The APC® by Schneider Electric Smart-UPS® SURTA1500XL/2200XL is a high performance
uninterruptible power supply (UPS). It provides protection for electronic equipment from utility power
blackouts, brownouts, sags, and surges; small utility fluctuations and large disturbances. The UPS also
provides battery backup power until utility power returns to safe levels or the batteries are fully
discharged.
Inventory
All models120 Vac models
• UPS• PowerChute® Utility CD
• Front bezel• USB communication cable
• Serial communication cable
• Literature kit containing:
–Product documentati on
–Smart-UPS® User Manuals CD
–Safety Guide
–Warranty information
Accessories
Install accessories prior to connecting power to the UPS.
Refer to the APC Web site, www.apc.com for available accessories.
Optional accessories
• External battery pack (XLBP)
• USB communication cables
• Network Management Card (NMC)
Safety
Read the Safety Guide included in the package before installing the UPS.
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage.
Recycle the packaging.
SURTA 1500XL/1500XLJ/220 0XL Series 100/120 Vac Tower/Ra ck-M oun t 2U2
Product Overview
X
Front display panel
Load
Test
su0311b
Button or
IndicatorDescription
ON button: has three functions.
The
Test
Bypass
On Battery
Press this button to turn on the UPS.
Press this button to initiate a Cold Start. Cold Start is not a normal condition. When there is
no utility power and UPS is off, press and hold this button to restore power to UPS. UPS
will emit two beeps. During second beep, release the button.
Press this button to initiate a Self-Test.
Automatic: The UPS performs a self-test automatically when turned on, and every two
weeks there after by default. During self-test, UPS briefly operates on battery power.
Manual: Press and hold
ON button for a few seconds to initiate self-test.
The Off button: This button is used to switch UPS off.
The Bypass LED illuminates indicating that the UPS is in bypass mode. Utility power is sent
directly to connected equipment during bypass mode operation. Bypass mode operation is the
result of an internal UPS fault, an overload condition or a selection made through NMC or
PowerChute software.
Battery operation is not available while the UPS is in bypass mode.
Refer to “Troubleshooting” on page 10 in this manual.
The On Battery LED illuminates indicating that the UPS is supplying battery power to
connected equipment
Battery Charge
The On Line LED illuminates when the UPS is drawing utility power and performing double
On Line
Overload
conversion to supply power to connected equipment.
The Overload LED illuminates indicating that the UPS is experiencing an overload condition.
Refer to “Troubleshooting” on page 10 in this manual.
Fault
The Fault LED illuminates indicating that the UPS detects an internal fault.
Refer to “Troubleshooting” on page 10 in this manual.
The Battery Fault illuminates indicating that one or more b atteries are disconnected or must be
Battery
Fault
replaced.
Refer to “Troubleshooting” on page 10 in this manual.
3SURTA 1500XL/1500XLJ/2200XL Series 100/120 Vac Tower/Rack-Mount 2U
Front Display Panel
FeatureDescription
100V
118.0
108.7
99.3
90.0
80.6
Rear panel
120V
138.2
128.8
119.5
110.1
100.8
The UPS has a diagnostic feature that indicates utility voltage.
The UPS starts a self-test as part of this procedure. The self-test does not affect voltage
display.
Press and hold the
ON button to view utility voltage bar graph indicator. As soon as the On
Line LED starts flashing indicating a self-test is in progress, the five-LED Battery Charge
indicator to the right of the display panel will show utility input voltage.
Refer to diagram for voltage reading.
Values are not listed on the UPS.
Indicators on the UPS show the voltage is between the displayed value on list and the next
higher value.
Refer to “Troubleshooting” on page 10 in this manual.
SERIAL COM-serial communication por t for:
Power management software
Interface kits
Use only interface kits supplied or approved by APC. Any other serial
interface cable will be incompatible with UPS connector.
Serial and USB communication ports cannot be used simultaneously.
USB COM-USB communication port
120 Vac models: USB communication cable
100 Vac models: USB communication cables and software are available as
accessories.
Contact APC at www.apc.com for purchase information.
Emergency Power Off (EPO) terminal allows the user to connect the UPS to a
suo0523a
central EPO system.
SITE WIRING FAULT indicator-the LED illuminates when the UPS detects a
building wiring fault.
TVSS GND-The UPS features a chassis ground located on the UPS rear panel
for connecting the ground leads on transient voltage devices
Outlets for connecting electronic equipment.
UPS power cable for connecting to utility power.
SmartSlot for optional NMC or PowerChute accessories.
External battery pack connector. The UPS will support up to 10 XLBPs.
SURTA 1500XL/1500XLJ/220 0XL Series 100/120 Vac Tower/Ra ck-M oun t 2U4