Thank you for chosing an APC Silcon UPS. Please read this Installation Guide thoroughly prior to
installing the system. It provides important information on safe and efficient installation.
The installation and use of this product must comply with national, federal, state, municipal and
local codes.
Safety Symbols used in this manual
WARNING! Indicates a hazard which, if not avoided, could result in injury or death.
CAUTION! Indicates a hazard which, if not avoided, could result in damage to
the product or other property.
NOTICE!
WARNING!
This UPS unit contains hazardous AC and DC voltages. Only qualified electricians should install the
UPS, AC line and external batteries, and must be familiar with batteries and battery installation.
Before installing, maintaining or servicing the UPS, shut off the UPS and disconnect all sources of AC
and DC power.
As the UPS has no built-in disconnection devices to switch off external AC and DC input power, ensure
that disconnection devices are provided as separate parts in connection with the installation!
The installer must provide each external disconnecting device for this UPS system with labels with the
following text:
“Isolate the Uninterruptible Power Supply (UPS) as instructed in this guide before working on circuit”.
AC and/or DC voltage will always involve a potential risk of AC voltage at UPS output generated from
either batteries or utility. To avoid equipment damage or personal injury, always assume that there
may be voltage at UPS output.
This system is equipped with an auto-start function. If activated the system may start without warning.
Refer to “Programming” section for information on de-activation.
TEST BEFORE YOU TOUCH!
To reduce the risk of fire or electric shocks, install the UPS and external batteries in a temperature and
humidity controlled indoor area, free of conductive contaminants.
UPS batteries are high-current sources. Shorting battery terminals or DC terminals, DC busbars can
cause severe arcing, equipment damage and injury. A short circuit can cause a battery to explode.
Always wear protective clothing and eye protection and use insulated tools when working on batteries.
Read and pay attention to this important information.
CAUTION!
This unit contains components sensitive to electrostatic discharge (ESD). If you do not follow the ESD
procedures, you may cause severe damage to electronic components.
PLEASE RECYCLE
The shipping materials for the APC Silcon UPS are recyclable. Please save for later use or dispose of
them appropriately.
990-4049
2Installation Guide APC Silcon 240-320kW 480V UPS
Contents:
1.0 Introduction 5
1.1Tools and Equipment5
2.0 Unpacking/Identification of Equipment 6
3.0 Installation 9
3.1Requirements on Site9
3.2Dimensions and Weight9
3.2.1Dimensions and Weight of UPS9
3.3Footprints10
3.3.1UPS Cabinet Footprints10
3.3.2Conduit Entrance Plate in bottom of the system11
3.3.3Top Cable Entry12
4.0 External Connection 13
4.1Connecting the UPS13
4.1.1Connecting AC and DC Power Cables (Dual Utility Connection)14
4.1.2Seperation of AC from DC1 and DC216
4.1.3Top or Bottom Cable Entry17
4.1.4Dual and Single Utility Supply18
4.1.5Switching from Dual to Single Utility Input20
4.1.6Connection Terminals22
4.1.7Torque Specifications22
4.1.8Grounding22
4.2System Integration Interface24
4.2.1Connecting the System Integration Interface Board (SII-board)25
6.5.8Principale Diagrams for Isolation Transformer72
6.6Intersystem Synchronization Unit74
7.0 System Specifications 75
7.1Technical Data75
8.0 Appendix 76
8.1Table 1. Installation Planning Data76
8.2Table 2 – Table 310-1677
9.0 Warranty 79
9.1APC Silcon Series® Limited Factory Warranty79
10.0 How to Contact APC 80
990-4049
4Installation Guide APC Silcon 240-320kW 480V UPS
Introduction
1.0Introduction
Power regulation varies from country to country, and the information given in this installation
guide can therefore only be of a general nature. Electricians should always refer to national and
local electrical codes prior to installing the UPS system.
WARNING!
Heavy equipment. To prevent personal injury or equipment damage, take extreme care when
handling and transporting UPS cabinet and equipment.
1.1Tools and Equipment
This section lists all tools and equipment required to install all UPS configurations. See also
section 4 for further details on connection.
WARNING!
Ensure that front doors are in place and that internal front cover is fastened by screws before
attempting to lift or transport the system.
Tools:
• 10mm socket
• 13mm socket-deep
• 17mm socket
• 3/4” or 19mm socket-deep
• 3/4” or 19mm combo wrench
• Small flathead/regular screwdriver
• #3 philips screwdriver
• Compression lug crimping tool
• Knock-out set (for conduit)
Equipment:
• Compression lugs for cable terminations
• Cable to Service Bypass Panel from system feeder
• Cable to UPS input from service bypass panel
• Cable to Service Bypass Panel from UPS output
• Cable from Service Bypass Panel to customer distribution
• Cable to UPS input from external batteries/external Battery Breaker Box
(systems = with external battery)
• Solid core, control wire to UPS from Service Bypass Panel
• Solid core, control wire to UPS from external batteries/external Battery Breaker Box
Unless otherwise specified by the shipping company, use a fork lift to unload equipment from
pallet.
1. Unpack system.
2. Verify compliance between type label on reverse side of front door and system ordered.
Check input and output voltage.
3. Copy the type label data to label copy below for easy identification of the system.
4. Use a fork lift to transport the system to installation site.
Copy of type label (without battery):
990-4049
6Installation Guide APC Silcon 240-320kW 480V UPS
Unpacking/Identification of Equipment
Main UPS system
The UPS is a battery back-up system. Unconditioned power is fed to UPS input. The UPS
supplies conditioned power.
Service Bypass Panel
AC utility power for critical load is led through the service bypass panel while UPS is shut
down for maintenance
Battery Breaker Box
The APC Battery Breaker Box is required if the UPS is installed with an external battery. The
Battery Breaker Box provides overcurrent and short-circuit protection.
Isolation Transformers are used for galvanic isolation of utility power and conditioned power.
Seismic Anchoring
Seismic anchoring stabilizes the UPS in seismic areas.
NEMA 12 C
NEMA 12 covers are used in locations with potential risks of liquid discharge or leakage above
UPS system.
over
Remote Display
Use remote display to monitor UPS
NOTICE!
Contact your local APC representative or APC Support if you have any questions
990-4049
8Installation Guide APC Silcon 240-320kW 480V UPS
Installation
3.0Installation
3.1Requirements on Site
All system parts are accessible from front or top of UPS. Cable entries are accessible from top
or bottom. The system may be installed close to walls as long as free space is allowed for system
doors to open.
For ventilation and service purposes allow for free space of a minimum of 3 foot above and in
front of UPS. Never install systems in direct sunlight.
WARNING!
For safety reasons do not stand on UPS. Keep UPS cabinet surface free of any objects
Prior to connecting the UPS, refer to section 6: Options and Accessories to ensure that UPS
options are correctly interphased.
WARNING!
Read warnings on page 2 of this manual before continuing.
To access cable terminals, open front door, remove screws and lift off the 4 front covers
(remember earth wire on rear side). Power cable entry at bottom: Remove front covers 2 and 3.
Power cable entry at top: Remove front covers 1 and 2. Remove cover 4.
Connecting AC
and DC
power cables
UPS system with cover– doors open
1
2
4
3
UPS system without cover and doors
Connecting
communication
cables
Connecting Ground
NOTICE!
Always keep AC, DC and communication cables separate.
Supply the UPS from grounded 3-wire/4-wire WYE service.
NOTICE!
Ensure correct phase rotation of input voltage.
NOTICE!
Keep UPS input and output conductors in separate conduits.
NOTICE!
Keep AC and DC conductors in separate conduits.
NOTICE!
Keep batteries 1 and 2 (DC conductors) in separate conduits.
WARNING!
Keep UPS power conductors and UPS control wiring in separate conduits.
4.1.2 Seperation of AC from DC1 and DC2
Use the 2 pieces of polycarbonate (supplied with the UPS) to separate AC from DC1 and DC2.
Standard length of polycarbonate adjusted for top cable entry. Adjust length of polycarbonate
to fit bottom entry where applicable.
UPS units contain hazardous AC and DC voltages. Only qualified electricians should install UPS,
AC line and external batteries, and must be familiar with batteries and battery installation.
Before installing, maintaining or servicing the UPS, shut off the UPS and disconnect all sources
of AC and DC power.
As the UPS has no built-in disconnection devices to switch off external AC and DC input power,
ensure that disconnection devices are provided as separate parts in connection with the
installation!
The installer must provide each external disconnecting device for this UPS system with labels
with wording as follows:
“Isolate the Uninterruptible Power Supply (UPS) as instructed in this guide
before working on circuit”
AC and/or DC voltage will always involve a potential risk of AC voltage at UPS output generated
from either batteries or utility. To avoid equipment damage or personal injury, always assume
that there may be voltage at UPS output.
This system is equipped with an auto-start function. If activated the system may start without
warning. Refer to “Programming Parameters” for information on de-activation.
TEST BEFORE YOU TOUCH!
To reduce the risk of fire or electric shocks, install the UPS and external batteries in a
temperature and humidity controlled indoor area, free of conductive contaminants.
UPS batteries are high-current sources. Shorting battery terminals or DC terminals or DC
busbars can cause severe arcing, equipment damage and injury. A short circuit can cause a
battery to explode. Always wear protective clothing and eye protection and use insulated tools
when working with working near batteries.
CAUTION!
This unit contains components sensitive to electrostatic discharge (ESD). If you do not follow the
ESD procedures, you may cause severe dammage to electronic components.
The UPS is fitted with dual utility input as standard. If dual utility is not available or not
needed, a small modification has to be made. See section 4.1.5 switching from dual to single
utility input.
Working Principle of Dual Utility (2 utility supplies)
Q3
Utility 2
Q10
Q1
Utility 1
NOTICE!
Max. phase shift between utility 1 and 2: less than
Refer to section 7.0 System Specifications for frequency tolerance of utility 1 and 2, and voltage.
Utility 1 supports the load in normal operation. Utility 2 supports the load through the static and
service bypass switch.
Working Principle of Single Utility (1 utility supply)
Utility 1/2
Q1
Utility 2
Utility 1
APC Silcon UPS
±
3.
Q3
Utility 1/2
Q2
Q2
Output
Output
APC Silcon UPS
NOTICE!
Refer to section 7.0 System Specifications for frequency and voltage tolerance of utility 1.
Utility 1 or 2 supports the load in normal operation or through the static service bypass switch.
Ensure correct phase rotation of utility input voltage! Max. power cable size: 500 kcmil.
NOTICE!
With a 3-wire input, the UPS can only be 3-wire loaded (Phase-to-phase).
NOTICE!
If an MCCB is used in stead of external input fuses, the MCCB load capacity must be 8xIn
(nominal current) for min.10 ms.
NOTICE!
Gland plate in bottom of system must be mounted.
Wiring
Select wire size based on the data in Table 1, and the ampacities in Table 2 of this manual, a
reprint of Table 310-16 and associated notes of the National Electrical Code (NFPA 70).
See section 8.0 Appendix.
Use commercially available UL approved solderless lugs for the wire size required for your
application. Connect wire to the lug using tool and procedure specified by the lug
manufacturer.
Input, output and DC cables are routed in separate conduits.
All AC cables rated 600V.
DC cables for 480V systems rated 1000V unless otherwise stated.
CAUTION!
At a switch mode load of 100% the neutral must be rated for 173% output phase current.
NOTICE!
φ
“phase”
“risk of electric shock”
Terminal for Equipment Grounding Conductor
E
Terminal for Grounding Electrode Conductor
NOTICE!
Terminals marked and are electrically connected to the terminal marked “E”
NOTICE!
For grounding, refer to local legal regulations.
CAUTION!
Read warnings on page 2 of this manual before continuing.
If no UPS neutral inputs are connected to a grounded service neutral conductor according to
local NEC code reguirements, provisions must be made as follows:
a) Bonding jumper must be mounted between output terminals X005:N and X005:E
b) Output terminal X500:E, marked “Grounding electrode terminal”, must be connected by
grounding electrode conductor to a local grounding electrode according to NEC 250-26
Input
stud size
Battery
stud size
Output
stud sizePEstud size
System earth
stud size
4.1.8.2 Equipment Grounding
Terminals marked intended for equipment grounding.
Provisions must be made as follows:
Input equipment ground terminal(s) must be connected to grounding electrode(s) provided for
the service entrance(s)
Refer to chapter 4.1.5 Changing from dual to single utility input
Single Utility
Dual Utility
System Integration Interface (SII) is the control link between UPS and system main switches
as shown above. The purpose of the SII is to ensure correct operation of switches without losing
system output power.
WARNING!
Even with all AC and DC sources switches off, SII may receive high voltage from external alarm
and signal circuit field wiring.
Auxiliary contacts on the main switches transmit SII-board inputs. Lamps on Service Bypass
Panel and Battery Breaker Box/Battery Cabinet indicate “green light” for operation of output
switches.
SII-board also integrates input facilities for emergency shut-down and temperature
compensation of charge voltage for external battery (also used with battery monitoring).
“Battery operation” and “Common fault” are the two main status SII-board relay signals.
4.2.1 Connecting the System Integration Interface Board (SII-board)
SII Board
X004
X012
X001
S002
X003
X005
S001
NOTICE!
If the UPS is equipped with an Emergency Power Off (EPO) facility all input sources must be
equipped with disconnecting devices.
Terminal rows: X003 and X004 (auxiliary contacts)
When switching Q001, Q002, Q010, Battery Breaker 1 or Battery Breaker 2 from “ON or 1” to
“OFF or 0”, the auxiliary contact must open BEFORE the corresponding main contacts are
opened. When switching Q001, Q002, Q010, Battery Breaker 1 or Battery Breaker 2 the
opposite way from “OFF or 0” to “ON or 1”, the auxiliary contact has to close with a maximum
delay of 0.5 seconds from the time the corresponding main contacts are closed.
• This type of auxiliary contact is called a “late make” contact. (This also means that
it will “break early” when activated in opposite direction)
• This auxiliary contact is also called “Normally Open” (NO), because the auxiliary
contact will be open when the main contacts are open
• Please note that the above term “NORMALLY” has nothing to do with NORMAL
UPS OPERATION MODE
When switching Q003 from “OFF or 0” to “ON or 1”, the auxiliary contact has to open BEFORE
the corresponding main contacts are closed. When switching Q003 the opposite way from “ON
or 1” to “OFF or 0”, the auxiliary contact has to close with a maximum delay of 0.5 seconds from
the time when the corresponding main contacts are opened.
• This type of auxiliary contact is called an “early break” contact. (This also means that
it will “make late” when activated in the opposite direction)
• The auxiliary contact is also called “Normally Closed” (NC), because the auxiliary
contact will be closed when the main contacts are open
• Please note that the above term “NORMALLY” has nothing to do with NORMAL
UPS OPERATION
CAUTION!
All wiring to alarm and signal circuit fields to be rated 300V (minimum).
X005 (output relays)
The battery operation signal is received with a 30-second delay. This function is inactive
during battery tests. Common fault relay facility is programmable (standard factory
setting: 10 sec.) See APC Silcon User Guide for details.
Maximum nominal voltage on contact circuits is 277VAC. If two different phases are involved,
maximum phase to neutral voltage should be below 160VAC. Please note that phase L1 is
already present on the System Integration Interface board, supplied from the Service Bypass
Panel. Therefore, if a phase is needed for alarm or signal purposes, Phase L1 should be used”.
Terminals X001, X003, X005, X004, X012:
Cable size AWG18 to AWG14, use solid copper conductors only.
Control cables must be separated from AC and DC power cables.
Parallel Board
The built-in parallel board connects two or more UPS systems in parallel, either to obtain
increased system reliability or to obtain higher output power. The parallel board also ensures
correct load-sharing between parallel systems.
NOTICE!
For reliability reasons, APC recommends separate battery packs in redundant/parallel
configurations.
To prepare the UPS for parallel/redundant mode, disconnect all sources of AC and DC power
supply to the UPS and connect the ribbon cable from the parallel board to the main controller
board. (The ribbon cable is delivered with the UPS).
CAUTION!
Do not connect ribbon cable in single configurations. Ribbon cable is for parallel operation only.
Complete the parallel system set-up by connecting the external control cables (see below).
Follow instructions in section 5.3 Programming of this guide to execute necessary
reprogramming.
External multicore cable with 14 wires + shield
to other parallel units
990-4049
External Control Cables
External multicore cable has a 15-pin SUB-D male connector at either end. Connect pin 1 to
pin 1, and pin 2 to pin 2 etc. up to pin 15 - except pin 8, which need not be connected.
Shield is connected to plug cover at both ends.
Terminals X020 and X021 for control cables are located on parallel board. Connect X020 in
UPS1 to X021 in UPS2 and X020 in UPS2 to X021 in UPS3 etc. Connect X020 in last UPS to
X021 in UPS1.
(Cable is delivered with the UPS).
Power Cables
To optimize load-sharing in parallel operation, external power circuits must be “symmetrical”:
Power input and output cables must have same length and identical cross-sections.
8 (X009)Normal OperationUPS running in normal operation (Status)
9 ##
(X010)
10 ##
(X011)
11 ##
(X012)
12
(X013)
13 ##
(X014)
14
(X015)
15
(X016)
16 ##
(X017)
Bypass Outside
Tolerance
Output Outside
Tolerance
System OverloadOutput load over 100%
High Equipment
Temperature or
Inverter Fuse Blown
Battery OFF
Battery OperationUPS running in battery operation (Status)
Bypass OperationUPS running in bypass operation (Status)
Stand-by OperationUPS in stand-by mode
Service Bypass
Operation
Boost Charge
Operation
Battery Voltage Outside
Tolerance
Battery Condition FaultABM detected battery weak
Common FaultAll alarms as mentioned above (except relays
Bypass voltage RMS value outside tolerance
Bypass wave form (fast detector) outside tolerance
Bypass frequency outside tolerance
Output voltage RMS value outside tolerance
Output wave form (fast detector) outside tolerance
Output frequency outside tolerance
Delta inverter current limiter active
Main inverter current limiter active
Static switch temperature too high
Main inverter failure (temperature too high or fuse blown)
Delta inverter temperature too high
Magnetics temperature too high
Isolation transformer optional temperature too high
Battery temperature too high
Battery Breaker Box battery OFF
(Hot stand-by, parallel systems only)
Service bypass switch active
UPS boost charging on battery
DC voltage too high (shut down)
DC voltage under warning level
DC voltage too low (shut down)
The ComInterface having 2 ports - is used when an interaction between UPS and e.g. a
computer system has to be established. The main purpose is to ensure monitoring and if
needed, a controlled shut down of the computer in case of failures in the utility supply.
4.5.1 Connections
Smart
Slot
X005, 25 pin SUB D female. ComPort
X008,25 pin SUB D male.
Serial port RS232.
For service use.
4.6SmartSlot for APC Silcon 240-320kW UPS
A UPS system alone provides excellent protection from brief power problems. However, during
an extended power outage an unattended computer system will eventually shut down due to
battery capacity exhaustion. To prevent data corruption when the UPS shuts down, the
computer must be informed by the UPS of impending shut down and take appropriate filesaving measures. This important function is called UPS monitoring. The UPS's computer
interface port is the means by which your UPS communicates with a computer system.
Some computer operating systems have built-in UPS monitoring. These systems require
various hardware interfaces. Interface kits for all major operating systems that support UPS
monitoring are available from your dealer.
APC SmartSlot for APC Silcon Series UPS's has been designed for reliable and maintenancefree service in combination with your American Power Conversion (APC) Silcon UPS Series
uninterruptible power supply (UPS).
4.6.1 SmartSlot Accessories
SmartSlot at the front of the frame accomodate up to 3 accessory cards. Before installing any
SmartSlot accessory, ensure it is a compatible "APC Silcon DUPSK" model.
1. Share-UPS TM, provides automatic shutdown of up to two additional servers.
2. Measure-UPS TM II, provides environmental information such as ambient temperature
and humidity.
3. Call-UPS TM, works with an external modem to provide out-of-band UPS manegement
4. WEB/SNMP Management card, provides web based UPS management.
If your UPS configuration uses more than one SmartSlot device, you must install them in the
correct order for them to work together properly.
Priority of SmartSlot devices:
A SmartSlot device with higher priority is to be placed in the SmartSlort accessory slot with
the higher number. Refer to the following table.
Priority of APC accessories:
Install SmartSlot accessories as dictated by the following table. An accessory with higher
priority is to be placed in the accessory slot with the higher number.
To install accessories, perform the following steps:
1) Make sure that the APC Silcon UPS is powered off.
2) Install the SmartSlot accessories into the housings on the front of the chassis.
See the instructions supplied with the accessories and “Priority of APC accessories.”
Lowest
Low-numbered
If your UPS has one SmartSlot accessory slot
If your UPS has exactly one SmartSlot accessory slot, use this accessory slot for the SmartSlot
device with the lowest priority.
a) The servicing of batteries requires battery knowledge and should only be carried out or
supervised by qualified electricians familiar with batteries. Keep unauthorized personnel
away from batteries.
b) Use identical battery types and numbers when replacing batteries. See battery supplier
manual for further details.
c) CAUTION - Do not dispose of batteries in a fire. Batteries may explode.
d) CAUTION - Avoid rough treatment and opening of batteries. Released electrolyte is harmful
to skin and eyes, and may be toxic.
e) CAUTION - Batteries may cause electric shocks and high voltage short-circuit current.
Follow the precautions below when working with batteries:
1. Remove watches, rings and other metal objects
2. Use tools with insulated handles
3. Wear rubber gloves and boots
4. Do not leave tools or metal parts on top of batteries
5. Disconnect charging source prior to connecting batteries
6. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove
unwanted ground source. Any contact with grounded batteries may result in electric
shocks. The likelihood of such shocks will be reduced if grounds are removed during
installation and maintenance.
Installation and use of this product must comply with all national, federal, state, municipal or
local codes. If you need assistance, please have your UPS model and serial number ready and
call APC. See “How to Contact APC” in this guide.
Find more information on the APC World Wide Web site at http://www.appc.com.
WARNING!
The entire system contains HAZARDOUS AC/DC VOLTAGES from several power sources.
Some terminals and components are live even with the system being switched off!
ONLY qualified electricians may install batteries and national and local codes must be followed.
NO APC Silcon UPS may have built-in batteries if connected to external batteries!
NEVER install batteries not complying with APC specifications. Falling that, the installer takes
over full responsibility!
NEVER lift or transport connected/installed batteries
The APC Battery Breaker Box is required if the UPS is installed with an external battery. The
Battery Breaker Box provides overcurrent and short-circuit protection.
Select wire size based on the data in Table 1 and ampacities in Table 2 of this manual, a reprint
of Table 310-16 and associated notes of the National Electrical Code (NFPA 70).
Fixing centres in
rear of enclosure
See measurements
in below table
SKU No.TypeUPSDimensions
SL0901712Battery Breaker Box
SL0901713Battery Breaker Box
240kW 480V
320kW 480V
240kW 480V36.22/920 x 33.46/850
320kW 480V36.22/920 x 33.46/850
HxWxD* [in/mm]
x 7.09/180
x 7.09/180
Fixing centres
AxB [in/mm]
24.41/620 x 25.59/
650
24.41/620 x 25.59/
650
CAUTION!
Check correct polarity when connecting DC cables.
NOTICE!
Terminal for Equipment Grounding Conductor is marked
NOTICE!
For grounding, refer to local legal regulations.
4.7.2 Mounting and Connection of Battery Breaker Box
All AC cables rated 600V.
DC cables must be rated 1000V, unless otherwise stated.
4.7.3 UPS with External Battery via Battery Breaker Box
4.8UPS Installations in Computer Rooms
IMPORTANT! Follow the instructions below when installing UPS-systems in computer rooms:
1. - Only systems with external batteries may be installed.
- All battery cabinets must be UL listed and must be approved for use in computer rooms.
- Refer to APC Design Guide for correct DC disconnection/overcurrent if alternative battery
cabinet makes are used.
- All batteries used in computer rooms, must comply with R/C (BAZR2) and must be flame
rated according to UL 94V2, UL 94V1 or UL 94V0.
2. The system must be provided with switch gear facility with trip function for all switches for
Emergency Power Off function (EPO). See principle diagram below.
3. The system must be provided with EPO function for the disconnection of all AC and DC
sources. See principal diagram below.
Activate EPO switch to switch off UPS system. All switch gear switches are tripped. UPS will
discharge capacitors within 5 minutes.
Test EPO function at yearly service inspection.
CAUTION!
Remember to secure load prior to EPO testing.
Monitor noise level in computer room when all equipment is in operation (UPS, computers,
servers, printers, air conditioning etc.) Take precautionary measures according to
Occupational Noise Exposure Recommendation if necessary.
Diagram for Emergency Power Off (EPO) principle has to be established prior to EPO and UPS
installations. Battery Breaker Box and switch gear must be installed with “shunt trip”.
Use external power supply from “Utility” and UPS output before reaching Q002, when tripping
Battery Breakers and switchgear.
EPO circuit and UPS are interconnected to “OFF” and “ON” push buttons, through the System
Integration Interface card terminals X001. On the System Integration Interface card, the
selection switch S002 for internal or external power supply may be set.
Position 2, external supply X001:1, + 12V and X001:2, GND
EPO switches must have break functions. Supply current loop of 20mA internally or externally
by selecting switch S002 on System Integration Interface. Use external supply with 12Vdc or
20mA current generator.
The EPO switch is interconnected to an electronic control system (not available from APC)
supplying the Battery Breaker Box and switch gear tripping function with an external 480/
277Vac 50/60Hz supply from Utility 2 (if available) or Utility 1 and UPS output before Q002.
The combination of 2 break functions (one for UPS system and one for external switch gear)
allows for a quick system shutdown in an emergency situation.
NOTICE!
Emergency Power Off function requires a special Service Bypass Panel with tripp function
Below table shows operating parameters programmable from keyboard. Only qualified users
should amend programming parameters.
5.1Parameters
ParameterSetting*Comments
Bypass operationYES, NOYES will switch the system into bypass
LanguageGB, D, F, DK, S, SF,
NL, PL, CZ, E, P, SK,
H
AutostartYES, NOAutomatic restart by utility return (1 min. delay).
Remote shutdown activeYES, NOShutdown of UPS by remote signal when in
Remote shutdownHIGH, LOWNature of remote shutdown signal level
Remote shutdown time0, 1, 2, 3, 4, 5, 6, 7, 8,
9, 10 min.
Battery capacity test–Initiates back-up time check. Time measured
Battery monitor test **–Initiates checks of battery condition by 25%
Automatic battery test**OFF, 3,6 monthsActivates the battery monitor test in cyclic
Battery monitor reset**–Press the and key to reset alarm
mode***
Languages of text in display
Ensures quick battery recharge.
battery operation. Saves battery energy.
Time delay on remote shutdown of UPS
from start until it reaches low DC warning level
(See User Guide, section 6.0).
discharging.
intervals.
(flashing light).
Boost chargeYES, NOYES results in boost charge (10 hours)
Autoboost chargeYES, NOYES results in boost charge after battery
Enter new dateYYMMDDSet to local date
Enter new timeHHMMSSSet to local time (24 hour clock)
* Factory settings in bold
** For stystems with avctive Battery Monitor only
*** Do not leave system running in bypass mode (static bypass) for extended periods of time, as
System configuration parameters are vital for correct system operation and are passwordprotected.
Incorrect programming may damage battery or cause output voltage to be lost during
operation!
System Configuration Parameters (password protected)
ParameterSetting*Comments
Isolation Transformer
Input
Isolation Transformer
Output
Delta Soft Start Time1, 10, 20, 40 sec. Input current switching in ramp function. Use
External SSW availableYES, NOYES for systems with external static bypass
Normal Charge Voltage410-460V
Boost Charge Voltage438-460V
Low Battery warning336-384V
Low Battery shut-down310-336V
Synchronization0.25, 0.5, 1, 2, 4
High Battery Temperature 15-40°C/59-
Common fault delay0, 10, 20,
Reset operation mode lock YES, NOYES resets system locked in bypass or battery
Expected back-up time
(min.)
Battery Capacity in (Ah)0.1-999.9
Highest Station Address2-9Highest station address in parallel system
Station Address1-9Station address in parallel system
* Bold text refers to standard factory setting
**Advanced Battery Monitor
YES, NOYES, if optional input isolation transformer is
available
YES, NOYES, if optional output isolation transformer is
available
higher values for smaller/unstable diesel
generators
switch
Setting of float charge voltage at 20°C/68°F
438V
438V
346V
326V
Hz/sec.
104°F
35°C/95°F
30 sec.
0.1-999.9
5.0
7.0
(Automatic compensation for temperature
deviations)
Setting of boost charge voltage at 20°C/68°F
(Automatic compensation for temperature
deviations)
Discharged Battery warning
Switches off system at minimum permissible
battery voltage
Synchronization speed. Higher values used at
unstable utility frequencies.
Alarm - Ambient battery temperature too high
Delay before common fault alarm relay is
activated
operation mode caused by system failures (only
applicable for service personnel)
Expected UPS back-up time in minutes when
running at 100% ohmic load. Time used by
ABM**
Total Battery capacity in Ah.
Setting used by ABM**.
APM Test Mode ActiveYES, NOYES, if APM*** test mode is active
Battery ConnectionCommon,
* Bold text refers to standard factory setting
**Advanced Battery Monitor
***Advanced Power Management
5.2.1 Programming Example - Change Boost Charge Voltage to 446V
Redundant +1
Parallel +1
Separate
Use only in parallel systems.
Disabled: APM*** off.
Redundant +1: Redundant operation with one unit
being inactive in parallel system
Parallel +1: Redundant operation with all units in
operation.
Common: if common battery is used in parallel
system.
Separate: if separate battery is used
NOTICE!
Change charge voltages, battery warning limit, shut down voltages and high battery temperature
limit by entering the actual value. See example above.
5.3Programming Parameters for Advanced Parallel Operation.
To use the advanced parallel functions the following parameters must be programmed:
1. “Station number”
2. “Highest station address”
3. “Advanced power management”
4. “APM test mode active”
5. “Battery connection”
5.3.1 Description of Settings.
1. “Station number”
• Valid station numbers: 1-9 stating the UPS parallel address in system.
2. “Highest station number”
• Valid station numbers: 2-9 stating the number of UPSs in system.
3. “Advanced power management”
• “Disabled”: Advanced Power Management is inactive.
• “PARALLEL+1”: Advanced Power Management is activated when the system operates
• “REDUNDANT+1”: Advanced power management is activated when the system
4. “APM test mode active”
• “No”: Stand-by-time will be 24 hours - on-line time will be 48 hours. (xN systems).
• “Yes”: Stand-by-time will be 1 min. - on-line time will be 2 min. (xN systems).
5. “Battery connection”
• “Separate”: Separate battery for this UPS.
• “Common”: Common battery in a parallel system.
as PARALLEL N+1, meaning that one system can be isolated without overloading the
remaining systems (N systems/UPSs).
operates as REDUNDANT N+1, meaning that one system can be isolated without
overloading the remaining systems (N systems/UPSs) with one spare system.
NOTICE!
“Common”: Common battery in a parallel system. When this setting is chosen, the highest
battery temperature that can be found in the parallelled systems is used (for charge voltage
compensation).
NOTICE!
Common battery pack is a technical possibility.
However, APC recommends separate battery pack due to a higher safety degree in connection
with redundant/parallel operation.
The UPS system is designed for both situations.
5.3.2 Programming Example
Example with four systems in parallel with separate batteries.
• Program the station addresses 1-4: 1 for UPS 1, 2 for UPS 2, 3 for UPS 3, and 4 for UPS
4.
• All UPS systems have to be programmed to “Highest station address” :4.
• If APM should not be tested, “APM test mode active” must be “NO”.
• If a system is isolated due to service the station numbers must be reprogrammed for the
remaining active systems starting with number 1 and ending with maximum number of
active systems. No numbers must be left in this sequence. Furthermore, “Highest
station address” must be changed to number of active UPS’s in parallel.
5.4Battery Monitor
Installation of new batteries:
To avoid false alarms, the above procedure MUST be followed.
NOTICE!
Contact your local dealer if you have any questions regarding changing parameters.
Check correct phase connection of inputs and outputs.
Wiring
Select wire size based on the data in Table 1, and the ampacities in Table 2 of this manual, a
reprint of Table 310-16 and associated notes of the National Electrical Code (NFPA 70).
Use commercially available UL approved solderless lugs for the wire size required for your
application. Connect wire to the lug using tool and procedure specified by the lug manufacurer.
Check correct phase connection of inputs and outputs.
Wiring
Select wire size based on the data in Table 1, and the ampacities in Table 2 of this manual, a
reprint of Table 310-16 and associated notes of the National Electrical Code (NFPA 70).
Use commercially available UL approved solderless lugs for the wire size required for your
application. Connect wire to the lug using tool and procedure specified by the lug
manufacturer.
Drill 16 holes for Ø10mm bolts at installation site according to dimensioned sketch.
With the holes drilled in the UPS, position the system correctly and slide the 8 seismic
anchoring angles into the bars (see illustration above). Tighten the angles in the holes, using
bolts and plain washers.
NOTICE!
Tighten all bolts in all 8 angles to the floor. Floor bolts not supplied
With the remote display unit data may be displayed at distances of up to 25m from UPS. For
extended communication distance, see below.
Remote display may easily be connected to UPS via one of the two serial communication ports
on the communication interface board.
To obtain a transmission distance of up to 3.2km normal RS232C signal levels must be
converted to a long distance communication standard. The converter must be placed outside
the UPS cabinet.
6.4.1 Extension of Remote Display Communication Distance
The remote display communicates with the UPS through a 3-wire RS232 interface. The remote
display is a DTE (Data Terminal Equipment) employing a SUB-D 9-pin female connector.
Communication speed: 9600 bps.
For communication distances, see table below. Insert converters if longer distances are
necessary, or if communication cables are led through magnetically noisy areas. Converters
must comply with local regulations
Remote Display Communication Extensions
Standard
(RS232)
Max. distance80/25 ft/m10000/3200 ft/m
Converter Manufacture
Art. Code
RS232 BLACK BOX connectorSub-D 25-pin female
BLACK BOX interconnector4-screw terminal
Two converter boxes are required for a communication distance extension: One
box near the UPS for the conversion from RS232C to a long distance communication standard,
and another box at the other end to convert back to RS232C, which is to be connected to the
Remote Display. The converter provides optical signal isolation. Both converter boxes must be
supplied by an uninterruptible power source.
6.4.1.1 Connections Without Converter
Connect a 25-pin female Sub-D and a 9-pin male Sub-D connector with a 3-wire shielded cable,
as shown in the table below. Connect shield at one end only.
Pin Connection for Interconnection Cable (without converter)
Host (DTE)Remote Display (DTE)
25-pin female
pin No.
2 (TXD)2 (RXD)
3 (RXD)3 (TXD)
7 (GND)5 (GND)
House (shield)No Connection
6.4.1.2 Connections With Converter
Connections to be made according to converter manual.
Pin connection example only:
Pin Connections for cable
from host to ME800A-R2.
Host
(DTE)
25-pin female
pin No.
2 (TXD)332 (RXD)
ME800A-R2
(DCE)
25-pin male
pin No
9-pin male
pin No.
Pin connection for cable from
ME800A-R2 to Remote Display
ME800A-R2
(DCE)
25-pin male
pin No
Remote Display
(DTE)
9-pin male
pin No
3 (RXD)223 (TXD)
7 (GND)775 (GND)
House (Shield)No connectionNo connectionHouse (Shield)
The ME800A-R2 must be set up as a DCE with no RTS/DTR control.
The interconnection cable between the two ME800A-R2 boxes is a 4-wire twisted pair
telephone cable with or without shield. The shield improves noise immunity but reduces
maximum communication distance.
Wiring for alarm and signal circuit field to be rated 300V (minimum).
Rear viewFront view
screws
Cable entry from
bottom and rear
1. Turn 180° to loosen the 4 screws
2. Remove front cover
6.4.2.2 Remote Display Power Supply
3. Mount back plate
4. Connect cables
Rear view
DP9-FUtility adapter
The remote display is supplied by normal AC power with no battery back-up. For UPS data
transmission to remote display to remain unaffected during power failure, the remote display
must be supplied from an uninterruptible power source.
Converters used to extend communication distance must also be supplied from uninterruptible
power sources.
Rating: Refer to Local/National electrical codes.
Communication voltage ±15V
6.4.3 Remote Display Use
The remote display is an inactive unit unable to influence the operation of the UPS: Some of
the alarms visible on the internal display are also available on the remote display (See the
Alarm section in the APC Silcon User Guide).
6.4.3.1 Initiating the Remote Display
After having connected the supply the display will show:
Remote Display: “APC Silcon UPS”
DC
Remote Display, DB9-M
6.4.3.2 Communication Fault
Communication fault between UPS and remote display will appear in the display as follows:
“Data transmission interrupted”
6.4.3.3 Remote Display Setting
Use # Stack to select language and type of UPS connected to remote display.
ParameterSettingComments
LanguageGB,D,F,DK, S, SF,NL, PL, CZ,
E, P, SK, H, I
HostSDC charger, DP300E, 300EType of UPS connected to
6.4.3.4 Operation
See Operation section in the APC Silcon User Guide.
See Display of Measured Value in the APC Silcon User Guide.
Time reading and utility 2 current not visible from remote display.
6.4.3.6 Alarms
See Alarms section in the APC Silcon User Guide.
6.5Isolation Transformer Module
CAUTION!
Use only one type of isolation transformers for dual utility input.
Isolation transformer modules can be used in the following configurations:
1. Between utility supply and UPS input, in a 3-phase Delta-service-phase or midpoint of 2
phases (grounded)
2. Between utility supply and UPS input for galvanic isolation
3. Between UPS output and load for galvanic isolation
4. Between UPS output and load for voltage stepping from 480V - 208V/Y 120V required
Do not use switch gear to bypass isolation transformers. If bypassed, damaging circulation
currents may occur, even with a unity turn ratio.
Coupling Methods
Configuration of isolation transformers is as Delta-WYE with accessible neutral (Dyn11)
NOTICE!
Check correct phase connection of inputs and outputs.
CAUTION!
At 100% switch mode load, the neutral must be rated for 173% output phase current.
Recommended use:
• 3 wires in/out
• 3 wires in/4 wires out
• 4 wires in/out
NOTICE!
All external cable dimensions are recommeded sizes only. Refer to local regulations.
6.5.1 Requirements on Site
All isolation transformer parts are accessible from front or top (cable entries accessible from
bottom). Isolation transformer may be placed close to walls, allowing free space for the front
door to open. Allow free space for ventilation slots for sufficient cooling.
Do not expose isolation transformers to direct sunlight.
Intersystem Synchronization Unit System (ISU System)
The ISU system consists of inter-connected ISUs. One ISU system may consist of up to 5 ISUs,
regardles of ISU configuration. The ISU system synchronizes the voltage of parallel operation
systems running in battery operation.
The ISU system may also include one or more external synchronization sources,
e.g. a gen-set or a non-APC Silcon UPS system.
Synchronization accuracy of the ISU is better than 2
Schematic overview of ISU system (example):
UPS 1B
Parallel
Operation
UPS 1A
UPS 3A
System 1
ISU
1
ISU
3
Parallel
Operation
System 3
UPS 1C
ISU System
UPS 3C
o
.
UPS 2A
UPS 2B
Parallel
Operation
System 2
ISU
2
ISU
4
ISU
5
UPS 2C
Ext.
sync
Source
UPS 4
UPS 3B
Intersystem Synchronization Unit (ISU)
The ISU is an active part of an ISU system, serving as the interface to the sources and the ISU
system.
The ISU can be connected to a parallel UPS configuration, using the standard parallel
communication controller in the parallel operation system.
(See Intersystem Synchronization Unit User’s Manual for further details.)
1. Nominal (Nom) Input current based on rated load.
2. Maximum (Max:) Input current based on full battery recharge + nominal load.
3. Recommendation: Input and Output cables run in separate conduits.
4. Suggested Input overcurrent protection based on continuous full load
Maximum Input current. Suggested Load Side Overcurrent Protection based on Nominal current.
Breakers sized per NEC 220-3 and NEC 240-3(b). 80% rated breakers assumed. Trip rating based on
NEC 240-6(a) standard breaker sizes.
5. Nominal battery voltage assumed to be 2.0 volts/cell (lead technology).
6. Recommendation: All cables should be sized in accordance with NEC 210-19 FPN No. 4
branch feeder voltage drop of 3%. Voltage drop not considered in above chart. Application
specific Input Cable ampacities may vary from above chart.
7. Breaker/Fuse selection based on Nom input current is acceptable provided battery recharge time is
short.
Consult factory for application specific assistance.
8. Grounding conductor ampacities: Refer to NEC Article 250-122 and NEC Table 250-122.
Neutral conductors ampacities: Refer to NEC Article 310-15.
9. All wiring to be in accordance with all applicable national and/or local electrical codes.
10. Nominal Battery Discharge current based on full rated load, and nominal Battery voltage.
11.Maximum Battery Discharge current based on full rated load at end of Discharge.
12. Heat rejection calculated at nominal full load capacity.
A.Not more than 3 current carrying conductors in raceway assumed; ambient temperature of 30°C
(86°F) assumed. Cable ampacity next size above Overcurrent Protection provided by others.
B. Temperature rating of conductors: 90°C (194°F). Reference Table 310-16 of NEC, 75°C column,
using copper conductors. 75°C (167°F) cable terminal connectors assumed.
C.Reference: NEC handbook 1999. Consult local codes for possible variations.
D.All cable and breaker/fuse ratings are supplied as guidelines only. These guidelines are minimum
recommendations only not substitutes for review and compliance with NEC and local codes.
Consult with your licensed engineer for site specific applications.
8.2Table 2 – Table 310-16
Allowable Ampacities of Insulated Conductors rated 0-2000 Volts, 60° to 90°C (140° to
1
194°F)
Not More than Three Conductors in Raceway or Cable or Earth (Directly Buried), based on Ambient
Temperature of 30° (86°F)
SizeTemperature Rating of Conductor (See Table 310-13)Size
APC warrants that the unit, when properly installed and commissioned by APC or APC authorized
service personnel, shall be free from defects in materials and workmanship for a period of (1) year
from the date of installation or maximum 18 months after manufacturing. In the event that the unit
fails to meet the foregoing warranty, APC shall for a period of one (1) year repair or replace any
defective parts, without charge for on-site labor and travel if trained & authorized APC personnel
has conducted start-up of the unit.
An APC Start-Up Service must be performed/completed by APC or APC authorized service
personnel or the on-site factory warranty will be voided and replacement of defective parts only will
be covered. APC shall have no liability and no obligation to repair the installed unit if non-authorized
APC personnel performed the start-up and such start-up caused the unit to be defective.
APC SHALL NOT BE LIABLE UNDER THE WARRANTY IF ITS TESTING AND EXAMINATION
DISCLOSE THAT THE ALLEGED DEFECT IN THE PRODUCT DOES NOT EXIST OR WAS
CAUSED BY PURCHASER’S OR ANY THIRD PERSON’S MISUSE, NEGLIGENCE, IMPROPER
INSTALLATION OR TESTING, UNAUTHORIZED ATTEMPTS TO REPAIR OR MODIFY, OR ANY
OTHER CAUSE BEYOND THE RANGE OF THE INTENDED USE, OR BY ACCIDENT, FIRE,
LIGHTNING OR OTHER HAZARD.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR
OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT
OR IN CONNECTION HEREWITH. APC DISCLAIMS ALL IMPLIED WARRANTIES OF
MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. APC’S
EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO
OBLIGATION OR LIABILITY WILL ARISE OUT OF, APC’S RENDERING OF TECHNICAL OR
OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING
WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES
AND REMEDIES. THE WARRANTIES SET FORTH ABOVE, CONSTITUTE APC’S SOLE
LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH
WARRANTIES. APC’S WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED
TO ANY THIRD PARTIES.
IN NO EVENT SHALL APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE
LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE
DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS,
WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT,
NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC HAS BEEN ADVISED IN ADVANCE
OF THE POSSIBILITY OF SUCH DAMAGES.