American Power Conversion 240-320kW User Manual

APC Silcon 240-320kW 480V UPS Installation Guide
Copyright ©2001 APC Denmark ApS
This manual is subject to
a commitment on the part of the vendor.
Thank You!
Thank you for chosing an APC Silcon UPS. Please read this Installation Guide thoroughly prior to installing the system. It provides important information on safe and efficient installation.
The installation and use of this product must comply with national, federal, state, municipal and local codes.
Safety Symbols used in this manual
WARNING! Indicates a hazard which, if not avoided, could result in injury or death.
CAUTION! Indicates a hazard which, if not avoided, could result in damage to
the product or other property.
NOTICE!
WARNING!
This UPS unit contains hazardous AC and DC voltages. Only qualified electricians should install the UPS, AC line and external batteries, and must be familiar with batteries and battery installation. Before installing, maintaining or servicing the UPS, shut off the UPS and disconnect all sources of AC and DC power. As the UPS has no built-in disconnection devices to switch off external AC and DC input power, ensure that disconnection devices are provided as separate parts in connection with the installation! The installer must provide each external disconnecting device for this UPS system with labels with the following text: “Isolate the Uninterruptible Power Supply (UPS) as instructed in this guide before working on circuit”.
AC and/or DC voltage will always involve a potential risk of AC voltage at UPS output generated from either batteries or utility. To avoid equipment damage or personal injury, always assume that there may be voltage at UPS output. This system is equipped with an auto-start function. If activated the system may start without warning. Refer to “Programming” section for information on de-activation.
TEST BEFORE YOU TOUCH!
To reduce the risk of fire or electric shocks, install the UPS and external batteries in a temperature and humidity controlled indoor area, free of conductive contaminants. UPS batteries are high-current sources. Shorting battery terminals or DC terminals, DC busbars can cause severe arcing, equipment damage and injury. A short circuit can cause a battery to explode. Always wear protective clothing and eye protection and use insulated tools when working on batteries.
Read and pay attention to this important information.
CAUTION!
This unit contains components sensitive to electrostatic discharge (ESD). If you do not follow the ESD procedures, you may cause severe damage to electronic components.
PLEASE RECYCLE
The shipping materials for the APC Silcon UPS are recyclable. Please save for later use or dispose of them appropriately.
990-4049
2 Installation Guide APC Silcon 240-320kW 480V UPS
Contents:
1.0 Introduction 5
1.1 Tools and Equipment 5
2.0 Unpacking/Identification of Equipment 6
3.0 Installation 9
3.1 Requirements on Site 9
3.2 Dimensions and Weight 9
3.2.1 Dimensions and Weight of UPS 9
3.3 Footprints 10
3.3.1 UPS Cabinet Footprints 10
3.3.2 Conduit Entrance Plate in bottom of the system 11
3.3.3 Top Cable Entry 12
4.0 External Connection 13
4.1 Connecting the UPS 13
4.1.1 Connecting AC and DC Power Cables (Dual Utility Connection) 14
4.1.2 Seperation of AC from DC1 and DC2 16
4.1.3 Top or Bottom Cable Entry 17
4.1.4 Dual and Single Utility Supply 18
4.1.5 Switching from Dual to Single Utility Input 20
4.1.6 Connection Terminals 22
4.1.7 Torque Specifications 22
4.1.8 Grounding 22
4.2 System Integration Interface 24
4.2.1 Connecting the System Integration Interface Board (SII-board) 25
4.3 Parallel Board 29
4.4 Relay Board 31
4.4.1 Relay Board Functions 31
4.4.2 Cable Sizes 33
4.5 Communication Interface / Smart Slot 34
4.5.1 Connections 34
4.6 SmartSlot for APC Silcon 240-320kW UPS 34
4.6.1 SmartSlot Accessories 35
4.6.2 Multiple SmartSlot Installation - introduction 35
4.6.3 APC Silcon Battery Cabinets 37
4.7 Battery Breaker Box 39
4.7.1 Interconnection 40
4.7.2 Mounting and Connection of Battery Breaker Box 40
4.7.3 UPS with External Battery via Battery Breaker Box 41
4.8 UPS Installations in Computer Rooms 41
4.8.1 EPO Principle 42
4.8.2 Emergency Power Off (EPO) for UPS 44
5.0 Programming 46
5.1 Parameters 46
5.1.1 Programming Keys 47
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 3
5.1.2 Programming Example - Switch to Bypass Operation 47
5.2 System Configuration 49
5.2.1 Programming Example - Change Boost Charge Voltage to 446V 50
5.2.2 Programming Example - Change to Output Isolation Transformer Available 51
5.3 Programming Parameters for Advanced Parallel Operation. 52
5.3.1 Description of Settings. 52
5.3.2 Programming Example 52
5.4 Battery Monitor 53
6.0 Options/Accessories 54
6.1 Diagrams for Service Bypass Panel for Single Operation, Single and Dual Utility 54
6.2 Seismic Anchoring 62
6.2.1 Mounting Seismic Anchoring 63
6.3 NEMA 12 Cover (IP31) 64
6.3.1 Mounting NEMA 12 Cover 64
6.4 Remote Display 65
6.4.1 Extension of Remote Display Communication Distance 65
6.4.2 Remote Display Installation 67
6.4.3 Remote Display Use 68
6.5 Isolation Transformer Module 69
6.5.1 Requirements on Site 69
6.5.2 Cabinets and Dimensions 70
6.5.3 Footprints 70
6.5.4 Connecting Isolation Transformer 70
6.5.5 Recommended Cable Lugs and Crimping Tools 70
6.5.6 Isolation Transformer - Diagram Delta WYE configuration (Dyn11) 71
6.5.7 Isolation Transformer Grounding 71
6.5.8 Principale Diagrams for Isolation Transformer 72
6.6 Intersystem Synchronization Unit 74
7.0 System Specifications 75
7.1 Technical Data 75
8.0 Appendix 76
8.1 Table 1. Installation Planning Data 76
8.2 Table 2 – Table 310-16 77
9.0 Warranty 79
9.1 APC Silcon Series® Limited Factory Warranty 79
10.0 How to Contact APC 80
990-4049
4 Installation Guide APC Silcon 240-320kW 480V UPS
Introduction
1.0 Introduction
Power regulation varies from country to country, and the information given in this installation guide can therefore only be of a general nature. Electricians should always refer to national and local electrical codes prior to installing the UPS system.
WARNING!
Heavy equipment. To prevent personal injury or equipment damage, take extreme care when handling and transporting UPS cabinet and equipment.
1.1 Tools and Equipment
This section lists all tools and equipment required to install all UPS configurations. See also section 4 for further details on connection.
WARNING!
Ensure that front doors are in place and that internal front cover is fastened by screws before attempting to lift or transport the system.
Tools:
• 10mm socket
• 13mm socket-deep
• 17mm socket
• 3/4” or 19mm socket-deep
• 3/4” or 19mm combo wrench
• Small flathead/regular screwdriver
• #3 philips screwdriver
• Compression lug crimping tool
• Knock-out set (for conduit)
Equipment:
• Compression lugs for cable terminations
• Cable to Service Bypass Panel from system feeder
• Cable to UPS input from service bypass panel
• Cable to Service Bypass Panel from UPS output
• Cable from Service Bypass Panel to customer distribution
• Cable to UPS input from external batteries/external Battery Breaker Box (systems = with external battery)
• Solid core, control wire to UPS from Service Bypass Panel
• Solid core, control wire to UPS from external batteries/external Battery Breaker Box
• Conduit necessary for above listed cabling
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 5
Unpacking/Identification of Equipment
2.0 Unpacking/Identification of Equipment
NOTICE!
Unless otherwise specified by the shipping company, use a fork lift to unload equipment from pallet.
1. Unpack system.
2. Verify compliance between type label on reverse side of front door and system ordered. Check input and output voltage.
3. Copy the type label data to label copy below for easy identification of the system.
4. Use a fork lift to transport the system to installation site.
Copy of type label (without battery):
990-4049
6 Installation Guide APC Silcon 240-320kW 480V UPS
Unpacking/Identification of Equipment
Main UPS system
The UPS is a battery back-up system. Unconditioned power is fed to UPS input. The UPS supplies conditioned power.
Service Bypass Panel
AC utility power for critical load is led through the service bypass panel while UPS is shut down for maintenance
Battery Breaker Box
The APC Battery Breaker Box is required if the UPS is installed with an external battery. The Battery Breaker Box provides overcurrent and short-circuit protection.
Battery Cabinet
For storage and protection of battery bank.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 7
Unpacking/Identification of Equipment
Isolation Transformer
Isolation Transformers are used for galvanic isolation of utility power and conditioned power.
Seismic Anchoring
Seismic anchoring stabilizes the UPS in seismic areas.
NEMA 12 C
NEMA 12 covers are used in locations with potential risks of liquid discharge or leakage above UPS system.
over
Remote Display
Use remote display to monitor UPS
NOTICE!
Contact your local APC representative or APC Support if you have any questions
990-4049
8 Installation Guide APC Silcon 240-320kW 480V UPS
Installation
3.0 Installation
3.1 Requirements on Site
All system parts are accessible from front or top of UPS. Cable entries are accessible from top or bottom. The system may be installed close to walls as long as free space is allowed for system doors to open.
For ventilation and service purposes allow for free space of a minimum of 3 foot above and in front of UPS. Never install systems in direct sunlight.
WARNING!
For safety reasons do not stand on UPS. Keep UPS cabinet surface free of any objects
3.2 Dimensions and Weight
3.2.1 Dimensions and Weight of UPS
UPS
240kW 480V 70.86/1800 74.80/1900 31.50/800 4432/2014,5
320kW 480V 70.86/1800 74.80/1900 31.50/800 4432/2014,5
Cabinet
Height inch/mm
74.80/1900 in./mm wide
70.86/1800 in./mm
Width inch/mm
Depth inch/mm
Weight lbs./kgs
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 9
Installation
3.3 Footprints
3.3.1 UPS Cabinet Footprints
NOTICE!
Dimensions indicated in inches / milimeters and lbs. / kgs
74.80/1900
73.85/1876
71.05/1805
70.86/1800
REAR
UTILITY 1
DC
OUT-
PUT
UTILITY2
COM
62.20/1580
59.44/1510
54.20/1377
51.45/1307
42.40/1077
FRONT
32.56/827
29.80/757
3.74/95
0.95/24 0
0
1.02/26
1.81/46
6.14/156
7.87/200
990-4049
30.47/774
31.50/800
25.98/660
14.37/365
15.94/405
10 Installation Guide APC Silcon 240-320kW 480V UPS
3.3.2 Conduit Entrance Plate in bottom of the system
REAR
UTILITY 1
Installation
LEFT
UTILITY 2 OUTPUT DC
0
10.14/257.5
FRONT
Cable entries need to be punched in the UPS cabinet. Follow diagram for correct orientation of power and control cables to be led into the UPS.
19.78/502.5
COM
COM
RIGHT
30.39/771.9
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 11
Installation
3.3.3 Top Cable Entry
Cable entries need to be punched in the UPS cabinet. Follow diagram for correct orientation of power and control cables to be led into the UPS.
17.72/450
REAR
11.61/295
7.68/195
LEFT
UTILITY 1-2/ OUTPUT/ DC
COM
0
0
3.31/84
16.28/413.5
FRONT
26.12/663.5
RIGHT
990-4049
12 Installation Guide APC Silcon 240-320kW 480V UPS
External Connection
4.0 External Connection
4.1 Connecting the UPS
Prior to connecting the UPS, refer to section 6: Options and Accessories to ensure that UPS options are correctly interphased.
WARNING!
Read warnings on page 2 of this manual before continuing.
To access cable terminals, open front door, remove screws and lift off the 4 front covers (remember earth wire on rear side). Power cable entry at bottom: Remove front covers 2 and 3. Power cable entry at top: Remove front covers 1 and 2. Remove cover 4.
Connecting AC and DC power cables
UPS system with cover– doors open
1
2
4
3
UPS system without cover and doors
Connecting communication cables
Connecting Ground
NOTICE!
Always keep AC, DC and communication cables separate.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 13
External Connection
4.1.1 Connecting AC and DC Power Cables (Dual Utility Connection)
990-4049
Top bar – Utility 2 (L1, L2, L3) Bottom bar – Output (N/E, L1, L2, L3)
Top bar – Ext. DC (X003±, X004±) Bottom bar – Utility 1 (N, L1, L2, L3)
Connection in the bottom of the cabinet
14 Installation Guide APC Silcon 240-320kW 480V UPS
External Connection
Dual Utility Connection
Seen from front
E
N
L3
L2
L1
Utility 2 – X002 Output – X005
L1
N
Ext. DC Utility 1 – X001
L3
L2
Seen from side
Utility 2 X002
Output
X005
Ext. DC
Utility 1
X001
WARNING!
Bottom cabinet connection must be grounded.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 15
External Connection
WARNING!
Supply the UPS from grounded 3-wire/4-wire WYE service.
NOTICE!
Ensure correct phase rotation of input voltage.
NOTICE!
Keep UPS input and output conductors in separate conduits.
NOTICE!
Keep AC and DC conductors in separate conduits.
NOTICE!
Keep batteries 1 and 2 (DC conductors) in separate conduits.
WARNING!
Keep UPS power conductors and UPS control wiring in separate conduits.
4.1.2 Seperation of AC from DC1 and DC2
Use the 2 pieces of polycarbonate (supplied with the UPS) to separate AC from DC1 and DC2. Standard length of polycarbonate adjusted for top cable entry. Adjust length of polycarbonate to fit bottom entry where applicable.
Polycarbonate
Polycarbonate
990-4049
16 Installation Guide APC Silcon 240-320kW 480V UPS
External Connection
4.1.3 Top or Bottom Cable Entry
For top cable entry, move copper angle bar to bottom.
Angle bar
Unscrew bolt, take out the split, move the angle bar down, insert split, and tighten the bolt
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 17
External Connection
4.1.4 Dual and Single Utility Supply
WARNING!
UPS units contain hazardous AC and DC voltages. Only qualified electricians should install UPS, AC line and external batteries, and must be familiar with batteries and battery installation.
Before installing, maintaining or servicing the UPS, shut off the UPS and disconnect all sources of AC and DC power.
As the UPS has no built-in disconnection devices to switch off external AC and DC input power, ensure that disconnection devices are provided as separate parts in connection with the installation!
The installer must provide each external disconnecting device for this UPS system with labels with wording as follows:
Isolate the Uninterruptible Power Supply (UPS) as instructed in this guide before working on circuit
AC and/or DC voltage will always involve a potential risk of AC voltage at UPS output generated from either batteries or utility. To avoid equipment damage or personal injury, always assume that there may be voltage at UPS output.
This system is equipped with an auto-start function. If activated the system may start without warning. Refer to Programming Parameters for information on de-activation.
TEST BEFORE YOU TOUCH!
To reduce the risk of fire or electric shocks, install the UPS and external batteries in a temperature and humidity controlled indoor area, free of conductive contaminants.
UPS batteries are high-current sources. Shorting battery terminals or DC terminals or DC busbars can cause severe arcing, equipment damage and injury. A short circuit can cause a battery to explode. Always wear protective clothing and eye protection and use insulated tools when working with working near batteries.
CAUTION!
This unit contains components sensitive to electrostatic discharge (ESD). If you do not follow the ESD procedures, you may cause severe dammage to electronic components.
The UPS is fitted with dual utility input as standard. If dual utility is not available or not needed, a small modification has to be made. See section 4.1.5 switching from dual to single utility input.
990-4049
18 Installation Guide APC Silcon 240-320kW 480V UPS
External Connection
Working Principle of Dual Utility (2 utility supplies)
Q3
Utility 2
Q10
Q1
Utility 1
NOTICE!
Max. phase shift between utility 1 and 2: less than Refer to section 7.0 System Specifications for frequency tolerance of utility 1 and 2, and voltage. Utility 1 supports the load in normal operation. Utility 2 supports the load through the static and service bypass switch.
Working Principle of Single Utility (1 utility supply)
Utility 1/2
Q1
Utility 2
Utility 1
APC Silcon UPS
±
3.
Q3
Utility 1/2
Q2
Q2
Output
Output
APC Silcon UPS
NOTICE!
Refer to section 7.0 System Specifications for frequency and voltage tolerance of utility 1. Utility 1 or 2 supports the load in normal operation or through the static service bypass switch.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 19
External Connection
4.1.5 Switching from Dual to Single Utility Input
Follow steps 1 and 2 to switch from dual to single input.
In the static switch the following modifications have to be made for single utility input
1) Remove fiber bar (55322) by unscrewing bolts and by mounting copper bars as below
Fiber bar
Copper bars
2) Switch the connector in Con3 to Con1.
990-4049
20 Installation Guide APC Silcon 240-320kW 480V UPS
External Connection
CAUTION!
Ensure correct phase rotation of utility input voltage! Max. power cable size: 500 kcmil.
NOTICE!
With a 3-wire input, the UPS can only be 3-wire loaded (Phase-to-phase).
NOTICE!
If an MCCB is used in stead of external input fuses, the MCCB load capacity must be 8xIn (nominal current) for min.10 ms.
NOTICE!
Gland plate in bottom of system must be mounted.
Wiring
Select wire size based on the data in Table 1, and the ampacities in Table 2 of this manual, a reprint of Table 310-16 and associated notes of the National Electrical Code (NFPA 70). See section 8.0 Appendix.
Use commercially available UL approved solderless lugs for the wire size required for your application. Connect wire to the lug using tool and procedure specified by the lug manufacturer.
Input, output and DC cables are routed in separate conduits. All AC cables rated 600V. DC cables for 480V systems rated 1000V unless otherwise stated.
CAUTION!
At a switch mode load of 100% the neutral must be rated for 173% output phase current.
NOTICE!
φ
phase
risk of electric shock
Terminal for Equipment Grounding Conductor
E
Terminal for Grounding Electrode Conductor
NOTICE!
Terminals marked and are electrically connected to the terminal marked E
NOTICE!
For grounding, refer to local legal regulations.
CAUTION!
Read warnings on page 2 of this manual before continuing.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 21
External Connection
4.1.6 Connection Terminals
Terminals – 480V
Terminal Type
240kW M12 M12 M12 M10 M12
320kW M12 M12 M12 M10 M12
The terminals for the control & alarm cables are screw clamps for cable size AWG18 to AWG14. All other terminals are stud terminals.
4.1.7 Torque Specifications
Stud size M6 M8 M10 M12
Torque 66/7.5 lb-in/Nm 133/15 lb-in/Nm 266/30 lb-in/Nm 443/50 lb-in/Nm
4.1.8 Grounding
4.1.8.1 System Grounding
If no UPS neutral inputs are connected to a grounded service neutral conductor according to local NEC code reguirements, provisions must be made as follows:
a) Bonding jumper must be mounted between output terminals X005:N and X005:E
b) Output terminal X500:E, marked “Grounding electrode terminal”, must be connected by
grounding electrode conductor to a local grounding electrode according to NEC 250-26
Input
stud size
Battery
stud size
Output
stud sizePEstud size
System earth
stud size
4.1.8.2 Equipment Grounding
Terminals marked intended for equipment grounding.
Provisions must be made as follows:
Input equipment ground terminal(s) must be connected to grounding electrode(s) provided for the service entrance(s)
990-4049
22 Installation Guide APC Silcon 240-320kW 480V UPS
E terminal
Ground terminals
External Connection
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 23
External Connection
4.2 System Integration Interface
NOTICE!
Refer to chapter 4.1.5 Changing from dual to single utility input
Single Utility
Dual Utility
System Integration Interface (SII) is the control link between UPS and system main switches as shown above. The purpose of the SII is to ensure correct operation of switches without losing system output power.
WARNING!
Even with all AC and DC sources switches off, SII may receive high voltage from external alarm and signal circuit field wiring.
990-4049
24 Installation Guide APC Silcon 240-320kW 480V UPS
External Connection
Auxiliary contacts on the main switches transmit SII-board inputs. Lamps on Service Bypass Panel and Battery Breaker Box/Battery Cabinet indicate “green light” for operation of output switches.
SII-board also integrates input facilities for emergency shut-down and temperature compensation of charge voltage for external battery (also used with battery monitoring). “Battery operation” and “Common fault” are the two main status SII-board relay signals.
4.2.1 Connecting the System Integration Interface Board (SII-board)
SII Board
X004
X012
X001
S002
X003
X005
S001
NOTICE!
If the UPS is equipped with an Emergency Power Off (EPO) facility all input sources must be equipped with disconnecting devices.
Terminal rows: X003 and X004 (auxiliary contacts)
When switching Q001, Q002, Q010, Battery Breaker 1 or Battery Breaker 2 from “ON or 1” to “OFF or 0”, the auxiliary contact must open BEFORE the corresponding main contacts are opened. When switching Q001, Q002, Q010, Battery Breaker 1 or Battery Breaker 2 the opposite way from “OFF or 0” to “ON or 1”, the auxiliary contact has to close with a maximum delay of 0.5 seconds from the time the corresponding main contacts are closed.
• This type of auxiliary contact is called a “late make” contact. (This also means that it will “break early” when activated in opposite direction)
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 25
External Connection
• This auxiliary contact is also called “Normally Open” (NO), because the auxiliary contact will be open when the main contacts are open
• Please note that the above term “NORMALLY” has nothing to do with NORMAL UPS OPERATION MODE
When switching Q003 from “OFF or 0” to “ON or 1”, the auxiliary contact has to open BEFORE the corresponding main contacts are closed. When switching Q003 the opposite way from “ON or 1” to “OFF or 0”, the auxiliary contact has to close with a maximum delay of 0.5 seconds from the time when the corresponding main contacts are opened.
• This type of auxiliary contact is called an “early break” contact. (This also means that it will “make late” when activated in the opposite direction)
• The auxiliary contact is also called “Normally Closed” (NC), because the auxiliary contact will be closed when the main contacts are open
• Please note that the above term “NORMALLY” has nothing to do with NORMAL UPS OPERATION
CAUTION!
All wiring to alarm and signal circuit fields to be rated 300V (minimum).
X005 (output relays) The battery operation signal is received with a 30-second delay. This function is inactive during battery tests. Common fault relay facility is programmable (standard factory setting: 10 sec.) See APC Silcon User Guide for details.
Maximum nominal voltage on contact circuits is 277VAC. If two different phases are involved, maximum phase to neutral voltage should be below 160VAC. Please note that phase L1 is already present on the System Integration Interface board, supplied from the Service Bypass Panel. Therefore, if a phase is needed for alarm or signal purposes, Phase L1 should be used”.
Terminals X001, X003, X005, X004, X012:
Cable size AWG18 to AWG14, use solid copper conductors only.
990-4049
26 Installation Guide APC Silcon 240-320kW 480V UPS
External Connection
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 27
External Connection
990-4049
28 Installation Guide APC Silcon 240-320kW 480V UPS
External Connection
4.3 Parallel Board
CAUTION!
Control cables must be separated from AC and DC power cables.
Parallel Board
The built-in parallel board connects two or more UPS systems in parallel, either to obtain increased system reliability or to obtain higher output power. The parallel board also ensures correct load-sharing between parallel systems.
NOTICE!
For reliability reasons, APC recommends separate battery packs in redundant/parallel configurations.
To prepare the UPS for parallel/redundant mode, disconnect all sources of AC and DC power supply to the UPS and connect the ribbon cable from the parallel board to the main controller board. (The ribbon cable is delivered with the UPS).
CAUTION!
Do not connect ribbon cable in single configurations. Ribbon cable is for parallel operation only.
Complete the parallel system set-up by connecting the external control cables (see below). Follow instructions in section 5.3 Programming of this guide to execute necessary reprogramming.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 29
External Connection
UPS 1 UPS 2 UPS 3
Parallel Board
X020:15-pin SUB-D female X021:15-pin SUB-D female
External multicore cable with 14 wires + shield to other parallel units
990-4049
External Control Cables
External multicore cable has a 15-pin SUB-D male connector at either end. Connect pin 1 to pin 1, and pin 2 to pin 2 etc. up to pin 15 - except pin 8, which need not be connected.
Shield is connected to plug cover at both ends. Terminals X020 and X021 for control cables are located on parallel board. Connect X020 in UPS1 to X021 in UPS2 and X020 in UPS2 to X021 in UPS3 etc. Connect X020 in last UPS to X021 in UPS1. (Cable is delivered with the UPS).
Power Cables
To optimize load-sharing in parallel operation, external power circuits must be “symmetrical”: Power input and output cables must have same length and identical cross-sections.
30 Installation Guide APC Silcon 240-320kW 480V UPS
4.4 Relay Board
External Connection
Relays
All relays are “fail safe”: In alarm modes, relay coil will be de-energized.
Relay shown in alarm position
1
2
3
4.4.1 Relay Board Functions
NOTICE!
If communication to controller lost alarm is active, ALL relays will indicate failure.
Relay Number Message Alarm Trigging Events
1 ## (X002)
Utility Outside Tolerance
Maximum load: 8.0A – 250VAC
0.3A – 60VDC
Minimum load: 0.05A – 6VAC
0.05A – 6VDC
Utility voltage RMS value outside tolerance Utility wave form (fast detector) outside tolerance Utility frequency outside limits
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 31
External Connection
Relay Number Message Alarm Trigging Events
2 ## (X003)
3 ## (X004)
4 (X005)
5 (X006) Fan Fault Blocked or faulty fan
6 (X007)
7 (X008) Battery Breaker Box
8 (X009) Normal Operation UPS running in normal operation (Status)
9 ## (X010)
10 ## (X011)
11 ## (X012)
12 (X013)
13 ## (X014)
14 (X015)
15 (X016)
16 ## (X017)
Bypass Outside Tolerance
Output Outside Tolerance
System Overload Output load over 100%
High Equipment Temperature or Inverter Fuse Blown
Battery OFF
Battery Operation UPS running in battery operation (Status)
Bypass Operation UPS running in bypass operation (Status)
Stand-by Operation UPS in stand-by mode
Service Bypass Operation
Boost Charge Operation
Battery Voltage Outside Tolerance
Battery Condition Fault ABM detected battery weak
Common Fault All alarms as mentioned above (except relays
Bypass voltage RMS value outside tolerance Bypass wave form (fast detector) outside tolerance Bypass frequency outside tolerance
Output voltage RMS value outside tolerance Output wave form (fast detector) outside tolerance Output frequency outside tolerance
Delta inverter current limiter active Main inverter current limiter active
Static switch temperature too high Main inverter failure (temperature too high or fuse blown) Delta inverter temperature too high Magnetics temperature too high Isolation transformer optional temperature too high Battery temperature too high
Battery Breaker Box battery OFF
(Hot stand-by, parallel systems only)
Service bypass switch active
UPS boost charging on battery
DC voltage too high (shut down) DC voltage under warning level DC voltage too low (shut down)
ABM detected defective battery (ABM = Advanced Battery Monitor)
8+9+10+11) Internal power supply fault System locked in operation mode Internal memory fault Internal communication fault
## Delay programmable in XXXXXX stack Common fault delay. Settings 0,10,20,30 seconds. See section 5.2: System configuration in this guide.
990-4049
32 Installation Guide APC Silcon 240-320kW 480V UPS
External Connection
NOTICE!
Alarm Trigging Events 1-2-3-9-10-11-13 activates the corresponding alarm relay after the delay.
Alarm Trigging Events 4-5-6-7-8-12-14-15 activates the corresponding alarm relay momentarily.
Common fault relay 16 is activated at the same time as relay 1-2-3-4-5-6-7-12-13-14-15, or in any of the below situations:
Internal power supply fault
System locked in operation mode
Internal memory fault
Internal communication fault
4.4.2 Cable Sizes
Cable sizes 24 AWG - 12 AWG are suitable. Use copper conductors only. Cable sizes depend on current demand and ambient temperature.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 33
External Connection
4.5 Communication Interface / Smart Slot
The ComInterface having 2 ports - is used when an interaction between UPS and e.g. a computer system has to be established. The main purpose is to ensure monitoring and if needed, a controlled shut down of the computer in case of failures in the utility supply.
4.5.1 Connections
Smart Slot
X005, 25 pin SUB D female. ComPort
X008,25 pin SUB D male. Serial port RS232.
For service use.
4.6 SmartSlot for APC Silcon 240-320kW UPS
A UPS system alone provides excellent protection from brief power problems. However, during an extended power outage an unattended computer system will eventually shut down due to battery capacity exhaustion. To prevent data corruption when the UPS shuts down, the computer must be informed by the UPS of impending shut down and take appropriate file­saving measures. This important function is called UPS monitoring. The UPS's computer interface port is the means by which your UPS communicates with a computer system.
990-4049
34 Installation Guide APC Silcon 240-320kW 480V UPS
External Connection
Some computer operating systems have built-in UPS monitoring. These systems require various hardware interfaces. Interface kits for all major operating systems that support UPS monitoring are available from your dealer.
APC SmartSlot for APC Silcon Series UPS's has been designed for reliable and maintenance­free service in combination with your American Power Conversion (APC) Silcon UPS Series uninterruptible power supply (UPS).
4.6.1 SmartSlot Accessories
SmartSlot at the front of the frame accomodate up to 3 accessory cards. Before installing any SmartSlot accessory, ensure it is a compatible "APC Silcon DUPSK" model.
1. Share-UPS TM, provides automatic shutdown of up to two additional servers.
2. Measure-UPS TM II, provides environmental information such as ambient temperature and humidity.
3. Call-UPS TM, works with an external modem to provide out-of-band UPS manegement
4. WEB/SNMP Management card, provides web based UPS management.
4.6.2 Multiple SmartSlot Installation - introduction
If your UPS configuration uses more than one SmartSlot device, you must install them in the correct order for them to work together properly.
Priority of SmartSlot devices:
A SmartSlot device with higher priority is to be placed in the SmartSlort accessory slot with the higher number. Refer to the following table.
Priority of APC accessories:
Install SmartSlot accessories as dictated by the following table. An accessory with higher priority is to be placed in the accessory slot with the higher number.
Acessory P/N Priority Position
Web/SNMP Management Card AP9606S Highesst High-numbered slot
Call-UPS® // AP9608 Second-highest
Interface expander AP9607 Second-lowest
Measure-UPS® // AP9612T
AP9612TH
Installing accessories – procedure
To install accessories, perform the following steps:
1) Make sure that the APC Silcon UPS is powered off.
2) Install the SmartSlot accessories into the housings on the front of the chassis. See the instructions supplied with the accessories and “Priority of APC accessories.”
Lowest
Low-numbered
If your UPS has one SmartSlot accessory slot
If your UPS has exactly one SmartSlot accessory slot, use this accessory slot for the SmartSlot device with the lowest priority.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 35
External Connection
Installation in APC Silcon 240kW and 320kW
For installation of multiple SmartSlot devices in 240kW and 320kW, refer to the numbering shown in the figure that follows:
1
23
Smart Slot
990-4049
36 Installation Guide APC Silcon 240-320kW 480V UPS
External Connection
4.6.3 APC Silcon Battery Cabinets
IMPORTANT SAFETY INSTRUCTIONS
a) The servicing of batteries requires battery knowledge and should only be carried out or
supervised by qualified electricians familiar with batteries. Keep unauthorized personnel away from batteries.
b) Use identical battery types and numbers when replacing batteries. See battery supplier
manual for further details.
c) CAUTION - Do not dispose of batteries in a fire. Batteries may explode.
d) CAUTION - Avoid rough treatment and opening of batteries. Released electrolyte is harmful
to skin and eyes, and may be toxic.
e) CAUTION - Batteries may cause electric shocks and high voltage short-circuit current.
Follow the precautions below when working with batteries:
1. Remove watches, rings and other metal objects
2. Use tools with insulated handles
3. Wear rubber gloves and boots
4. Do not leave tools or metal parts on top of batteries
5. Disconnect charging source prior to connecting batteries
6. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove unwanted ground source. Any contact with grounded batteries may result in electric shocks. The likelihood of such shocks will be reduced if grounds are removed during installation and maintenance.
Installation and use of this product must comply with all national, federal, state, municipal or local codes. If you need assistance, please have your UPS model and serial number ready and call APC. See “How to Contact APC” in this guide.
Find more information on the APC World Wide Web site at http://www.appc.com.
WARNING!
The entire system contains HAZARDOUS AC/DC VOLTAGES from several power sources. Some terminals and components are live even with the system being switched off!
ONLY qualified electricians may install batteries and national and local codes must be followed.
NO APC Silcon UPS may have built-in batteries if connected to external batteries!
NEVER install batteries not complying with APC specifications. Falling that, the installer takes
over full responsibility!
NEVER lift or transport connected/installed batteries
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 37
External Connection
4.6.3.7 Installation of Batteries
See Installation Guide for Battery Cabinet for:
• Preparing Batteries and UPS
• Dimensions and Weight
• Connecting Batteries
WARNING!
Before proceding, ensure that power supplies have been disconnected from UPS for a minimum of 5 minutes.
CAUTION!
Follow Start-up Procedure in the APC Silcon User Guide.
Diagram - UPS with Battery Cabinet
System Integration Interface
APC Silcon Battery Cabinet
APC Silcon
UPS
Battery Breaker trip for EPO
990-4049
38 Installation Guide APC Silcon 240-320kW 480V UPS
External Connection
4.7 Battery Breaker Box
The APC Battery Breaker Box is required if the UPS is installed with an external battery. The Battery Breaker Box provides overcurrent and short-circuit protection.
Battery Breaker Box
APC Silcon UPS
Battery
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 39
External Connection
4.7.1 Interconnection
NOTICE!
Select wire size based on the data in Table 1 and ampacities in Table 2 of this manual, a reprint of Table 310-16 and associated notes of the National Electrical Code (NFPA 70).
Fixing centres in
rear of enclosure
See measurements
in below table
SKU No. Type UPS Dimensions
SL0901712 Battery Breaker Box
SL0901713 Battery Breaker Box
240kW 480V
320kW 480V
240kW 480V 36.22/920 x 33.46/850
320kW 480V 36.22/920 x 33.46/850
HxWxD* [in/mm]
x 7.09/180
x 7.09/180
Fixing centres
AxB [in/mm]
24.41/620 x 25.59/ 650
24.41/620 x 25.59/ 650
CAUTION!
Check correct polarity when connecting DC cables.
NOTICE!
Terminal for Equipment Grounding Conductor is marked
NOTICE!
For grounding, refer to local legal regulations.
4.7.2 Mounting and Connection of Battery Breaker Box
All AC cables rated 600V.
DC cables must be rated 1000V, unless otherwise stated.
Weight
[lbs/kg])
198 / 90
198 / 90
990-4049
40 Installation Guide APC Silcon 240-320kW 480V UPS
External Connection
4.7.3 UPS with External Battery via Battery Breaker Box
4.8 UPS Installations in Computer Rooms
IMPORTANT! Follow the instructions below when installing UPS-systems in computer rooms:
1. - Only systems with external batteries may be installed.
- All battery cabinets must be UL listed and must be approved for use in computer rooms.
- Refer to APC Design Guide for correct DC disconnection/overcurrent if alternative battery cabinet makes are used.
- All batteries used in computer rooms, must comply with R/C (BAZR2) and must be flame rated according to UL 94V2, UL 94V1 or UL 94V0.
2. The system must be provided with switch gear facility with trip function for all switches for Emergency Power Off function (EPO). See principle diagram below.
3. The system must be provided with EPO function for the disconnection of all AC and DC sources. See principal diagram below.
Activate EPO switch to switch off UPS system. All switch gear switches are tripped. UPS will discharge capacitors within 5 minutes.
Test EPO function at yearly service inspection.
CAUTION!
Remember to secure load prior to EPO testing.
Monitor noise level in computer room when all equipment is in operation (UPS, computers, servers, printers, air conditioning etc.) Take precautionary measures according to Occupational Noise Exposure Recommendation if necessary.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 41
External Connection
4.8.1 EPO Principle
Diagram for Emergency Power Off (EPO) principle has to be established prior to EPO and UPS installations. Battery Breaker Box and switch gear must be installed with “shunt trip”.
Use external power supply from “Utility” and UPS output before reaching Q002, when tripping Battery Breakers and switchgear.
EPO circuit and UPS are interconnected to “OFF” and “ON” push buttons, through the System Integration Interface card terminals X001. On the System Integration Interface card, the selection switch S002 for internal or external power supply may be set.
S002
Choose either: Emergency shutdown connection between:
Position 1, internal supply X001:3 and X001:4
Position 2, external supply X001:1, + 12V and X001:2, GND
EPO switches must have break functions. Supply current loop of 20mA internally or externally by selecting switch S002 on System Integration Interface. Use external supply with 12Vdc or 20mA current generator.
The EPO switch is interconnected to an electronic control system (not available from APC) supplying the Battery Breaker Box and switch gear tripping function with an external 480/ 277Vac 50/60Hz supply from Utility 2 (if available) or Utility 1 and UPS output before Q002.
The combination of 2 break functions (one for UPS system and one for external switch gear) allows for a quick system shutdown in an emergency situation.
NOTICE! Emergency Power Off function requires a special Service Bypass Panel with tripp function
breakers.
990-4049
42 Installation Guide APC Silcon 240-320kW 480V UPS
Principle diagram
Utility 2
Utility 1
Q10
Trip function
Q1
Trip function
Input
Input
Trip function External bat­tery cabinet or battery room
External Connection
All switch gear switches must be provided with trip function
Q3
UPS
Output
EPO X001
EPO SW
Q2
Trip function
Output
Load
All battery breakers in external battery cabinets or battery room must be provided with trip function
User-supplied electronics
For tripping of all battery breaker and switch gear switches
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 43
External Connection
4.8.2 Emergency Power Off (EPO) for UPS
UPS systems installed in a computer room MUST have external batteries with EPO trip­function in Battery Breaker Box and in switch gear.
System Configuration for Dual Utility
Utility 2
Q10
Input
Q3
User-supplied external PSU for tripping of battery breakers in external battery cabinet or battery room and switch gear switches.
UPS
Output
Load
Q2
Utility 1
Dual Utility Matrix
DC Utility 2 Utility 1 Possible UPS operation
0 0 0 Off 0 Nothing to trip
0 0 1 X Under
0 1 0 Bypass operation only 1
0 1 1 Bypass operation only 1
1 0 0 Battery operation only 1
1 0 1 Normal/battery operation 1
1 1 0 Bypass/battery operation 1
1 1 1 Normal/bypass/battery
Q1
Input
External DC
modes
operation
Tripping
Supply
1
Note
installation only
990-4049
44 Installation Guide APC Silcon 240-320kW 480V UPS
Single configuration for Single Utility
Q1
Utility
Input
External Connection
Q3
User-supplied external PSU for
tripping of battery breakers in external
battery cabinet or battery room and
switch gear switches.
Q2
UPS
External DC
Output
Load
Single Utility Matrix
DC Utility Possible UPS operation modes Tripping
Supply
0 0 Off 0 Nothing to trip
0 1 Bypass operation 1
1 0 Battery operation only 1
1 1 Normal/bypass/battery operaiton 1
Note
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 45
Programming
5.0 Programming
Below table shows operating parameters programmable from keyboard. Only qualified users should amend programming parameters.
5.1 Parameters
Parameter Setting* Comments
Bypass operation YES, NO YES will switch the system into bypass
Language GB, D, F, DK, S, SF,
NL, PL, CZ, E, P, SK,
H
Autostart YES, NO Automatic restart by utility return (1 min. delay).
Remote shutdown active YES, NO Shutdown of UPS by remote signal when in
Remote shutdown HIGH, LOW Nature of remote shutdown signal level
Remote shutdown time 0, 1, 2, 3, 4, 5, 6, 7, 8,
9, 10 min.
Battery capacity test Initiates back-up time check. Time measured
Battery monitor test ** Initiates checks of battery condition by 25%
Automatic battery test** OFF, 3,6 months Activates the battery monitor test in cyclic
Battery monitor reset** Press the and key to reset alarm
mode***
Languages of text in display
Ensures quick battery recharge.
battery operation. Saves battery energy.
Time delay on remote shutdown of UPS
from start until it reaches low DC warning level (See User Guide, section 6.0).
discharging.
intervals.
(flashing light).
Boost charge YES, NO YES results in boost charge (10 hours)
Autoboost charge YES, NO YES results in boost charge after battery
Enter new date YYMMDD Set to local date
Enter new time HHMMSS Set to local time (24 hour clock)
* Factory settings in bold ** For stystems with avctive Battery Monitor only *** Do not leave system running in bypass mode (static bypass) for extended periods of time, as
batteries are not recharged in bypass mode.
990-4049
operation (10 hours).
46 Installation Guide APC Silcon 240-320kW 480V UPS
5.1.1 Programming Keys
Display
Alarm LED Green: OK Red: Alarm
Displays time
Exits a mode
Accesses alarm stack
NOTICE!
Display accuracy is ± 1%, ± 1 digit.
Programming
Scrolls up through list
Scroolls down through list
Stores parameter/ enter parameter stack
Silences the audible alarm
/
Chooses parameters
5.1.2 Programming Example - Switch to Bypass Operation
NOTICE!
Do not leave in by-pass mode for extended periods in order not to affect battery capacity.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 47
Programming
Return to normal operation
Follow same procedure to program other parameters.
990-4049
48 Installation Guide APC Silcon 240-320kW 480V UPS
Programming
5.2 System Configuration
System configuration parameters are vital for correct system operation and are password­protected. Incorrect programming may damage battery or cause output voltage to be lost during operation!
System Configuration Parameters (password protected)
Parameter Setting* Comments
Isolation Transformer Input
Isolation Transformer Output
Delta Soft Start Time 1, 10, 20, 40 sec. Input current switching in ramp function. Use
External SSW available YES, NO YES for systems with external static bypass
Normal Charge Voltage 410-460V
Boost Charge Voltage 438-460V
Low Battery warning 336-384V
Low Battery shut-down 310-336V
Synchronization 0.25, 0.5, 1, 2, 4
High Battery Temperature 15-40°C/59-
Common fault delay 0, 10, 20,
Reset operation mode lock YES, NO YES resets system locked in bypass or battery
Expected back-up time (min.)
Battery Capacity in (Ah) 0.1-999.9
Highest Station Address 2-9 Highest station address in parallel system
Station Address 1-9 Station address in parallel system
* Bold text refers to standard factory setting
**Advanced Battery Monitor
YES, NO YES, if optional input isolation transformer is
available
YES, NO YES, if optional output isolation transformer is
available
higher values for smaller/unstable diesel generators
switch
Setting of float charge voltage at 20°C/68°F
438V
438V
346V
326V
Hz/sec.
104°F
35°C/95°F
30 sec.
0.1-999.9
5.0
7.0
(Automatic compensation for temperature deviations)
Setting of boost charge voltage at 20°C/68°F (Automatic compensation for temperature deviations)
Discharged Battery warning
Switches off system at minimum permissible battery voltage
Synchronization speed. Higher values used at unstable utility frequencies.
Alarm - Ambient battery temperature too high
Delay before common fault alarm relay is activated
operation mode caused by system failures (only applicable for service personnel)
Expected UPS back-up time in minutes when running at 100% ohmic load. Time used by ABM**
Total Battery capacity in Ah. Setting used by ABM**.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 49
Programming
Parameter Setting* Comments
APM*** Mode Active Disabled
APM Test Mode Active YES, NO YES, if APM*** test mode is active
Battery Connection Common,
* Bold text refers to standard factory setting **Advanced Battery Monitor ***Advanced Power Management
5.2.1 Programming Example - Change Boost Charge Voltage to 446V
Redundant +1 Parallel +1
Separate
Use only in parallel systems. Disabled: APM*** off. Redundant +1: Redundant operation with one unit being inactive in parallel system Parallel +1: Redundant operation with all units in operation.
Common: if common battery is used in parallel system. Separate: if separate battery is used
NOTICE!
Change charge voltages, battery warning limit, shut down voltages and high battery temperature limit by entering the actual value. See example above.
990-4049
50 Installation Guide APC Silcon 240-320kW 480V UPS
Programming
5.2.2 Programming Example - Change to Output Isolation Transformer Available
NOTICE!
Change parameters by pressing the key once or several times. See example above.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 51
Programming
5.3 Programming Parameters for Advanced Parallel Operation.
To use the advanced parallel functions the following parameters must be programmed:
1. “Station number”
2. “Highest station address”
3. “Advanced power management”
4. “APM test mode active”
5. “Battery connection”
5.3.1 Description of Settings.
1. “Station number”
• Valid station numbers: 1-9 stating the UPS parallel address in system.
2. “Highest station number”
• Valid station numbers: 2-9 stating the number of UPSs in system.
3. “Advanced power management”
• “Disabled”: Advanced Power Management is inactive.
• “PARALLEL+1”: Advanced Power Management is activated when the system operates
• “REDUNDANT+1”: Advanced power management is activated when the system
4. “APM test mode active”
• “No”: Stand-by-time will be 24 hours - on-line time will be 48 hours. (xN systems).
• “Yes”: Stand-by-time will be 1 min. - on-line time will be 2 min. (xN systems).
5. “Battery connection”
• “Separate”: Separate battery for this UPS.
• “Common”: Common battery in a parallel system.
as PARALLEL N+1, meaning that one system can be isolated without overloading the remaining systems (N systems/UPSs).
operates as REDUNDANT N+1, meaning that one system can be isolated without overloading the remaining systems (N systems/UPSs) with one spare system.
NOTICE!
Common: Common battery in a parallel system. When this setting is chosen, the highest battery temperature that can be found in the parallelled systems is used (for charge voltage compensation).
NOTICE!
Common battery pack is a technical possibility. However, APC recommends separate battery pack due to a higher safety degree in connection with redundant/parallel operation. The UPS system is designed for both situations.
5.3.2 Programming Example
Example with four systems in parallel with separate batteries.
• Program the station addresses 1-4: 1 for UPS 1, 2 for UPS 2, 3 for UPS 3, and 4 for UPS
4.
• All UPS systems have to be programmed to “Highest station address” :4.
990-4049
52 Installation Guide APC Silcon 240-320kW 480V UPS
Programming
• If APM should not be tested, “APM test mode active” must be “NO”.
• If a system is isolated due to service the station numbers must be reprogrammed for the
remaining active systems starting with number 1 and ending with maximum number of active systems. No numbers must be left in this sequence. Furthermore, “Highest station address” must be changed to number of active UPS’s in parallel.
5.4 Battery Monitor
Installation of new batteries:
To avoid false alarms, the above procedure MUST be followed.
NOTICE!
Contact your local dealer if you have any questions regarding changing parameters.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 53
Options/Accessories
6.0 Options/Accessories
6.1 Diagrams for Service Bypass Panel for Single Operation, Single and Dual Utility
Principle diagram: Service Bypass Panel for single operation
Service bypass Panel
System input
System output
APC Silcon
UPS
Battery
Battery Breaker Box
990-4049
54 Installation Guide APC Silcon 240-320kW 480V UPS
Options/Accessories
6.1.0.1 APC Silcon UPS with Service Bypass Panel and External Battery via Battery Breaker Box (Single Utility) 3-wire grounded WYE service
Utility input 1
System
Output
Service Bypass Panel
APC Silcon UPS
System Integration Interface
Battery Breaker Trip for EPO
Temp. sensor
Battery 2
Battery Breaker Box
Battery 1
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 55
Options/Accessories
6.1.0.2 APC Silcon UPS with Service Bypass Panel and External Battery via Battery Breaker Box (Dual Utility) 3-wire grounded WYE service
System
Output
Utility input 1
APC Silcon UPS
Utility input 2
Service Bypass Panel
Grounding Electrode
System Integration Interface
Battery Breaker Trip for EPO
Temp. sensor
Battery 2
Battery Breaker Box
Battery 1
990-4049
56 Installation Guide APC Silcon 240-320kW 480V UPS
Options/Accessories
6.1.0.3 Mounting and Connecting
NOTICE!
φ “phase
risk of electric shock
Terminal for Equipment Grounding Conductor
E Terminal for Grounding Electrode Conductor
NOTICE!
For grounding, refer to local legal regulations.
NOTICE!
Check correct phase connection of inputs and outputs.
Wiring
Select wire size based on the data in Table 1, and the ampacities in Table 2 of this manual, a reprint of Table 310-16 and associated notes of the National Electrical Code (NFPA 70).
Use commercially available UL approved solderless lugs for the wire size required for your application. Connect wire to the lug using tool and procedure specified by the lug manufacurer.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 57
Options/Accessories
6.1.0.4 Service Bypass Panel for parallel redundant operation, single Utility
Principle Diagram: Service Bypass Panel for redundant operation.
Service Bypass Panel
System input
Control
cables
System output
APC Silcon UPS
Battery
Battery Breaker Box
Battery
APC Silcon UPS
990-4049
58 Installation Guide APC Silcon 240-320kW 480V UPS
Options/Accessories
6.1.0.5 Parallel/Redundant UPS with Service Bypass Panel and External Battery via Battery Breaker Box (Single Utility) 3-wire grounded WYE service
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 59
Options/Accessories
6.1.0.6 Parallel/Redundant UPS with Service Bypass Panel and External Battery via Battery Breaker Box (Dual Utility) 4-wire grounded WYE service
990-4049
60 Installation Guide APC Silcon 240-320kW 480V UPS
Options/Accessories
6.1.0.7 Mounting and Connecting
NOTICE!
φ “phase
risk of electric shock
Terminal for Equipment Grounding Conductor
E Terminal for Grounding Electrode Conductor
NOTICE!
For grounding, refer to local legal regulations.
NOTICE!
Check correct phase connection of inputs and outputs.
Wiring
Select wire size based on the data in Table 1, and the ampacities in Table 2 of this manual, a reprint of Table 310-16 and associated notes of the National Electrical Code (NFPA 70).
Use commercially available UL approved solderless lugs for the wire size required for your application. Connect wire to the lug using tool and procedure specified by the lug manufacturer.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 61
Options/Accessories
6.2 Seismic Anchoring
69.36/1762
67.79/1722
49.76/1264
48.18/1224
990-4049
28.28/7185
3.21/815
28.11/714
26.53/674
7.01/178
5.43/138
0
0
62 Installation Guide APC Silcon 240-320kW 480V UPS
Options/Accessories
7
8 seismic angles
6.2.1 Mounting Seismic Anchoring
Drill 16 holes for Ø10mm bolts at installation site according to dimensioned sketch.
With the holes drilled in the UPS, position the system correctly and slide the 8 seismic anchoring angles into the bars (see illustration above). Tighten the angles in the holes, using bolts and plain washers.
NOTICE!
Tighten all bolts in all 8 angles to the floor. Floor bolts not supplied
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 63
Options/Accessories
6.3 NEMA 12 Cover (IP31)
77.75/1975 in/mm
76.37/1940 in/mm
74.80/1900 in/mm
6.89/175 in/mm
NOTICE!
NEMA 12 cannot be used with top cable entry.
6.3.1 Mounting NEMA 12 Cover
• Replace all screws on the top cover (1) with distance stays (3) and plastic locking (2)
• Mount NEMA 12 cover with plain washer (4), spring washer (5), and screw (6) on the
4 distance stays
6
5
3
2
1
4
990-4049
64 Installation Guide APC Silcon 240-320kW 480V UPS
Options/Accessories
6.4 Remote Display
With the remote display unit data may be displayed at distances of up to 25m from UPS. For extended communication distance, see below.
Remote display may easily be connected to UPS via one of the two serial communication ports on the communication interface board.
To obtain a transmission distance of up to 3.2km normal RS232C signal levels must be converted to a long distance communication standard. The converter must be placed outside the UPS cabinet.
6.4.1 Extension of Remote Display Communication Distance
The remote display communicates with the UPS through a 3-wire RS232 interface. The remote display is a DTE (Data Terminal Equipment) employing a SUB-D 9-pin female connector. Communication speed: 9600 bps.
For communication distances, see table below. Insert converters if longer distances are necessary, or if communication cables are led through magnetically noisy areas. Converters must comply with local regulations
Remote Display Communication Extensions
Standard (RS232)
Max. distance 80/25 ft/m 10000/3200 ft/m
Converter Manufacture Art. Code
RS232 BLACK BOX connector Sub-D 25-pin female
BLACK BOX interconnector 4-screw terminal
Two converter boxes are required for a communication distance extension: One box near the UPS for the conversion from RS232C to a long distance communication standard, and another box at the other end to convert back to RS232C, which is to be connected to the
No converter BLACK BOX
Short-haul Modem Async
ME800A-R2
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 65
Options/Accessories
Remote Display. The converter provides optical signal isolation. Both converter boxes must be supplied by an uninterruptible power source.
6.4.1.1 Connections Without Converter
Connect a 25-pin female Sub-D and a 9-pin male Sub-D connector with a 3-wire shielded cable, as shown in the table below. Connect shield at one end only.
Pin Connection for Interconnection Cable (without converter)
Host (DTE) Remote Display (DTE)
25-pin female pin No.
2 (TXD) 2 (RXD)
3 (RXD) 3 (TXD)
7 (GND) 5 (GND)
House (shield) No Connection
6.4.1.2 Connections With Converter
Connections to be made according to converter manual.
Pin connection example only:
Pin Connections for cable from host to ME800A-R2.
Host (DTE)
25-pin female pin No.
2 (TXD) 3 3 2 (RXD)
ME800A-R2 (DCE)
25-pin male pin No
9-pin male pin No.
Pin connection for cable from ME800A-R2 to Remote Display
ME800A-R2 (DCE)
25-pin male pin No
Remote Display (DTE)
9-pin male pin No
3 (RXD) 2 2 3 (TXD)
7 (GND) 7 7 5 (GND)
House (Shield) No connection No connection House (Shield)
The ME800A-R2 must be set up as a DCE with no RTS/DTR control.
The interconnection cable between the two ME800A-R2 boxes is a 4-wire twisted pair telephone cable with or without shield. The shield improves noise immunity but reduces maximum communication distance.
990-4049
66 Installation Guide APC Silcon 240-320kW 480V UPS
Options/Accessories
6.4.2 Remote Display Installation
6.4.2.1 Connecting RS232C and Utility Adapter
CAUTION!
Wiring for alarm and signal circuit field to be rated 300V (minimum).
Rear view Front view
screws
Cable entry from bottom and rear
1. Turn 180° to loosen the 4 screws
2. Remove front cover
6.4.2.2 Remote Display Power Supply
3. Mount back plate
4. Connect cables
Rear view
DP9-F Utility adapter
The remote display is supplied by normal AC power with no battery back-up. For UPS data transmission to remote display to remain unaffected during power failure, the remote display must be supplied from an uninterruptible power source.
Converters used to extend communication distance must also be supplied from uninterruptible power sources.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 67
Options/Accessories
6.4.2.3 Remote Display Cables
RS232C to RS232C cable:
APC Silcon, DB25-F
X
NOTICE!
Connect shield at one end only
Rating: Refer to Local/National electrical codes. Communication voltage ±15V
6.4.3 Remote Display Use
The remote display is an inactive unit unable to influence the operation of the UPS: Some of the alarms visible on the internal display are also available on the remote display (See the Alarm section in the APC Silcon User Guide).
6.4.3.1 Initiating the Remote Display
After having connected the supply the display will show:
Remote Display: “APC Silcon UPS”
DC
Remote Display, DB9-M
6.4.3.2 Communication Fault
Communication fault between UPS and remote display will appear in the display as follows:
“Data transmission interrupted”
6.4.3.3 Remote Display Setting
Use # Stack to select language and type of UPS connected to remote display.
Parameter Setting Comments
Language GB,D,F,DK, S, SF,NL, PL, CZ,
E, P, SK, H, I
Host SDC charger, DP300E, 300E Type of UPS connected to
6.4.3.4 Operation
See Operation section in the APC Silcon User Guide.
990-4049
Language
remote display
68 Installation Guide APC Silcon 240-320kW 480V UPS
Options/Accessories
6.4.3.5 Display of Measured Value
See Display of Measured Value in the APC Silcon User Guide. Time reading and utility 2 current not visible from remote display.
6.4.3.6 Alarms
See Alarms section in the APC Silcon User Guide.
6.5 Isolation Transformer Module
CAUTION!
Use only one type of isolation transformers for dual utility input.
Isolation transformer modules can be used in the following configurations:
1. Between utility supply and UPS input, in a 3-phase Delta-service-phase or midpoint of 2 phases (grounded)
2. Between utility supply and UPS input for galvanic isolation
3. Between UPS output and load for galvanic isolation
4. Between UPS output and load for voltage stepping from 480V - 208V/Y 120V required
Do not use switch gear to bypass isolation transformers. If bypassed, damaging circulation currents may occur, even with a unity turn ratio.
Coupling Methods
Configuration of isolation transformers is as Delta-WYE with accessible neutral (Dyn11)
NOTICE!
Check correct phase connection of inputs and outputs.
CAUTION!
At 100% switch mode load, the neutral must be rated for 173% output phase current.
Recommended use:
• 3 wires in/out
• 3 wires in/4 wires out
• 4 wires in/out
NOTICE!
All external cable dimensions are recommeded sizes only. Refer to local regulations.
6.5.1 Requirements on Site
All isolation transformer parts are accessible from front or top (cable entries accessible from bottom). Isolation transformer may be placed close to walls, allowing free space for the front door to open. Allow free space for ventilation slots for sufficient cooling. Do not expose isolation transformers to direct sunlight.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 69
Options/Accessories
NOTICE!
For grounding, refer to local legal regulations.
NOTICE!
φ “phase
risk of electric shock
Terminal for Equipment Grounding Conductor
E Terminal for Grounding Electrode Conductor
NOTICE!
The terminals marked and are electrically connected to terminals E.
6.5.2 Cabinets and Dimensions
See the Installation Guide for Isolation Transformer.
6.5.3 Footprints
See the Installation Guide for Isolation Transformer
6.5.4 Connecting Isolation Transformer
See the Installation Guide for Isolation Transformer
6.5.4.1 External Temperature Alarm Cable*
Voltage rating must be 600V. Cable size can be 18 ot 14 AWG.
6.5.5 Recommended Cable Lugs and Crimping Tools
See section 4.1.6
990-4049
70 Installation Guide APC Silcon 240-320kW 480V UPS
Options/Accessories
6.5.6 Isolation Transformer - Diagram Delta WYE configuration (Dyn11)
X001 X002
L1
L1
Input
L2
L3
G
6.5.7 Isolation Transformer Grounding
6.5.7.1 System Grounding
See the installation guide for Isolation Transformer.
6.5.7.2 Equipment Grounding
L2
L3
N
E
G
X003
1
2
Output
Temperature alarm
Terminal marked is intended for equipment grounding.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 71
Options/Accessories
6.5.8 Principale Diagrams for Isolation Transformer
6.5.8.1 Single Utility and Single System Diagram
Service Bypass Panel
Utility Supply
6.5.8.2 Single Utility and Redundant System
Service Bypass Panel
Utility Supply
Output
Output
990-4049
72 Installation Guide APC Silcon 240-320kW 480V UPS
6.5.8.3 Dual Utility and Single System
Service Bypass Panel
Utility Supply 2
Utility Supply 1
6.5.8.4 Dual Utility and Redundant System
Options/Accessories
Output
Utility Supply 2
Utility Supply 1
Service Bypass Panel
Output
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 73
Options/Accessories
6.6 Intersystem Synchronization Unit
Intersystem Synchronization Unit System (ISU System)
The ISU system consists of inter-connected ISUs. One ISU system may consist of up to 5 ISUs, regardles of ISU configuration. The ISU system synchronizes the voltage of parallel operation systems running in battery operation.
The ISU system may also include one or more external synchronization sources, e.g. a gen-set or a non-APC Silcon UPS system.
Synchronization accuracy of the ISU is better than 2
Schematic overview of ISU system (example):
UPS 1B
Parallel Operation
UPS 1A
UPS 3A
System 1
ISU
1
ISU
3
Parallel Operation System 3
UPS 1C
ISU System
UPS 3C
o
.
UPS 2A
UPS 2B
Parallel Operation System 2
ISU
2
ISU
4
ISU
5
UPS 2C
Ext. sync Source
UPS 4
UPS 3B
Intersystem Synchronization Unit (ISU)
The ISU is an active part of an ISU system, serving as the interface to the sources and the ISU system.
The ISU can be connected to a parallel UPS configuration, using the standard parallel communication controller in the parallel operation system.
(See Intersystem Synchronization Unit User’s Manual for further details.)
990-4049
74 Installation Guide APC Silcon 240-320kW 480V UPS
7.0 System Specifications
7.1 Technical Data
Voltage 3x480V
Voltage tolerance Normal operation Normal operation
System Specifications
±15% ±10% standard ±4, 6 8% (programmable)
Input
Output
60Hz
Frequency
Input power factor
Current distortion Max. 5%
Voltage 3x480V
Voltage tolerance
Voltage distortion
Load power factor 0.9 lead to 0.8 lag
Frequency
Overload capacity Normal operation Normal operation Battery operation Bypass operation
±6 standard ±0.5-8% (programmable)
load 25% minimum 0.97 load 100% minimum 0.99
±1% static, symmetrical load ±3% static, symmetrical load ±5% 0-100% load step
Max. 3%, linear load Max. 5%, non-linear load
60Hz (utility synchronized) ±0.1% free running
200% - 60 seconds 125% - 10 minutes 150% - 30 seconds 125% - continuous
0-40°C/32-104°F (Temperatures
General
Ambient temperature
Humidity Protection class Safety Emission and Immunity Static bypass switch Auto restart Economy mode
above 25°C/77°F will reduce battery life time)
Max. 95% non-condensing NEMA1 UL 1778 FCC ClassA Built-in Programmable Programmable
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 75
Appendix
8.0 Appendix
8.1 Table 1. Installation Planning Data
Service (480V 3 Phase, 3 or 4 wire grounded Wye)
Bypass input breaker
*
Q3
Service Bypass Panel
Main Input Breaker*
Field
Wiring*
Q1
Q2
Load
(480V
3 Phase,
3 or 4 Wire)
UPS Module
Field Wiring*
Battery Bank
* Supplied by others
Input must be limited to less than 50 kAIC
Installation Planning Data
APC Silcon Series
AC Input (480V) Battery System DC AC Output (480V)
Power rating Service Load side Heat
Source P (kW) I (A) Min. Input Over- Full I
kW kVA Pf V Hz Nom. Max. Nom. Max.
120 120 1 480 60 126.8 140.0 152.5 168.0 1 x 4/0 225AT 2x384 127.0 166 194.8 144.0 200AT 23.2
160 160 1 480 60 167.5 186.0 201.5 224.0 1 x 350mcm 300AT 2x384 168.8 220 258.9 192.0 250AT 25.6
240 240 1 480 60 252.9 280.0 304.2 336.0 1 x 700mcm /
320 320 1 480 60 334.4 373.0 402.2 448.0 2 x 350mcm 600AT 2x384 335.4 437 514.4 385.0 500AT 49.1
400 400 1 480 60 415.8 460.0 500.1 560.0 2 x 350mcm 700AT 2x384 421.9 549 647.1 482.0 600AT 35.9
500 500 1 480 60 519.2 574.0 624.5 700.0 2 x 700 /
Notes 1 2 3,6,8,A,B,C,D 4,7,9,D 5 6,10 6,11 4,6,8,D 12
* Not provided by APC
Cable
(per phase)
2 x 4/0
3 x 350mcm
current
Protection*
450AT 2x384 252.1 328 386.7 289.0 400AT 44.0
900AT 2x384 525.8 685 806.4 602.0 800AT 65.5
V
(Vdc)
n
load
P(kW)
NomIMax
Disch
Disch
(A)
(A)
(A)
I
n
Protection*
Over- Rejec-
current
tion
kBTU/hr
Notes:
1. Nominal (Nom) Input current based on rated load.
2. Maximum (Max:) Input current based on full battery recharge + nominal load.
3. Recommendation: Input and Output cables run in separate conduits.
4. Suggested Input overcurrent protection based on continuous full load
Maximum Input current. Suggested Load Side Overcurrent Protection based on Nominal current. Breakers sized per NEC 220-3 and NEC 240-3(b). 80% rated breakers assumed. Trip rating based on
NEC 240-6(a) standard breaker sizes.
5. Nominal battery voltage assumed to be 2.0 volts/cell (lead technology).
6. Recommendation: All cables should be sized in accordance with NEC 210-19 FPN No. 4
branch feeder voltage drop of 3%. Voltage drop not considered in above chart. Application
990-4049
76 Installation Guide APC Silcon 240-320kW 480V UPS
Appendix
specific Input Cable ampacities may vary from above chart.
7. Breaker/Fuse selection based on Nom input current is acceptable provided battery recharge time is short. Consult factory for application specific assistance.
8. Grounding conductor ampacities: Refer to NEC Article 250-122 and NEC Table 250-122. Neutral conductors ampacities: Refer to NEC Article 310-15.
9. All wiring to be in accordance with all applicable national and/or local electrical codes.
10. Nominal Battery Discharge current based on full rated load, and nominal Battery voltage.
11.Maximum Battery Discharge current based on full rated load at end of Discharge.
12. Heat rejection calculated at nominal full load capacity.
A.Not more than 3 current carrying conductors in raceway assumed; ambient temperature of 30°C (86°F) assumed. Cable ampacity next size above Overcurrent Protection provided by others. B. Temperature rating of conductors: 90°C (194°F). Reference Table 310-16 of NEC, 75°C column, using copper conductors. 75°C (167°F) cable terminal connectors assumed. C.Reference: NEC handbook 1999. Consult local codes for possible variations. D.All cable and breaker/fuse ratings are supplied as guidelines only. These guidelines are minimum recommendations only not substitutes for review and compliance with NEC and local codes. Consult with your licensed engineer for site specific applications.
8.2 Table 2 – Table 310-16
Allowable Ampacities of Insulated Conductors rated 0-2000 Volts, 60° to 90°C (140° to
1
194°F)
Not More than Three Conductors in Raceway or Cable or Earth (Directly Buried), based on Ambient
Temperature of 30° (86°F)
Size Temperature Rating of Conductor (See Table 310-13) Size
AWG
or
kcmil
18
16 14* 12* 10*
8*
6 4 3 2 1
60°C
(140°F)
Types
TW
UF
– –
20 25 30 40
55 70 85 95
110
75°C
(167°F)
Types
FEPW,
RH,RHW,
THHW,
THW, THWN, XHHW,
USE, ZW
Copper
[A]
– –
20 25 35 50
65
85 100 115 130
90°C
(194°F)
Types TBS,SA, SIS,FEP,
FEPB,MI,
RHH,RHW-2
THHN, THHW, THW-2,
THWN-2,
USE-2,
XHH,XHHW,
XHHW-2,
ZW-2
14 18 25 30 40 55
75
95 110 130 150
60°C
(140°F)
Types
TW
UF
Aluminum or Copper-Clad
– – –
20 25 30
40 55 65 75 85
75°C
(167°F)
Types
RH,
RHW,
THHW,
THW, THWN, XHHW,
USE
Aluminum [A]
– – –
20 30 40
50 65 75 90
100
90°C
(194°F)
Types
TBS,SA
SIS, THHN, THHW,
THW-2,
THWN-2,
RHH,
RHW-2,
USE-2,
XHH,
XHHW,
XHHW-2,
ZW-2
– – –
25 35 45
60 75
85 100 115
AWG
kcmil
or
– – –
12* 10*
8
6 4 3 2 1
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 77
Appendix
1/0 2/0 3/0 4/0
250 300 350 400 500
600 700 750 800 900
1000 1250 1500 1750 2000
Ambi-
ent
Temp.
(°C)
21-25 26-30 31-35 36-40 41-45 46-50 51-55 56-60 61-70 71-80
1)
Reprinted with permisson of NFPA 70 - 1999, National Electrical Code ®, copyright © 2000. This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety.
125 145 165 195
215 240 260 280 320
355 385 400 410 435
455 495 520 545 560
For ambient temperatures other than 30°C (86°F), multiply the allowable
ampacities shown above by the appropriate factor shown below.
1.08
1.00
0.91
0.82
0.71
0.58
0.41
– – –
150 175 200 230
255 285 310 335 380
420 460 475 490 520
545 590 625 650 665
1.05
1.00
0.94
0.88
0.82
0.75
0.67
0.58
0.33
170 195 225 260
290 320 350 380 430
475 520 535 555 585
615 665 705 735 750
CORRECTION FACTORS
1.04
1.00
0.96
0.91
0.87
0.82
0.76
0.71
0.58
0.41
100 115 130 150
170 190 210 225 260
285 310 320 330 355
375 405 435 455 470
1.08
1.00
0.91
0.82
0.71
0.58
0.41
– – –
120 135 155 180
205 230 250 270 310
340 375 385 395 425
445 485 520 545 560
1.05
1.00
0.94
0.88
0.82
0.75
0.67
0.58
0.33
-
135 150 175 205
230 255 280 305 350
385 420 435 450 480
500 545 585 615 630
1.04
1.00
0.96
0.91
0.87
0.82
0.76
0.71
0.58
0.41
1/0 2/0 3/0 4/0
250 300 350 400 500
600 700 750 800 900
1000 1250 1500 1750 2000
Ambient
Temp.
(°F)
70-77 78-86 87-95
96-104 105-113 114-122 123-131 132-140 141-158 159-176
990-4049
78 Installation Guide APC Silcon 240-320kW 480V UPS
Warranty
9.0 Warranty
9.1 APC Silcon Series® Limited Factory Warranty
APC warrants that the unit, when properly installed and commissioned by APC or APC authorized service personnel, shall be free from defects in materials and workmanship for a period of (1) year from the date of installation or maximum 18 months after manufacturing. In the event that the unit fails to meet the foregoing warranty, APC shall for a period of one (1) year repair or replace any defective parts, without charge for on-site labor and travel if trained & authorized APC personnel has conducted start-up of the unit.
An APC Start-Up Service must be performed/completed by APC or APC authorized service personnel or the on-site factory warranty will be voided and replacement of defective parts only will be covered. APC shall have no liability and no obligation to repair the installed unit if non-authorized APC personnel performed the start-up and such start-up caused the unit to be defective.
APC SHALL NOT BE LIABLE UNDER THE WARRANTY IF ITS TESTING AND EXAMINATION DISCLOSE THAT THE ALLEGED DEFECT IN THE PRODUCT DOES NOT EXIST OR WAS CAUSED BY PURCHASERS OR ANY THIRD PERSONS MISUSE, NEGLIGENCE, IMPROPER INSTALLATION OR TESTING, UNAUTHORIZED ATTEMPTS TO REPAIR OR MODIFY, OR ANY OTHER CAUSE BEYOND THE RANGE OF THE INTENDED USE, OR BY ACCIDENT, FIRE, LIGHTNING OR OTHER HAZARD.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. APC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. APCS EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, APCS RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE, CONSTITUTE APCS SOLE LIABILITY AND PURCHASERS EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. APCS WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES.
990-4049
Installation Guide APC Silcon 240-320kW 480V UPS 79
How to Contact APC
10.0 How to Contact APC
APC Corporate
132 Fairgrounds Road West Kingston, RI 02892 USA
Telephone: 401 789-573 Fax: 401 789-3710
PowerFax™ : 800 347-FAXX
Pre-sales Technical Support 877-474-5266 (1-877-4Silcon)
Post-sales Technical Support 877-287-7835 (1-877-2UPS-TEK)
Web: www.apcc.com/support/contact/contact_support.cfm
APC Denmark
Silcon Allé DK-6000 Kolding Denmark
Telephone: + 45 75 54 22 55 Fax: + 45 72 19 03 50
Pre-sales Technical Support + 45 72 19 04 90
Post-sales Technical Support + 353 91 70 2000
Web: www.apcc.com/support/contact/contact_support.cfm
990-4049
80 Installation Guide APC Silcon 240-320kW 480V UPS
Loading...