APC AR3814 User Manual

Installation Manual
NetShelter® 24 U
AV Enclosure
AR3814
Introduction..................................................................... 1
Safety Warnings and Cautions...................................... 1
Unpacking the Enclosure............................................... 2
Component Identifica tion............................................... 3
Helpful Steps for Reinstalling a Door............................ 5
Removing and Reinstalling the Roof ............................ 6
Enclosure Installation..................................................... 7
Moving the Enclosure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Leveling the Enclosure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Reversing the Front Door. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Securing the Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Grounding the Enclosure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Equipment Installation.................................................. 14
Adjusting the Vertical Mounting Rails . . . . . . . . . . . . . . . . . . . . . . .14
Installing Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Cable Routing and Cable Management....................... 18
Vertical 0 U Accessory Channels . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Rear Door Cable Containment Bracket. . . . . . . . . . . . . . . . . . . . . . .18
Accessories................................................................... 19
Specifications................................................................ 22
APC Limited Factory Warranty.................................... 23
NetShelter 24 U AV Enclosure Installation Manual
i

Introduction

The American Power Conversion (APC®) NetShelter® AV Enclosure is a high-quality enclosure for storage of industry-st andard (EIA-310), 19-inch rack-mount hardware, which includes servers, voice, data, networking, security, audio-visual, and APC power protection equipment.
Various accessories are mentioned in this manual . For comple te details on any accessory, see the APC Web site, www.apc.com. T o qui ckly f ind a part on the APC Web site, enter the p art number i n the Search field.
For additional informati on about this product, see the product page on the APC Web site, www.apc.com

Safety Warnings and Cautions

Observe all Warnings and Cautions in this manual, plus the following.
Tip Hazard: This equipment is easi ly tipped. Use extreme caution when unpacking or moving.
Heavy: Use at least two people to unpack the enclosure.
Warning: To avoid damage or injury, do not use the roof a s a walkway.
1NetShelter 24 U AV Enclosure Installation Manual

Unpacking the Enclosure

Disclaimer

American Power Conversion is not responsible for damage sustained during reshi pment of this product.

Receiving inspection

Inspect the package and content s for shipping d amage, and make sure tha t all pa rts wer e sent. Repor t any damage immediately to the shipping agent. Repor t missing contents, damage, or other problems immediately to APC or your APC reseller.

Please Recycle

The shipping materials are recyclable. Save them for later use, or dispose of them appropriately.

Procedure

1. Move the shipping pallet to a firm, level surfac e in an open area . In spect for visible signs of shipping damage. If you detect shipping damage, contact APC Customer Support using the contact information on the back cover of this manual.
2. See the label on the packaging to determine where to cut the wrapping. Using sturdy shears or a utility knife, carefully remove the plastic stretch wrap surrounding the enclosure.
3. Remove the four cardboard corner protectors.
4. Remove and retain the two pallet-mounting brackets with mounting hardware that anchor the enclosure to the shipping pallet. Use a 13-mm wrench (not provided).
Note: Save the pallet-mounting brackets if you plan to bolt the enclosure to the floor .
5. With one person on each side of the enclosure, carefully roll it toward the rear of the pallet until the rear casters clear the back edge of the pallet. Continue to slide the enclosure until the rear casters touch the floor.
6. While one person carefully tips the enclos ur e slightly away from the pallet, ha ve the other person pull the pallet away from the enclosure. Set the enclosure gently on its casters.
Warning: Use caution when moving an empty enclosure on its casters; the enclosure may be unstable when pushed or pulled from the side. Push the enclosur e from the front or back when moving it on its casters. For extra sta bility, load 158 kg (350 lbs) of equipment into the bottom of the enclosure before moving it on its casters.
NetShelter 24 U AV Enclosure Installation Manual2

Component Identification

Enclosure

ns1712a
Roof with cable access (A R7214)
Enclosure frame
Side brace
Key for doors and side panels
Removable rear split doors (WAR7104)
Pallet/bolt-down bracket
 
Rear door cable contai nment bracket
Removable side pane l with lock
(AR7376; Qty 2) Hardware bag (see page 4)
Adjustable le veling feet
Caster
Removable and reversible front door
(WAR7004) Vertical mounting rail
Adjustable vertical 0 U accessory
channel
3NetShelter 24 U AV Enclosure Installation Manual
Hardware bag
ns1726a
TORX® T30/#2 Phillips wrench (1) #10-32 screws (60) M5 x 12 screws (4)
7-mm hole plugs (4) 5-mm hole
plugs (5)
Frame handle
cutout cover (2)
NetShelter 24 U AV Enclosure Installation Manual4

Helpful Steps for Reinstalling a Door

ns1729a
ns1730a
Note: Doors self-align on hinge pins when properly reinstalled.
1. At a 90-degree angle to the front of the enclosure, position the door over the hinge pins ().
ns1728a
2. Use slight pressure to pull the door away from enclosure; then lower the door
3. Connect the ground wire.
5NetShelter 24 U AV Enclosure Installation Manual

Removing and Reinstalling the Roof

ns1724a
× 2
NetShelter 24 U AV Enclosure Installation Manual6

Enclosure Installation

Moving the Enclosure

Caution: To avoid damaging the enclosure and causing a tip hazard, make sure the leveling
feet are up before moving the enclosure.
Casters. The enclosur e can be moved on its casters with up to 1021 kg (2,250 lbs) of equipment
installed.
Tip Hazard: Use caution whe n moving a n empty enclos ure on i ts ca sters . Push t he enclos ure from the front or back only; the enclosure may be unstable if pushed or pulled from the side. For extra stability, load 158 kg (350 lbs) of equipment into the bottom of the enclosure before moving it on its casters.
Eye bolts. The enclosure can be
lifted using eye bolts with up to 567 kg (1,250 lbs) of equipment installed. Use M10 eye bolts with a shoulder rated for 181 kg (400 lbs).
7NetShelter 24 U AV Enclosure Installation Manual

Leveling the Enclosure

1 4
m
m
1 3
m
m
ns1698a
Required tools:
Phillips screwdriver Level 13-mm open-ended wrench
Warning: The le veling feet at the corners provide a stable base if the floor is uneven, but they cannot compensate for a badly sloped surface.
T o adjust the leveling feet after equipment has been installed, use a 13-mm open-ended wrench (not provided).
NetShelter 24 U AV Enclosure Installation Manual8

Reversing the Front Door

ns1709a
ns1613a
If desired, you can reverse the front door so the door opens from the opposite side of the enclosure.
1. Remove the APC nameplate from the front door.
2. Remove the grounding wire using the TORX wrench (provided).
3. Remove the door handle assembly.
9NetShelter 24 U AV Enclosure Installation Manual
4. Remove the door .
ns1707a
ns1708a
ns1706a
5. Remove the hinges from the frame.
6. Reinstall the hinges on the opposit e side of the enclosure.
7. Remove screws securing the hinges in the door frame.
NetShelter 24 U AV Enclosure Installation Manual10
8. Reposition and reinstall hinge.
ns1705a
ns1615 a
9. Reinstall the door.
10.Reinstall the door handle assembly with the washe r and latch oriented as shown. The
washer is rotated 90 degrees from its original orientation ().
11.Reinstall the grounding wire with star washer. The star
washer must be installed under the grounding wire (see step 2).
12.Reinstall the APC nameplate on the front door.
11NetShelter 24 U AV Enclosure Installation Manual

Securing the Enclosure

ns1704a
For additional stabilization, secure the enclosure to the floor. Use fastener locations on the outside or inside of the enclosure, and choose from the accessories shown below.
Accessory SKU Description
Pallet/bolt­down brackets
NetShelter SX stabilizer plate
Bolt-down kit AR7701 Attaches to rack and
(provided with the enclosure; n ot available as a purchased part)
AR770 0 Attach es ex ternally to
Attaches to rack and floor internal ly or externally to provide additional stability without blocking cable access.
the rack and fl o o r to provide additional stability.
floor internal ly or externally to provide additional stability without blocking cable access. Meets UBC Zone-4 seismic anchoring requirements.
NetShelter 24 U AV Enclosure Installation Manual12

Grounding the Enclosure

ns1736a
Each enclosure should be grounded directly to the building ground using one of the designated grounding locations (two M6 thread ed inserts) at the top or bottom of the enclosure.
• Use a Common Bonding Network Jumper kit (for example, Listed [KDER] Panduit
RGCBNJ660PY or equivalent).
• Use paint-piercing washers betwe en ground terminal and enclosure frame or remove paint on
frame under ground terminals per NEC NFPA 70 Article 250.12.
• Torque screws to 6.9 N-m (60 in-lb).
• Do not ground one enclosure to another enclosure in a cascading style.
13NetShelter 24 U AV Enclosure Installation Manual

Equipment Installation

ns1701a
Installing equipment in the NetShelter AV Enclosure may require adjusting the vertical mounting rails to the correct depth for your equipment and then installing equipment.

Adjusting the Vertical Mounting Rails

Audio-visual equipm ent is secured to the vertical mounting rails in the NetShelter AV Enclosure. The vertical mounting rails are adju stable to accommodate the depth of your AV equipment. The vertical mounting rails come factory-installed for use with AV equipment that has a depth of 508 mm (20 in). The vertical mounting rails can be adjusted to be as close together as 191 mm (7.50 in) or as far apart as 680 mm (26.8 in), when the vertical 0 U accessory channels have been removed.
NetShelter 24 U AV Enclosure Installation Manual14
Perform the following steps to adjust a vertical mounting rail:
ns1711a
Warning: To avoid personal injury or d amage to the enclosure, perform thi s procedure without any equipment installed on the vertic al moun ting rails.
1. Unlock the vertical mounting rail. Use the TORX wrench (provided in the hardware bag) to loosen the screw—but do not remove.
15NetShelter 24 U AV Enclosure Installation Manual
2. Move the vertical mou nting rail to
ns1623 a
ns1624a
the desired location.
3. Check alignment. Note symbols (circle, triangle, or square) visible through the set of three holes at the top and bottom of the vertical mounting rail. Make sure the symbols match. If not, realign the vertical mounting rail.
– Vertical mounting rails adjust
in 6-mm (1/4-in) increments.
– Make sure the vertical
mounting rails on both sides of the enclosure are adjusted t o the same depth. Verify that the same symbols are visible.
4. Lock top and bottom of the vertical mounting rail.
NetShelter 24 U AV Enclosure Installation Manual16

Installing Equipment

1 U
7
6
5
ns1595a
Warning: To prevent the enclosu re from tipping over after equipme nt installation:
• Make sure you have secured the enclosure before ins talling equipment.
• Load the heaviest equipment first towar d the bottom of the enclosure to prevent the enclosure from becoming top-he a vy.
• Do not extend equipment on sliding rails until you have installed three or more pieces of similar- sized equipment or until you have install ed the stabilizer plate or bolt-down brackets.
• Do not extend more than one piece of equipmen t on sliding rails at a time.
Before getting started, make sure you have adjusted the vertical mounting rails as needed. To install rack-mount equipment in the NetShelter AV Enclosure:
1. Review the equipment manufacturer’s installation instructions.
2. Locate the top and bottom U-space on the vertical mounting rails. Every third hole on the mounting rails is numbered to indicate the middle of a U-space. A U-space consists of one of these numbered holes and one hole directly above and below it, as shown.
3. Install the equipment using the #10- 32 screws (provided). See the manufacture r’s instructions provided with the equipment for a dditional details.
17NetShelter 24 U AV Enclosure Installation Manual

Cable Routing and Cable Management

ns1702a
ns1725a

Vertical 0 U Accessory Channels

The vertical 0 U accessory channels provide toolless m ounting capabilities for APC Rack Power Dist ributi on Unit s (Rack PDU) and APC cable management accessories (see page 19). The vertical 0 U accessory channels also provide tie -off locations for cables.
The vertical 0 U ac cessory channels can be re-located in the enclosur e anywher e along the side braces. The standard position for the vertical 0 U accessory channels is in the rear of the enclosure, but they can be positioned anywhere along the side braces like the vertical mounting rails (see “Adjusting the Vertical Mounting Rails” on page 14).

Rear Door Cable Containment Bracket

NetShelter 24 U AV Enclosure Installation Manual18

Accessories

For additional infor mation, see the product page on the APC Web site, www.apc.com.
Accesso ry Part Numb er Descript ion
Copper busbar AR8395 20 U copper busbar
for NetShelter AV enclosures.
Shelf AR8125 Adjustable,
reversible shelf.
115 VAC roof fan tray
NetShelter A V 2 U rack fan panel
Top mount conduit acce ss adapter
ACF505 Includes four fan s t o
pull heated air out of the en closure.
ACF600 Includes four fans
for cooling AV equipment. Accessories include a temperature controller (ACF601), vent panel (ACAC40001), and vent panel with temperature display (ACAC40000).
AR7215 Allows option to
route cable into side of unit. Includes knock out panels for conduit.
NetShelter A V enclosure roof
AR7213 Includes conduit
knock-outs and brush strips for c able access.
19NetShelter 24 U AV Enclosure Installation Manual
Accesso ry Part Numb er Descript ion
Toolless hook and loop cable manager (Qty. 10)
Cable containment brackets (Qty. 6)
Vert i ca l ca bl e organizer
AR8621 Includes
ten 457-mm (18-in) hook and loop black cable straps that instal l in th e square holes in th e vertical 0 U accessory channel or the vertical mounting rail.
AR7710 Contains cables
along the vertical 0 U accessory channel. Instal ls without tools.
AR8442 Installs in a vertical
0 U accessory channels to facilitate vertical cable management and eliminates cable stress. Takes up zero U of space within the enclosure. Consists of two pieces of equal size that, when connected , sp an the height of a 42-U enclosure. Can be used in any APC enclosure.
Cable management rings (Qty. 5 large and 5 small)
AR8113A Fastens cabl es to
posts, mounti ng rails, or braces.
NetShelter 24 U AV Enclosure Installation Manual20
Accesso ry Part Numb er Descript ion
ns1156a
19-inch horizontal cable organizers
19-inch 2-U horizontal cable organizer pass-through
19-inch 1-U cable pass­through with brush strip
AR8602 (1 U)
Routes cables horizontally on the
AR8600 (2 U)
front or back of the 19-inch EIA
AR8601 (2 U
enclosure.
double sided)
AR8603 (2 U high density)
AR8425A (1 U)
AR8426A (2 U)
AR8428 Routes cables
horizontally or front­to-rear.
AR8429 Assists with
containing air in the enclosu r e an d providing an aesthetic so lution f or cable routing.
Zero-U accessory mounting bracket (Qty. 2)
Vertical fibe r organizer
AR7711 Zero U multi-
purpose accessory mounting b racket for 1 U and 2 U equipment, including Rac k PDUs.
AR8443A The vertical fiber
organizer provides a method to manage fiber cabling within an enclosure and mounts toolle ssly into the vertical 0 U accessory channel.
ns1145c
ns1163a
21NetShelter 24 U AV Enclosure Installation Manual

Specifications

Height 1199 mm (47.2 in) Width 600 mm ( 23.6 in) Dept h 825 mm (32.5 in) Net weight 81.65 kg (180 lb) Total open area (front door) 345 808 mm Total open area (rear door) 375 870 mm Open area per U (front door) 14 406 mm Open area per U (rear door) 15 658 mm Perforation pattern percentage 69% Percent of perforated area (front) 67% Percent of perforated area (rear) 73%
2
(536.0 in2)
2
(582.6 in2)
2
(22.3 in2)
2
(24.3 in2)
Clearance (for wiring between front
61.0 mm (2.4 in)
door and vertical rail) Weight rating: static load
1361 kg (3,000 lb) Weight rating: rolling 1021 kg (2,250 lb) Weight rating: shipping
Lower th e le v el in g feet if the stat ic we ig h t is
over 1020. 58 kg (2,250 lb).
Additional packaging may be required if the enclosure is reshipped
with equipment installed. See the APC Web site, www.apc.com, for details.
567 kg (1,250 lb)
NetShelter 24 U AV Enclosure Installation Manual22

APC Limited Factory Warranty

The limited warranty provided by American Power Conversion (APC®) in this Statement of Limited Factory Warranty applies only to Products you purchase for your commercial or industrial use in the ordinary course of your business.

Terms of Warranty

American Power Conve rsion warrants i ts products to be free from defects in materials and workmanship for a period of five years from the date of purchase. I ts obliga tion under this warranty is limited to repairing or replacing, at its sole disc re tion, any such defectiv e products. This warranty doe s not apply to equipment that has been damaged by accident, negligence, or misapplication or has been alt ered or modified in any way. Repair or repla cement of a defective product or part thereof does not extend the original warranty peri od. Any parts furnished under this warranty may be new or factory ­remanufactured.

Non-transferable Warranty

This warranty applies only to the orig inal purchaser who must have properly registered the product. Product may be registered at http://www.warranty.apc.com.

Exclusions

APC shall not be liable under the warranty if its te sting and examination disclose that the alleged defect in the product does not exist or was caused by end user’s or any third person’s misuse, negligence, improper installati on or testing. Further APC shal l not be liable under the warranty for unauthorized attempts to repair or modify wrong or inadequate electrical voltage or conne ction, inappropriate on-site operation conditions , co rrosive atmosphere, repair, insta llation, start-up by non-APC designated personnel, a change in location or operating use, exposure to the elements, Acts of God, fire, theft, or installation contr ary to APC recommendati ons or specific ations or in any event if the APC serial number has been alte red, def aced, or rem o ved , or an y other cause beyond the range of the intended use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. APC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A P ARTICULAR PURPOSE. APC EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, APC RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE APC SOLE LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. APC WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
23NetShelter 24 U AV Enclosure Installation Manual
IN NO EVENT SHALL APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBLY OF SUCH DAMAGES. SPECIFICALLY, APC IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTW ARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NO SALESMAN, EMPLOYEE OR AGENT OF APC IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY. WARRANTY TERMS MAY BE MODIFIED, IF AT ALL, ONLY IN WRITING SIGNED BY AN APC OFFICER AND LEGAL DEPARTMENT.

War ranty C laims

Customers with warranty claims issues may access the APC worldwide customer support network by visiting http://www.apc.com/support. Select your country from the country selection pull-down menu. Open the Support tab at the top of the web page to obtain contact information for customer support in your region.
NetShelter 24 U AV Enclosure Installation Manual24
APC Worldwide Customer Support
Customer support for this or any othe r APC product is available at no charge in any of the following ways:
• Visit the APC Web site to access documents in the APC Knowle dge Base and to submit c ustomer support requests.
www.apc.com (Corporate Headquarters)
Connect to loc alized APC Web sites for specific countries, each of which provides customer suppor t information.
www.apc.com/support/
Global support searchi ng APC Knowledge Base and using e-support.
• Contact the – Local, country-specific centers: go to www.apc.com/support/contact for contact information.
For information on how to obtain local customer support, contact the APC representative or other distributors from whom you purchased your APC product.
APC Customer Support Cente r by telephone or e-mail.
© 2010 APC by Schneider Electri c. APC, the APC logo, NetShelter, and InfraStruxure are owned by
Schnei der Ele ctric Industr ies S .A.S., America n Power Co nvers ion Cor porat ion, o r their a ff iliat ed comp anies.
All other trademar ks are property of their respective owners.
5/2010990-4300
Loading...