Read the instructions carefully to become familiar with the equipment before trying to install, operate,
service or maintain it. The following special messages may appear throughout this manual or on the
equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The additi on of this symbol to a Caution product safet y label indicates that a hazard exists that can result in
injury and product damage if the instructions are not followed.
The following safety messages may appear throughout this manual to warn of potential hazards.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in equipment damage and minor or
modera te in jury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in equipment damage.
™
Safety and General Information
Inspect the package contents upon receipt. Notify the carrier and dealer if there is any
damage.
Read the Safety Guide supplied with this unit before installing the UPS.
• Adhere to all local and national electrical codes.
• This UPS is intended for indoor use only.
• Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or
humidity.
• Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
• The battery typically lasts f or two to five years. Environmental factors impact battery life. Elevated
ambient temperatures , poor qual ity utility power, and frequent short duration discharges will shorten
battery life.
• Connect the UPS power cabl e directly to a wall outlet. Do not use surge protectors or extension cords.
• The batteries are heavy. Remove the batteries prior to installing the UPS in a rack.
• Always install external batte ry packs (XLBPs) at the bottom of the rack. The UPS must be installed
above the XLBPs.
• The UPS display interface will recognize as many as 10 external batte ry packs connected to the UPS.
However there is no limit to the number of XLBPs that can be used with the UPS.
• Refer to Specifications in the Operation manual for UPS and battery weight.
Inventory
Inspect the contents upon receipt. Notify the carrier and dealer if the unit is damaged.
Included with all models
1 pair rail cleats
8 pan head screws
1 pair tower stabili ze r br ac kets
Use 8 flat head screws to secure tower stabilizer brackets to the UPS
1 pair rack-mount brackets
Use 8 flat head screws to secure rac k-mo unt brackets to the UPS
Use 4 ornamental screws to secur e rack-m ount brackets to the rails
Install a cage nut in the rack to secure the top hole of each rack-mount
bracket in a four post rack
Rack-mount support brackets and hardware
1 pair support
brackets
Tw o pos t racks
10 screws
Four post racks
6 screws
6 washers
Included with High Voltage (HV) models
(1) Documentation CD
(1) PowerChute software CD
Included with models that have factory installed
Network Management Cards
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U2
Product Overview
su0343a
Electric
su0756a
GROUP 1GROUP 2
su0757a
Front panel features
1 Online LED
2 Power
3 On Battery LED
4 Site Wiring Fault LED
5 Replace Bat t e ry LED
6 LCD display screen
APC by Schneider
7
8
9
Rear panel features
1 SmartSlot7 Controllable Outlet Group 3
2 Chassis ground screw8 External battery pack connector
3 UPS utility power input9 EPO connector
4 Circuit Breaker reset: Serial port
5 Controllable Outlet Group 1; USB port
6 Controllable Outlet Group 2
ON/OFF button
UP/DOWN arrow keys
ENTER key
ESC key
2000 VA, 120 Vac Low V oltage3000 VA, 120 Vac Low Voltage
GROUP 3
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U3
2200/3000 VA, 230 Vac High Voltage3000 VA, 208 Vac Hig h Voltage
su0755a
su0754a
su0760a
GROUP 1
GROUP 2
GROUP 3
GROUP 1GROUP 3GROUP 2
Remove Battery
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
• The UPS + the battery weighs 41 kg (90.4 lb).
• The battery weighs 23.8 kg (52.4 lb). Remove the battery before installing the unit in a rack.
• Use the battery handle to lift and slide the battery out of the UPS.
Failure to follow these instructions can result in equipment damage and minor or moderate injury
123
su0758a
su0759a
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U4
Tower Configuration
su0774a
12
su0761a
s
u
0
7
6
3
a
34
s
u
0
7
6
4
a
5
su0762a
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U5
Rack-Mount Configuration
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• The equipment is heavy. Always practice safe lifting techniqu es adequate for the weight of the equipment.
• The UPS + the battery weighs 41 kg (90.4 lb).
• The battery weighs 23.8 kg (52.4 lb). Remove the battery before installing the unit in a rack.
• Use the battery handle to lift and slide the batt ery out of the UPS.
Failure to follow these instructions can result in equipment damage and minor or moderate injury
Tower to rack-mount conversion
12
s
u
0
7
6
4
b
s
u
0
7
6
3
b
34
b
3
8
5
0
u
s
su0761b
56
s
u
0
7
6
9
a
6
6
7
0
u
s
a
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U6
CAUTION
su0776a
7
7
0
a
DAMAGE TO EQUIPMENT OR PERSONNEL
• When installing equipment in a rack, always install external battery packs at the bottom of the rack.
• The UPS should always be installed above the external batter y pac ks in rack or stack configurations .
Failure to follow these instructions can result in equipment damage and minor or moderate injury
Two post r ack installation
s
u
123
s
u
0
7
6
8
a
456
su0773a
0
su0771a
su0772a
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U7
Four post rack installation
su0777a
Use an APC by Schneider Electric four post rail kit. To order the rail kit go to the APC by Schneider Electric
W eb site apc.com.
123
a
8
7
7
0
u
s
45
a
9
7
7
0
u
s
a
0
8
7
0
u
s
67
a
1
8
7
0
u
s
a
2
8
7
0
u
s
UPS Configuration
Connect Emergency Power Off feature
For instructions on how to connect the Emergency Power Off (EPO) switch, refer to the Operation and
Maintenance manual on the Documentation CD (supplied).
Configure controllable outlet groups
The outlets on the UPS are configured into groups. To utilize the controlled outlet features, use the
Advanced menus on the display interface and navigate to: Main Menu > Control > Outlet1 Control.
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U8
Electrical connections
CAUTION
RISK OF EQUIPMENT DAMAGE
• Adhere to all local and national electrical codes.
• Wiring should be performed by qualified electrician.
• Always connect the UPS to a grounded outlet.
Failure to follow these instructions can result in equipment damage
S
P
U
E
i
n
o
r
t
c
e
l
e
c
i
v
e
D
c
n
o
r
t
c
e
l
E
e
c
i
v
e
D
c
i
su0788a
Smart-UPS X 2000/2200/3000 VA XL Tower/Rack-Mount 4U9
®
Select models are ENERGY STAR
qualified.
For more information go to www.apc.com/site/recycle/index.cfm/energy-efficiency/energy-star/