American Power Conversion 208-220 User Manual

Smart-UPS® VT
10-30 kVA
208/220 V
Site Preparation and
Installation Manual
Smart-UPS® VT 10-30 kVA 208/220 V
Site Preparation and Installation Manual
IMPORTANT SAFETY INSTRUCTIONS –
SAVE THESE INSTRUCTIONS
This manual contains important instructions for the SUVT series that should be
followed during installation and maintenance of the UPS and Batteries
Smart-UPS® VT 10-30kVA, 208V, Site Preparation and Installation 990-1598A 1
Contents
Safety .....................................................................1
General Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Symbols used in this guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Environmental symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
General safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Introduction ............................................................3
UPS Family Range and Components . . . . . . . . . . . . . . . . . . . . . 4
13.85 in/352 mm Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
20.59 in/523 mm Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Serial number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Type label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
User interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Connection Interface (rear) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Foot print . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
APC Network Management Card AP9619 (installed in UPS)
and APC Humidity Sensor (Optional) . . . . . . . . . . . . . . . . . . . . . 9
Site Preparation .....................................................10
Installation Space Requirements . . . . . . . . . . . . . . . . . . . . . . . 10
Clearance for 20.59 in/523 mm Enclosures . . . . . . . . . . . . . . . 10
Clearance for stand-alone 13.85 in/352 mm Enclosures . . . . . . 11
Operating Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Heat dissipation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Audible noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Recommended current protection . . . . . . . . . . . . . . . . . . . . . . 13
Minimum breaker settings for 10 kVA UPS . . . . . . . . . . . . . . . . 13
Minimum breaker settings for 15 kVA UPS . . . . . . . . . . . . . . . . 14
Minimum breaker settings for 20 kVA UPS . . . . . . . . . . . . . . . . 14
Minimum setting of breakers for 30 kVA UPS . . . . . . . . . . . . . . 14
Recommended phase-conductor sizes [AWG] for a 86°F
(30°C) temperature environment . . . . . . . . . . . . . . . . . . . . . . . 15
EPO switch wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual i
Basic Wiring Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Site Preparation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Mechanical assembly ............................................ 18
Stabilizing Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Leveling Feet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Floor Anchoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Drilling floor holes for floor anchoring . . . . . . . . . . . . . . . . . . . 20
Hole positions for floor anchors (stand-alone Enclosures) . . . . . 20
Floor anchoring of stand-alone systems . . . . . . . . . . . . . . . . . . 21
Electrical Installation ............................................ 22
System-Electrical Information . . . . . . . . . . . . . . . . . . . . . . . . . 22
Source connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
One-line diagram for Smart-UPS VT 10, 15, 20, 30kVA,
208V, 3 phase, single mains . . . . . . . . . . . . . . . . . . . . . . . . . . 25
One-line diagram for Smart-UPS VT 10, 15, 20, 30kVA,
220V, 3 phase, single mains . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Input/Output Wiring – Single Mains (default) . . . . . . . . . . . . . 28
Input/Output Wiring – Dual Mains . . . . . . . . . . . . . . . . . . . . . 30
External Battery Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Wiring to battery bank or battery racks . . . . . . . . . . . . . . . . . . 32
Communication Wiring to EPO and Optional Equipment . . . . 33
Pin connections J106 (XR Enclosure) and J108 (EPO) . . . . . . . . 34
Pin connections J106 (UPS) to J200 (XR Enclosure - option) . . . 34
XR Enclosure, APC Maintenance Bypass Panel, and Generator
Control wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Pin connections J108 (for EPO wiring options) . . . . . . . . . . . . 36
Connection of APC Humidity Sensor . . . . . . . . . . . . . . . . . . . . 37
Front panel removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Wiring Verification Procedure . . . . . . . . . . . . . . . . . . . . . . . . . 40
Installation Site Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
ii Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B

Safety

General Safety Instructions

This guide contains important instructions that should be followed when handling the UPS, Battery
Enclosures, and batteries.

Symbols used in this guide

WARNING!
Risk of electric shock.
CAUTION!
Read this information to avoid equipment damage.
Indicates important information.
Note
Indicates that more information is available on this subject in a different section of this
manual.
Indicates that more information is available on the same subject in a different manual.

Environmental symbols

Temperature Ventilation
Humidity Dust/Fumes Altitude
requirements
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 1
Safety – General Safety Instructions

General safety

WARNING!
All electrical power and control wiring must be installed by a qualified electrician and
comply with local and national codes.
WARNING!
When connected, the UPS contains energy from both AC and DC sources. If the UPS
has dual mains supply, be aware of the two AC supply sources. Risk of electric shock -
parts inside the UPS are energized from the battery supply even the AC power is
disconnected.
WARNING!
Servicing of batteries should be performed or supervised by personnel knowledgeable
of batteries and the required precautions. Keep unauthorized personnel away from
batteries.
WARNING!
Batteries do not contain serviceable parts. Only APC authorized personnel may open
batteries.
WARNING!
Do not dispose of battery or batteries in a fire. The battery may explode. Do not open or
mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It
may be toxic.
WARNING!
Risk of Energy Hazard, 96 V, 7.2 Ampere-hour battery. Before replacing batteries,
remove watches, rings, or other metal objects. High energy through conductive
materials could cause severe burns.
WARNING!
When handling batteries, wear rubber gloves and boots. Do not lay tools or metal
objects on top of batteries.
WARNING!
When replacing a Battery Unit, replace with the same number of the APC SYBT1
(always replace a whole Battery Module (4 Battery Units) at a time).
WARNING!
Only trained personnel familiar with the construction and operation of the equipment
and the electrical and mechanical hazards involved, may install and remove system
components.
For configurations including customer-supplied external batteries, refer to
manufacturer’s battery installation and maintenance instructions.
2 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B

Introduction

Welcome to the Site Preparation and Installation Manual for the Smart-UPS® VT. This manual
contains information on how to prepare your site for the installation of the UPS and optional APC
equipment (also available at www.apc.com) and instructions on how to carry out the electrical/
mechanical installation. Separate manuals are available on:
• Receiving and Unpacking - part no. 990-1747
• Operation - part no. 990-1599
Keep the UPS free from loose objects to prevent obstruction of the airflow.
Note
For more information on APC products and services, visit us at www.apc.com
Note
Most illustrations show 20.59 in / 523 mm Enclosures but apply to both Enclosure sizes
(13.85 in / 352 mm and 20.59 in / 523 mm). Any differences between the two Enclosure
Note
sizes will be addressed in the manual.
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 3

UPS Family Range and Components

13.85 in/352 mm Enclosures

!
O ut pu t
P w r
Zo ne
Pr o be
10/100B
as e
­T
Reset
AP
10
9
/ 100
619 Network
Ma nage
me nt Card
EM
Seri al
:
Mode
l:
BATTER
Y UNIT
S eria
l:
Mode
l:
BATTERY U
NI T
Serial:
M o del
:
BATTERY UNIT
S e rial
:
M o de
l :
BATTERY UNIT
Serial:
Mo d el:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Ho t l i ne
i n U
S/Ca
Hotli
na
n
e
d
a i n
/
L E
A
Worldwide Support
ME
M :
Unit
A
+1 800
:
S
+35
eria
3
800
l
91 7
N o
4APC
0
2
000 n um
ber
A PC SKU
s
:
w
ww
. a pcc
. c o m/sup
Model
p ort /
servi
SUVTF10KB2F
c e/geomap_w
SUVT10KF1
Batte
o rl
r y Capacit
d .dfm
B
APC Smart-UPS VT 10kVA 20
2S
y
@–
SUVT10KF2B2S
w/
192V
1
A
B
ppa
at t.
DC
r ent
M
od
/
8
u
APC Smar
V
l e Ex
Ra
p.
Active
t
to
ed Input Current
2
t
SUVT10K
­UPS
Powe
VT
r
w/
1
7
F1
0k
.2Ah
2 Batt
B4S
V
A 208V
Ra
SUVT
.
APC Sma
Mod
t ed
ule
F1
Outp
0K
s
r
SUVT10K
t-UPS VT 10
ut
B
4
Cur
F
w
r
/
ent
1 Batt
F2
B4S
k
Bat
14
VA 2
.
Modu
. 4
te
A
APC
0
r
h
8V
y
l e Exp.
C ur
Sm
r e
a
SUVT10KF
nt
r
t
t
o 4
-UPS
w/2 Batt. Modules Exp. to 4
V
T 1 3 B4S
0kV
7 .
2A A 2
h
A
08V
P
C Smart-UPS VT 10kVA 208V SU V T10KF4B
w
/3 Batt
10kVA/8kW
14
4S
.
.
4
Mo
S
Ah
U
A
VTF15
P
d
C Sm
ul
e s E
KB2
ar
x p. to
t
­U
F
PS
4
27.1A
VT
w
1 0k
SUVT1
2
/ 4 Batt
1.6Ah
V
A 208V . Mo
5K
208V
F
d
2
ules
B2S
A
27.8 P C
A
Smart-UPS
2
8. 8
Ah
2 0
VT
8
V
w/
1 5kVA
2 Batt S U VT1
SUVTF15
208V
.
28.
M
5K
o
9A
du
F2B4S
l e
K
s
B4F
APC Smart
­UPS VT 15kVA 208V
SUVT1
1 4
.4Ah w/ 2
5KF3B
B at t .
M
4S
A
odu P C Smart-UPS VT 15kVA 208V
les E x p . t
S
o
U
4
w
VT15KF4B4S
/3 Batt. Mo
14.4Ah
du APC Smar
les E x p. to
t
-UPS VT 15k 4
SUVT20
w
SUVTF20KB4F
/4 Batt. M
V
2
A 20
1.6Ah
KF2B4
1
8V
5
APC Smart-UPS VT 20kVA 208V
kVA/ o dules
S
1 2k W
SUVT20K
w
4 0
/2
. 6
Ba
A
28.8Ah t t . Mod
F3
APC Smart
B4S
u
2 l e
0 s
8V Exp
­.
UPS
t o
41
4
w/
SUVT2
.
6A
V
3
T 20kVA 208V
B att. M
1
0
4
KF4B4S
. 4
o
Ah
208
du
APC
l e
V
s
S
Ex
S
UVTF3
ma
p . t
r t
-
o
UP
4
0
43
KB4F
S
S
.
UV
3
VT 20kVA 208V
A
T3
w/
2
0
4
1.6Ah
KF3B4
Ba
t t. Modu
S
APC S
l es
m art
SUVT30KF4B4S
-
UPS
2 0k
w/3 Batt. Modu
28.
VA/ V T 30kVA 208V
8
1
Ah
6 kW
APC
l
54
es
Voltage
.2A
Sm
Exp. to 4
a rt-UPS VT
2 08
&
5
Connection Types
V
w
3
5.5A
21
0
/ 4 Batt. Mo
kV
.
A
6
A 2
C
A
Input
h 0 8V
d
208V
ules
208Y/120V 4W+GND 60Hz
28.8Ah 3 0k
57.7A
VA/24k
AC Output
W
81.3A
208Y/120V 4W+GND
DC Input
Ba
208V
tt
Date
e
r i es
83 .
6
3A
i
0
n
Hz
stall
Da t
e for e d
+/- 192
20
1
8V
.
Re
V
p
Dat
lac
em
e
86.6A
fo
SEE INSTALLATION INSTRUCTION
e nt
r
2.
Replacement
BEFORE CONNEC SUPPLY
T I N
S
G TO
T HE
TH
IS R
E AR CO
P
V
LA
E
R
CED
M
US
O
T
N UPS
BE
8 8 5-2321C_rev04
Front Rear Front without front panel
Serial:
Model:
BATTERY UNIT
Serial:
Mode
l :
BATTERY UNIT
10-15 kVA

20.59 in/523 mm Enclosures

Hotline in US/Canada/LAM: +1 800 800 4APC Hotline in EMEA: +353 91 70 2000 Worldwide Support numbers: www.apcc.com/support/service/geomap_world.dfm
Unit Serial No
APC SKU
Model
SUVTF10KB2F
SUVT10KF1B2S
Battery Capacity
APC Smart-UPS VT 10kVA 208V
SUVT10KF2B2S
w/1 Batt. Module Exp. to 2
@– 192V DC
APC Smart-UPS VT 10kVA 208V
SUVT10KF1B4S
w/2 Batt. Modules
SUVTF10KB4F
7.2Ah
APC Smart-UPS VT 10kVA 208V
SUVT10KF2B4S
w/1 Batt. Module Exp. to 4 APC Smart-UPS VT 10kVA 208V
14.4Ah
SUVT10KF3B4S
w/2 Batt. Modules Exp. to 4 APC Smart-UPS VT 10kVA 208V
7.2Ah
SUVT10KF4B4S
w/3 Batt. Modules Exp. to 4
SUVTF15KB2F
14.4Ah
APC Smart-UPS VT 10kVA 208V
SUVT15KF2B2S
w/4 Batt. Modules
21.6Ah
APC Smart-UPS VT 15kVA 208V
28.8Ah
SUVT15KF2B4S
SUVTF15KB4F
w/2 Batt. Modules
SUVT15KF3B4S
APC Smart-UPS VT 15kVA 208V
14.4Ah w/2 Batt. Modules Exp. to 4 APC Smart-UPS VT 15kVA 208V
SUVT15KF4B4S
w/3 Batt. Modules Exp. to 4
14.4Ah
APC Smart-UPS VT 15kVA 208V
SUVT20KF2B4S
SUVTF20KB4F
21.6Ah
w/4 Batt. Modules
APC Smart-UPS VT 20kVA 208V
SUVT20KF3B4S
w/2 Batt. Modules Exp. to 4
28.8Ah
APC Smart-UPS VT 20kVA 208V
SUVT20KF4B4S
w/3 Batt. Modules Exp. to 4
SUVTF30KB4F
14.4Ah
APC Smart-UPS VT 20kVA 208V
SUVT30KF3B4S
21.6Ah
w/4 Batt. Modules
SUVT30KF4B4S
APC Smart-UPS VT 30kVA 208V
Voltage & Connection Types
28.8Ah w/3 Batt. Modules Exp. to 4 APC Smart-UPS VT 30kVA 208V
AC Input
21.6Ah
w/4 Batt. Modules
208Y/120V 4W+GND 60Hz
28.8Ah
AC Output
208Y/120V 4W+GND 60Hz
DC Input
Batteries Date installed
Date for 1.
+/- 192V
Replacement
Front
!
Output
P
wr
Zone
P r obe
10/1
R es
0
e
0
t
Bas
e
-T
AP9619 Netw
10/100
o rk Manag
e me
n t Ca
r d EM
!
Output
Pwr
Zone
P r obe
10/100Base-T
Re s et
AP9619 Network
1 0 /10 0
M a nage
m e n t
C ar d
E M
Blind plates cover empty
Serial:
Model:
battery bays
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Mode
l :
Apparent/
Rated Input Current
Active Power
Rated Output Current
Battery Current
10kVA/8kW
27.1A 208V
27.8A 208V
28.9A
15kVA/12kW
40.6A 208V
41.6A 208V
43.3A
20kVA/16kW
54.2A 208V
55.5A 208V
30kVA/24kW
57.7A
81.3A 208V
83.3A 208V
Date for 2.
SEE INSTALLATION INSTRUCTIONS
Replacement
86.6A
BEFORE CONNECTING TO THE SUPPLY THIS REAR COVER MUST BE PLACED ON UPS
885-2321C_rev04
Rear
Serial:
Model:
BATTERY UNIT
Front without
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
front panel 10-15 kVA
Front without
front panel 20-30 kVA
4 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B
Introduction – UPS Family Range and Components

Serial number

The serial number is available on the type label on the rear side of the UPS.

Type label

Hotline in US/Canada/LAM: +1 800 800 4APC Hotline in EMEA: +353 91 70 2000 Worldwide Support numbers: www.apcc.com/support/service/geomap_world.dfm
Unit Serial No
SUVTF10KB2F
SUVTF10KB4F
SUVTF15KB2F
APC SKU
SUVT10KF1B2S
SUVT10KF2B2S
SUVT10KF1B4S
SUVT10KF2B4S
SUVT10KF3B4S
SUVT10KF4B4S
SUVT15KF2B2S
Model
APC Smart-UPS VT 10kVA 208/220V
w/1 Batt. Module Exp. to 2
APC Smart-UPS VT 10kVA 208/220V
w/2 Batt. Modules
APC Smart-UPS VT 10kVA 208/220V
w/1 Batt. Module Exp. to 4
APC Smart-UPS VT 10kVA 208/220V
w/2 Batt. Modules Exp. to 4
APC Smart-UPS VT 10kVA 208/220V
w/3 Batt. Modules Exp. to 4
APC Smart-UPS VT 10kVA 208/220V
w/4 Batt. Modules
APC Smart-UPS VT 15kVA 208/220V
w/2 Batt. Modules
Battery Capacity
@± 192V DC
7.2Ah
14.4Ah
7.2Ah
14.4Ah
21.6Ah
28.8Ah
14.4Ah
Apparent/
Active Power
10kVA/8kW
Rated Input Current
27.1/25.5A 208/220V
Rated Output Current
27.8/26.2A 208/220V
Battery Current
28.9A
SUVT15KF2B4S
SUVTF15KB4F
SUVTF20KB4F
SUVTF30KB4F
Voltage & Connection Types
AC Input
208Y/120V 4W+GND 60Hz 220Y/127V 4W+GND 60Hz
SUVT15KF3B4S
SUVT15KF4B4S
SUVT20KF2B4S
SUVT20KF3B4S
SUVT20KF4B4S
SUVT30KF3B4S
SUVT30KF4B4S
208Y/120V 4W+GND 60Hz 220Y/127V 4W+GND 60Hz
AC Output
APC Smart-UPS VT 15kVA 208/220V
w/2 Batt. Modules Exp. to 4
APC Smart-UPS VT 15kVA 208/220V
w/3 Batt. Modules Exp. to 4
APC Smart-UPS VT 15kVA 208/220V
w/4 Batt. Modules
APC Smart-UPS VT 20kVA 208/220V
w/2 Batt. Modules Exp. to 4
APC Smart-UPS VT 20kVA 208/220V
w/3 Batt. Modules Exp. to 4
APC Smart-UPS VT 20kVA 208/220V
w/4 Batt. Modules
APC Smart-UPS VT 30kVA 208/220V
w/3 Batt. Modules Exp. to 4
APC Smart-UPS VT 30kVA 208/220V
w/4 Batt. Modules
DC Input
± 192V
Date
installed
14.4Ah
21.6Ah
28.8Ah
14.4Ah
21.6Ah
28.8Ah
21.6Ah
28.8Ah
Batteries
Date for 1.
Replacement
15kVA/12kW
20kVA/16kW
30kVA/24kW
Date for 2.
Replacement
40.6/38.4A 208/220V
54.2/51.2A 208/220V
81.3/76.7A 208/220V
41.6/39.4A 208/220V
55.5/52.5A 208/220V
83.3/78.7A 208/220V
SEE INSTALLATION INSTRUCTIONS
BEFORE CONNECTING TO THE
SUPPLY
THIS REAR COVER MUST BE
PLACED ON UPS
885-2321D_rev05
43.3A
57.7A
86.6A
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 5
Introduction – UPS Family Range and Components

User interface

Output
Pwr
!
Zone
Probe
 
10/100Base-T
Reset
10/100
AP9619 Network Manag
ement Card EM
Serial:
Model:
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
Serial:
Model:
Serial:
Model:
BATTERY UNIT
BATTERY UNIT
BATTERY UNIT
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Display: user-control interface used to configure the functionality, monitor the system, set alarm
thresholds, and to provide audible and visual alarms.
Network Management Card with Environmental Monitor (AP9619): used for remote system
control and monitoring, e-mail notifications etc.
®
Computer-interface port for the connection of computers with APC Powerchute
Mechanical Bypass Lever: used to bypass the upstream mains power around the UPS to support
software.
the load directly = internal mechanical bypass operation.
Service port (for APC maintenance personnel only).
6 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B
Display port for the connection of display communication cable.
Documentation storage.
Inlet for communication cables.

Connection Interface (rear)

Introduction – UPS Family Range and Components
Upper Cover Plate rear.
Upper part of Conduit Box.
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 7
Introduction – UPS Family Range and Components
Lower part of Conduit Box.
Power connection.
Communication wiring connection (EPO signalling, Battery Temperature Sensor).
Protective earth.

Foot print

Rear Rear
 
36.45 in/ 926 mm
Conduit Box.
Levelling feet.
20.59 in/523 mm
13.85 in/352 mm
Castors.
Communication cable inlets.
8 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B
Introduction – UPS Family Range and Components
APC Network Management Card AP9619 (installed in UPS) and APC Humidity Sensor
(Optional)
Humidity Sensor
Output
Pwr
!
Zone
Probe
10/100Base-T
Reset
10/100
AP9619 Network Management Card EM
For installing Humidity Sensor see “Connection of APC Humidity Sensor” on page 40.
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 9

Site Preparation

Installation Space Requirements

Clearance for 20.59 in/523 mm Enclosures

(A)
(B)
UPS
Conduit Box (F)
(C)
(E)
Space requirements in mm
Minimum clearance above Enclosure (A) 20.00 508
Enclosure depth (B) 32.99 838
Enclosure width (C) 20.59 523
Minimum rear service clearance* (compliant with NEC 110.26 for North America) (D)
Minimum front clearance (E) 40.00 1,000
Conduit Box, depth (F) 3.46 88
No side clearance required (add width of Stabilizing Brackets for floor anchoring if applicable)
Stabilizing Bracket width 3.34 85
(D)
(G)
36.00 914
00
Total installation depth, inclusive of Front Panel, Conduit Box and minimum front and rear clearances (G)
112.45 2,840
*) Minimum free rear space for ventilation 4 in/100 mm.
10 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B
Site Preparation – Installation Space Requirements

Clearance for stand-alone 13.85 in/352 mm Enclosures

(A)
(B)
UPS
Conduit Box (F)
(C)
(D)
(G)
(E)
Stabilizing Bracket, left and right
Space requirements in mm
Minimum clearance above UPS (A) 20.00 508
UPS depth (B) 32.99 854
UPS width 13.85 352
Minimum rear service clearance* (compliant with NEC 110.26
36.00 914
for North America) (D)
Minimum front clearance (E) 40.00 1,000
Conduit Box, depth (F) 3.46 88
No side clearance required (add width of Stabilizing Bracket for
00
floor anchoring if applicable)
Stabilizing Bracket width 3.34 85
Total installation depth, inclusive of Front Panel, Conduit Box
112.45 2.840
and minimum front and rear clearances (G)
*) Minimum free rear space for ventilation 4 in/100 mm.
For the stability of 13.85 in/352 mm stand-alone Enclosures, the Stabilizing Brackets
must always be mounted on both sides of the UPS. See Stabilizing Brackets.
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 11

Operating Environment

Operating conditions

Install the UPS in an indoor, temperature-controlled area, free of conductive
contaminants.
Note
Temperature
Range:
32° to 104°F /
0° to 40°C

Heat dissipation

UPS size
10 kVA 1,774 20 kVA 3,624
15 kVA 2,866 30 kVA 5,486

Audible noise

UPS Sizes
Keep Ventilated
Front-to-Rear
Airflow (see
space
considerations)
BTU/hr at fully
charged batteries UPS size
Audible noise at 100% load
(1.09 yard/1 m from the UPS)
Relative
Humidity: <95%
Non-condensing
No Conductive
Dust or
Corrosive
Fumes
(1.09 yard/1 m from the UPS)
Altitude derating table: 3,000 ft/914 m: 100% load 4,500 ft/1371 m: 95% load 6,000 ft/1828 m: 91% load 8,000 ft/2438 m: 86% load
10,000 ft/3048 m: 82% load
BTU/hr at fully
charged batteries
Audible noise at <70% load
10-15 kVA 54 dBA 45.4 dBA
20-30 kVA 58 dBA 48.5 dBA
12 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B

Recommended current protection

AC output over-current protection and AC output disconnect must be provided by the
customer.
Note
Dual/single mains configuration Connection 10 kVA 15 kVA 20 kVA 30 kVA Notes
Site Preparation – Operating Environment
Single Mains/bypass
input
Dual Mains input 35 A
Dual Bypass input 35 A
Any Output 35 A fast-
Note 1: If the available fault current of the installation is below 30 kA, a lower kAIC-rated breaker can be
used.
Note 2: For breaker settings, refer to below table listing available overload currents.
Note 3: If the available fault current of the installation is less than 1200 A for the 10 kVA and 15 kVA UPS
sizes, and below 2300 A for the 20 kVA and 30 kVA UPS sizes, a breaker (of the same value as for the
bypass input) can be used.
Note 4: Recommended maximum rating of a single-fuse configuration if the internal bypass is to be protected
during a load short-circuit.
35 A breaker (30 kAIC)
breaker (30 kAIC)
breaker (30 kAIC)
acting class J fuse
60 A breaker (30 kAIC)
60 A breaker (30 kAIC)
60 A breaker (30 kAIC)
60 A fast­acting class J fuse
80 A breaker (30 kAIC)
80 A breaker (30 kAIC)
80 A breaker (30 kAIC)
80 A fast­acting class J fuse
125 A breaker (30 kAIC)
125 A breaker (30 kAIC)
125 A breaker (30 kAIC)
125 A fast­acting class J fuse
1, 2
1, 2
3, 4

Minimum breaker settings for 10 kVA UPS

Overload Event Mains input Bypass input Output Duration Notes
Internal fault 2 kA 1.7 kA 14 kA <10 ms 1
800% overload bypass operation
150% overload normal/ battery operation
125% overload normal/ battery operation
Continuously 34 A 31 A 31 A
Note 1: For the output value, the short-circuit-level is indicated.
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 13
223 A 223 A 500 ms
42 A 30 s
35 A 60 s
Site Preparation – Operating Environment

Minimum breaker settings for 15 kVA UPS

Overload Event Mains input Bypass input Output Duration Notes
Internal fault 2.5 kA 2.1 kA 14 kA <10 ms 1
800% overload bypass operation
150% overload normal/ battery operation
125% overload normal/ battery operation
Continuously 51 A 46 A 46 A
Note 1: For the output value, the short-circuit-level is indicated
333 A 333 A 500 ms
63 A 30 s
52 A 60 s

Minimum breaker settings for 20 kVA UPS

Overload Event Mains input Bypass input Output Duration Notes
Internal fault 4 kA 3.4 kA 14 kA <10 ms 1
800% overload bypass operation
150% overload normal/ battery operation
125% overload normal/ battery operation
444 A 444 A 500 ms
84 A 30 s
70 A 60 s
Continuously 68 A 62 A 62 A
Note 1: For the output value, the short-circuit-level is indicated.

Minimum setting of breakers for 30 kVA UPS

Overload Event Mains input Bypass input Output Duration Notes
Internal fault 5 kA 4.2 kA 14 kA <10 ms 1
800% overload bypass operation
150% overload normal/battery operation
125% overload normal/battery operation
Continuously 102 A 92 A 92 A
Note 1: For the output value, the short-circuit level is indicated.
667 A 667 A 500 ms
125 A 30 s
105 A 60 s
14 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B
Site Preparation – Operating Environment
Recommended phase-conductor sizes [AWG] for a 86°F (30°C) temperature
environment
Mains input
UPS/AWG sizes
10 kVA 8 8 1
15 kVA 6 6 1
20 kVA 4 4 1
30 kVA 1 1 1
[AWG]
AC output [AWG]
DC input [AWG], 75°C Wire
Use Molex lug type or equivalent, and crimp to manufacturer’s specifications.
Note
Cable Size [AWG] Cable Lug Type Crimping Tool Die
12 YA12CL2TC38 MD7-34R W12CVT 0.2 in/6 mm
8 YA8CL2TC38 MD7-34R W8CVT 0.2 in/6 mm
6 YA6CL2TC38 MD7-34R W5CVT 0.2 in/6 mm
4 YA4CL2TC38 MD7-34R W4CVT 0.2 in/6 mm
1 YA1CL2TC38 MD7-34R W1CVT 0.2 in/6 mm
)
Terminal Bolt Diameter
WARNING!
At 100% non-liniear load (EN50091-3 standard), the neutral shall be rated for 200%
phase current.

EPO switch wiring

The UPS must be connected to either a dry contact or a 24VDC Emergency Power Off (EPO) switch.
See “Pin connections J108 (for EPO wiring options)” on page 37
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 15

Basic Wiring Overview

AC input power
DC power
Communication Interface
AC power (output)
EPO
EPO
Maintenance
Bypass Panel
(Optional Equipment)
XR Enclosure(s) (Optional, 4 Max.)
16 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B
UPS

Site Preparation Checklist

System components. Have you –
Site Preparation. Have you –
  
Arrival Preparation. Have you –
 
determined minimum battery run time requirement based on load (kW and kVA) and selected the proper number of APC XR Enclosures (SUVTBXR2B6S, SUVTXR2B6S and SUVTBXR6B6S, SUVTXR6B6S) and Battery Unit (SYBT1). Always install a whole Battery Module (4 Battery Units) at a time.
considered Service Program or Extended Warranty plan?
verified that input voltage and current are available?
considered correct operating space, floor strength (see Installation Space Requirements), cooling, and environment (see Operating Environment).
reviewed all electrical work to determine wiring requirements?
verified that space and handling equipment are available to receive the UPS/XR Enclosure? (Including unloading the UPS/XR Enclosure from the delivery truck).
scheduled an authorized electrician to install the UPS/XR Enclosure?
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 17

Mechanical assembly

Stabilizing Brackets

Always install the Stabilizing Brackets on the 13.85 in/352 mm Enclosure (shipped with the UPS) to
enhance the stability of the Enclosure.
Attach the Stabilizing Bracket to the UPS Enclosure re-using the screws used to secure
the UPS to the pallet during shipment.
Note
!
Ou tput
Pwr
Zone
P robe
10/100Base-T
R e set
AP96
1 0/ 100
1 9 Net
w o rk Management Card EM
Serial:
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Mode
BATTERY UNIT
Stabilizing
Bracket
:
S er
ial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
l:
Serial:
Model:
BATTERY UNIT
If the Enclosure needs to be moved after Stabilizing Brackets have been attached to the Enclosure,
the Stabilizing Brackets must be pushed up into their high position.
Loosen the two screws of both Stabilizing Brackets, and push the bracket up into the high
position.
When the Enclosure has reached its new position, push the Bracket into its “down” position
again, and tighten the screws.
WARNING!
For stability reasons, do not remove Stabilizing Brackets from 13.85 in/352 mm
Enclosures.
18 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B

Leveling Feet

Verify that the installation has been electrically wired before setting the leveling feet.
Note

Setting the leveling feet

Set the leveling feet to ensure the UPS is horizontal when it is in its final operating position. Use a 13/
14-mm wrench (shipped with UPS) to adjust all 4 leveling feet from front to back, and left to right,
until the pads make solid contact with the floor. Use a bubble level to check the Enclosure is
horizontal.
13/14-mm wrench
CAUTION!
To avoid equipment damage, do not push or pull the UPS after the leveling feet have
been lowered.
When the Leveling Feet have been set, remember to reinstall the Front Panel.
See Front Panel section.
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 19

Floor Anchoring

If floor anchoring is required in your area, read this section. If not, proceed to
Operating Environment. However, if you install a 13.85 in/352 mm Enclosure, it must
Note

Drilling floor holes for floor anchoring

Note

Hole positions for floor anchors (stand-alone Enclosures)

always be equipped with the Stabilizing Bracket for enhanced stability (not necessary
to bolt the Stabilizing Bracket to the floor in non-seismic areas).
If the UPS installation requires floor anchoring, the UPS installation must be anchored to
the floor, re-using the brackets that also secured the UPS to the pallets when shipped. For
easy determination of where to drill the holes, refer to the applicable drawings below
indicating hole positions and size.
5.78in/ 147mm
5.11in/ 130mm
5.11in/ 130mm
5.11in/ 130mm
5.11in/ 130mm
5.11in/ 130mm
0.92in/
23.5mm
Rear
Floor anchor holes: Ø 10 mm
20.59 in/523 mm Enclosure
26.3in/575mm 15.9in/404mm
25in/650mm
Rear
Floor anchor holes: Ø 10 mm
13.85 in/352 mm
Enclosure
Refer to this drawing for floor anchor positions for 20.59 in/523 mm.
Refer to this drawing for 13.85 in/352 mm.
20 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B
Mechanical assembly – Floor Anchoring
Recommended minimum number of floor bolts per Enclosure: 4 (1 in each corner).
Recommended floor bolt size: 5/16(3/8) in/8 mm.
Note

Floor anchoring of stand-alone systems

In seismic areas, it is recommended that the installation be bolted to the floor, and that the batteries be
secured in the Enclosure by the Battery Securing Brackets.
For floor anchoring, use the 2 transport brackets that were used to secure the UPS to the pallet
during transport.
Serial:
Model:
Serial:
Model:
Serial:
Model:
Serial:
Model:
BATTERY UNIT
BATTERY UNIT
BATTERY UNIT
Serial:
Model:
Serial:
Model:
Serial:
Model:
BATTERY UNIT
BATTERY UNIT
BATTERY UNIT
Serial:
Model:
Serial:
Model:
Serial:
Model:
BATTERY UNIT
BATTERY UNIT
BATTERY UNIT
Floor Anchoring Bracket (re-use of transport bracket)
Serial:
Model:
Serial:
Model:
BATTERY UNIT
BATTERY UNIT
BATTERY UNIT
Align the 4 holes in the bottom angle of the Floor Anchoring Bracket on either side of the
Enlosures to the pre-drilled holes in the floor
Front Panel
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 21

Electrical Installation

System-Electrical Information

WARNING!
All electrical power and power control wiring must be installed by a qualified electrician,
and must comply with local and national regulations for maximum power rating.
UPS ratings 208 V
Input voltage / Bypass voltage (V) 3-phase
Input current (nominal, per phase) (A) 24.3 36.5 48.2 72.9
Maximum input current per phase (continuous, at minimum mains voltage)
Input current protection for mains source or single mains supply (external to UPS, not supplied) (A)
Input current protection for bypass source in dual mains configuration (external to UPS, not supplied) (A)
Input frequency (Hz) range 40-70 40-70 40-70 40-70
Output voltage (on line). (V) Minimum and maximum values (+/- 1%)
Output current (nominal, per phase) (A) 27.8 41.6 55.5 83.3
Maximum output current (in bypass only at 110% overload per phase)
10 kVA 8 kW
208Y/ 120 V
26.7 40.2 53.0 80.1
3x35 3x60 3x80 3x125
35 60 80 125
120/208 120/208 120/208 120/208
30.5 45.8 61.1 91.6
15 kVA 12 kW
3-phase 208Y/ 120 V
20kVA 16 kW
3phase 208Y/ 120 V
30 kVA 24 kW
3-phase 208Y/ 120 V
Neutral output current (with 100% switch mode load) (A)
Output current protection (external to UPS, not supplied) (A)
Output frequency range (Hz) 50/60 50/60 50/60 50/60
DC overcurrent protection and disconnect switch for external safety: DC voltage rating of the battery supply Maximum available short-circuit current
22 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B
48.1 72.1 96.2 144.2
40 60 80 120
27.8
+/- 192 10 kA
41.8
+/- 192 10 kA
55.7
+/- 192 10 kA
83.5
+/- 192 10 kA
Electrical Installation – System-Electrical Information
UPS ratings 220 V
10 kVA 8 kW
Input voltage / Bypass voltage (V) 3-phase
220Y/ 127 V
15 kVA 12 kW
3-phase 220Y/ 127 V
20kVA 16 kW
3-phase 220Y/ 127 V
30 kVA 24 kW
3-phase 220Y/ 127 V
Input current (nominal, per phase) (A) 22.9 34.6 46.5 68.9
Maximum input current per phase (continuous, at
25.2 38.0 50.1 75.8
minimum mains voltage)
Input current protection for mains source or single
3x35 3x60 3x80 3x125
mains supply (external to UPS, not supplied) (A)
Input current protection for bypass source in dual mains
35 60 80 125
configuration (external to UPS, not supplied) (A)
Input frequency (Hz) range 40-70 40-70 40-70 40-70
Output voltage (on line). (V)
127/220 127/220 127/220 127/220
Minimum and maximum values (+/- 1%)
Output current (nominal, per phase) (A) 26.2 39.4 52.5 78.7
Maximum output current
28.9 43.3 57.7 86.6
(in bypass only at 110% overload per phase)
Neutral output current (with 100% switch mode load)
45.5 68.2 90.9 136.4
(A)
Output current protection (external to UPS, not
40 60 80 120
supplied) (A)
Output frequency range (Hz) 50/60 50/60 50/60 50/60
DC overcurrent protection and disconnect switch for
26.4
39.6
52.7
78.9 external safety: DC voltage rating of the battery supply Maximum available short-circuit current
+/- 192 10 kA
+/- 192 10 kA
+/- 192 10 kA
+/- 192 10 kA
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 23
Electrical Installation – System-Electrical Information

Source connections

WARNING!
The UPS must be supplied from a 208Y/120 V or 220Y/127 V 4W + GND 60Hz source.
CAUTION!
Verify clockwise phase-rotation (L1, L2, L3) and make sure a neutral connection is
present.
For recommended “Recommended current protection” , see The Site Preparation
section.
CAUTION!
The installation must comply with all local and national codes.
Refer to NEC Articles 310-15, 310-16 for further information.
8
24 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B
Electrical Installation – System-Electrical Information

One-line diagram for Smart-UPS VT 10, 15, 20, 30kVA, 208V, 3 phase, single mains

XR Battery Cabinet
DC Input
Breaker
8
10kVA, 27.8A 15kVA, 41.7A 20kVA, 55.6A 30kVA, 83.3A
10kVA, 22.2A 15kVA, 33.3A 20kVA, 44.4A 30kVA, 66.6A
2
5
Utility source
(provided by others)
3PH 208Y/120V
4 wire + ground
10kVA, 27.8A 15kVA, 41.7A 20kVA, 55.6A 30kVA, 83.3A
Maintenance Bypass Panel
Q1(UIS)
3P
2
UPS
MIB 10kVA, 35A.T. 15kVA, 60A.T. 20kVA, 80A.T. 30kVA, 125A.T.
2
10kVA, 27.8A 15kVA, 41.7A 20kVA, 55.6A 30kVA, 83.3A
10kVA, 27.8A 15kVA, 41.7A 20kVA, 55.6A 30kVA, 83.3A
1
Notes:
1. Must be 4 wire + ground WYE source provided by others.
2. Dashed lines between units (- - -) represent AC/DC cabling provided by others.
3. Input overcurrent protection is based on 80% rating – any deviation please contact APC.
4. AC Power cabling is 4 wire + ground at 208VAC 3-phase.
5. Separate conduits, 2 wire + ground
6. UPS input and output cables must be in separate conduits.
7. Power wiring and control wiring must be in separate conduits
8. XR Battery Enclosure can be bayed to UPS. Baying kit has to be purchased as an option. XR Battery Enclosure is available without breaker with DC fuses only. Up to 4 XR Battery Enclosures can be connected to UPS to extend backup time.
9. Single mains installation is a default. Dual Mains option requires custom entineering. Please refer to APC Custom Engineering group and drawing# CEG­SUVT10kF-SD for details.
10. Installation must comply with all applicable national and local codes.
10kVA, 27.8A 15kVA, 41.7A 20kVA, 55.6A 30kVA, 83.3A
Q2/UOS)
2
4P
F1, 3P
2
UPS System Output 10kVA, 15lVA,
20kVA and 30kVA
208V 3ph – 4 wire + ground or
120V 1ph – 2 wire + ground
MBS
3P
Q3(BPS)
4P
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 25
Electrical Installation – System-Electrical Information

One-line diagram for Smart-UPS VT 10, 15, 20, 30kVA, 220V, 3 phase, single mains

XR Battery Cabinet
DC Input
Breaker
8
10kVA, 26.2A 15kVA, 39.4A 20kVA, 52.5A 30kVA, 78.7A
10kVA, 22.2A 15kVA, 33.3A 20kVA, 44.4A 30kVA, 66.6A
2
5
Utility source
(provided by others)
3PH 220Y/127V
4 wire + ground
10kVA, 26.2A 15kVA, 39.4A 20kVA, 52.5A 30kVA, 78.7A
Maintenance Bypass Panel
Q1(UIS)
3P
2
UPS
MIB 10kVA, 35A.T. 15kVA, 60A.T. 20kVA, 80A.T. 30kVA, 125A.T.
2
10kVA, 26.2A 15kVA, 39.4A 20kVA, 52.5A 30kVA, 78.7A
10kVA, 26.2A 15kVA, 39.4A 20kVA, 52.5A 30kVA, 78.7A
1
Notes:
1. Must be 4 wire + ground WYE source provided by others.
2. Dashed lines between units (- - -) represent AC/DC cabling provided by others.
3. Input overcurrent protection is based on 80% rating – any deviation please contact APC.
4. AC Power cabling is 4 wire + ground at 208VAC 3-phase.
5. Separate conduits, 2 wire + ground
6. UPS input and output cables must be in separate conduits.
7. Power wiring and control wiring must be in separate conduits
8. XR Battery Enclosure can be bayed to UPS. Baying kit has to be purchased as an option. XR Battery Enclosure is available without breaker with DC fuses only. Up to 4 XR Battery Enclosures can be connected to UPS to extend backup time.
9. Single mains installation is a default. Dual Mains option requires custom entineering. Please refer to APC Custom Engineering group and drawing# CEG­SUVT10kF-SD for details.
10. Installation must comply with all applicable national and local codes.
10kVA, 26.2A 15kVA, 39.4A 20kVA, 52.5A 30kVA, 78.7A
Q2/UOS)
2
4P
F1, 3P
2
UPS System Output 10kVA, 15kVA,
20kVA and 30kVA
220V 3ph – 4 wire + ground or
127V 1ph – 2 wire + ground
MBS
3P
Q3(BPS)
4P
26 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B

Wiring

Make sure the UPS is in its location of use before wiring begins.
Note
CAUTION!
Verify clockwise phase-rotation (L1, L2, L3) and make sure a neutral connection is
present.
Power terminal lug diameter: minimum 0.2 in/6 mm.
Torque value: 45 lbf-in/7Nm.
Note
If floor anchoring is required, attach the Floor Anchoring Brackets to the UPS now.
Follow step 1 under Floor Anchoring (Option).
Note
Electrical Installation – Wiring
Note
Please leave a copy of your wiring diagram with the customer to facilitate maintenance
and troubleshooting.
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 27

Input/Output Wiring – Single Mains (default)

The UPS is designed for both single (default) and dual mains installations. Follow the below steps to
install the UPS in a single-mains installation.
The illustrations show a 20.59 in/523 mm Enclosure, but installation procedures are
identical for 13.85 in/352 mm Enclosures).
Note

Wiring procedure – single mains

Conduit box (top part)
Conduit box (bottom part)
MBP Conduit
Output
N
N
EPO Conduit
Input
Loosen the (6) M4 screws from the cover of the cable termination area on the rear, and remove.
Loosen the (2) M4 screws (1 each side) from the top part of the Conduit Box. Loosen the M4
screws attaching it to the bottom part (2 screws in a 13.8 5in/352 mm Enclosure, 3 screws in a
20.59 in/523 mm Enclosure), and remove.
28 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B
Loosen the (4) M4 screws (2 each side) from the bottom part of the Conduit Box and remove.
Punch 2 holes in the marked areas of the Conduit Box bottom to fit the size of the conduit pipes,
and reattach the Conduit Box bottom to the Enclosure, re-using the (4) M4 screws.
Install conduit pipes in the Conduit Box.
Run cables through the conduit pipes and the bottom of the Conduit Box, pull behind the bar
and up into the input/output area.
Reinstall the top part of the Conduit Box to the Enclosure, following reverse installation
procedures.
Mains input cables
Neutral
  
Attach input cable lugs to L1, L2 and L3 input busbars (left side in the UPS – on the front of the
L
1
L
2
L
3
N
N
L
1
L
2
L
3
 
Neutral
Output cables
Ground cables
busbar), using the provided M6 torx screws. Attach output cable lugs to L1, L2 and L3 output
busbars, using the provided M6 torx screws. Attach N x 2 where shown, using the provided torx
screws.
Attach Ground x 2 where shown, using the provided torx screws.
Fasten cables with cable ties.
Reinstall rear cover.
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 29

Input/Output Wiring – Dual Mains

The UPS is designed for single mains installation as default. Follow the below instructions to install
the UPS in a dual-mains installation
The illustrations show 20.59 in/523 mm Enclosures, but the installation procedures are
identical for 13.85 in/352 mm Enclosures).
Note

Wiring procedure – dual mains

Conduit box (top part)
Conduit box (bottom part)
MBP Conduit
Input
N
Bypass
C
B
N
A
EPO Conduit
Output
Loosen the (6) M4 screws from the cover of the cable termination area, and remove.
Loosen the (2) M4 screws (1 each side) from the top part of the Conduit Box. Loosen the M4
screws attaching it to the bottom part (2 screws in a 13.8 5in/352 mm Enclosure, 3 screws in a
20.59 in/523 mm Enclosure), and remove.
Loosen the (4) M4 screws (2 each side) from the bottom part of the Conduit Box and remove.
30 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B
Electrical Installation – Input/Output Wiring – Dual Mains
Punch 3 holes in the Conduit Box bottom to fit the size of the conduit pipes, and reattach the
Conduit Box bottom to the Enclosure, re-using the (4) M4 screws.
Install conduit pipes in the Conduit Box bottom.
Run cables through the conduit pipes and the bottom of the Conduit Box. Guide the cables
behind the bar and up into the input/output area.
Reinstall the top part of the Conduit Box to the Enclosure, following reverse deinstallation
procedures (described in a previous step).
Remove the (2) M6 screws from Brackets A, B, and C and remove all 3 brackets.
Utility
input
cables
Neutral
Attach input cable lugs to L1, L2 and L3 input busbars (left side in the UPS – on the front of the
L
1
L
2
L
3
N
L
1
L
2
L
3
L
1
L
2
L
3
N
N
   
 
Neutral
Bypass input cables
Output cables
Neutral
Ground cables
busbar), using the provided M6 torx screws. Attach bypass cable lugs to L1, L2, L3 bypass
busbars, using the provided torx screws. Attach output cable lugs to L1, L2, L3 output busbars,
using the provided torx screws.
Attach N x 3 where shown., using the provided torx screws.
Attach Ground x 3 where shown.
Fasten all cables with cable ties.
Reinstall rear cover.
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 31

External Battery Wiring

Wiring to battery bank or battery racks

L
1
L
2
L
3
N
L
1
L
2
L
3
L
1
L
2
L
3
N
Bat+
N
Bat-
N
N
Attach DC cables to upper part of busbars as shown.
For configurations including customer-supplied external batteries, refer to manufacturer’s
battery installation and maintenance instructions.
32 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B

Communication Wiring to EPO and Optional Equipment

EPO switch must be connected to a NEC Class 2 wiring.
Note
Use only 28-16AWG copper wire for the connection of the Emergency Power Off (EPO)
and other optional equipment. Keep all other wiring and uninsulated live parts separate of
Note
Note
other NEC Class 2 circuits.
Do not connect any circuits to the EPO terminal block unless it can be confirmed that the
circuit is a NEC Class 2 circuit.
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 33
Electrical Installation – Communication Wiring to EPO and Optional Equipment

Pin connections J106 (XR Enclosure) and J108 (EPO)

L
1
L
2
L
3
N
N
L
1
L
2
L
3
J106 Pin Connections:
8 Ext. charging control return
7 External control of charging
6 Q3 active return
5 Q3 active
4 Battery measurement supply*
3 Battery unit quantity*
2 Max. battery temperature*
1 Battery measurement return*
* Should be used with APC XR
J108 Pin Connections:
1 Normally open EPO
2 Normally open EPO return
3 Normally closed EPO
4 Normally closed EPO return
5 +24V SELV supply
6 SELV ground
Enclosures only

Pin connections J106 (UPS) to J200 (XR Enclosure - option)

Pins 1 through 4 are for battery measurement (only applicable to APC XR Enclosures).
Pins 5 & 6 are for external maintenance bypass Q3. When Q3 is closed, signals are fed back to the
UPS controller.
Pins 7 & 8 are for external charge control. When 7 & 8 are closed, the UPS charges batteries with a
pre-defined percentage (0-100%) of the maximum charging power. To be used in generator
applications, or if special codes requires control of charging.
34 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B
Electrical Installation – Communication Wiring to EPO and Optional
When connecting the Q3 auxiliary signal, use gold-plated N/C auxiliary switch on Q3.
Note

XR Enclosure, APC Maintenance Bypass Panel, and Generator Control wiring

J106
8
7
6
5
4
3
2
1
Charging control switch
Q3 switch
4
3
2
1
J200 (XR Batteries)
Pins 1 through 4 are for battery measurement (only applicable to APC XR Enclosures).
Pins 5 through 6 are for external maintenance bypass Q3.
Pins 7 and 8 are for external charge control.
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 35
Electrical Installation – Communication Wiring to EPO and Optional Equipment

Pin connections J108 (for EPO wiring options)

EPO switch wiring. The UPS must be connected to either a dry contact or a 24V
Power Off (EPO) switch.
Connect the EPO cable, using one of the following 4 wiring configurations.
1: Dry Contracts
Normally Open
2: +24V Normally Open
J108
1
2
3
4
5
6
J108
1
2
3
4
5
6
EPO circuit
EPO circuit
EPO is activated when pin 1 is
connected to pins 3, and 5
EPO is activated when an
isolated SELV 24V
is supplied on pin 1 with
reference to pin 2.
Emergency
DC
voltage
DC
3: Dry Contacts
Normally Closed
4: +24V Normally
Closed
J108
1
2
3
4
5
6
J108
1
2
3
4
5
6
EPO circuit
EPO circuit
EPO is activated when a
connection from pin 3 to pin 5
is opened
EPO is activated when a SELV
24V
voltage removed from
DC
pin 3 with reference to pin 5
36 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B

Connection of APC Humidity Sensor

Front panel removal

Out p ut
Pwr
!
Zone
P rob e
1 0/ 1
00B
a se-T
R e se
t
10
/ 10
0
AP9619 Net
w o rk
Managem
ent
Car d EM
Serial:
Model:
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
BATTERY UNIT
Serial:
Model:
Serial:
Model:
BATTERY UNIT
BATTERY UNIT
Serial:
Model:
Serial:
Model:
BATTERY UNIT
BATTERY UNIT
Serial:
Model:
Serial:
Model:
BATTERY UNIT
BATTERY UNIT
To remove a Front Panel, turn screw clockwise to unlocked position.
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Pull top of Front Panel free of UPS.
Lift the Front Panel free of the two slots at the bottom of the Enclosure.
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 37
Electrical Installation – Connection of APC Humidity Sensor
The Humidity Sensor is provided in a plastic bag attached to the front of the UPS.
Note
Output
Pwr
!
Zone
Probe
10/100Base-T
Reset
10/100
AP9619 Network Management Card EM
Output
Pwr
!
Zone
Probe
10/100Base-T
Reset
10/100
AP9619 Network Management
C ard EM
Serial:
Serial:
Model:
Serial:
Model:
Serial:
Model:
Serial:
Model:
BATTERY UNIT
BATTERY UNIT
BATTERY UNIT
BATTERY UNIT
Serial:
Model:
Serial:
Model:
Serial:
Model:
Serial:
Model:
BATTERY UNIT
BATTERY UNIT
BATTERY UNIT
BATTERY UNIT
Serial:
Model:
Serial:
Model:
Serial:
Model:
Serial:
Model:
BATTERY UNIT
BATTERY UNIT
BATTERY UNIT
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
Serial:
Model:
Serial:
Model:
Serial:
Model:
BATTERY UNIT
BATTERY UNIT
BATTERY UNIT
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Serial:
Model:
BATTERY UNIT
Remove the 2 screws from the cable inlet at the front – and remove cable-inlet plate.
Guide the cable through the hole in the bottom plate and up through the cable inlet.
See “Foot print” on page 8 to locate the communication cable inlet.
38 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B
Electrical Installation – Connection of APC Humidity Sensor
Guide the cable up alongside the side panel and insert the Humidity Sensor plug into the socket
marked “Probe”.
Fasten the cable to the side panel with enclosed cable ties.
Remount the cable-inlet plate.
Place the Humidity Sensor where applicable.
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 39

Wiring Verification Procedure

Do not connect batteries in the UPS.
Note
Use following procedure to verify that the UPS has been wired properly:
1. If your installation includes an XR Enclosure, make sure that the DC breaker (if
available) is in the OFF position and that both 125A fuses are removed from the
XR Enclosure.
2. Check that the power wiring is torqued to 45 lbf.in/7Nm.
3. If your installation includes an XR Enclosure, remount the 125A fuses in the XR
Enclosure and check that the DC breaker (if available) on the XR Battery
Enclosure is in the ON position.
4. Please leave a wiring diagram on site for service / technical support personnel.
If a problem occurs, phone Customer Support at (1) (800) 800-4272 (US and Canada).
Refer to rear cover for contact numbers in other countries.
Note
Note
Note
If you have purchased any optional equipment, refer to product-specific manuals.
Start-up must be performed by APC authorized personnel only. Call APC to scedule a
free 5x8 Start-up service.
40 Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 990-1598B

Installation Site Checklist

This checklist should be completed by the electrician after the wiring has been completed:
Installed at (company name, date, contact)__________________________________________
Name and telephone number of electrician: ___________________________________________
UPS serial number: ______________________________________________________________
Input Circuit Breaker size and type: _________________________________________________
Output fuse size and type: ________________________________________________________
Location of protection devices (room):______________________________________________
Breaker ID: ___________________________________________________________________
EPO type: ____________________________________________________________________
Wire size and type: _____________________________________________________________
Ground connection method and location: ________________________________________
990-1598B Smart-UPS® VT 10-30 kVA, 208/220 V Site Preparation and Installation Manual 41
APC Worldwide Customer Support
Customer support for this or any other APC product is available at no charge in any of the following ways:
• Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests.
www.apc.com (Corporate Headquarters)
Connect to localized APC Web sites for specific countries, each of which provides customer support information.
www.apc.com/support/
Global support searching APC Knowledge Base and using e-support.
• Contact an APC Customer Support center by telephone or e-mail.
Regional centers:
Direct InfraStruXure Customer Support Line (1) (877) 537-0607 (toll free)
APC headquarters U.S., Canada (1)(800) 800-4272 (toll free)
Latin America (1)(401)789-5735 (USA)
Europe, Middle East, Africa (353)(91)702000 (Ireland)
Japan (0) 35434-2021
Australia, New Zealand, South Pacific area (61) (2) 9955 9366 (Australia)
Local, country-specific centers: go to www.apc.com/support/contact for contact information.
Contact the information on how to obtain local customer support.
APC representative or other distributor from whom you purchased your APC product for
Entire contents copyright © 2005 American Power Conversion. All rights reserved.
Reproduction in whole or in part without permission is prohibited. APC, the APC logo, and
Smart-UPS VT are trademarks of American Power Conversion Corporation and may be
registered in some jurisdictions. All other trademarks, product names, and corporate names
are the property of their respective owners and are used for informational purposes only.
990-1598B 06/2005
*990-1598B*
Loading...