Introduction
Introduction
About this unit
Redundant power and output voltage monitoring for Broadband cable systems is provided with the use of two APC Automatic Disconnect Switches and two Ferroresonant Power Supplies (FRP).
Safety
Electrical Warnings
Do not work alone under hazardous conditions.
High current through conductive materials could cause severe burns.
Do not work alone under hazardous conditions.
High current through conductive materials could cause severe burns.
Do not handle any metallic connector before the power hs been disconnected.
When grounding cannot be verified disconnect the equipment from the utility power outlet before installing or connecting to other equipment. Reconnect the power cord only after all connections are made.
Check that the power cord(s), plug(s), and socket(s) are in good condition.
Replacement of fuses or other parts must be with identical types and ratings. Substitution of nonidentical parts may cause safety and fire hazards.
In order to maintain compliance with the EMC directive for products sold in Europe, output cords attached to the UPS should not exceed 10 meters in length.
Specifications
Environmental Specifications
Temperature
Humidity
Elevation
Operating: 32° to 122°F (0° to 50°C) Storage: 5
0 to 95%
0 to 10,000 feet (0 to 3,000 meters)
° to 122°F (-15° to 50°C)
Broadband Automatic Disconnect Switch User Manual 3
Installation
Electrical Specifications
Input
Utility Power Cable
Connection
Nominal Voltage
Allowable Input range
Maximum Current
Input Current Limiting
Three Position
Terminal Block
220 V 63 V
165-270 V 40-75 V
15 A 18 A
10 A N/A
Output
Connection
Allowable Output range
Initial Connection Delay
Time to connect attached FRP
to cable system after output
failure
Three Position
Terminal Block
N/A 350 mS maximum
Physical Specifications
Characteristic Specification
Height/Width/Depth
Wei gh t
15” x 7” x 8” (38.1 x 17.8 x 20.3 cm)
14 lbs (6.4 kg)
Terminal Block to Coax Center Conductor
Terminal Block to Coax Center Conductor I
Cable Adapter (5/8-24)
Cable Adapter (5/8-24)
40-75 V
Primary - None
Secondary - 5.5 seconds
Installation
Unpack
Read the Safety Guide before installing this unit. The User Manual and Safety Guide are accessible on the APC Web site, www.apc.com.
Inspect the unit upon receipt. Notify the carrier and dealer if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents:
4 Broadband Automatic Disconnect Switch User Manual
Installation
Automatic Disconnect Switch enclosure
Two mounting brackets
Four screws
UPS literature kit containing: – product documentation – safety information warranty information
One F Connector nut
Schematic Overview of the Automatic Disconnect Switch System
The user must designate the primary and secondary power supply. Refer to Reset/Test in the Operation section of this manual for details.
Primary FRP supplying power
Primary FRP supplying power
Primary FRP supplying power
to two buildings
to two buildings
Primary Power Supply
Primary Power Supply
Primary Power Supply
220 VAC
220 VAC
220 VAC
FRP1 FRP2
FRP1 FRP2
FRP1 FRP2
63 VAC
63 VAC
cable
cable
cable
63 VAC blocking
blocking
blocking element
element
element
CS
CS
CS
Power
Power
Power
to two buildings
63 VAC63 VAC
63 VAC63 VAC
63 VAC63 VAC
Secondary Power
Secondary Power
Secondary Power
220 VAC
220 VAC
220 VAC
CS
CS
CS
Power
Power
Power
63 VAC
63 VAC
63 VAC blocking
blocking
blocking element
element
element
cable
cable
cable
Bulding 2 cable
Bulding 2 cable
Bulding 1 cable
Bulding 1 cable
Bulding 1 cable
Broadband Automatic Disconnect Switch User Manual 5
Bulding 2 cable
Installation
Mount the Automatic Disconnect Switch on the Wall
Do not operate the UPS where there is excessive dust or the temperature or humidity are outside the specified limits.
The Automatic Disconnect Switch enclosure has side vents. To ensure adequate air flow in and around the unit there must be 1” (2.5 cm) of space on the right and left sides of the enclosure.
Mount the Automatic Disconnect Switch enclosure on the wall using screws appropriate for the weight of the unit and the mounting surface material.
Install the Mounting Brackets on the Automatic Disconnect Switch Enclosure
When securing the mounting brackets to the enclosure two screws must be used in each bracket.
Utility Power Connections
Installation must be performed by a qualified electrician. Adhere to all local, state, federal, and/or National Electric
Code (NEC) regulations regarding location, permits and electrical wiring.
Install an approved 20 A high magnetic circuit breaker on the input side of the Automatic Disconnect Switch.
6 Broadband Automatic Disconnect Switch User Manual
Utility wiring panel with holes for wires
Input Hardwire
Output Hardwire
Hardwire the Automatic Disconnect Switch
Step
Remove the utility wiring panel located on top of unit.
When required apply a strain relief grommet to the utility wiring panel holes.
Installation
Step
Route the building wiring through the holes in the utility wiring panel.
Connect the 220 V building wiring to the Input Hardwire terminal block.
Step
Route the input wiring for the FRP/FLM through the hole in the utility wiring panel.
Connect the FRP/FLM input wiring to the Output Hardwire terminal block.
Step
Reinstall the utility wiring panel. Secure the panel with the screw removed in Step .
Broadband Automatic Disconnect Switch User Manual 7
Installation
Cable System Connections
F-Connector Installation
USB Cable Tie Wrap Lance
USB Connector
Cable Modem Utility Power IEC Recepticle
Coax Output
Coax Input
F Connector
8 Broadband Automatic Disconnect Switch User Manual
Coax Connection
Installation
Coax Output­Connects to Cable System
Coax Input­Connects to FRP Output
Broadband Automatic Disconnect Switch User Manual 9
Installation
Cable Modem Connection
The cable modem utility power, F-connector, and USB connectors are located on the back of the cable modem.
Secure the appropriate cables to these connectors before installing the cable modem in the enclosure.
USB Cable
Tie Wrap Lance
F Connector
USB Connector
c
o
L
r
e
w
o
P
l
a
e
t
o
P
R
m
e
o
w
r
e
Cable Modem
Connect the appropriate cables to the cable modem IEC receptacle, the USB port, and the F-connector located on inside the enclosure.
Using the lance on the enclosure secure a tie wrap to the USB cable if required.
Utility Power IEC Recepticle
10 Broadband Automatic Disconnect Switch User Manual
Start Up
Primary/Secondary Access Panel
To remove the access panel covering the Primary/Secondary Select button remove the screw that secures the panel to the enclosure. Slide the access panel slightly to the right and then pull the access panel toward you.
Operation
Indicators and Controls
Operation
Local Power
Remote Power
Reset/Test
Local 63V Fault
Primary/ Secondary Select
Primary
Secondary 220V Normal
Circuit Breaker
Local Power Remote Power
Reset/Test
Local 63V Fault
Primar y/ Secondary Select
Primar y Secondary 220V Nor mal
Circuit Breaker: The circuit breaker protects the 220 V input from overload conditions.
Local Power: Green LED indicates that the Automatic Disconnect Switch is providing power to the cable
system.
Remote Power: Green LED indicates the cable system is receiving power from a source other than the Automatic Disconnect Switch.
Broadband Automatic Disconnect Switch User Manual 11
Operation
Reset/Test: Functionality of this control is dependant upon Automatic Disconnect Switch status.
Primary Status
The primary Automatic Disconnect Switch is supplying power to the cable system. The Local Power LED will be illuminated. The Reset/Test button will do nothing.
When the primary Automatic Disconnect Switch is not supplying power to the cable system the Remote Power LED will be illuminated. The Automatic Disconnect Switch will perform a test to measure the output voltage from the local FRP.
Secondary Status
The secondary Automatic Disconnect Switch is supplying power to the cable system. The Local Power LED will be illuminated. The secondary Automatic Disconnect Switch will momentarily disconnect the local power from the cable system allowing the primary system to supply power. If the primary system begins to supply power, the secondary system will remain disconnected. If the primary system fails to supply power, the secondary system will immediately begin supplying power to the cable system.
When the secondary Automatic Disconnect Switch is not supplying power to the cable system the Remote Power LED will be illuminated. The Automatic Disconnect Switch will perform a test to measure the output voltage from the local FRP.
Local 63 V Fault: Green LED indicates:
The FRP/FLM output is outside the specified range during a test.
The output failed while the Automatic Disconnect Switch was supplying power.
Primary/Secondary Select: This control is used to establish the Automatic Disconnect Switch as the primary or secondary power source for the cable system.
Primary: Green LED indicates that the Automatic Disconnect Switch is the primary power source.
Secondary: Green LED indicates that the Automatic Disconnect Switch is the secondary power source.
220 V Normal: Green LED indicates that 220 V input is present and within specified limits.
Cable Modem
The cable modem functions only when power is supplied by the Automatic Disconnect Switch to an FRP. If the FRP fails the cable modem will continue to function.
12 Broadband Automatic Disconnect Switch User Manual
Troubleshooting, Service, Contact, Warranty and Regulatory Information
Troubleshooting, Service, Contact, Warranty and Regulatory Information
Troubleshooting
Use this chart to solve minor installation and operation problems. Refer to the APC Web, site www.apc.com with complex problems.
Problem and/or Possible Cause Solution
Unit is on and the 220 V Normal LED is not illuminated
The unit is not wired properly. Check that the input and output wiring are not reversed.
The circuit breaker is tripped. Reset the circuit breaker.
The 220 V power is outside the specified limits.
Check that the 220 V power is within specified limits. Refer to Specifications in this manual.
Unit is on and the Local 63 V Fault LED is illuminated
The unit is not connecting power to the cable system.
Check that the coax connections are not reversed.
Check that the FRP/FLM output is within specified limits. Refer to Specifications in this manual.
Secondary unit will not switch to Remote power when the Test button is pressed
Remote power system is not functioning. This is normal operation. Verify that the Remote power system is working.
Primary unit is indicating Remote power
Primary unit was powered up after the secondary unit.
This is normal operation. Press the Reset button on the secondary unit to transfer power to the primary unit.
The primary FRP/FLM output is not within specified limits. Refer to Specifications in this manual.
Limited Warranty
American Power Conversion (APC) warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support. Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase. This warranty does not apply to equipment that has been damaged by accident, negligence, or misapplication or has been altered or modified in any way. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase.
EXCEPT AS PROVIDED HEREIN, AMERICAN POWER CONVERSION MAKES NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to the purchaser.
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL APC BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, APC is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise.
Broadband Automatic Disconnect Switch User Manual 13
Troubleshooting, Service, Contact, Warranty and Regulatory Information
Service
If the unit requires service do not return it to the dealer. Follow these steps:
1. Review the problems discussed in Troubleshooting to eliminate common problems.
2. If the problem persists, contact APC Customer Support through the APC Web site, www.apc.com. – Note the model number of the unit, the serial number, and the date purchased. If you call APC
Customer Support, a technician will ask you to describe the problem and attempt to solve it over the phone. If this is not possible, the technician will issue a Returned Material Authorization
Number (RMA#). – If the unit is under warranty, repairs are free. – Procedures for servicing or returning products may vary internationally. Refer to the APC Web
site for country specific instructions.
3. Pack the unit in its original packaging. If this is not available, refer to the APC Web site for information about obtaining a new set.
Pack the UPS properly to avoid damage in transit. Never use Styrofoam beads for packaging.
Damage sustained in transit is not covered under warranty.
4. Mark the RMA# on the outside of the package.
Return the unit by insured, prepaid carrier to the address given to you by Customer Support.
Contact APC
Refer to the APC Web site, www.apc.com. Select the appropriate country from the country selection field, and select the Support tab at the top of the web page.
Regulatory Agency Approvals and Radio Frequency Warnings
FCC Compliance Notice
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy. If it is not installed and used in accordance with the instruction manual, it may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case users will be required to take whatever measures may be necessary to correct the interference at their own expense.
®
LISTED 42C2
E95463
Entire contents copyright © 2004 by American Power Conversion Corporation. All rights reserved. Reproduction in whole or in part without permission is prohibited.
APC, Smart-UPS, and PowerChute are registered trademarks of American Power Conversion Corporation. All other trademarks are the property of their respective owners.
14 Broadband Automatic Disconnect Switch User Manual
Loading...