American Power Conversion 250 A User Manual

Operation
InfraStruXure
Generation System
TM
Power
250 A
208/480 V
Audience
This manual is intended for users of the InfraStruXure™ Smart Distribution Panel with Automatic Transfer Switch (ATS). It provides important safety warnings and instructions, an overview of the ATS components, a detailed discussion about the ATS display interface, instructions on how to add components to the ATS, and technical specifications.
Companion manuals
For additional information about your InfraStruXure Power Generation System, refer to the following sheets and manuals. The initial part numbers are listed below. Be aware that some of the documentation may have undergone one or more revisions (A, B, etc.):
ATS Unpacking Sheet (990-1842)
Electrical Installation Manual (990-1844)
Generator Reference Manual (990-1846)
Network Management Interface User’ s Guide (available on the APC Web site or the Utility CD) (990-1993)
How to find updates to this manual
You can check for updates to this manual by clicking on the User Manuals link on the Support page of the APC Web site (www.apc.com). Choose Power Generation and then InfraStruXure Power Generation. From the list of InfraStruXure Power Generation manuals, look for the latest letter revision (A, B, etc.) of the initial part number app earing on the back cover of this manual (990-1845).
InfraStruXure Power Generation System i
Contents
Safety ......................................................................1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Save these instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety symbols used in this manual . . . . . . . . . . . . . . . . . . . 1
Cross-reference symbols used in this manual . . . . . . . . . . . . . 1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
The I nf ra S tr u X u r e P o w e r G e n e r a t i on S y ste m is an optional standby system
Wire sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Total power off procedure . . . . . . . . . . . . . . . . . . . . . . . . . 3
Operating environment . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
. . . . . . . . . . . . . . . . . . . . . . . 2
Overview .................................................................5
InfraStruXure Power Generation System . . . . . . . . . . . . . . . . . . 5
How the InfraStruXure Power Generation System Operates . . . . 6
Operation of the ATS during a utility failure when automatic operation is enabled
Generator start sequence . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Generator cool-down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Open and closed transfers . . . . . . . . . . . . . . . . . . . . . . . . . 8
Fuel monitoring/runtime calculation . . . . . . . . . . . . . . . . . . . 9
Smart Distribution Panel with ATS . . . . . . . . . . . . . . . . . . . . . . 11
Front view, door closed . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Front view, door open . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ATS panel board, left side . . . . . . . . . . . . . . . . . . . . . . . . . 13
ATS panel board, right side . . . . . . . . . . . . . . . . . . . . . . . . 14
. . . . . . . . . . . . . . . . . . 6
InfraStruXure Power Generation System iii
ATS Component Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Motorized switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Automatic operation control panel . . . . . . . . . . . . . . . . . . . 16
User connection plate . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
ATS monitoring unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
ATS label kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Operation ............................................................. 19
Automatic Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
How to place the InfraStruXure Power Generation System in automatic operation
How to reset automatic operation on the ATS and on the generator
Problem—loss of automatic operation . . . . . . . . . . . . . . . . 21
. . . . . . . . . . . . . . . . . . . . . . 20
Emergency Manual Operation . . . . . . . . . . . . . . . . . . . . . . . . . 22
Warning—before you operate the ATS manually . . . . . . . . . 22
How to power the load from the generator . . . . . . . . . . . . . 23
How to return to powering the load from utility . . . . . . . . . . 25
. . . . . . . . . . . . . 19
Total Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Display Interface.................................................... 29
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Top-level status screens . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Top-level menu screen . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Navigating through screens . . . . . . . . . . . . . . . . . . . . . . . 31
Password-protected screens . . . . . . . . . . . . . . . . . . . . . . . 31
Load-Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Total Load by Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Total Load Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
ATS/Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
ATS Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
S1-Utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
S2-Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
ATS Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Generator Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
iv InfraStruXure Power Generation System
Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
View Test Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Run/View Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Test Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Test Duration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
How a test occurs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Stats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
View Active Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Alarm/Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Alarm Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Alarm Beeper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Clearing latched alarms . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Config. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
System/Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Contacts & Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Electrical Config . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Factory Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Manufacturer Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
System ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Firmware Updates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Reset 100% Fuel Level . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Communication Configuration................................49
ATS Management Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
InfraStruXure Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Network management interfaces . . . . . . . . . . . . . . . . . . . . 49
Configuring the InfraStruXure Manager . . . . . . . . . . . . . . . . . . 50
Connect the ATS to the InfraStruXure Manager . . . . . . . . . . . 50
InfraStruXure Power Generation System v
Configuring the ATS Network Management Interface. . . . . . . . 51
Connect the ATS to your network . . . . . . . . . . . . . . . . . . . 51
Configuration overview . . . . . . . . . . . . . . . . . . . . . . . . . . 52
TCP/IP configuration methods . . . . . . . . . . . . . . . . . . . . . . 52
Device IP Configuration Wizard . . . . . . . . . . . . . . . . . . . . . 52
BOOTP & DHCP configuration . . . . . . . . . . . . . . . . . . . . . . 53
Local access to the control console . . . . . . . . . . . . . . . . . . 55
Remote access to the control console . . . . . . . . . . . . . . . . . 55
Control console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
How to Access the ATS Network Management Interface. . . . . . 57
Web interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Telnet and SSH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
FTP and SCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
How to Recover From a Lost Network
Management Interface Password . . . . . . . . . . . . . . . . . . . . . . . 60
Customizing and Updating the ATS ....................... 61
How to Connect User Input Contacts and
Relay Outputs to the ATS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
How to connect contacts to the user interface board . . . . . . 62
How to Connect an EPO Switch to the ATS . . . . . . . . . . . . . . . 63
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Connect an EPO switch to the user interface board and test the switch
Safety warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
How to Allow Easy Access to the ATS Display Interface . . . . . . 67
How to Add Sub-Feed Output Distribution
Circuit Breakers to the ATS. . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Output distribution circuit breakers available from APC . . . . . 68
Circuit breaker adapter modules available from APC . . . . . . . 69
Determine the configuration of the panel . . . . . . . . . . . . . . 69
Allowed circuit breaker combinations . . . . . . . . . . . . . . . . . 70
Preparing the breakers for installation . . . . . . . . . . . . . . . . 72
Parts and tools needed for installation procedures . . . . . . . . 73
Installing breakers on the ATS panel bus . . . . . . . . . . . . . . . 74
. . . . . . . . . . . . . . . . . . . . . . . . . 64
vi InfraStruXure Power Generation System
How to Download Firmware Updates . . . . . . . . . . . . . . . . . . . 76
From a local computer . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Specifications .........................................................77
Smart Distribution Panel with ATS . . . . . . . . . . . . . . . . . . . . . . 77
Appendix: Custom Installations ..............................81
If Source 2 is a Second Utility. . . . . . . . . . . . . . . . . . . . . . . . . . 81
Differences in your system from information presented in this manual
. . . . . . . . . . . . . . . . . . . . . . . . . 81
If Source 2 is a Generator that i s
Not an APC InfraStruXure Generator . . . . . . . . . . . . . . . . . . . . 82
Differences in your system from information presented in this manual
. . . . . . . . . . . . . . . . . . . . . . . . . 82
Index .....................................................................83
InfraStruXure Power Generation System vii

Safety

y

Overview

Save these instructions

This manual contains important instructions that must be followed during installation, operation, and maintenance of the InfraStruXure Power Generation System.

Safety symbols used in this manual

Indicates an electrical hazard, which, if not avoided, could result in injury or
Electrical
DANGER
death.
Indicates a hazard, which, if not avoided, could result in severe personal injury or substantial damage to product or other property.
Indicates a potential hazard, which, if not avoided, could result in personal injury or damage to product or other property.
Caution
Indicates a heavy load that should not be lifted without assistance.
Heav
Indicates important information.
Note

Cross-reference symbols used in this manual

Indicates that more information is available on the same subject in a different section of this manual.
Indicates that more information is available on the same subject in a different manual.
See also
InfraStruXure Power Generation System 1

Warnings

The components in the InfraStruXure Power Generation System can pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents, be aware of the dangers and act safely . Read and follow all of the safety instructions and warnings i n this manual and in all of your component manuals.

The InfraStruXure Power Generation System is an optional standby system

The Generator and Automatic Transfer Switch (ATS) that you purchased from APC is classified as an Optional Standby System because it provides backup or standby power to data centers in the event of a sustained power failure.
The InfraStruXure Power Generation System is not to be classified as an Emergency System that is essential for safety to human life (e.g., fire pumps, operating room and life-support equipment in hospitals) as legally required by municipal, state, federal, or other governmental codes.
The InfraStruXure Power Generation System is not to be classified as a Legally Required Standby System, as it is not supplying power to aid in fire fighting, rescue operations, control of health hazards (e.g., sewage) and similar operations as required by municipal, state, federal, or other governmental codes.
Emergency and Legally Required Systems are not allowed to rely on municipal fuel for operation, or municipal water for cooling. Emergency and Legally Required Systems specify dual-fuel systems, with one of them being a two-hour, on-site fuel supply.
Your InfraStruXure Power Generation System is not to be classified as an Integrated Electrical System, as an orderly shutdown is not required to prevent damage to the generator. The generator is not to be paralleled with another generator.
Your generator will operate at its rated load without being refueled for a minimum of six hours, and should run with no load for a minimum of 12 hours.
Your generator can be without electrical power to the load terminals of the ATS for a maximum of 60 seconds, but will typically be without power for no more than 10 seconds.

Wire sizing

This product was designed to include an APC-manufactured 250-amp ATS. All wiring recommendations were sized for this amperage in accordance with the National Electrical Code (NEC). However, this does not prevent you from using the ATS at a lower amperage with smaller wire sizes. If you decide to operate this ATS at a lower amperage, ensure that the wire sizes are in accordance with NEC guidelines and your local codes.
2 InfraStruXure Power Generation System

Installation

For complete installation instructions, refer to the Electrical Installation Manual.
See also
Install the ATS in accordance with the National Electrical Code (NFPA 75) in the United S tates, or in accordance with the Canadian Electrical Code (CSA C22.1-02) in Canada.
When connecting Source 1 power to the ATS, install an external circuit breaker to protect against over-current conditions. The external circuit breaker must be rated at 250 A, with a symmetrical ampere rating of 35,000 rms.

Total power off procedure

To reduce the risk of electric shock or injury to personnel, disconnect all sources of power supply before servicing. To disconnect all sources of supply, follow this procedure:
Warnings
1. Set the Automatic Operation switch on the dead front of the ATS to Disable.
2. Set the Source 1 switch on the ATS to OFF.
3. Set the Source 2 switch on the ATS to OFF.
4. Set the main Source 1 circuit breaker to OFF.
5. Set the main Source 2 circuit breaker to OFF.
6. If Source 2 is a generator, set the generator control switch to OFF. If OFF is not an option, set
the generator control switch to Manual.

Operating environment

The ATS is designed for indoor use only; protect from water and conductive contaminants.
Temperature: 23 to 104°F (–5 to 40°C) Humidity: 0–95%, non-condensing Elevation: 6,562 ft (2000 m)
InfraStruXure Power Generation System 3

Overview

InfraStruXure Power Generation System

The InfraStruXure Power Generation System consists of a diesel-powered generator and a Smart Distribution Panel with Automatic Transfer Switch (ATS). The ATS is connected to both the utility (Source 1) and the generator (Source 2), with the utility as the preferred source. The ATS can alternatively be connected to a second utility. The ATS is designed for installation on the data center floor, which places power distribution closer to your data center equipment. Labels provide a quick visual indication of which ATS sub-feed breaker is supplying power to each piece of equipment. The diagram below provides examples of data center equip ment that can be connected to the ATS.
Air Conditioner Chiller
Air Conditioner
Condenser/OHE
Source 2
Generator
Air Conditioner
Circulator Pump
ATS
InfraStruXure System/
UPS and Distribution
InfraStruXure
Air Conditioner/ CRAC
Distribution
Panel
Source 1
InfraStruXure Power Generation System 5
Utility
Service Entrance Panel
How the InfraStruXure Power Generation
System Operates

Operation of the ATS during a utility failure when automatic operation is enabled

Your data center equipment is typically powered by the utility [Source 1] (
), while
the generator [Source 2] remains off. When the level
Generator Stopped
Load
Powered by
Utility.
Generator
is Off
of incoming utility power falls below a specified threshold (
), the ATS
signals the generator to start
). After the generator
(
Generator
Cool-Down
starts and attains the necessary power to support the load, the ATS performs an open transfer to the generator (
).
The generator then continues to support your data center equipment (
) until an
Retransfe r to
Utility
(Open o r Cl osed)
Utility
Resto red
Load
Powered
by Generator
acceptable flow of utility power is restored (
). The
utility power must remain stable for a specified length of time (Line Stable setting) and the generator must run for at least the duration of its minimum run-time (Min on Gen setting) before the load will be retransferred to the utility ( generator cools down (
). The retransfer to the utility can be either open or closed. Following retransfer, the
) and eventually stops.
Generator Started
Generator Started
Open Transfe r
to Generator
Utility Failure
Generator
Start
Sequence
For more information.
See page 33 for a description of how the ATS determines the line quality is bad. See page 7 for a detailed description of the generator start sequence. See page 8 for detailed descriptions of open and closed transfers. See page 7 for a detailed description of generator cool-down. See page 35 for information about the Line Stable setting. See page 35 for information about the Min on Gen setting.
6 InfraStruXure Power Generation System
How the InfraStruXure Power Generation System Operates

Generator start sequence

The generator start sequence is followed only if the Crank setting in the Operating Settings menu on the Generator Settings screen on the ATS display interface is set to Yes. If enabled, the following sequence will occur:
After a start signal is initiated, either by the ATS or manually, and the generator battery is good, the generator engine will crank and the generator should start. If the generator does not start, it will crank for the length of the Crank Time, and then rest for the length of the Rest Time. The generator will repeat this pattern for the number of times set in Crank Cycles before discontinuing further attempts to start. Check the messages on the display interface for reasons why the generator did not start.
On the generator controller interface, the LEDs track conditions during the start sequence:
LED Behavior on the Generator Controller Interface
Start sequence initiated: Generator Started: Generator Failed to Start:

Generator cool-down

After the generator has finished powering the load and utility power has been restored, the generator will enter a 60-second cool-down period. NOTE: This 60-second cool-down period is a
recommendation from the generator manufacturer. The specified 60-second
cool-down period can
only be re-adjusted (at the ATS) by an APC service technician.
InfraStruXure Power Generation System 7
How the InfraStruXure Power Generation System Operates

Open and closed transfers

When transfers are not occurring, one switch is ON and one switch is OFF.
During a closed transfer, the second switch will turn ON before the first switch turns OFF, creating a brief period of time when both switches are ON.
Closed Transfer
Source 1 Source 1 Source 2
Source 2
t=miliseconds
During an open transfer, the first switch will turn OFF before the second switch turns ON, creating a period of time when neither source is connected. This period is commonly referred to as neutral time. Neutral time is defined by the configurable Open Xfer Time.
Open Transfer
Source 1 Neutral Source 2
t=seconds
You can set whether or not to Allow Closed transfers under the Transfer Setup item on the ATS Setup menu on the display interface (see page 35 for details about these settings). If the Allow Closed setting is Yes, the ATS will always seek to perform closed transfers. In order for a closed
transfer to occur, the voltage and frequency for both sources must be acceptable and both sources must be synchronized. The ATS monitors both sources for synchronization before transferring. If the time it takes for the sources to become synchronized exceeds the configured Max Sync Time, the ATS will perform an open transfer instead. During a closed transfer, the ATS also takes into account the time it takes for the switch to actuate. This results in a seamless transfer in which non-UPS­protected equipment is uninterrupted and the UPS time on battery is reduced or even eliminated.
If the Allow Closed setting is No, the ATS will never perform closed transfers; it will only perform open transfers (see page 35 for details about these settings).
8 InfraStruXure Power Generation System
How the InfraStruXure Power Generation System Operates

Fuel monitoring/runtime calculation

Fuel monitoring is a unique feature of the InfraStruXure Power Generation System. Fuel level is monitored at the generator (if purchased through APC) and load is measured at the ATS. These measurements are used to calculate runtime, as explained in the following paragraph:
Fuel is monitored by a level sensor in the generator fuel tank (calibrated to the bottom of the tank) that changes readings every -inch of fuel-level change. From these fixed-level points, the ATS counts the number of gallons of fuel used (based on load over time) and subtracts this amount from the fixed-level fuel amount to provide an accurate estimate of fuel level. Runtime is then calculated based on the fuel-usage rate at the current load and the remaining fuel in the tank. Once a new fuel­level point is reached, the value of the calculated fuel used is reset and the computation begins again.
The Fuel Level and Runtime Estimate are displayed on the Generator Status screen on the ATS display interface. In addition, the following Fuel Alarm Limits are displayed in the Alarms menu. Corresponding values can be set for these limits:
Percent Fill: If the amount of fuel as a percentage falls below this value, an alarm condition exists.
Runtime: If the estimated runtime falls below this value, an alarm condition exists.
InfraStruXure Power Generation System 9
Smart Distribution Panel with ATS

Front view, door closed

Knockouts are provided on the roof, the
sides, and the floor of the ATS for running utility and generator input wires and for distributing power to equipment in your data center . Co nn ectin g condu it to the ATS does not require drilling. Use a knockout punch to enlarge a knockout, if necessary.
The user connection plate is attached to
the ATS monitoring unit. The plate can be removed, simplifying access to input contact, relay output, network, and EPO connections. These connections can likewise be routed through a knockout in the plate (see “User connection plate” on page 16 for more information) to avoid wiring complications.
The bottom access panel can be
removed for better access to the panel board. Use a #2 Phillips screwdriver to remove the two M6 flat-head screws securing the panel to the enclosure.
The perforated steel front door protects
against ready access to the switches, the circuit breakers, and the display interface (see page 29). To access the display interface without opening the front door, simply remove the display’s Plexiglas covering (see page 67 for instructions).
InfraStruXure Power Generation System 11
Smart Distribution Panel with ATS

Front view, door open

Remove the dead front to
obtain access to the panel board for maintenance and wiring.
The Source 1 motorized
switch (see “Motorized switches” on page 15) controls operation of the Source 1 input switch.
The automatic operation
control panel is used to set the generator to automatic operation or, alternatively, to remove the generator from automatic operation (see “Automatic operation control panel” on page 16).
The Source 1 lamp lights
green when the Source 1 switch is ON (closed).
The display interface
provides a local interface for viewing status data, configuring settings, and operating the ATS. The display interface has an LCD, a five-button panel, basic status lights, and a beeper (see “Display Interface” on page 29 for detailed information about the contents and operation of each screen).
 
pg0010c
The sub-feed output breakers provide power to equipment in the data center (see page 68 for
detailed information about installing these breakers). The Source 2 lamp lights green when the Source 2 switch is ON (closed).
The Source 2 motorized switch (see “Motorized switches” on page 15) controls operation of the
Source 2 input switch. Use the latches to open the dead front.
12 InfraStruXure Power Generation System

ATS panel board, left side

Smart Distribution Panel with ATS
The handle aids removal of the panel board
assembly from the ATS enclosure. At least two people are required to remove the panel board assembly (refer to the Electrical Installation Manual for instructions).
The Source 1 fuse block regulates input to
the Source 1 control transformer for subsequent powering of the Source 1 motorized switch and ATS monitoring unit.
The Source 1 control transformer outputs
120 VAC and 18 VAC to the Source 1 motorized switch and the ATS monitoring unit after stepping down the 480 V or 208 V input.
The communication converter allows the
generator and the ATS to communicate. The ATS monitoring unit houses a central
board assembly that communicates with several monitoring boards located throughout the ATS (see “ATS monitoring unit” on page 17 for detailed information).
Behind this access panel is the A TS interface
circuit board. Use a Phillips or standard screwdriver to remove the panel.
The Source 2 input switch accepts input
wires from the generator (refer to the Electrical Installation Manual for connection instructions).
WARNING: Only a certified electrician should connect the generator to the ATS!
This switch and fuse block regulate the 120 VAC supply to the generator for powering the
block heater and battery charger. The wheel extensions on the panel board assembly allow removal of the assembly during
installation. Removing the panel board assembly makes it easier to pull wires into the ATS.
InfraStruXure Power Generation System 13
Smart Distribution Panel with ATS

ATS panel board, right side

The Source 1 input switch accepts input wires
from the utility (refer to the Electrical Installation Manual for connection
instructions).
WARNING: Only a certified electrician should connect utility power to the ATS!
Behind this access panel are the Source 1 volt-
sensing circuit board and the distribution panel volt-sensing circuit board. Use a Phillips or standard screwdriver to remove the panel.
The Source 1 current transformers monitor
the input current of each incoming phase from the utility. The data gathered from these transformers is displayed on the Total Load by
Phase screen, which is accessed through the Load Meter menu on the display interface.
Behind this access panel is the Source 2 volt-
sensing circuit board. Use a Phillips or standard screwdriver to remove the panel.
The Source 2 control transformer outputs
120 VAC and 18 VAC to the Source 2 motorized switch after stepping down the 480 V or 208 V input.
The Source 2 fuse block regulates input to the
Source 2 control transformer for subsequent powering of the Source 2 motorized switch.
14 InfraStruXure Power Generation System

ATS Component Details

Motorized switches

The operating lever indicates the present position of the motorized switch [OFF TRIP, or O N (
)]. This lever is also used
(),
during manual operation of the switch (see “Emergency Manual Operation” on page 22 for proper operating procedures).
The on/off selector allows the operator to choose whether or not the motorized switch controls the input switch. The selector should only be used for the purpose of implementing emergency manual operation (see page 21 for more information).
Pressing the trip button immediately trips the motorized switch. If this button is pressed during automatic operation, the operating lever will move to the OFF
() position.
WARNING: Do not press this button while load is connected!
When the motorized switch is in the OFF
() position, attach a lock-out tag to the withdrawal
prevention lock for added safety. The operating lever key is used during manual operation of the motorized switch to assist in
turning the operating lever. The key is provided in the hardware bag with the ATS.
Before operating the motorized switches, review “Emergency Manual Operation” on page 22. Failure to follow proper procedures could cause personal injury or
DANGER
damage to the equipment.
InfraStruXure Power Generation System 15
ATS Component Details

Automatic operation control panel

For more detailed information concerning Automatic Operation of the InfraStruXure Power Generation System, see “Automatic Operation” on page 19.
The Not in Automatic Operation
LED is lit when the ATS is NOT in automatic operation. This typically occurs when the automatic operation switch is set to Disable. In rare instances, the
Not in Automatic Operation
LED will be lit when the automatic operation switch is in the Enable position (see page 21 for more information). Use the Automatic Operation switch to select whether the generator should automatically
turn on after a loss of power.

User connection plate

For location and description of the user connection plate, see number 2 on page 11. For clarity, the plate is shown facing upwards, as opposed to its factory-installed downward-facing position. The user interface board, the primary component on the plate, accepts most connections described below.
Connect the ATS to either the network
or the InfraStruXure Manager through the surge-protected ethernet port. This port protects your network connection from power surges.
The user interface board has four input
contact connections for monitoring Normally Open (NO) or Normally Closed (NC) dry contacts (see page 46 and page 61 for more information).
The user interface board has four relay
output connections to accommodate NO or NC dry contacts (see page 46 and page 61 for more information).
Connect an Emergency Power-Off switch at one of th e three EP O connec tion choices:
24 VDC, 24 VAC, or contact closure (see page 63 for more information).
16 InfraStruXure Power Generation System

ATS monitoring unit

885-2288
LINK RX/TX
  
NETWORK
RESET
ARMED
EPO
STATUS
TRIPPED
TEST
NC
NO
10= G RN
100=ORN
DISPLAY
RS-232
ATS Component Details
This port connects to the Source 2 volt-sensing circuit
board, the Source 1 volt-sensing circuit board, the Source 1 current transformers, and the distribution panel volt-sensing circuit board. This port connects to the ATS interface circuit board.
The display port (RJ-45) connects the monitoring unit
to the display interface. The power LED indicates whether the monitoring unit
is receiving power. The console port (DB-9) is used to configure items
12345678910111213
relating to servicing and for communication with the generator (see item 4 on page page 13).
NOTE: A laptop computer can be connected to this
25 24 23 22 21 20 19 18 17 16 15 14
port for configurations. The EPO DIP switches configure the EPO input for
the type of EPO switch that is connected: Normally
POW ER
Open (NO) or Normally Closed (NC). When the EPO Arm/Test rocker is in the Test
position, engaging the EPO switch will not cause the load to be shut down. When the rocker is in the Armed
9600-8-N-1
CONSOLE PORT
position, engaging the EPO switch turns OFF the ATS Source 1 and Source 2 switches and engages the generator’s emergency stop button. When the EPO switch is engaged, the Not in Automatic LED on the ATS is lit (see page 64 for more information about testing the EPO switch).
The EPO Armed LED is lit green when the rocker is in the Armed position. The LED is dark when
the rocker is in the Test position. The EPO Tripped LED is lit red when the EPO switch is engaged (the EPO button is pressed),
regardless of the state of the EPO Arm/Test rocker. The reset button resets the network processor; it does not reset the ATS or the monitoring unit.
The network port connects to the surge-protected ethernet port on the user connection plate (see
page 16 for more information about the surge-protected ethernet port). This port connects to the ATS interface circuit board.
The optional User/EPO Contacts port is connected to the user interface board on the user connection
plate attached to the roof of the ATS. This port supports relay outputs (4), input contacts (4), and one EPO input (see page 16 for more information).
InfraStruXure Power Generation System 17
ATS Component Details

ATS label kit

ATS Label—Place this label on the outside of the ATS enclosure to identify the ATS, and to associate it with the appropriate source: either Source 1 or Source 2.
Source Label—Use a Source 1 label at the primary utility breaker to identify which ATS it is feeding. Use a Source 2 label in instances where a secondary utility breaker is employed instead of a generator.
Generator Label—Use these labels (3 total) at the generator to identify which ATS it is feeding. Place one label on each long side of the generator near the brand name labels, and place one label on the door where the generator controller is located.
Single-Pole Label—Use these labels with each single-pole breaker on the ATS distribution panel to identify which data center equipment it is feeding. Use the marker (supplied) to write on the label.
Three-Pole Breaker Label—Use these labels with each three-pole breaker on the ATS distribution p ane l to identify which data center equipment it is feeding. Use the marker (supplied) to write notes on the lower portion of the label. The labels are customized for typical components in an InfraStruXure system. Blank labels are also included for components that do not have pre-marked labels.
Front Bezel Label—If not employing a generator for Source 2, use one of these labels to replace the Generator Power System label on the left­hand side of the bezel. Y ou can use either the Automatic T ransfer Switch or the Standby Power System label to describe your system.
ATS Dead Front Source Label—Use these alternate labels for Source 1 and Source 2 if you do not want Utility and Generator to describe your sources. These labels allow you to use Primary and Secondary or Normal and Alternate to describe Source 1 and Source 2.
18 InfraStruXure Power Generation System

Operation

Automatic Operation

How to place the InfraStruXure Power Generation System in automatic operation

1. Ensure utility power is available. If the utility is not available, the ATS will signal the generator to start.
2. Ensure the
3. Set the ATS Automatic Operation switch to Enable.
/Manual/Auto switch on the generator control panel is in the Auto position.
4. Ensure the Not In Automatic Operation LED is unlit (see page 21 for information about uncommon behavior of this LED).
“How the InfraStruXure Power Generation System Operates” on page 6 summarizes automatic operation of the InfraStruXure Power Generation System.
InfraStruXure Power Generation System 19
Automatic Operation

How to reset automatic operation on the ATS and on the generator

Resetting automatic operation on the ATS. If the Not in Automatic Operation LED is lit and
the Automatic Operation switch is in the Enable position, you will need to reset automatic operation after the event that caused this condition is corrected (see page 21 for a detailed description of events that might lead to this condition). You can also clear certain alarms by resetting automatic operation at the ATS (see “Clearing latched alarms” on page 44 for more information).
To reset automatic operation on the ATS, set the Automatic Operation switch to Disable () and then back to Enable ().

Resetting automatic operation on the generator. If the ATS display interface reports a
generator shutdown alarm and the Alarm LED is lit red, you must reset automatic operation on the generator to clear the alarm (the Shutdown LED on the generator control panel will also be lit red). Events that lead to this condition include engaging the data center EPO switch and engaging the E-stop button on the generator. If any EPO was engaged, the switch must be disengaged before automatic operation can be reset. If shutdown was not caused by an EPO, contact APC customer support (see the back cover of this manual). To reset automatic operation on the generator:
Set the
Acknowledge/Reset button.
/Manual/Auto switch on the generator control panel to . Press the Fault
Return the
/Manual/Auto switch to Auto.
20 InfraStruXure Power Generation System
Automatic Operation

Problem—loss of automatic operation

Typically, the Not In Automatic Operation LED tracks the state of the Automatic Operation switch (e.g., the LED is lit when the Automatic Operation switch is in the Disable position). If the Not In Automatic Operation LED is lit while the Automatic Operation switch is in the position, check messages on the display interface to determine which of these conditions exist:
1. The ATS unsuccessfully attempted to actuate either the Source 1 or Source 2 switch. This identifies the existence of one of the following situations:
– The Source 1 switch cannot turn ON (closed) – The Source 1 switch cannot turn OFF (open) – The Source 2 switch cannot turn ON (closed) – The Source 2 switch cannot turn OFF (open)
When the ATS cannot actuate a switch, it will attempt to actuate the switch several more times before discontinuing further attempts. There are two causes of this condition:
Enable
The load is receiving power from the utility, and the Source 1 switch trips.
When the Source 1 switch trips, the ATS will try to reclose the switch. If the switch cannot be closed, the ATS will start the generator and then close the Source 2 switch. The load will be powered by the generator and the ATS will revert to Not in Automatic Operation mode until it is reset (see page 20).
The load is receiving power from the generator, and the Source 2 switch trips.
When the Source 2 switch trips, the ATS will try to reclose the switch. After several attempts, one of two things will happen depending on whether utility power is available:
• If utility power is not available, the generator will continue to run until utility power becomes available. Once utility power is available, the ATS will switch to the utility and turn off the generator . The utility will supply power to the ATS, and the ATS will remain in Not in Automatic Operation mode until automatic operation is reset (see page 20).
• If utility power is available, the ATS will switch to the utility and turn off the generator. The utility will supply power to the ATS, and the ATS will remain in Not in Automatic Operation mode until automatic operation is reset (see page 20).
2. The data center EPO switch that is connected to the ATS EPO interface was engaged. When the data center EPO is engaged, the Source 1 and Source 2 switches are tri pped open. The
generator’s emergency stop signal becomes engage d and the ATS is no longer supplying output power. The ATS immediately goes into Not in Automatic Operation mode and stays in this mode until the system is reset. To reset the system, disengage the data center EPO switch and reset automatic operation on the generator and on the ATS (see page 20).
InfraStruXure Power Generation System 21

Emergency Manual Operation

Warning—before you operate the ATS manually

The procedures in this section only apply to situations where automatic operation through the ATS is impossible. One example would be the ATS monitoring unit’s inability to function. If automatic operation through the ATS is impossible and you must power your load from the generator, follow the instructions in “How to power the load from the generator” on page 23.
The ATS switches should be operated manually ONLY when automatic operation is disabled. If automatic operation is enabled, the ATS will attempt to actuate the switches to
Caution
DANGER
return to the preferred source.
All transfers performed when automatic operation is disabled must be open transfers—BOTH switches must be turned OFF before the switch for the desired source is turned ON. Attempting a closed transfer will damage equipment.
22 InfraStruXure Power Generation System

How to power the load from the generator

1. Set the ATS Automatic Operation switch to Disable.
Emergency Manual Operation
2. Ensure the Source 2 switch is OFF (
).
3. At the generator: a. Set the
/Manual/Auto switch on the generator
control panel to Manual.
b. Press the Manual Run/Stop button if you need to start
the generator. Pressing this button activates the engine control system
and the starting system. The starter will begin cranking and, after a few seconds, the engine should start.
Press
4. Turn the Source 1 switch OFF (
):
a. Set the selector on the Source 1 switch to Manual.
The operating lever will swing out when the selector is set to Manual.
b. Turn the Source 1 switch counterclockwise to OFF
). Use the operating lever key for easier operation.
(
InfraStruXure Power Generation System 23
Emergency Manual Operation
5. Turn the Source 2 switch ON ()
:
a. Set the selector on the Source 2 switch to Manual.
The operating lever will swing out when the selector is set to Manual.
b. Turn the Source 2 switch clockwise to ON (
). Use the
operating lever key for easier operation.
c. Close the operating levers on both the Source 1 and Source 2 switches, and then set the
selectors back to Auto to lock the switches in place.
6. Ensure the generator is powering the load. The downstream UPS should not be using battery power and the load equipment should be operating.
7. Check the control panel of the generator for visible alarms indicating possible problems. Refer to the troubleshooting section of this manual, if necessary.
24 InfraStruXure Power Generation System

How to return to powering the load from utility

1. Ensure the ATS Automatic Operation switch is set to Disable.
Emergency Manual Operation
2. Ensure the Source 1 switch is OFF (
3. Turn the Source 2 switch OFF ( a. Set the selector on the Source 2 switch
to Manual. The operating lever will swing out
when the selector is set to Manual.
b. Turn the Source 2 switch
counterclockwise to OFF ( operating lever key for easier operation.
4. Turn the Source 1 switch ON ( a. Set the selector on the Source 1 switch
to Manual.
). Use the
):
).
):
The operating lever will swing out when the selector is set to Manual.
b. Turn the Source 1 switch clockwise to
). Use the operating lever key for
ON (
easier operation.
c. Close the operating levers on both the Source 1 and Source 2 switches, and then set the
selectors back to Auto to lock the switches in place.
InfraStruXure Power Generation System 25
Emergency Manual Operation
5. Turn the generator OFF by following this procedure:
a. Ensure the
/Manual/Auto switch on
the generator control panel is set to Manual.
b. Press the Manual Run/Stop button.
Pressing this button causes the generator to complete its normal shutdown sequence.
Press
26 InfraStruXure Power Generation System

Total Power Off

Before servicing the system, follow the procedure below to disconnect all sources of power supply and reduce the risk of electric shock or injury:
1. Set the ATS Automatic Operation switch to Disable.
2. Set the Source 1 switch to OFF ( a. Set the selector on the Source 1 switch to Manual.
The operating lever will swing out when the selector is set to Manual.
b. Turn the Source 1 switch counterclockwise to OFF (
easier operation.
):
). Use the operating lever key for
InfraStruXure Power Generation System 27
Total Power Off
3. Set the Source 2 switch to OFF (): a. Set the selector on the Source 2 switch to Manual.
The operating lever will swing out when the selector is set to Manual.
b. Turn the Source 2 switch counterclockwise to OFF (
easier operation.
4. Set the main Source 1 circuit breaker to OFF (
). Use the operating lever key for
).
5. Set the main Source 2 circuit breaker to OFF ( control switch to OFF (
). If OFF is not an option, set the generator control switch to Manual.
). If Source 2 is a generator, set the generator
28 InfraStruXure Power Generation System

Display Interface

Overview

The ATS display interface is used to configure settings, set alarm thresholds, and provide audible and visual alarms.
Load On
Check Log
Gen Set On
Alarm

Load On LED When lit green, all output phases are within the limits
specified by the output alarm limit thresholds.
Check Log LED When lit yellow, at least one new alarm condition has
been detected.
ESC
?

Gen Set On LED When lit green, the generator is running. Alarm LED When lit red, an alarm condition exists. LCD For viewing alarms, status data, instructional help, and
configuration items.
Up and Down
navigation buttons
Selects menu items and accesses information.
ENTER button Opens menu items and inputs changes to system
parameters.
HELP button Launches context-sensitive help. Press the
HELP button
for information about each item on the screen and for instructions about performing certain tasks.
ESC button Returns to previously displayed screen.
InfraStruXure Power Generation System 29
Overview

Top-level status screens

After system start-up, a brief introduction screen is displayed and then the display interface scrolls automatically and continuously through five screens of basic status information. Press the Up or Down arrows to interrupt automatic scrolling and view a specific status screen.
Source: S1-Utility S1: Ok Fuel: xxx% Runtime:1 day 12 hr
Volts-Out L1-2: xxx L2-3: xxx L3-1: xxx
S2: OFF
Volts-Sx L1-2: xxx L2-3: xxx L3-1: xxx
Load Current:
L1: 000 L2: 000 L3: 000
Neut:
000
Total Output Loading
kW: 000 kVA: 000 Freq: 000
No Active Alarms System Date/Time:
Jun-24 2004 07:58
PF:
%LD: xxx
000
If you have scheduled one or more tests, the displa y interface shows the scheduled test screen (below) each time a self-test commences. To cancel an ongoing self-test, press rests on the ABORT NOW?
option.
Scheduled test will start in xxx sec.
ABORT NOW?
ENTER when the selector arrow

Top-level menu screen

Press ENTER to open any of the following top-level menu screens:
Load-Meter ATS/Voltage Generator Testing
If the display interface is inactive for the time specified in the Time-out setting, it will revert to the initial basic monitoring screens.
Note
For descriptions of the top-level menu choices, see the sections devoted to each top­level menu starting on page 32.
Stats Alarms Config Help
30 InfraStruXure Power Generation System

Navigating through screens

Overview
To open any screen, press the Up or Down arrow until the selector ( selection. Press
ENTER to view the selected screen.
Load-Meter ATS/Voltage Generator Testing
Stats Alarms Config Help
Contacts In: 02of04 Name: User Switch #2 Normal: Open Status: Open
When configuring settings, press the Up or Down arrows until the selector ( press
rests next to the setting you want to change, and then
ENTER. If the setting is a list of choices, an input arrow (
will appear next to the setting. Press the Up or Down arrow until your desired change appears. Press
On some screens, continue arrows (
ENTER to select the setting.
indicate there are
additional screens to view in the category. Press the Up or Down arrow to view these additional screens.
rests next to your desired
Contacts In: 02of04 Name: User Switch #2 Normal: Open Status: Open
System/Network Electrical Configuration Panel Configuration Manufacturer Data
Product Data Factory Defaults Firmware Updates

Password-protected screens

When configuring or changing settings, the display interface prompts you for your password. To enter your password:
1. Press the Up or Down arrow until the correct letter is displayed, and then press
ENTER.
Enter Password:
*******
After pressing ENTER, the character you entered is displayed as an asterisk and the input arrow moves to the next space. Select the next
Note
2. Press
password character and then
ENTER twice after entering your password.
ENTER, etc.
See “System Password” on page 45 to change your password.
InfraStruXure Power Generation System 31

Load-Meter

Total Load by Phase Total Load Summary Power Factor Sub-Feed Monitoring

Total Load by Phase

For each phase (L1, L2, L3), the following is displayed:
kVA The apparent power provided, in kilovolt-amps. Iout The output %LD The load as a percentage of the maximum allowable load.
RMS load current.

Total Load Summary

For the total load supported, the following is displayed:
kW The active power drawn by the load, in kilowatts. kVA The apparent power provided, in kilovolt-amps. Freq The frequency, in hertz. PF The power factor, or the ratio between active power and apparent power (kW/kVA), that is
being supplied to the load.
%LD The load as a percentage of the maximum allowable load.

Power Factor

The following power factor data is displayed for each phase (L1, L2, L3):
kVA The apparent power provided, in kilovolt-amps. kW The active power drawn by the load, in kilowatts. PF The power factor, or the ratio between active power and apparent power (kW/kVA), that is
being supplied to the load.
32 InfraStruXure Power Generation System

ATS/Voltage

ATS Position: S1
S1-Utility: OK S2-Generator: OFF ATS Setup

ATS Position

One of the following options is displayed to describe the selected source:
S1 The Source 1 switch is ON (closed). Source 1 is connected to the output. S2 The Source 2 switch is ON (closed). Source 2 is connected to the output. NEUT The Source 1 and Source 2 switches are OFF (open). Neither source is connected to the output. S1&S2! The Source 1 and Source 2 switches are ON (closed). This is an alarm condition.

S1-Utility

One of the following is displayed to describe the condition of the input from Source 1.
OK Source 1 is acceptable, as defined in the Transfer Points menu (see page 35). BAD Source 1 is not acceptable, as defined in the Transfer Points menu (see page 35).
Press
ENTER when the selector arrow rests at the S1-Utility item to display the following:
L1-2, L2-3, L3-1 The Source 1 line-to-line input voltage. L1, L2, L3 The Source 1 line-to-neutral input voltage. These readings are only displayed on Wye
systems.
Frequency The frequency of the utility input, in hertz (Hz). Qual Describes the quality of the input from Source 1. One of the followin g condi tions is
displayed:
Source Good: The source is acceptable, as defined in the Transfer Points menu.
Low Voltage: The input voltage is below the configured Low voltage Transfer Point
on one or more of the phases.
High Voltage: The input voltage exceeds the configured High voltage Transfer Point
on one or more of the phases.
Phase Imbalance: The percent voltage difference between two phases, as defined by the Phase Balance setting in the Trans fer Points menu, has been exceeded.
Freq Range: The frequency is outside the configured Freq range, as defined in the Transfer Points menu.
Bad Rotation: The phase rotation does not match the configured Phase Sequence, as defined in the Transfer Points menu.
Phase Sequence Lists the phase rotation (e.g., A-B-C) of the Source 1 input.
InfraStruXure Power Generation System 33
ATS/Voltage

S2-Generator

One of the following is displayed to describe the condition of the input from Source 2.
OK Source 2 is acceptable, as defined in the Transfer Points menu (the generator is
running).
OFF The generator is not running. BAD Source 2 is not acceptable, as defined in the Transfer Points menu, even though the A TS
is commanding the generator to run.
ENTER when the selector arrow rests at the S2-Generator item to display the following:
Press
L1-2, L2-3, L3-1 The Source 2 line-to-line input voltage. L1, L2, L3 The Source 2 line-to-neutral input voltage. These readings are only displayed on Wye
systems.
Frequency The frequency of the Source 2 input, in hertz (Hz). Qual Describes the quality of the input from Source 2. One of the following conditions is
displayed:
Source Good: The source is acceptable, as defined in the Transfer Points menu.
Low Voltage: The input voltage is below the configured Low voltage Transfer Point
on one or more of the phases.
High Voltage: The input voltage exceeds the configured High voltage Transfer Point
on one or more of the phases.
Phase Imbalance: The percent voltage difference between two phases, as defined by the Phase Balance setting in the Trans fer Points menu, has been exceeded.
Freq Range: The frequency is outside the configured Freq range, as defined in the Transfer Points menu.
Bad Rotation: The phase rotation does not match the configured Phase Sequence, as defined in the Transfer Points menu.
Phase Sequence Lists the phase rotation (e.g., A-B-C) of the Source 2 input.
34 InfraStruXure Power Generation System

ATS Setup

Press ENTER when the selector arrow rests at the ATS Set up item to change the following settings:
Transfer Points The voltage-sensing point at which you would transfer to the other source, based on
voltage and frequency.
S1-Utility: The input voltage reading for Source 1.
Low: The low voltage limit that causes the ATS to switch from Source 1 to Source 2.
Press
ENTER to change this setting.
High: The high voltage li mi t that causes the ATS to switch from Source 1 to Source 2.
Press
ENTER to change this setting.
Other Settings: The settings on this screen determine when the source is OK, and
define the quality of the source. Press to change the following settings or thresholds:
Freq: The frequency cannot vary beyond this configured range (+/– x.xx Hz). –Phase Balance: The percent voltage difference between two phases cannot exceed
this configured setting (%).
Phase Sequence: The phase rotation (default is A- B-C) must match this configured
setting.
ENTER when the selector arrow rests at this item
ATS/Voltage
Transfer Setup The following settings can be changed in this menu:
Open Xfers: Defines how long BOTH the Source 1 and Source 2 switches will be OFF
(open) during an open transfer (see page 8 for a definition of open transfers).
Allow Closed: Enables/disables closed transfers (see page 8 for a definition of closed
transfers).
Max Sync: The maximum time allotted for the A TS to attempt a closed transfer before
it performs an open transfer.
ATS Delay Settings: The time delay settings that affect transfers and retransfers. –Gen Start: The amount of time allotted between when the generator receives a start
signal and when the generator starts (default is 0).
Line Stable: If the ATS switches to Source 2 after a failure in Source 1, and Source 1
is restored, the Line Stable setting is the amount of time (in seconds) allotted for Source 1 to become acceptable before the ATS returns to it (default is 3 minutes).
Min on Gen: The minimum time the generator must run before the A TS retransfers to
utility (default is 15 minutes).
InfraStruXure Power Generation System 35
ATS/Voltage
ATS Blocking Transfer Blocking: Defines conditions that will prevent the ATS from transferring
from Source 1 to Source 2. The following is displayed on the Transfer Blocking screen: –Block Transfer: Lists configured input contacts that will prevent a transfer from
occurring.
Map: Choose from the following input contact s to block a transfer:
C1: Contact 1 C2: Contact 2 C3: Contact 3 C4: Contact 4
Apply Now: After you have made changes on this screen, choose this option and
press
ENTER to save your changes.
Retransfer Blocking: Defines conditions that will prevent the ATS from transferring
from Source 2 to Source 1. The following is displayed on the Retransfer Blocking screen:
Block Retransfer: Lists configured input contacts that will prevent a retransfer from
occurring. Map: Choose from the following input contacts to block a retransfer: C1: Contact 1 C2: Contact 2 C3: Contact 3 C4: Contact 4
Apply Now: After you have made changes on this screen, choose this opt ion and
press
ENTER to save your changes.
Gen Start Blocking: Defines input contacts that will prevent the generator from
starting because of a line failure: –Block Gen Start: Lists configured input contacts that will prevent the generator from
starting.
Map: Choose from the following inpu t contacts to block the generator from starting:
C1: Contact 1 C2: Contact 2 C3: Contact 3 C4: Contact 4
Apply Now: After you have made changes on this screen, choose this opt ion and
press
ENTER to save your changes.
Other Settings S1 Name: Create a unique name for Source 1 (maximum of 9 characters). The default
is Utility.
S2 Name: Create a unique name for Source 2 (maximum of 9 characters). The default
is Generator.
Preferred: Displays the preferred source (Source 1).
36 InfraStruXure Power Generation System

Generator

Generator Status Fuel & Runtime Statistics & Maint. Generator Settings

Generator Status

The following items are available on this menu:
Generator Status This screen displays the following conditions to describe the Gen State:
Off: The generator is not running.
Cranking: The generator is starting.
Running: The generator is running.
Idle: The generator is running, but not supplying power to the load.
E-Stop: The Emergency Power-Off switch has been actuated on the generator or
the ATS.
Fault: The generator is unabl e to start.
No Com: The ATS has lost communication with the generator.
Mode Sw provides the position of the generator ’s switch must be in Auto for the generator to start, based on the state of the run/stop contact. Auto, Manual, or Off is displayed to describe the position of the switch.
The following settings can be accessed through this menu:
Engine Run: Shows the current state of the run/stop contact, which signals the generator's engine to start and stop. The state can be Run or Off. Automatic control of this signal is disabled when the Not in Automatic Operation LED on the ATS is lit.
Engine Parameters: View the following measured data relating to operation of the generator's engine:
–Battery Voltage –Oil Pressure –Coolant Temperature
Fuel & Runtime This screen displays the following:
• Type: The type of fuel the generator uses (diesel).
Tank Size: The size of the fuel tank on the generator (in gallons or liters).
Fuel Level: The percentage of fuel left in the generator fuel tank.
Runtime Estimate: How much time (xx days zz hours) the ge nerator can r un based on the fuel level and load, and the load value (in kW) used to calculate runtime.
Statistics & Maint. Lifetime Statistics: Scroll through a list of items that accumulates over the life of
the generator, including: –Last Maintenance Date –Engine Starts –Total kWh –Total Runhours
–Engine RPM –Coolant Level –Oil Level
/Manual/Auto switch. The
InfraStruXure Power Generation System 37
Generator
Maintenance Record: Scroll through a list of items that accumulates after the
maintenance record is reset, including: –Last Maintenance Date –Operating Days –Engine Starts –Total kWh –Total Runhours
Next Maintenance: View the month and year of the next scheduled maintenance and the
number of days remaining until the next scheduled maintenance. Reset the maintenance record so that the data in the Maintenance Record menu returns to zero.
Generator Settings This screen allows you to access the following settings:
Operating Settings
–Start Delay The amount of time the generator waits after initiation of the start
signal before it begins powering the load. This setting is configurable on the generator control panel (default is 0).
–Stop Delay The amount of time between when the start signal is removed and
when the generator stops. This setting is configurable on the generator control panel (default is 0).
–Crank Settings The following settings can be changed in the generator service
menus by service personnel.
Crank: Indicates whether the crank cycle is enabled. If the crank
cycle is not enabled, the generator will continue attempting to start until the battery dies.
Crank Cycles: The number of crank cycles the generator will go
through when attempting to start (default is 3).
Crank Time: The amount of time the generator will crank during
a crank cycle (default is 15 seconds).
Rest Time: The amount of time the generator will rest after it
cranks during a crank cycle (default is 15 seconds).
NOTE: APC does not recommend changing the default values of the generator settings described above.
Manufacturer Data
–Fuel System The type of fuel the generator uses (default is diesel). –Tank Size The size of the fuel tank on the generator (in gallons or liters). –Final Assy Date Date the generator was assembled at the factory. –Model Number Generator model number from Cummins –GenSet S/N The serial number of the generator. –Voltage Config Nominal input voltage (208 V or 480 V). –Alternator Freq Nominal frequency setting of the alternator output (50 or 60 Hz). –Gen kW Rating The power rating of the generator (80 kW or 125 kW).
Gen Output Adjust
–Voltage Displays the desired alternator output voltage (configurable on the
generator control panel).
–Frequency Displays the desired alternator output frequency (configurable on
the generator control panel).
38 InfraStruXure Power Generation System
®
.

Testing

View Test Log Run/View Test Test Schedule Test Duration

View Test Log

Displays all logged test results in a scrolling list. For each item, the screen provides the Gen Start test and the Load Test results with a date and time stamp of when the test occurred.

Run/View Test

Use this menu to run a test now, or to view a test that is in progress.
Engine Start Test If a test is in progress, the screen displays Test Progress and the time remaining in
the test. If you want to stop the test, select the and then press
ENTER.
ABORT NOW? item on this screen
If you want to run a start test now, select Run Test Now from the confirmation screen and then press
ENTER. The test will run based on the parameters set on the
Test Duration menu. If you do not want to run a start test now, choose No from the confirmation screen and then press
ENTER.
System Load Test If a test is in progress, the screen displays Test Progress and the time remaining in
the test. If you want to stop the test, select the and then press
ENTER.
ABORT NOW? item on this screen
If you want to run a load test now, select Run Test Now from the confirmation screen and then press
ENTER. The test will run based on the parameters set on the
Test Duration menu. If you do not want to run a load test now, choose No from the confirmation screen and then press
ENTER.
InfraStruXure Power Generation System 39
Testing

Test Sch edu le

Use this menu to schedule a test in the future.
Define Schedule Set the test schedule by changing the following parameters:
Gen Start: Choose when to perform a generator start test. Choices are Never, Monthly, Weekly, or Daily.
Day: The choices for Day depend on the choice made for Gen Start:
If you chose a GenStart of Never: The Day is not configurable. If you chose a GenStart of Monthly: Choose to perform the test on the 1st, 2nd,
3rd, or 4th week of the month on a specific day of the week.
If you chose a GenStart of Weekly: Choose to perform the test on any day of the week.
If you chose a GenStart of Daily: Choose to perform the test Everyday, on Weekdays (Monday through Friday), or on Weekends (Saturday and Sunday).
Time: Set the time of day the test will run. The time is set on a 24-hour clock.
Load Test: Choose to test the generator with the data center load applied. Choose to perform the load test By Month, Monthly, Never, or All.
Choosing Monthly for the Load Test ensures this test will take place on the first occurrence of the Gen Start Test.
Gen Start: Monthly Day: 1st Monday Time: 14:30 Load Test: Monthly
Next Test Lists the date and time of the next test.

Test Dur ati on

The following items are available on this menu:
Warm Up Set the amount of time, in seconds (up to 999), that the generator will warm up
during a test.
Loaded If the Load Test option is selected, set the amount of time, in minutes (up to 999),
that the generator will run with the data center load applied.
Cooldown Set the amount of time, in seconds (up to 999), that the generator will cool down
after the test.
40 InfraStruXure Power Generation System

How a test occurs

A
When a test is not in progress, the ATS waits for a test to occur. Initiate a test by scheduling one using the Test Schedule screen on the display interface, or by starting a test immediately through the Run/View Test screen. Once you have initiated a test, the ATS starts counting down until the next test will begin (the Next Test item on the Test
Schedule menu). Once the Next Test time expires, the ATS will
signal the generator to start. The generator will then crank in an attempt to start. If the generator does not start, the test fails and the A TS logs that the test failed. If the generator starts, and the ATS determines that Source 2 is OK, the test will begin with the configurable Warm Up time. Once the Warm Up time expires, the ATS determines whether or not you want to perform a System Load Test. This is a test the generator runs with the data center load applied.
Log
Test
Failed
TS Waiting
to Test
Schedul ed or Manu al Test Initiated
ATS Test
Countdown
Countdown Expires
Generator
Cranking
Source 2 is Good
ATS Test Warm-Up
Warm-up Time Expires
Load Test?
Test ATS
With Load
Loaded time expires
Unloaded
Test
Unloaded time expires
Yes
Testing
Log
Test
Passed
No
If the test does not include a System Load Test, the ATS
Generator
Stopping
proceeds to the unloaded test stage. If the test includes a System Load Test, the ATS transfers to Source 2. The transfer can be open or closed, depending on how the Allow Closed setting is configured on the ATS Setup menu. The load test occurs for the length of the Loaded time and, once the loaded time expires, the ATS will retransfer to Source 1 and then proceed to the unloaded test stage.
During the unloaded test stage, the generator runs for the duration of the configurable Unloaded Test ti me. Once the Unloaded Test time expires, the generator stops and the ATS logs either that the test was successful or that it failed. The ATS di splays test resul ts on the View Test Log menu on the Testing screen.
InfraStruXure Power Generation System 41

Stats

Statistics: 00 of 00 Name of statistic here XX,XXXX
Reset
Scroll through a list of items that accumulates after the statistics record is reset, including:
Reset All
Open Xfer Count: The number of open transfers since this statistic was reset.
Closed Xfer Count: The number of closed transfers since this statistic was reset.
Generator Fuel Used: The amount of fuel used since this statistic was reset.
Source 1 Bad Count: The number of times Source 1 was not acceptable, as defined in the Transfer Points menu, since this statistic was reset.
S1 Low Volts Count: The number of times the Source 1 input voltage went below the configured Low voltage Transfer Point on one or more of the phases since this statistic was reset.
S1 High Volts Count: The number of times the Source 1 input voltage exceeded the configured High voltage Transfer Point on one or more of the phases since this statistic was reset.
S1 Bad Freq Count: The number of times the Source 1 input voltage went outside the configured Freq range, as defined in the Transfer Points menu, since this statistic was reset.
S1 Imbalance Count: The numb er of times the percent voltage difference between two phases, as defined by the Phase Balance setting in the Transfer Points menu, was exceeded on Source 1 since this statistic was reset.
Total Time S1 Bad: The total amount of time Source 1 was not acceptable, as defined in the Transfer Points menu, since this statistic was reset.
Maximum Time S1 Bad: The longest amount of time Source 1 was not acceptable, as defined in the Transfer Points menu, since this statistic was reset.
Minimum Time S1 Bad: The shortest amount of time Source 1 was not acceptable, as defined in the Transfer Points menu, since this statistic was reset.
Time on Source 1: The total amount of time Source 1 was selected since this statistic was reset.
Time on Source 2: The total amount of time Source 2 was selected since this statistic was reset.
Reset Reset only the statistic that is shown on the screen by pressing
following the prompts.
Reset All Reset all of the statistics by pressing
42 InfraStruXure Power Generation System
ENTER and following the prompts.
ENTER and

Alarms

View Active Alarms Alarm/Event Log Alarm Setup Alarm Beeper

View Active Alarms

View a list of all currently existing alarms . When an alarm is present on the system, the Alarm LED on the ATS display interface is lit red. Choosing View Active Alarms turns off the LED.

Alarm/Event Log

The following items are available on this menu:
New Logged Items View only alarms and events logged since New Logged Items was last viewed.
The existence of a new alarm causes the Check Log LED on the ATS di splay interface to light orange. Choosing New Logged Items turns off the LED.
Entire Log View every item in the alarm/event log. When a new alarm is added to the log, the
Check Log LED lights orange. Choosing Entire Log turns off the LED. Clear Log Erase all of the items currently in the alarm/event log. Clr Latched Alarms Erase only the latched alarms that currently exist in the alarm/event log (see
“Clearing latched alarms” on page 44 for more information).

Alarm Setup

Configure the alarm limits (or thresholds) on this menu:
Loading Limits Iout-Alarm Limits:
Low: If the output current of any phase falls below this value, an alarm condition
exists. The value is set as a percentage of the ATS rating, and is shown in amps.
High: If the output current of any phase exceeds this value, an alarm condition
exists. The value is set as a percentage of the ATS rating, and is shown in amps.
Neut: If the output neutral current exceeds this value, an alarm condition exists.
The value is set as a percentage of the ATS rating, and is shown in amps.
Voltage Limits Vout-Alarm Limits:
Low: If the output voltage of any phase falls below this value, an alarm condition
exists. The value is set as a percentage of the nominal system voltage, and is shown in volts.
High: If the output voltage of any phase exceeds this value, an alarm condition
exists. The value is set as a percentage of the nominal system voltage, and is shown in volts.
InfraStruXure Power Generation System 43
Alarms
Fuel Alarm Limits Low Fuel Alarms:
Percent Fill: If the amount of fuel as a percentage falls below this value, an alarm
condition exists (see “Fuel monitoring/runtime calculation” on page 9 for more information).
Runtime: If the estimated runtime falls below this value, an alarm condition
exists (see “Fuel monitoring/runtime calculation” on page 9 for more information).
Other Limits Other Limits:
Frequency: If the frequency is outside this range, an alarm condition exists.
Alarm Delay: Before an output alarm condition officially exists, the specified
limit must be exceeded for this amount of time (in seconds). The advantage of the delay is that it filters out short alarm conditions, which are normal in ATS operation. For example, when utility power is shut off, the AT S wi ll interpret this as a low-voltage condition; however, once the generator begins operation, this alarm is meaningless. An Alarm Delay of more than 15 seconds may prevent display of the low-voltage alarm in this example. The Alarm Delay applies to all Voltage, Loading, Frequency, and Runtime limits.

Alarm Beeper

Once the alarm beeper sounds, it will continue to beep every 30 seconds. Touching any button on the ATS display interface will de-activate the beeper. Use this menu option to turn Off the beeper so that it never sounds when an alarm occurs, or turn On the beeper after you have turned it off. The default is On.

Clearing latched alarms

When an alarm is present, the Alarm LED on the ATS display interface is lit red. To clear latched alarms, you must acknowledge them differently than other alarms. The following are considered latched alarms:
Test Complete-Failed: The system has failed a self-test.
Gen Start Failure: The generator failed to start. To clear a latched alarm and turn off the LED, choose the Clr Latched Alarms option on the Alarm/Event
Log menu of the Alarms screen. You can also clear latched alarms by resetting automatic operation on the ATS. Set the Automatic Op erati on switch to Disable (

) and then back to Enable ().
44 InfraStruXure Power Generation System

Config

System/Network Contacts & Relays Sub-Feed Config. Electrical Config.
Factory Defaults Manufacturer Data System ID Firmware Updates

System/Network

This menu consists of the following items:
System Password Password: You can change the system password required to access protected
Timeout: Set the time the display interface will wait for user input before it
Invalidate NOW: Allows you to re-enter your system password for viewing
screens and fields in the display interface. Enter a string of up to eight alphanumeric characters, and then add the underline character (_) to indicate the end of the string. The default password is apc.
reverts to the initial scrolling of status screens. Select 1, 2, 5, 10 (the default), or 30 minutes; or 1, 2, or 4 hours; or forever.
password-protected screens.
Date/Time Date: Set using the following fo rm at: dd-mmm yyyy.
Time: Set using the following format: hh:mm:ss
Local Interface Contrast: Set the screen contrast for the LCD. Select from 1 (high contrast) to 8
(low contrast).
Key Click: Choose On for an audible click whenever you press a navigation button. Choose Off to disable the click.
Beeper Volume: Select High, Medium, Low, or Off to adjust the loudness of both the audible beeper and the click.
Metric Units: Choose On to view all data as metric values (e.g., meters) and Off to view data as U.S. standard units (e.g., feet).
Network Config IP: The system IP address.
SM: The subnet mask, which iden tifies the subnetwork on which the ATS operates.
GW: The default gateway used by the ATS. The MAC address is displayed in brackets at the bottom of the screen.
InfraStruXure Power Generation System 45
Config

Contacts & Relays

The ATS can monitor external contact closure events. Possible applications include:
• Magnetic contact switches
• Window foil
• Tamper switches
• Heat detectors You can set input contacts to cause alarm conditions based on their current state in relation to a user-defined
normal state. Relay outputs can map internal al arms and events to outside devices. Use the Contacts &
Relays screen to display and configure information about input contacts and relay outputs.
Input Contacts Scroll through the list to display information about each of the installed contact
inputs. For example, 02of04 displays information about the second of four installed input contacts.
Name: The name of this input contact (maximum of 14 alphanumeric characters).
Normal: The normal positio n of this input contact, either Open or Closed.
Status: The actual position of this input contact. If the actual position is not the
normal position, an alarm condition occurs.
Relay Outputs Scroll through the list to display information about each of the installed relay
outputs. For example, 04of04 displays information about the fo urth of the four available relay outputs.
Name: The name of this relay output (maximum of 14 alphanumeric characters).
Normal: The normal positio n of this relay output, either Open or Closed.
Status: The actual position of this relay output.
• Water sensors
• Pressure sensors
• Building smoke and fire detection systems
Output Relay Map Configure th e relay outputs using the
Output Relay Map. Each Relay Map corresponds to a relay output. For example, Relay Map 01of04 corresponds to the first
of four relay outputs. The second line, in brackets [ ], lists the items you have selected to map to the selected relay. The third line allows you to select the alarms to which you want to map the relay:
A! Any Alarm V1 Source 1 Quality Bad V2 Source 2 Quality Bad Vo Output Voltage Alarm
† †
R Run/Start Contact ON S2 Source 2 Selected F Fuel/Runtime Alarm L Any Load Alarm Au ATS Not-in-Auto Mode S! The Source 1 and Source 2 switches are ON (closed) C1 Contact 1 C2 Contact 2 C3 Contact 3 C4 Contact 4
If you map all three of the voltage alarms (V1, V2, Vo), the map will display the following: V12o
If you map all four of the contact alarms (C1, C2, C3, C4), the map will display the
following: C1234
‡ ‡ ‡ ‡
Relay Map: 01of 04 [XX,XX,XX] Map: Input Voltage Apply Now
46 InfraStruXure Power Generation System

Electrical Config

The following items are available on this menu:
Voltage Specifies the input voltage rating of the ATS. Switch Rating Specifies the amperage rating of the ATS. Frequency Specifies the frequency rating of the ATS. DC Backup Specifies whether or not the ATS monitoring unit is receiving back-up power from
the generator battery.

Factory Defaults

Use this option on the Config screen to reset all ATS settings to their factory default valu es.

Manufacturer Data

Config
Use this option on the Config screen to display a scrollable list containing information about the ATS. This information is useful when requesting service or product updates. The following information is displayed:
• Manufacturer Name
• Date of Manufacture
• Date of Calibration
• Hardware Revision
• Firmware Revision
• Serial Number
• Model Number

System ID

The following items are available on this menu:
System Name Set a unique name for your InfraStruXure Power Generation System. Location Specify the physical location of the system in relation to your data center. Contact Identify the person to notify concerning questions or problems with regard to the
system.

Firmware Updates

Use this option on the Config screen to download updated firmware to the ATS.

Reset 100% Fuel Level

Use this option after the generator’s tank has been filled to reset the ATS to acknowledge a 100-percent fuel level. The ATS can now begin calculating accurate fuel-consumption rates and run-time information.
InfraStruXure Power Generation System 47

Communication Configuration

ATS Management Options

Overview

There are two options for managing your system. You can manage the ATS, along with the rest of your InfraStruXure equipment, through the InfraStruXure Manager (APC LAN); or you can manage your system through APC’s network management interfaces (User LAN).

InfraStruXure Manager

The InfraStruXure Manager is a rack-mount management device that coordinates the management functions of APC InfraStruXure-Certified devices installed in your data center. It provides a single interface to view and configure all APC InfraStruXure-Certified devices (see “Configuring the InfraStruXure Manager” on page 50 for configuration instructions).
For more information about the InfraStruXure Manager , refer to the Installation and Configuration Manual included with the InfraStruXure Manager.
See also

Network management interfaces

The control console and Web interfaces provide menus with options for managing your system (see “Configuring the ATS Network Management Interface” on page 51 for configuration instructions).
For more information about the internal user interfaces, refer to the InfraStruXure Power Generation System’s on-line Network Management User’s Guide.
See also
®
The SNMP interface allows you to use an SNMP browser with the PowerNet Information Base (MIB) to manage your system (see “Configuring the ATS Network Management Interface” on page 51 for configuration instructions).
To use the PowerNet MIB with an SNMP browser, refer to the PowerNet® SNMP Management Information Base (MIB) Reference Guide, which is provided on the
See also
InfraStruXure Power Generation System’s Utility CD.
Management
InfraStruXure Power Generation System 49

Configuring the InfraStruXure Manager

Connect the ATS to the InfraStruXure Manager

1. Connect a CAT-5 network cable to the surge-protected ethernet port on the user connection plate. The arrow in the illustration below is pointing to the port. The figure on page 11 shows the location of the user connection plate on the roof of the ATS.
You can make this connection from inside the enclosure, or you can remove the user connection plate from the ATS to make the connection. A Phillips or standard screwdriver is needed to loosen the two captive screws. Use the knockout in this plate to route the cable. If you decide to remove the plate, make sure not to disturb the existing connections.
2. Run the connected CAT-5 network cable through the knockout in the user connection plate to the InfraStruXure Manager Hub.
3. Configure the InfraStruXure Manager only after all APC InfraStruXure-Certified equipment has been installed, the network cable has been connected to the InfraStruXure Manager Hub, and start-up of the system has been completed.
For detailed configuration instructions, refer to the Installation and Quick-Start Manual included with your InfraStruXure Manager.
See also
50 InfraStruXure Power Generation System

Configuring the ATS Network Management Interface

Connect the ATS to your network

1. Connect a CAT-5 network cable to the surge-protected ethernet port on the user connection plate. The arrow in the illustration below is pointing to the port. The figure on page 11 shows the location of the user connection plate on the roof of the ATS.
You can make this connection from inside the enclosure, or you can remove the user connection plate from the ATS to make the connection. A Phillips or standard screwdriver is needed to loosen the two captive screws. Use the knockout in this plate to route the cable. If you decide to remove the plate, make sure not to disturb the existing connections.
2. Run the connected CAT-5 network cable through the knockout in the user connection plate to your network connection.
3. Configure the TCP/IP settings of the ATS (see “Configuration overview” on page 52 for further instructions).
InfraStruXure Power Generation System 51
Configuring the ATS Network Management Interface

Configuration overview

You must configure the following TCP/IP settings before the ATS can operate on a network:
• IP address of the ATS (only needed for manual address assignment)
• Subnet mask
• Default gateway If a default gateway is unavailable, use the IP address of a usually running
computer that is located on the same subnet as the ATS. The ATS will use the default gateway to test the network at times when traffic is very light. Refer to
Note
“Watchdog Features” in the “Introduction” of the InfraStruXure Power Generation System’s on-line Network Management User’s Guide for more information about the watchdog role of the default gateway.

TCP/IP configuration methods

Use one of the following methods to define the TCP/IP settings needed by the ATS:
• Device IP Configuration Wizard (see “Device IP Configuration Wizard” on this page).
• BOOTP or DHCP server (see “BOOTP & DHCP configuration” on page 53).
• Local computer (see “Local access to the control console” on page 55).
• Networked computer (see “Remote access to the control console” on page 55).

Device IP Configuration Wizard

You can use the Device IP Configuration Wizard on a Windows NT®, Windows 2000, or Windows XP computer to discover unconfigured ATS systems and configure their basic TCP/IP settings.
To configure one or more ATSs by exporting configuration settings from a configured ATS, refer to “How to Export Configuration Settings” in the on-line Network
See also
Management User’s Guide on the Utility CD.
1. Insert the InfraStruXure Power Generation System’s Utility CD into a computer on your network.
2. Launch the Wizard, when prompted. If prompted to restart the computer, access the Wizard from the Start menu after the computer has restarted.
3. Wait for the Wizard to discover the first unconfigured ATS, then follow the on-screen instructions.
If the Start a Web browser when finished option is enabled, you can use apc for both the User Name and the Password to access the ATS through your browser.
Note
52 InfraStruXure Power Generation System
Configuring the ATS Network Management Interface

BOOTP & DHCP configuration

The Boot Mode setting, a TCP/IP option in the ATS’s Network menu, identifies how the TCP/IP settings will be defined. The possible settings are Manual, DHCP only , BOOTP only , and DHCP & BOOTP (the default setting).
The DHCP & BOOTP setting assumes that a properly configured DHCP or BOOTP server is available to provide TCP/IP settings to ATSs. If these servers are unavailable,
Note
see “Device IP Configuration Wizard” on page 52, “Local access to the control console” on page 55, or “Remote acc ess to the contro l console” on pa ge 55 to configure the needed TCP/IP settings.
With Boot Mode set to DHCP & BOOTP, the ATS attempts to discover a properly configured server. It first searches for a BOOTP server, and then a DHCP server, and repeats this pattern until it discovers a BOOTP or DHCP server.
For more information, see “BOOTP” on this page or “DHCP” on page 54.
Note
BOOTP. Use an RFC951-compliant BOOTP server to configure the TCP/IP settings for the ATS.
The BOOTP setting assumes that a properly configured BOOTP server is available to provide TCP/IP settings to ATSs. If a BOOTP server is unavailable, see “Device IP Configuration Wizard” on page 52, “Local access to the control console” on page 55, or
Note
“Remote access to the control console” on page 55 to configure the TCP/IP settings.
1. Make sure the BOOTP setting, a TCP/IP option in the ATS’s Network menu, is enable d.
2. Enter the ATS’s MAC and IP addresses, the subnet mask and default gateway settings, and an optional Bootup file name in the BOOTPTAB file of the BOOTP server.
For the MAC address, look on the Quality Assurance slip included with the ATS.
See also
3. When the ATS reboots, the BOOTP server provides it with the TCP/IP settings.
– If you specified a bootup file name, the ATS attempts to transfer that file from the BOOTP
server using TFTP or FTP. The ATS assumes all settings specified in the bootup file.
– If you did not specify a bootup file name, the ATS can be configured remotely by using
Telnet or the Web interface: User Name and Password are both apc, by default.
To create the bootup file, refer to your BOOTP server documentation.
See also
InfraStruXure Power Generation System 53
Configuring the ATS Network Management Interface
DHCP. Use an RFC2131/RFC2132-compliant DHCP server to configure the TCP/IP settings for the
ATS.
This section summarizes ATS communication with a DHCP server. For more detailed information about how a DHCP server is used to configure network settings for an ATS,
See also
refer to “DHCP Configuration” in the InfraStruXure Power Generation System’ s on- line Network Management User’s Guide.
1. The ATS sends out a DHCP request with the following identifiers: – A Vendor Class Identifier (APC, by default) – A Client Identifier (the ATS’s MAC address value, by default) – A User Class Identifier (identification of the ATS’s application firmware, by default)
2. A properly configured DHCP server responds with a DHCP offer that includes all of the
settings the ATS needs for network communication. The DHCP offer also includes the Vendor Specific Information option (DHCP option 43). By default, the ATS will ignore DHCP offers that do not encapsulate the APC cookie in the Vendor Specific Information option using the following hexidecimal format:
Option 43 = 01 04 31 41 50 43
where
– the first byte ( – the second byte ( – the remaining bytes (
01) is the code
04) is the length 31 41 50 43) are the APC cookies
Refer to your DHCP server documentation to add code to the Vendor Specific Information option. To disable the APC cookie requirement, see “Local access to the control console” on page 55.
T o change the control console’s DHCP Cookie Is setting, use the Advanced option in the TCP/IP menu (see “Remote access to the control console” on page 55).
54 InfraStruXure Power Generation System
Configuring the ATS Network Management Interface

Local access to the control console

Use a local computer that connects to the ATS through the console port on the ATS monitoring unit to access the control console. If accessing the ATS on the local control console, you will not receive any information about the generator.
1. Select a serial port on your local computer, and disable any service using that port.
2. Connect the configuration cable (APC part # 940-0103) to the selected port on the computer and to the console port on the ATS monitoring unit.
®
3. Run a terminal program (such as HyperTerminal
) on your computer and configure the port for
9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control. Save the changes.
4. Press
ENTER to display the User Name prompt.
5. Use apc for both the User Name and the Password.
6. See “Control console” on page 56 to finish the configuration.

Remote access to the control console

From any computer on the same subnet as the ATS, you can use ARP and Ping to assign the ATS an IP address, and then Telnet to access that ATS’s control console for configuring its TCP/IP settings.
After an ATS has its IP address configured, you can use Telnet, without first using ARP and Ping, to access that ATS.
Note
1. Use ARP to define an IP address for the ATS, and use the ATS’s MAC address in the ARP command. For example, to define an IP address of 156.205.14.141 for an ATS that has a MAC address of 00 c0 b7 63 9f 67, use one of the following commands:
– Windows command format:
arp -s 156.205.14.141 00-c0-b7-63-9f-67
– LINUX command format:
arp -s 156.205.14.141 00:c0:b7:63:9f:67
For the MAC address, look on the Quality Assurance slip included with the ATS.
See also
InfraStruXure Power Generation System 55
Configuring the ATS Network Management Interface
2. Use Ping with a size of 113 bytes to assign the IP address defined by the ARP command. For the IP address defined in step 1, use one of the following Ping commands:
– Windows command format:
ping 156.205.14.141 -l 113
– LINUX command format:
ping 156.205.14.141 -s 113
3. Use Telnet to access the ATS at its newly assigned IP address. For example:
telnet 156.205.14.141
4. Use apc for both the User Name and the Password.
5. See “Control console” on this page to finish the configuration.

Control console

After logging on at the control console, as described in “Local access to the control console” on page 55 or “Remote access to the control console” on page 55, proceed as follows:
1. Choose Network from the Control Console menu.
2. Choose TCP/IP
from the Network menu.
3. If you are not using a BOOTP or DHCP server to configure the TCP/IP settings, select the Boot Mode menu. Select Manual boot mode, and then press
ESC to return to the TCP/IP menu
(changes will take effect when you log out).
4. Set the System
5. Press
CTRL-C to exit to the Control Console menu.
IP, Subnet Mask, and Default Gateway address values.
6. Log out (option 4 in the Control Console menu).
If you disconnected a cable during the procedure described in “Local access to the control console” on page 55, reconnect that cable and restart the associated service.
Note
56 InfraStruXure Power Generation System

How to Access the ATS Network Management Interface

Use the procedures in this section to access the ATS from the public LAN. If you want to access the ATS through the APC LAN, refer to the InfraStruXure Manager ’s
Note

Web int erface

You can use Microsoft® Internet Explorer 5.0 (and higher) or Netscape® 4.0.8 (and higher, except Netscape 6.x) as your browser to access the ATS through its Web interface. Other commonly available browsers may also work, though they have not been fully tested by APC.
When utilizing the Web browser to configure ATS options or to view the event log, use either of the following:
• The HTTP protocol (enabled by default), which provides authentication by user name and
Installation and Quick-Start Manual.
password (but with no encryption).
• The more secure HTTPS protocol, which provides extra security through Secure Socket Layer (SSL) to encrypt user names, passwords, and data being transmitted. It also provides authentication of Network Management Cards by means of digital certificates.
To access the Web interface and configure the security of your device on the network:
1. Identify the ATS by its IP address or DNS name (if configured).
2. Enter the user name and password (the defaults are apc and apc for an Administrator, and device and apc for a Device Manager).
3. Select and configure the type of security you want (this option is available only for Administrators).
Refer to “Security” in the InfraStruXure Power Generation System’s on-line Network Management User’ s Guide for information about choosing and setting up your network security. Use the Web/SSL option of the Network menu to enable
See also
or disable the HTTP or HTTPS protocols.
InfraStruXure Power Generation System 57
How to Access the ATS Network Management Interface

Teln et a nd S SH

You can access the control console through Telnet or Secure SHell (SSH), depending on which is enabled (an Administrator can enable these access methods through the Telnet/SSH option of the Network menu). By default, Telnet is enabled. Enabling SSH automatically disables Telnet.
Telnet for basic access. Telnet provides the basic security of authentication by user name and
password, but not the high-security benefits of encryption. To use Telnet to access an ATS’s control console from any computer on the same subnet:
1. At a command prompt, use the following command line, and then press
telnet address
ENTER:
For address, use the ATS’s IP address or DNS name (if configured).
2. Enter the user name and password (the defaults are apc and apc for an Administrator, and device and apc for a Device Manager).
SSH for high-security access. If choosing the high security of SSL for the Web interface, use
Secure SHell (SSH) to access the control console. SSH encrypts user names, passwords, and transmitted data.
The interface, user accounts, and user access rights are the same when accessing the control console through either SSH or T elnet. In order to use SSH, you must have an SSH client prog ram installed on your computer and SSH must be properly configured.
Refer to the InfraStruXure Power Generation System’s on-line Network Management User’s Guide for more information about configuring and using SSH.
See also

SNMP

After adding the PowerNet MIB to a standard SNMP MIB browser, you can use that browser for SNMP access to the ATS. The default read community name is public; the default read/write community name is private.
If you enable SSL and SSH for their high-security authentication and encryption, disable SNMP. Allowing SNMP access to the ATS compromises the high security implemented by choosing SSL and SSH. To disable SNMP, you must be an
Note
58 InfraStruXure Power Generation System
Administrator; use the SNMP option from the Network menu.
How to Access the ATS Network Management Interface

FTP a nd SCP

You can use FTP (enabled by default) or Secure CoPy (SCP) to transfer new firmware to the ATS, or to access a copy of the ATS’s event logs. SCP provides the higher security of encrypted data transmission and is enabled automatically when you enable SSH.
If you enable SSL and SSH for their high-security authentication and encryption, disable FTP. Allowing file transfer to the ATS through FTP compromises the high
Note
security implemented by choosing SSL and SSH. To disable FTP, you must be an Administrator; use the FTP Server option from the Network menu.
To access the ATS through FTP or SCP, the default user name and password are apc and apc for an Administrator, and device and apc for a Device Manager . In the command line, use the IP address of the unit.
Refer to the InfraStruXure Power Generation System’s on-line Network Management User’s Guide to use FTP or SCP to retrieve log files from the ATS or to transfer
See also
firmware files to the ATS.
InfraStruXure Power Generation System 59

How to Recover From a Lost Network Management Interface Password

Disregard the procedure in this section if the APC InfraStruXure Manager is included with your system. Refer to the InfraStruXure Manager’s Installation and Quick-Start
Note
1. Select a serial port on your local computer, and disable any service using that port.
2. Connect the configuration cable (APC part # 940-0103) to the selected port on the computer and
3. Run a terminal program (such as HyperTerminal®) on your computer and configure the port as
Manual for information about recovering from a lost password.
to the console port on the
follows:
– 9600 bps – 8 data bits –no parity
ATS monitoring unit.
– 1 stop bit – no flow control
4. Press
5. Press the Reset button on the ATS monitoring unit. The Status LED will flash alternately
6. Press
7. From the Control Console menu, select System, then User Manager.
8. Select Administrator and then change the User Name and Password settings, both of which
ENTER, repeatedly if necessary, to display the User Name prompt. If you are unable to
display the User Name prompt, verify the following:
– The serial port is not in use by another application. – The terminal settings are correct as specified in step 3. – The correct cable is being used as specified in step 2.
orange and green. Press the Reset button on the ATS monitoring unit again while the LED is flashing to temporarily reset the user name and password to their defaults.
ENTER as many times as necessary to redisplay the User Name prompt, then use the
default apc for the user name and the password (if you take longer than 30 seconds to log on after the User Name prompt is redisplayed, you must repeat step 5 and log on again).
are now defined as apc.
9. Press
60 InfraStruXure Power Generation System
CTRL-C and log off before reconnecting any cable you may have disconnected, and before
restarting any service you may have disabled.

Customizing and Updating the ATS

How to Connect User Input Contacts and Relay Outputs to the ATS

Overview

The ATS can monitor external contact closure events. Possible applications include:
• Magnetic contact switches
• Window foil
• Tamper switches
• Heat detectors
• Water sensors
• Pressure sensors
• Building smoke and fire detection systems
You can set input contacts to cause alarm conditions based on their current state in relation to a user­defined normal state. Relay outputs can map internal alarms and events to outside devices (see “Contacts & Relays” on page 46 for information about setting up alarms).
Make contact closure connections (NO or NC) at the user interface circuit board located on the user
USER INTERFACE
© 2001 APC
MADE IN USA
connection plate. You can make eight connections—
+
four input contacts and four relay outputs. The user
1 234
Contact Inp uts
Contact Output s
EPO 24V
ATS EN
AC/DC
EPO
Contact
ATS 1
ATS 0
ATS 2
connection plate is on the roof of the ATS enclosure.
The terminal block on the user interface board accepts wire sizes from 12 to 30 AWG or 2.5 to 0.2 mm
Note
2
.
You can make these connections from inside the enclosure, or you can remove the user connection plate from the ATS to make the connections. A Phillips or standard screwdriver is needed to loosen the two captive screws. Use the knockout in this plate to route cables to the user interface board. If you decide to remove the plate, make sure not to disturb the existing connections.
InfraStruXure Power Generation System 61
How to Connect User Input Contacts and Relay Outputs to the ATS

How to connect contacts to the user interface board

To connect and monitor your contacts:
1. Choose one or more terminals on the user interface board for connecting contacts. The user interface board is connected to the User/EPO port on the ATS monitoring unit.
2. From the ATS display interface: a. Press b. Select Config from the top-level menu screen and press
c. Select Contacts & Relays from the Config menu screen and press
ESC or ENTER to go to the top-level menu screen.
Load-Meter ATS/Voltage Generator Testing
System/Network Contacts & Relays Sub-Feed Config. Electrical Config.
Stats Alarms Config Help
ENTER.
ENTER.
d. Select the type of contact you are connecting: Contact Inputs or Relay Outputs.
Contact Inputs Relay Outputs Output Relay Map
You will be prompted for your password to configure these items.
Note
e. Press the Up or Down arrow to select the appropriate
contact number and press
f. Press the Down arrow to enter a unique Name for the
contact and to configure the Normal state of the contact
ENTER.
Contact In 02 of 04 Name User Contact 4 Normal: Open Status: Open
(Open or Closed). The default Normal state is Open.
ENTER to select the item you wish to configure.
Press
g. Connect contact wires (300 V-rated cabling required) to the terminal block on the user
interface board. You will need a 2.5-mm standard screwdriver.
h. Run the wires out the roof of the ATS to your contact’s location.
Ensure the wires are pr operly retained and kept away fr om high-voltage wires and breakers.
Caution
62 InfraStruXure Power Generation System

How to Connect an EPO Switch to the ATS

If you do not connect an EPO switch to the ATS, be sure to set the Arm/Test rocker on the ATS monitoring unit to Test.
Note

Overview

Connecting the switch. The Emergency Power Off
USER INTERFACE
(EPO) switch connects to the user interface board on the
© 2001 APC
MADE IN USA
user connection plate. The user connection plate is located on the roof of the ATS. Connect an EPO switch
1 234
to the user interface board (shown at right) using one of
Contact Inp uts
the following connections:
• Contact closure (Recommended!)
•24 VAC
• 24 VDC
The terminal block on the user interface board accepts
2
wire sizes from 12 to 30 AWG or 2.5 to 0.2 mm
.
Note
You can make this connection from inside the enclosure, or you can remove the user connection plate from the ATS to make the connection. A Phillips or standard screwdriver is needed to loosen the two captive screws. Use the knockout in this plate to route cables to the user interface board. If you decide to remove the plate, make sure not to disturb the existing connections.
Contact Output s
+
EPO 24V
ATS EN
AC/DC
EPO
Contact
ATS 1
ATS 0
ATS 2
Configuring and testing. The configuring and testing of the
885-2288
switch is performed through the EPO interface on the ATS
EPO
TRIPPED
ARMED
TEST
NC
NO
monitoring unit. The figure on the right shows the monitoring unit and the location of the EPO LEDs and DIP switches.
APC offers an optional InfraStruXure EPO System (EPW9). Contact your APC sales representative, or
Note
visit the APC Web site (www.apc.com) for more information.
InfraStruXure Power Generation System 63
USER / EPO CONTACTSTO UPS
12345678910111213
LINK RX/TX
NETWORK
STATUS
RESET
TRIPPED
ARMED
EPO
TEST
NO NC
25 24 23 22 21 20 19 18 17 16 15 14
10=G RN
100=ORN
DISPLAY
POWER
RS-232
9600-8 -N-1
CONSOLE PORT
How to Connect an EPO Switch to the ATS
Ext

Connect an EPO switch to the user interface board and test the switch

1. Connect the switch to the EPO connection terminals on the user interface board. Read the label next to the terminal block to determine which terminals correspond to your signal type:
Contact Closure—Normally Open
USER INTERFACE
© 2001 APC
MADE IN USA
External set of Normally Open Voltage-free Contacts
– +
1 234
Contact Inp uts
Contact Output s
EPO 24V
ATS EN
AC/DC
EPO
Contact
ATS 1
ATS 0
ATS 2
– Contact Closure—Normally Closed
USER INTERFACE
© 2001 APC
MADE IN USA
1 234
Contact Inp uts
Contact Output s
– +
EPO 24V
ATS EN
AC/DC
EPO
Contact
ATS 1
ATS 0
ATS 2
External set of Normally Open Voltage-free Contacts
– 24VAC/VDC—Normally Open
ernal set of
Normally Open Voltage-free Contacts
USER INTERFACE
© 2001 APC
MADE IN USA
24 VAC or 24 VDC Power Supply
– +
1 234
Contact Inpu ts
Contact Output s
EPO 24V
ATS EN
AC/DC
EPO
Contact
ATS 1
ATS 0
ATS 2
2. Verify that the EPO DIP switches on the ATS monitoring unit are configured properly for your signal type. The labels above the switches and the figure below show the correct settings for both the Normally Open (NO) and Normally Closed (NC) configurations.
Location of switches
on ATS monitoring unit
64 InfraStruXure Power Generation System
How to Connect an EPO Switch to the ATS
3. Test the EPO switch to ensure it is wired properly and working correctly:
a. Place the Arm/Test rocker switch on the ATS monitoring unit in the Test position. The EPO
state LEDs should be off and the ATS display interface should show the following alarm (in addition to any other active alarms):
Active Alarm xxofxx EPO Ready To Test
b. Engage the EPO switch (if your switch is momentary, engage while one person is watching
the EPO state LEDs and another is at the EPO switch).
c. Observe the EPO LEDs. If the switch is wired properly and working correctly, both of the
EPO state LEDs should light red when the switch is engaged.
d. If the test was successful, return the Arm/Test rocker switch to the Arm position. The ATS
display interface will clear the EPO test mode alarm. If the test was not successful, refer to the following troubleshooting chart:
Problem Action
Neither state LED was lit red when the EPO switch was engaged.
• Check the wiring to your EPO switch.
• Check to make sure the EPO DIP switch configuration is correct for your switch (NO or NC). See step 2 on the previous page for proper configuration instructions.
Only one of the state LEDs was lit red when the EPO switch was engaged.
• Check to make sure the EPO DIP switch configuration is correct for your switch (NO or NC) and retest. See step 2 on the previous page for proper configuration instructions.
• If the switch is configured correctly and both LEDs did not light red after retesting, contact APC customer support (see the back cover of this manual).
e. Repeat this test for each EPO switch installed.
4. After testing is completed, ensure the Arm/Test rocker switch is in the Arm position on the
ATS monitoring unit.
InfraStruXure Power Generation System 65
How to Connect an EPO Switch to the ATS

Safety warnings

Hazardous voltage from the branch circuit must be isolated from the 24 VAC, 24 VDC, and contact closure terminals. 24 VAC and 24 VDC are considered Class 2 circuits as defined in Article 725 of the National Electrical Code (NFPA 70) and Section 16 of the Canadian Electrical Code (C22.1).
A Class 2 circuit is a source having limited voltage and energy capacity:
a. If an Inherently Limited Power Source, then voltage and energy are limited to less than
30 VAC, 30 VDC, and 8 A.
b. If not an Inherently Limited Power Source, then voltage and ener gy are limited to less than
30 VAC, 60 VDC, and 250 VA, while current is limited to 1000/Vmax. The fuse is limited to 5A if less than 20 VAC or 20 VDC; or 100/V maximum if less than 30 VAC or 60 VDC.
If using a 24 VAC, 24 VDC, or contact closure connection to the EPO, include one of the following UL-listed wire types:
• CL2 Class 2 cable for general purpose use
• CL2P Plenum cable for use in ducts, plenums, and other environmental air space
• CL2R Riser cable for use in a vertical-run shaft from floor to floor
• CL2X Limited Use cable for usage in dwellings or in a raceway
• For installations in Canada, the cable should be CSA Certified, type ELC (extra-low-voltage control cable).
If not using a CL2 cable, route the EPO wiring in conduit that does not contain any branch circuit wiring.
66 InfraStruXure Power Generation System

How to Allow Easy Access to the ATS Display Interface

The ATS comes with a Plexiglas cover plate that can be installed in the front door to protect against access to the display interface. When installed, access to the interface requires opening the front door.
To attach the cover plate, peel off the paper strips on the top and bottom of the plate to expose the adhesive. Press the plate into place from inside the door.
To remove the cover plate and gain ready access to the display interface, open the front door and press firmly on the plate from outside the door as shown below. You may need to use a screwdriver or other flat tool to pry the plate away from the inside of the door.
InfraStruXure Power Generation System 67

How to Add Sub-Feed Output Distribution Circuit Breakers to the ATS

The ATS panel bus must be completely de-energized before adding breakers!
Electrical
Hazard

Output distribution circuit breakers available from APC

Part Number Description Height on Panel
PG1P15AT1B 15A, single-pole breaker, T1 frame 1.00in/25.4mm PG1P20AT1B 20A, single-pole breaker, T1 frame 1.00in/25.4mm PG1P25AT1B 25A, single-pole breaker, T1 frame 1.00in/25.4mm PG1P30AT1B 30A, single-pole breaker, T1 frame 1.00in/25.4mm PG3P15AT1B 15A, three-pole breaker, T1 frame 3.00 in/76.2mm PG3P20AT1B 20A, three-pole breaker, T1 frame 3.00 in/76.2mm PG3P25AT1B 25A, three-pole breaker, T1 frame 3.00 in/76.2mm PG3P30AT1B 30A, three-pole breaker, T1 frame 3.00 in/76.2mm PG3P40AT1B 40A, three-pole breaker, T1 frame 3.00 in/76.2mm PG3P50AT1B 50A, three-pole breaker, T1 frame 3.00 in/76.2mm PG3P60AT1B 60A, three-pole breaker, T1 frame 3.00 in/76.2mm PG3P70AT1B 70A, three-pole breaker, T1 frame 3.00 in/76.2mm PG3P80AT1B 80A, three-pole breaker, T1 frame 3.00 in/76.2mm PG3P90AT1B 90A, three-pole breaker, T1 frame 3.00 in/76.2mm PG3P100AT1B 100A, three-pole breaker, T1 frame 3.00in/76.2mm PG3P125AT3B 125A, three-pole breaker, T3 frame 4 .13in/104.9mm PG3P150AT3B 150A, three-pole breaker, T3 frame 4 .13in/104.9mm PG3P175AT3B 175A, three-pole breaker, T3 frame 4 .13in/104.9mm PG3P200AT3B 200A, three-pole breaker, T3 frame 4 .13in/104.9mm PG3P225AT3B 225A, three-pole breaker, T3 frame 4 .13in/104.9mm
Circuit breaker adapter modules are required when mounting breakers onto the panel bus in the ATS. Refer to “Circuit breaker adapter modules available from APC” on page 69.
Note
68 InfraStruXure Power Generation System
How to Add Sub-Feed Output Distribution Circuit Breakers to the ATS

Circuit breaker adapter modules available from APC

Adapter modules are required when mounting breakers onto the panel bus in the ATS. Each adapter module can accommodate two breakers.
APC’s adapter modules are sized to fit all of the circuit breaker types described on the previous page: T1 single-pole breakers, T1 three-pole breakers, and T3 three-pole breakers. Two types of T1 single­pole adapters are offered: one that plugs into either L1 or L3, and one that plugs into L2. When adding single-pole breakers, try to keep the loads balanced among L1, L2, and L3.
PGT11PADAP T1 single-pole adapter module for plugging into L1 or L3 PGT1L21PADAP T1 single-pole adapter module for plugging into L2 PGT13PADAP T1 three-pole adapter module PGT33PADAP T3 three-pole adapter module

Determine the configuration of the panel

Before installing circuit breakers on the ATS panel bus, be sure enough space is available on the bus. Use the information below and in the next section to determine configurations.
ABB T1 single-pole breakers
T1 single-pole adapter
module
ABB T1 three-pole breakers
T1 three-pole adapter
module
Amount of space available
on the 250A ATS
Distribution Panel Bus
ABB T3 three-pole breakers
T3 three-pole adapter
module
InfraStruXure Power Generation System 69
How to Add Sub-Feed Output Distribution Circuit Brea kers to th e ATS

Allowed circuit breaker combinations

The panel bus on your ATS allows a variety of circuit breaker combinations. Use the following information as a guide in determining your circuit breaker combination.
Combination #1.
Type of Breaker # of Modules # of Breakers Space Occupied Space Remaining
T3 3-pole 2 4 8.26 in (209.8 mm) 1.94 in (49.6 mm) T1 3-pole 0 0 0 1.94 in (49.6 mm) T1 1-pole 1 2 1.00 in (25.4 mm) 0.94 in (24.2 mm)
Combination #2.
Type of Breaker # of Modules # of Breakers Space Occupied Space Remaining
T3 3-pole 1 2 4.12 in (104.9 mm) 6.08 in (154.5 mm) T1 3-pole 2 4 6.00 in (152.4 mm) 0.08 in (2.1 mm) T1 1-pole 0 0 0 0.08 in (2.1 mm)
Combination #3.
Type of Breaker # of Modules # of Breakers Space Occupied Space Remaining
T3 3-pole 0 0 0 10.2 in (259.4 mm) T1 3-pole 3 6 9.00 in (228.6 mm) 1.2 in (30.8 mm) T1 1-pole 1 2 1.00 in (2.54 mm) 0.2 in (5.4 mm)
Combination #4.
Type of Breaker # of Modules # of Breakers Space Occupied Space Remaining
T3 3-pole 0 0 0 10.2 in (259.4 mm) T1 3-pole 3 6 9.00 in (228.6 mm) 1.2 in (30.8 mm) T1 1-pole 0 0 0 1.2 in (30.8 mm)
Combination #5.
Type of Breaker # of Modules # of Breakers Space Occupied Space Remaining
T3 3-pole 0 0 0 10.2 in (259.4 mm) T1 3-pole 2 4 6.00 in (152.4 mm) 4.2 in (107.0 mm) T1 1-pole 4 8 4.00 in (101.6 mm) 0.2 in (5.4 mm)
70 InfraStruXure Power Generation System
How to Add Sub-Feed Output Distribution Circuit Breakers to the ATS
Combination #6.
Type of Breaker # of Modules # of Breakers Space Occupied Space Remaining
T3 3-pole 0 0 0 10.2 in (259.4 mm) T1 3-pole 1 2 3.00 in (76.2 mm) 7.2 in (183.2 mm) T1 1-pole 6 12 6.00 in (152.4 mm) 1.2 in (30.8 mm)
Combination #7.
Type of Breaker # of Modules # of Breakers Space Occupied Space Remaining
T3 3-pole 0 0 0 10.2 in (259.4 mm) T1 3-pole 1 2 3.00 in (76.2 mm) 7.2 in (183.2 mm) T1 1-pole 7 14 7.00 in (177.8 mm) 0.2 in (5.4 mm)
Combination #8.
Type of Breaker # of Modules # of Breakers Space Occupied Space Remaining
T3 3-pole 0 0 0 10.2 in (259.4 mm) T1 3-pole 0 0 0 10.2 in (259.4 mm) T1 1-pole 8 16 8.00 in (203.2 mm) 2.2 in (26.2 mm)
Combination #9.
Type of Breaker # of Modules # of Breakers Space Occupied Space Remaining
T3 3-pole 0 0 0 10.2 in (259.4 mm) T1 3-pole 0 0 0 10.2 in (259.4 mm) T1 1-pole 9 18 9.00 in (228.6 mm) 1.2 in (30.8 mm)
Combination #10.
Type of Breaker # of Modules # of Breakers Space Occupied Space Remaining
T3 3-pole 0 0 0 10.2 in (259.4 mm) T1 3-pole 0 0 0 10.2 in (259.4 mm) T1 1-pole 10 20 10.00 in (254.0 mm) 0.2 in (5.4 mm)
InfraStruXure Power Generation System 71
How to Add Sub-Feed Output Distribution Circuit Brea kers to th e ATS

Preparing the breakers for installation

Certain breakers require preparation before installation onto their adapter module. Preparation procedures are described below. The identified parts are included with your circuit breaker kit.
ABB T1 single-pole breaker
Input
Output
Bracket Adapter
Slide the bracket adapter onto the output side of the T1 single-pole breaker. The bracket adapter is used to attach the breaker to its adapter module.
ABB T1 three-pole breaker
Input
Output
The T1 three-pole breaker requires no additional preparation.
\
ABB T3 three-pole breaker
Square Nut Retainer
Input
Saddle Lug
Retainer
Saddle Lug
M8 Washer
M8 Bolt
M8 Square Nut
Output
The input and output sides of the T3 three-pole breaker require preparation : On the input side, follow these steps for each of the three pole positions:
1. Place an M8 square nut into a square nut retainer, then insert the retainer into the pole position.
2. Slide an M8 washer onto an M8 bolt, then insert the bolt into the pole position by loosely attaching it to the M8 square nut that was installed in the previous step.
On the output side, follow these steps for each of the three pole positions:
1. Slide a saddle lug into the pole position. You may need to loosen the bolt in the lug.
2. Insert a saddle lug retainer into the pole position.
72 InfraStruXure Power Generation System
How to Add Sub-Feed Output Distribution Circuit Breakers to the ATS

Parts and tools needed for installation procedures

All assembly parts needed for installation procedures are included with the circuit breaker kits.
Tools required
Phillips screwdriver
Allen wrench
T25 Torx driver
T1 three-pole breaker assembly
T1 three-pole
adapter module
T1 three-pole breakers
M4×70 screws and washers
Breaker brackets
M6 x 12 Torx screws
M4×70 screws and washers
T1 single-pole breaker assembly
T1 single-pole
adapter module
T1 single-pole breakers
M3×75 screws, washers and retainers
Breaker brackets
M6×12 Torx screws
M4×15 screws and washers
T3 three-pole breaker assembly
T3 three-pole
adapter module
T3 three-pole breakers
M4×70 screws and washers
Breaker brackets
M6 x 12 Torx screws
M4×70 screws and washers
InfraStruXure Power Generation System 73
How to Add Sub-Feed Output Distribution Circuit Brea kers to th e ATS

Installing breakers on the ATS panel bus

Use the following procedure to install a T1 three-pole breaker assembly on a 250 A ATS panel bus. The steps are identical for installing the T1 single-pole and T3 three-pole breakers.
1. Attach the adapter module to the ATS panel bus wrench to turn the module locks
().
(), and secure it in place using an Allen
2. Snap the circuit breakers onto the adapter module’s bus screwdriver to tighten an M4×70 screw
().
(). Lock in place using a Phillips
3. Attach the breaker brackets to slots in the panel board frame driver to tighten an M6×12 Torx screw using a Phillips screwdriver to tighten an M4×70 screw
74 InfraStruXure Power Generation System
(). Attach each breaker to its appropriate bracket
().
(). Secure using a T25 Torx
How to Add Sub-Feed Output Distribution Circuit Breakers to the ATS
4. Install dividers in the circuit breakers by sliding the dividers, one at a time, into the notches in the breaker.
For more information about the Divider Kits for ATS circuit breakers, refer to the Installation Instructions (990-2245) provided with your Divider Kit.
See also
InfraStruXure Power Generation System 75

How to Download Firmware Updates

The InfraStruXure ATS with Power Distribution requires the downloading of multiple files to update the firmware. Be sure to select all relevant files from the APC Web site for downloading, and repeat the following procedure each time you download an individual firmware file.
To download a firmware upgrade to your ATS, refer to “File Transfers” in the InfraStruXure Power Generation System’s on-line Network Management Interface
See also

From a local computer

1. Select a serial port on your local computer, and disable any service using that port.
2. Connect the configuration cable (APC part # 940-0103) to the selected port on the computer and
User’s Guide on the Utility CD.
to the console port on the ATS monitoring unit.
3. Run a terminal program (such as HyperT erminal
®
) on your computer and configure the port for
9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control. Save the changes.
4. Press
ENTER twice to display the User Name prompt.
5. Enter your User Name and Password (apc is the default Administrator user name and
password) and press
ENTER.
6. From the Control Console menu, select System, then Tools, then File Transfer, then XMODEM.
7. The system will prompt you with press
ENTER.
Perform Transfer with XMODEM -CRC? Type Yes and
8. The system will then prompt you to choose a transfer rate and to change your terminal settings to match the transfer rate. Press
ENTER to set the ATS to accept the download.
9. In the terminal program, send the file using the XMODEM protocol. Upon completion of the transfer, the console will prompt you to restore the baud rate to normal.
Do not interrupt the download.
Caution
The ATS network management interface will reboot when the download is complete.
76 InfraStruXure Power Generation System

Specifications

Smart Distribution Panel with ATS

Electrical
Current Rating 250 A Voltage Class 480 VAC Voltage Available 208/120 Wye, 480 Delta, 480 Wye Maximum Power 208 kW Frequency 50/60 Hz Nominal, ±5 Hz Interrupting Rating 35 kAIC ATS Main Protection Magnetic fixed ATS Switched Poles Three EPO connection Dry contact and 24 VDC EPO operation Disconnects all outputs Output Distribution MCCB ABB Tmax T1 and T3 up to 225 A Output Poles Three Output Breaker Max Ampacity 225 A Length of Breaker Bus Section 10.2 in/260 mm Number of 100A Breaker Frames Six T1 3-Pole Number of 225A Breaker Frames Four T3 3-Pole Output Distribution Protection Type Thermal Magnetic
Physical
Dimensions
Height 75.0 in/1905 mm Width 28.0 in/711 mm
Depth 14.5 in/368 mm Weight 482 lb/218 kg Shipping Dimensions
Height 81.0 in/2057 mm
Width 34.0 in/864 mm
Depth 34.0 in/864 mm
Maximum Shipping Weight 482 lb/219 kg Cooling Natural convection Enclosure NEMA 1 with drip protection; Raven black Access Control Key-locked door and fastener-locked deadfront, user-removable
cover for user keypad/display and password
InfraStruXure Power Generation System 77
Smart Distribution Panel with ATS
Installation and Wiring 208V 480V
Maximum Utility Input Over-current
225 A UL-listed Breaker (50kAIC)
Protection Required Utility Input Connection Type 4W + G 3W + G or 4W+G
Size of upstream utility circuit breaker 250 A 200 A Recommended wire size if 30°C Recommended wire size if 40°C Recommended protective earth size
† †
4/0 AWG 3/0 AWG
300 kcmil 3/0 AWG
4 AWG 6 AWG
Generator Input Connection Type 4W + G 3W + G or 4W+G
Output power of generator 80 kW 125 kW Size of generator output breaker 250 A 200 A Recommended wire size if 30°C Recommended wire size if 40°C Recommended protective earth size
Supply to Generator Heater and Charger
Recommended wire size
Voltage
† †
Hard-wire from transformer in ATS to double duplex NEMA 5-20 outlet box on generator
Two 12 AWG stranded copper 120 VAC
4/0 AWG 3/0 AWG
300 kcmil 3/0 AWG
4 AWG 6 AWG
Installation type Floorstanding secured to wall (concrete screws included) Input/Output Cabling Top and bottom routing Rear Access Required No NEC Access Clearances • Three feet to an insulated surface
• Three feet to grounded parts, including concrete walls, if 208/1 20 V
• 3 1/2 feet to grounded parts, including concrete wal ls, if 480/277 V
• Three feet to other live parts, if 208/120 V
• Four feet to other live parts, if 480/277 V
Always follow the National Electrical Code (NFPA 75) or the Canadian Electrical Code (CSA C22.1-02) and local codes when installing the InfraStruXure Power Generation System. The AC Power Input wire sizes provided in this document are recommendations only. The ATS is provided with a panel board to supply power to multiple loads. Since loading could increase after the product’s initial installation, the AC Power Input wires were selected for the maximum current that can be delivered by the panel board. If the ATS is purchased to supply a calculated load rated less than the panel board, and the load will never increase, smaller wires can be used if the requirements specified in the NEC, the CEC, and local codes are followed.
††
Wire sizes to loads shall be in accordance with the ratings of the circuit breakers selected to power the loads.
78 InfraStruXure Power Generation System
Smart Distribution Panel with ATS
Environmental
Operating Temperature Range 23 to 104°F/–5 to 40°C ; The average temperature over a
24-hour period should not exceed 95°F/35°C. Operating Relative Humidity 5 to 95%, non condensing Operating Elevation 0 to 6,562 ft/0 to 2000 m Storage Temperature Range –13 to 131°F/–25 to 55°C; The average temperature over a 24-
hour period should not exceed 158°F/70°C Storage Relative Humidity 5 to 95%, non condensing Storage Elevation 0 to 49,200 ft/0 to 15000 m
Compliance
Safety UL & cUL Listed to UL 67 (UL1008 for ATS) Emissions FCC Verified Class A, Per standard FCC 47 CFR Part 15 Electrostatic Discharge (ESD) IEC 61000-4-2 Electrical Fast Transients (EFT) IEC 61000-4-4 Surge Transient IEC 61000-4-5 Continuous Electromagnetic Susceptibility IEC 61000-4-3
InfraStruXure Power Generation System 79

Appendix: Custom Installations

If Source 2 is a Second Utility

Differences in your system from information presented in this manual

The ATS was designed for operation with an APC InfraStruXure generator, and this manual assumes that Source 2 is an APC InfraStruXure generator. If using a secondary utility instead of a generator, almost all references to the “generator” should be considered references to your second utility as well. However, the following sections will not apply to your system and should be disregarded:
• “Generator start sequence” on page 7
• “Generator cool-down” on page 7
• “Fuel monitoring/runtime calculation” on page 9
• “Communication converter,” (item 4) on page 13
• “Resetting automatic operation on the generator” on page 20
• “Generator” on page 37
• “Fuel Alarm Limits” on page 44
If your installation includes a secondary utility source, the APC Field Service Engineer performing your start-up will configure your ATS to operate with two utility sources.
Note
InfraStruXure Power Generation System 81

If Source 2 is a Generator that is Not an APC InfraStruXure Generator

Differences in your system from information presented in this manual

The ATS was designed for operation with an APC InfraStruXure generator, and this manual assumes that Source 2 is an APC InfraStruXure generator. If using a non-APC generator instead of an APC generator, almost all references to the “generator” will still be applicable. However, non-APC generators will generally function differently than APC generators. Therefore, the following sections will not apply to your system and should be disregarded:
• “Generator start sequence” on page 7
• “Generator cool-down” on page 7
• “Fuel monitoring/runtime calculation” on page 9
• “Communication converter,” (item 4) on page 13
• “Resetting automatic operation on the generator” on page 20
• “Generator” on page 37
• “Fuel Alarm Limits” on page 44
If your installation includes a non-APC generator, the APC Field Service Engineer performing your start-up will configure your ATS to operate with this generator.
Note
82 InfraStruXure Power Generation System
Index
A
Access panel, on panel board, 13
14 Accessing the display interface Agency approvals Alarm beeper Alarm LED Alarm/event log
, 79
, 44
, 29
, 43
, 67
Alarms
clearing latched configuring limits
viewing active Alarms screen Allow closed setting Arm/Test rocker switch Armed LED ATS product description ATS/Voltage screen Automatic operation
loss of
, 21
, 44
, 4344
, 43
, 4344
, 8
, 17
, 17
, 1114
, 3336
, 1921
placing the generator system in
to
, 19
resetting on the ATS
generator
, 20
Automatic operation control
panel
, 12, 16
Automatic operation switch
, 16
B
Bad line quality, 6 BOOTP configuration
, 53
Bottom access panel, location
of
, 11
Buttons (navigational/operational)
on display interface, 29
C
Check log LED, 29 Circuit board port Circuit breaker panel, determining
configuration of
, 17
, 69
Circuit breakers
, 6875
adapter modules, 69 available from APC
, 68
combinations of, 70 installing on the ATS panel
board
, 74
preparing for installation tools needed for installation
Closed transfers
, 8
, 72
, 73
Communication converter, location
of
, 13
Compatible ATS equipment Compliance
, 79
Components, of the ATS Config screen
, 4547
, 5
, 1518
Configuration
electrical of ATS communication of contacts and relays of system and network of the EPO switch
Console port
, 47
, 4960
, 46
, 45
, 63
, 17
Control console, local and remote
access to Coolant temperature limit Cool-down period, of generator Crank cycles Crank setting Crank time Custom installations Customizing the ATS
, 5556
, 7
, 7
, 7
, 7
, 7
, 81-82
, 6175
D
Dead front, description, 12 Dead front source label DHCP configuration DIP switches
, 17
Display interface
location of
, 12
navigating through screens obtaining easy access to screens
, 3247
top-level screens
Display port
, 17
, 18
, 54
, 2947
, 31
, 67
, 30
E
Electrical configuration, 47 Electrical specifications Elevation, for operation Emergency manual operation
, 77
, 3
, 22
powering the load from the
generator
, 2324
returning to powering the load
from utility mains
, 2526
Emergency Power Off
Arm/Test rocker switch
, 17
connecting the switch to the
ATS
, 6366
contacts port, location of DIP switches safety warnings where connected
, 17
, 66
, 16
Emissions verifications Engine start test
, 39
Environment, for operation Environmental specifications EPO contacts port, location of
, 17
, 79
, 3
, 79
, 17
EPO. See Emergency Power Off. Equipment, compatible with the
ATS
, 5
Ethernet port, on user connection
plate
, 16
F
Factory defaults, resetting the, 47 Firmware updates, how to
download Front bezel label Front door, description
, 76
, 18
, 11
Front view
door closed door open
, 11
, 12
FTP, for transferring new firmware
to the ATS Fuel monitoring Fuel status, where displayed Fuse block, on panel board
, 59
, 9
, 37
, 13
G
Generator label, 18
InfraStruXure Power Generation System 83
Generator power, condition of, 34 Generator screen
, 3738
Generator status, where
displayed Generator, non-APC Get set on LED
, 37
, 82
, 29
H
Handle, on panel board, 13 Humidity, for operation
, 3
I
InfraStruXure manager
connecting and configuring overview
, 49
, 50
Input contacts
configuring connecting to the ATS
where connected Inspection warnings Installation specifications Installation warnings Interference, radio frequency IP configuration wizard
, 46
, 6162
, 16
, 3
, 78
, 3
, 87
, 52
K
Knockouts, location of, 11
L
Labels, on the ATS, 18 Latches, on dead front LCD, on display interface
, 12
, 29
LEDs
generator controller interface
on display interface
, 29
Lifetime statistics, where
displayed Line stable setting Load on LED Load-meter screen
, 37
, 6
, 29
, 32
M
Maintenance record, where
displayed Management options, for the
ATS
, 38
, 49
, 7
Manual operation
, 22
Manuals, accompanying this part
number
, i
Manufacturer data, for the
generator Manufacturer data, of the ATS Max sync time Min gen runtime setting
, 38
, 47
, 8
, 6
Monitoring unit
detailed description location of
, 13
Motorized switches
, 17
, 15
N
Navigation buttons, on display
interface
, 29
Network management interfaces
accessing
, 57
connecting and
configuring
overview
, 5156
, 49
Network port, on monitoring
unit
, 17
Not in automatic operation LED
, 16
O
Open transfers, 8 Open Xfer
configuring time
viewing statistics on Operating environment Operating lever key, for motorized
switches
Operating lever, on motorized
switches
Operating settings, for
generator
Operation
during a utility mains failure
of the ATS
of the power generation
system
, 35
, 8
, 42
, 3
, 15
, 15
, 38
, 6
, 1928
, 69
P
Panel board
installing circuit breakers left side right side
, 13
, 14
, 74
Password
changing for protected screens
, 45
, 31
lost management interface
password
Physical specifications
, 60
, 77
Power generation system,
overview
Power LED
, 5
, 17
Powering the load from the
generator
, 2324
Powering the load from utility
mains, how to return to
, 2526
Product description, of the
ATS
, 1114
R
Radio frequency interference, 87 Relay outputs
configuring connecting to the ATS where connected
, 46
, 6162
, 16
Reset button, on monitoring
unit
, 17
Resetting statistics Rest time, of the generator
, 42
, 7
Runtime status, where
displayed
, 37
S
S1 name, configuring the, 36 S1-utility
condition of
setting up transfer voltage S2 name, configuring the S2-generator, condition of Safety compliance Safety symbols used in this
manual
SCP, for transferring new firmware
to the ATS
Screens, on display interface
47
, 33
, 35
, 36
, 34
, 79
, 1
, 59
, 32
84 InfraStruXure Power Generation System
Selector switch, on motorized
switch
, 15
Service, obtaining
. See back cover
Single-pole label, 18 SNMP interface SNMP, for accessing the ATS
, 49
, 58
Source 1 control transformer,
location of
, 13
Source 1 current transformer,
location of
Source 1 fuse block, location of
, 14
, 13
Source 1 input switch, location
of
, 14
Source 1 lamp, location of
, 12
Source 1 motorized switch, location
of
, 12
Source 2
if it is a utility mains
connection
, 81
if it is not an APC ISX
generator
, 82
Source 2 control transformer,
location of
Source 2 fuse block, location of
, 14
, 14
Source 2 input switch, location
of
, 13
Source 2 lamp, location of
, 12
Source 2 motorized switch, location
of
, 12
Source label Specifications
, 18
, 77-79
SSH, for accessing the control
console Stats screen Sub-feed breakers, location of System ID menu System load test
, 58
, 42
, 12
, 47
, 39
T
TCP/IP configuration methods, 52 Telnet, for accessing the control
console Temperature, for operation Test log, how to view
, 58
, 3
, 39
Testing
configuring duration of how a test occurs
, 40
, 41
how to initiate or view a test of the EPO switch schedule
, 3, 40
Testing screen Three-pole breaker label
, 63
, 3941
, 18
Tools, for circuit breaker
installation
Total power off
, 73
, 3, 2728
Transfer blocking, configuring
conditions for Transfer setup Transfers, open and closed Trip test button Tripped LED
, 36
, 8
, 8
, 15
, 17
U
Updates, to this manual, i User connection plate
connecting the EPO switch detailed description location of
, 11
, 16
User contacts port, location of Utility power, condition of
, 33
W
Warnings, 23
for emergency manual
operation for Emergency Power Off for installation for motorized switches
Web interface Wheel extensions, on the panel
board Wire size, how to determine Wiring specifications Withdrawal prevention lock
, 22
, 66
, 3
, 15
, 49, 57
, 13
, 2
, 78
, 15
, 39
, 64
, 17
InfraStruXure Power Generation System 85
Radio Frequency Interference
Changes or modifications to this unit which are not expressly approved by the party responsible for compliance could void
Caution
the user’s authority to operate this equipment.
USA—FCC
Canada—ICES
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with this user manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference. The user will bear sole responsibility for correcting such interference.
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
APC Worldwide Customer Support
Customer support for this or any other APC product is available at no charge in any of the following ways:
• Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests.
www.apc.com (Corporate Headquarters)
Connect to localized APC Web sites for specific countries, each of which provides customer support information.
www.apc.com/support/
Global support searching APC Knowledge Base and using e-support.
• Contact an APC Customer Support center by telephone or e-mail. – Regional centers
Direct InfraStruXure Customer Support Line APC headquarters U.S., Canada Latin America
Europe, Middle East, Africa (353)(91)702000 (Ireland) Japan (0) 35434-2021 Australia, New Zealand, South Pacific area
(1)(877)537-0607 (toll free) (1)(800)800-4272 (toll free) (1)(401)789-5735 (USA)
(61) (2) 9955 9366 (Australia)
– Local, country-specific centers: go to www.apc.com/support/contact for contact information.
Contact the
APC representative or other distributor from whom you purchased your APC product for
information on how to obtain local customer support.
Entire contents copyright 2007 American Power Conversion Corporation. All rights reserved.
Reproduction in whole or in part without permission is prohibited. APC, the APC logo, and InfraStruXure
are trademarks of American Power Conversion Corporation. All other trademarks, product names, and
corporate names are the property of their respective owners and are used for informational purposes only.
07/2007990-1845C
*990-1845C*
Loading...