (in addition to any other active
alarms):
Active Alarm xxofxx EPO Ready To Test
2. Engage the EPO switch. (If your switch is momentary, engage it with one person watching the
EPO state LEDs, and another at the EPO switch.)
3. Observe the EPO LEDs. If the switch is wired and working properly, when the switch is
engaged, both of the EPO state LEDs are red.
60 80kW InfraStruXure PDU—Operation and Configuration
Customizing and Updating the PDU
4. If the test was successful, place the Arm/Test rocker switch back to the Arm position. The
PDU display interface will clear the EPO test mode alarm. If the test was not successful, see the
troubleshooting chart:
Problem Action
5. Repeat this test for each EPO switch installed.
6. Ensure that the Arm/Test rocker switch is in the Arm position on the monitoring unit.

Safety warnings

Neither state LED was red
when the EPO switch was
engaged
Only one of the state LEDs
was red when the EPO switch
was engaged
• Check the wiring to your EPO switch
• Check to make sure the EPO DIP
switch configuration is correct for
your switch (NO or NC).
• Check to make sure the EPO DIP
switch configuration is correct for
your switch (NO or NC) and test
again.
• If the switch is configured correctly
and both LEDs are not red after testing
again, contact customer support at a
number on the back cover of this
manual.
Hazardous voltage from the branch circuit must be isolated from the 24VAC, 24 VDC, and contact
closure. 24VAC and 24VDC are considered Class 2 circuits as defined in Article 725 of the National
Electrical Code (NFPA 70) and Section 16 of the Canadian Electrical Code (C22.1).
A Class 2 circuit is a source having limited voltage and energy capacity as follows:
a. If an Inherently Limited Power Source, voltage and energy are limited to less than 30VAC,
less than 30VDC, and 8A.
b. If not an Inherently Limited Power Source, voltage and energy are limited to less than
30VAC, less than 60VDC, 250VA, and the current is limited to 1000/Vmax. The fuse is
limited to 5A if less than 20VAC or 20VDC, or 100/V maximum if less than 30VAC or
60VDC.
80kW InfraStruXure PDU—Operation and Configuration 61
Customizing and Updating the PDU
If you choose to use a 24VAC, 24VDC, or contact closure connection to the EPO, use one of the
following UL-listed wire types:
• CL2 Class 2 cable for general purpose use
• CL2P Plenum cable for use in ducts, plenums, and other space used for environmental air
• CL2R Riser cable for use in a vertical run shaft from floor to floor
• CL2X Limited Use cable for use in dwellings and for use in a raceway
• For installation in Canada, the cable should be CSA certified, type ELC (extra-low-voltage
control cable).
If you do not use a CL2 cable, route the EPO wiring in conduit that does not contain any branch
circuit wiring.
62 80kW InfraStruXure PDU—Operation and Configuration

How to Connect User Input Contacts and Relay Outputs to the PDU User Connection Plate

Overview

Make contact closure connections
(NO or NC) at the user connection
USER INTERFACE
plate to monitor dry contacts. You can
make eight connections—four input
contacts and four relay outputs.
The figure at the right shows the
location of the user connection plate
on the roof of the PDU enclosure.
You can make connections from
inside the enclosure, or you can
remove the user connection plate and
make your connections.
© 2001 APC
MADE IN USA
1 234
Contact Inputs
Contact Out puts
– +
EPO 24V
EPO
ATS 1
ATS 0
ATS 2
AC/DC
Contact
ATS EN
Remove the plate using a Phillips or
standard screwdriver to loosen the
two captive screws. Use the knockout
in the plate to route cables to and from
the user connection plate. If you
remove the plate, make sure that you
do not disturb the existing
connections.
80kW InfraStruXure PDU—Operation and Configuration 63
Customizing and Updating the PDU
How to connect contacts to the PDU monitoring unit.
1. Choose one or more contact numbers on the User/EPO contacts port on the user connection
plate to which you will connect the contacts. The user connection plate connects to the PDU
monitoring unit.
2. From the PDU display interface:
a. Press the
b. Select Contacts on the top-level menu screen, and press the
c. Select Contact Inputs (or Relay Outputs) and press
ESC or ENTER key to go to the top-level menu screen.
Load-Meter Volt-Meter
Contacts Breakers
Alarms Panel
Config Help
ENTER to display the contact inputs (or
ENTER key.
relay outputs) screen.
>Contact Inputs >Relay Outputs >Alarm Relay Map
d. Select Contact In and press the
ENTER key to select the number of the contacts you are
connecting. The continue arrow will appear next to the contact number.
Contact In:01of04 Name:User Contact 1 Normal: Open Status: Closed
e. Press the Up or Down arrow key to select the appropriate contact number, and press the
ENTER key.
f. Press the Down arrow key to enter a unique Name for the contact and to configure the
Normal state of the contact (Open or Closed). The default Normal state is Open. Press the
ENTER key to select the item to configure.
You will be prompted for your password to configure these items.
Note
3. Connect contact wires (300V-rated cabling required) to the User Contacts terminal block on the
user connection plate. You will need a 2.5-millimeter standard screwdriver.
4. Run the wires from the user connection plate to your contact’s location.
Ensure that wires are properly retained and away from high voltage lines and breakers.
Warning
64 80kW InfraStruXure PDU—Operation and Configuration
How to Download Firmware Upgrades

Upgrading the PDU monitor processor

You can download available PDU monitor processor upgrades through the PDU display interface.
The most obvious indication that a firmware upgrade is necessary occurs when the Network
Management Card and the monitor processor stop communicating. This lack of communication
causes the PDU’s data to no longer be accesible through the display interface and a SysData
Mismatch alarm to occur. When this alarm occurs, perform the following steps to upgrade the PDU
monitor processor firmware:
1. Upgrade the PDU Network Management Card.
For instructions on how to upgrade the PDU’s Network Management Card,
refer to the online Network Management User’s Guide on the Utility CD
See also
2. At the PDU display interface, select Config, and then Firmware Updates. You will receive the
following screen:
provided with your InfraStruXure PDU.
Press any key to download the upgrade.
If you do not receive the SysData Mismatch alarm, but want to check for
available firmware upgrades, you can do so by performing step 2 in the
Note
procedure above.

Downloading firmware upgrades from a local computer

To download a firmware upgrade and transfer it to your PDU, see “File Transfers” in
the InfraStruXure PDU’s online Network Management User’s Guide on the Utility CD.
See also
1. Select a serial port at the local computer, and disable any service that uses that port.
2. Use the configuration cable to connect the selected port to the console port on the PDU
monitoring unit.
3. Run a terminal program (such as HyperTerminal
®
) and configure the selected port for 9600 bps,
8 data bits, no parity, 1 stop bit, and no flow control. Save the changes.
4. Press
ENTER twice to display the User Name prompt.
80kW InfraStruXure PDU—Operation and Configuration 65
Customizing and Updating the PDU
5. Enter your User Name and Password (both apc, for administrators only) and press the ENTER
key.
6. From the Control Console menu, select System, then Too ls, then File Transfer, then
XMODEM.
7. The system will then prompt you with
and press
ENTER.
Perform transfer with XMODEM -CRC? Typ e Yes
8. The system will then prompt you to choose a transfer rate and to change your terminal settings
to match the transfer rate. Press
ENTER to set the PDU to accept the download.
9. In the terminal program, send the file using XMODEM protocol. Upon completion of the
transfer, the console will prompt you to restore the baud rate to normal.
Do not interrupt the download.
Caution
The PDU network management interface will reboot when the download is complete.
66 80kW InfraStruXure PDU—Operation and Configuration

Specifications

80kW InfraStruXure PDU

Performance
Transformer Efficiency (if installed) 97%
System Full Load Output Rating 80kW
System Monitoring
Of Current Distribution branch monitoring (optional), subfeed
Of Voltage AC main input, bypass input, output at distribution panels,
output of fuses
Of Bypass Bypass breaker positions, bypass lamp cue/feedback
Switches/ Breakers Status Bypass breaker positions, input switch positions, cross tie
output switch position
Transformer Temperature Sensor 180°C (triggers a warning through the PDU monitoring unit)
Branch Current Monitoring
Parameters Maximum current (RMS): 95A
Maximum current (peak): 135A Maximum crest factor: 3 Minimum current: 0.5A Measurement accuracy: ± 0.5A or 5% of reading (whichever is greater) Maximum wire size: 0.35in (8.89mm)
Electrical PD80F6FK1-M PD80G6FK1-M PD80L6FK1-M
Input
Nominal Voltage 208V Delta 480V Delta 600 V Delta
Nominal Bypass Voltage 208V WYE
Nominal Current 251A 109A 87A
Max. Current 350A 150A 125 A
Output
Nominal Voltage 208:120V WYE
Frequency 57–63 Hz
Max. Continuous Nominal Current 277.5A
Nominal Current 222A
Wiring
PDU to UPS 4W + G (AC mains input) 4W (Bypass input)
UPS to PDU 4W 4W 4W
PDU to Distribution Panels 4W + G 4W + G 4W + G
80kW InfraStruXure PDU—Operation and Configuration 67
Specifications
Electrical PD80F6FK1-M PD80G6FK1-M PD80L6FK1-M
Power Cables to Enclosures/ Rack PDUs 4W + G 4W + G 4W + G
Power Cable Connections L21-20 L21-20 L21-20
Power Cable Lengths Various Various Various
Power Cable Wiring (Top Exit) Accommodates 10 + cables
Power Cable Wiring (Bottom Exit) Accommodates 10 + cables
Subfeed
Subfeed Wiring (3 -phase) 4W + G 4W + G 4W + G
Subfeed Connector System 100A, pin and sleeve
Subfeed Voltage 208:120V 208:120V 208:120V
Subfeed Current 80A 80A 80A
Panels
Panel Style
3-phase 3-phase 3-phase
Number of Panels (per PDU) 1 maximum 1 maximum 1 maximum
Positions per Panel 42 42 42
3-phase Breakers per Panel 10 (with 4 subfeeds)
3-phase Subfeeds per Panel 4 maximum 4 maximum 4 maximum
1-phase Breakers per Panel 30 (with 4 subfeeds)
Panel Rating 240V/400A per phase
Panel Board Accessibility Through rear of unit
Relay Outputs
Nominal Switching Capacity 1A at 30VDC
Maximum Switching Power 30W
Maximum Switching Voltage 60VDC
Maximum Switching Current 2ADC
Maximum Carrying Current 2ADC
Surge Ratings 2kV per Bellcore TA-NWT-001089
1.5kV per FCC part 68
Physical PD80F6FK1-M PD80G6FK1-M PD80L6FK1-M
Dimensions (H × W × D)
PDU 81 × 29 × 36 in (2057 × 737 × 914 mm)
AC Power Trough 7.5 × 4.0 × 29.0 in (190 ×100 × 740 mm)
Ramp (L × W) 45 × 6 in (1143 × 150 mm)
Weig ht
PDU with a Transformer 2100 lb (953 kg)
PDU without a Transformer 1284 lb (583 kg)
68 80kW InfraStruXure PDU—Operation and Configuration
Specifications
Physical PD80F6FK1-M PD80G6FK1-M PD80L6FK1-M
Shipping with a Transformer 2200 lb (1000 kg)
Shipping without a Transformer 1384 lb (628 kg)
Service
Access Front and rear
Clearance
208 V: Greater than or equal to 36 in (914 mm) 480 V: Greater than or equal to 42 in (1067 mm)
Transformer (if installed)
Type Isolation Isolation/Step-Down
Configuration Delta to WYE
Maximum Power Rating 112.5 kVA
Maximum Current Rating 312A 135A 108A
Construction Cu. windings, open core
Temperature Rating 180°C (Class H)
Maximum Temperature Rise 302°F (150°C)
Main AC Power Feeds Top or bottom feed, lugs sized for 600 mcm
Environmental
Operating Environment Indoor use only; protect from water and conductive
contaminates
Temperature
Operating 32 to 104° F (0 to 40°C)
Storage 5 to 113° F (–15 to 45°C)
Humidity
Operating 0–95%, non-condensing
Storage 0–95%, non-condensing
Acoustic Noise Emission Less than or equal to 50 dBA
Compliance
Approvals UL, cUL
80kW InfraStruXure PDU—Operation and Configuration 69

Product Information

InfraStruXure Standard Warranty

APC warrants that all components of the InfraStruXure system will be free from defect in material
and workmanship for a period of two years from the date of start up when start up has been
performed by APC authorized service personnel*. If assembly services are included in the original
purchase and are also performed by APC authorized service personnel, APC offers an additional year
of parts warranty and the first year of on site Next Business Day coverage at no additional charge. I
the event that the system fails to meet the forgoing warranty, APC shall repair or replace, at its sole
discretion, any such defective parts. Under this warranty, APC will ship all parts to your site at no
cost to be available for you the next business day after APC is notified of this requirement. If you
choose to upgrade the system to include an on site contract, APC offers modular service packages to
match your needs.
Each point product incorporated into the system has a separate factory warranty that is applied when
sold as a standalone unit. When incorporated into an InfraStruXure solution, the unit will be covered
by the InfraStruXure warranty. In cases where one warranty favors the customer over the other, the
stronger of the two warranties will take precedence. The InfraStruXure factory warranty covers only
those parts appearing on the bill of materials for that solution. Megawatt UPS systems are not
covered under the InfraStruXure factory warranty.
Battery functionality is typically impacted by age and environmental conditions, and therefore certain
requirements must be met by the end-user. Failure to adhere to these requirements may put the battery
warranty at risk. APC-supplied batteries must always be kept (whether stored or installed) in a
climate-controlled environment, and should be re-charged at a minimum of every three (3) months.
The battery environment must be free of excessive moisture, construction dirt, corrosive elements, or
other contaminants. The temperature range must be maintained at 41 to 95° F (5 to 35° C).
*All warranties are null and void unless startup is performed by authorized an APC Global Services
service center.
APC SHALL NOT BE LIABLE UNDER THIS WARRANTY IF ITS TESTING AND
EXAMINATION DISCLOSE THAT THE ALLEGED DEFECT IN THE PRODUCT DOES NOT
EXIST OR WAS CAUSED BY PURCHASER'S OR ANY THIRD PERSON'S MISUSE,
NEGLIGENCE, IMPROPER INSTALLATION OR TESTING, UNAUTHORIZED ATTEMPTS TO
REPAIR OR MODIFY, OR ANY OTHER CAUSE BEYOND THE RANGE OF THE INTENDED
USE, OR BY ACCIDENT, FIRE, LIGHTNING OR OTHER HAZARD.
80kW InfraStruXure PDU—Operation and Configuration 71
Product Information
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR
OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS
AGREEMENT OR IN CONNECTION HEREWITH. APC DISCLAIMS ALL IMPLIED
WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A
PARTICULAR PURPOSE. APC’S EXPRESS WARRANTIES WILL NOT BE ENLARGED,
DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT
OF, APC’S RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN
CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES
ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE
WARRANTIES SET FORTH ABOVE. CONSTITUTE APC’S SOLE LIABILITY AND
PURCHASER’ EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. APC’S
WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD
PARTIES.
IN NO EVENT SHALL APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE
LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE
DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE
PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE
OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC HAS BEEN ADVISED
IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES.
72 80kW InfraStruXure PDU—Operation and Configuration

Life-Support Policy

APC Three-Phase Systems

As a general policy, American Power Conversion Corporation and its affiliates and subsidiaries
worldwide (APC) do not recommend the use of any of its products in life support applications where
failure or malfunction of the APC product can be reasonably expected to cause failure of the life
support device or to significantly affect its safety or effectiveness. APC does not recommend the use
of any of its products in direct patient care. APC will not knowingly sell its products for use in such
applications.
Examples of devices considered to be life support devices are neonatal oxygen analysers, nerve
stimulators (whether used for anesthesia, pain relief, or other purposes), autotransfusion devices,
blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems,
peritoneal dialysis systems, neonatal ventilator incubators, ventilators for both adults and infants,
anesthesia ventilators, infusion pumps, and any other device designated as “critical” by the
U.S.F.D.A.
80kW InfraStruXure PDU—Operation and Configuration 73

How to Obtain Service

If you ordered on-site service, see your entitlement certificate and terms and conditions
of the service before following the procedure described below. An on-site service
Note

How to contact APC

Customer support for this or any other APC product is available at no charge in any of the following
ways:
• Visit the APC Web site to access documents in the APC Knowledge Base and to submit any
contract entitles you to an on-site visit by an APC technician to assess the issue,
determine the problem, and replace parts, if needed. (Response time varies per contract).
customer support requests.
www.apc.com (Corporate Headquarters)
Connect to localized APC Web sites for specific countries, each of which provides customer
support information.
– www.apc.com/support/
Global support searching APC Knowledge Base and using e-support.
• Contact an APC Customer Support center by telephone or e-mail.
– Regional centers:
Direct InfraStruXure Customer Support Line (1) (877) 537-0607 (toll-free)
APC Headquarters U.S., Canada (1) (800) 800-4272
Latin America (1) (401) 789-5735 (USA)
Europe, Middle East, Africa (353) (91) 702000 (Ireland)
Japan (0) 35434-2021
Australia, New Zealand, South Pacific area (61) (2) 9955 9366 (Australia)
– Local, country-specific centers: go to www.apc.com/support/contact for contact
information.
Contact the APC representative or other distributor from whom you purchased your APC product for
information on how to obtain local customer support.
80kW InfraStruXure PDU—Operation and Configuration 74

Appendix

Changes in This Manual

Overview

The following list references the specific changes made to this manual since its last release
(990-1468B).

General Changes

Updated manual to reflect the InfraStruXure PDU’s network management capabilities.

Changes by page number

Page 11 Added section detailing the user connection plate.
Page 20 Updated instructions for connecting contacts to the PDU monitoring unit.
Pages 43–54 Added instructions for the PDU communication configuration.
Pages 60–61 Updated instructions for testing the Emergency Power Off switch.
Pages 63–63 Added instructions for connecting input contacts and relay outputs to the user connection
plate.
Page 65 Added instructions for downloading firmware updates.
Page 68 Added relay output specifications.
Page 74 Updated instructions for obtaining service from APC.
InfraStruXure PDU—Operation and Maintenance 75
Index
A
Access
to the control console
to the PDU through FTP
to the PDU through SCP
to the PDU through SNMP
Access holes, for cables
Active alarms
, 22
, 49
, 53
, 53
, 52
, 6
Add circuit breakers and power
cables, how to
Agency approvals
Alarm beeper
Alarm LED
Alarm relay map
Alarm/event log
, 5859
, 69
, 23
, 13
, 19
, 22
Alarms
on the PDU
viewing active
Alarms screen
Arm/test rocker switch
, 24
, 22
, 2224
, 10
B
BOOTP & DHCP configuration, 47
Branch Ckt
limits
, 25
loading
, 25
Branch current monitor ports
Breakers screen
, 21
, 10
Breakers. See circuit breaker.
Bypass input switch
Bypass LED
, 7
, 13
Bypass operation
how to return from
how to transfer the UPS into
, 34
, 31
C
Cable access holes, 6
Cables, how to add
Check log LED
, 58
, 13
Circuit breaker
42-position panel
adding to the PDU
cross tie output
determining size
for monitoring unit
MCCB subfeed
panel configuration
viewing status of a
, 9
, 58
, 7
, 2
, 7
, 7
, 26
, 21
Communication configuration
Companion manuals
Compliance
, 69
, i
Components, InfraStruXure
PDU
, 5
Config screen
, 2830
Configuration
alarm limits
BOOTP
BOOTP & DHCP
circuit breaker panel
date/time
DHCP
electrical
global panel
input
load test port
local interface
max power
network address
, 23
, 47
, 47
, 26
, 28
, 4748
, 29
, 27
, 29
, 29
, 28
, 29
, 28
of communication devices
54
output
, 29
overview
panel
subfeed port
system password
TCP/IP
, 45
, 26
, 29
, 28
, 46
Console port, on monitoring
unit
, 10
Contacts screen
Control console
for PDU management
, 1820
, 50
, 43
local and remote access to
50
, 43
, 43
, 49
Cross tie output circuit breaker
, 7
Cross-reference symbols used in
this manual
Customizing the PDU
, 1
, 5565
D
Date/time configuration, 28
Defaults, restoring factory
Device IP configuration wizard
Device name, setting the
DHCP configuration
Dimensions
, 68
DIP switches, EPO
Display interface
location
screens
, 1330
, 6
, 1430
alarms screen
breakers screen
config screen
contacts screen
load-meter screen
panel screen
password protected
volt-meter screen
Display port, on monitoring unit
, 30
, 46
, 30
, 4748
, 10, 60
, 2224
, 21
, 2830
, 1820
, 16
, 2527
, 15
, 17
, 10
Download firmware updates, how
to
, 65
E
Electric shock warnings, 3
Electrical
configuration
specifications
Emergency Power Off
connection point
safety warnings
testing the switch
warnings
EMI warnings
EPO. See Emergency Power Off.
Ethernet port, on user connection
plate
, 11
, 29
, 67
, 11
, 61
, 6061
, 3
, 4
80kW InfraStruXure PDU—Operation and Configuration 77
F
Factory defaults, resetting the, 30
Firmware updates, how to
download
, 65
Front view
door open
exterior
interior
FTP access to the PDU
Fuses
, 7
, 8
, 6
, 7
, 53
G
Global Panel Config, 27
Ground bar, location of
Ground lugs
, 7
Ground wire, location of
, 59
, 59
I
InfraStruXure Manager
as a PDU management option
configuration
, 44
, 43
connect the InfraStruXure PDU to
the
, 44
InfraStruXure Standard Warranty
Input cables, for UPS
, 8
, 71
Input contacts
connecting
connection location
information about
, 6364
, 11
, 18
Input power, maintenance performed
while the PDU is receiving
Input transformer
Installation warnings
, 9
, 2
, 2
K
Keys, for navigation, 13
L
LCD, 13
LEDs
EPO specific
on display interface
on monitoring unit
Leveling feet
Life-support policy
Load meter screen
Load on LED
, 60
, 13
, 10
, 6
, 73
, 16
, 13
Load test ports
, 9
Local access to the control console
Lock-out bracket
, 6
M
Main input switch, 7
Maintenance bypass operation
returning from
UPS, transferring into
Maintenance bypass panel
, 3436
, 3133
, 8
Maintenance performed while the
PDU is receiving input power
Maintenance warnings
Management options
, 2
, 4354
InfraStruXure Manager
, 2
, 43
Network management
interfaces
Manufacturer data
MCCB subfeed circuit breaker
, 43
, 30
, 7
Monitoring unit
circuit breakers
connecting contacts to
detailed description
location
, 7
, 20, 64
, 10
, 9
N
Navigation
keys
, 13
through screens
NetShelter VX enclosure
Network address configuration
, 14
, 5
, 28
Network management interface
accessing on a configured PDU
configuration
, 4554
recovering from a lost
password
, 54
Network port, on monitoring unit
Neutral bar, location of
Neutral wire, location of
, 59
, 59
O
Operation, 3142
maintenance bypass, returning
from
, 3436
maintenance bypass, transferring
the UPS into
, 3133
, 49
, 51
, 10
system, applying power to
total power off, ensuring
Orderable part list
, 56
Output cables, for UPS
, 3942
, 3738
, 8
P
Panel Configuration, 26
Panel screen
Part List
, 2527
, 56
Password
configure
protected-screens
recovering from a lost
Performance specifications
, 28
, 15
, 54
, 67
Ports
branch current monitor
load test
, 9
, 10
Power cables
adding to the PDU
bottom-feed access
location
sub-feed
, 6
, 6
UPS input and output
, 5859
, 78
, 8
R
Rack distribution panel, 5
Rear view, interior
, 9
Relay outputs
connecting
connection location
information about
specifications
, 6364
, 11
, 18
, 68
Remote access to the control
console
, 49
Reset button, on monitoring unit
Rocker switch, arm/test
, 60
S
Safety, 14
symbols used in this manual
warnings
SCP access to the PDU
Screens. See display interface or
individual screen name.
Service, obtaining
Shielding troughs
SNMP access to the PDU
, 24
, 53
, 74
, 6
, 52
, 10
, 1
78 80kW InfraStruXure PDU—Operation and Configuration
Specifications, 6769
electrical
performance
voltage
wiring
, 67
, 67
, 67
, 68
SSH, for accessing a network
management interface
, 52
Switches
arm/test rocker
bypass input
EPO DIP
main input
System ID
, 30
, 10
, 7
, 10
, 7
T
TCP/IP configuration methods, 46
Telnet, for accessing a network
management interface
Top-level status and menu
screens
, 14
Total power off procedure
38
Transformer, location
, 52
, 3, 37
, 9
Warranty
Web interface
, 7172
, 51
accessing a Network
management interface through
for PDU management
Wiring specifications
, 51
, 43
, 68
Wraparound maintenance bypass
panel
, 8
U
Updates
in this manual
to firmware
to this manual
, 75
, 65
, i
UPS
maintenance bypass, returning
from
, 3436
total power off, ensuring
38
transferring into maintenance
bypass operation
, 3133
User connection plate
detailed description
, 11
how to connect input contacts
and relay outputs
location
, 8
, 6364
V
Viewing active alarms, 22
Voltage specifications
Volt-meter screen
, 67
, 17
, 37
W
Warnings, 24
80kW InfraStruXure PDU—Operation and Configuration 79
APC Worldwide Customer Support
Customer support for this or any other APC product is available at no charge in any of the following ways:
• Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests.
www.apc.com (Corporate Headquarters)
Connect to localized APC Web sites for specific countries, each of which provides customer support information.
– www.apc.com/support/
Global support searching APC Knowledge Base and using e-support.
• Contact an APC Customer Support center by telephone or e-mail.
– Regional centers:
Direct InfraStruXure Customer Support Line (1) (877)537-0607 (toll free)
APC headquarters U.S., Canada (1)(800)800-4272 (toll free)
Latin America (1) (401)789-5735 (USA)
Europe, Middle East, Africa
Japan (0) 35434-2021
Australia, New Zealand, South Pacific area (61) (2) 9955 9366 (Australia)
– Local, country-specific centers: go to www.apc.com/support/contact for contact information.
Contact the information on how to obtain local customer support.
APC representative or other distributor from whom you purchased your APC product for
Entire contents © 2005 American Power Conversion. All rights reserved. Reproduction
in whole or in part without permission is prohibited. APC, the APC logo, NetShelter,
InfaStruXure, and Symmetra are trademarks of American Power Conversion
Corporation and may be registered in some jurisdictions. All other trademarks, product
names, and corporate names are the property of their respective owners and are used for
informational purposes only.
(353)(91)702000 (Ireland)
990-1468C 05/2005
*990-1468C*
Loading...