INSTALLATION INSTRUCTIONS
AND USERS MANUAL
HOT WATER STORAGE TANKS
MODEL: ST 1500-3000
FOREWORD
Before attempting to install this water heater please read the installation instructions.
An authorized installer must install the heater and commission it according to the local
valid requirements.
A.O. SMITH CANNOT ACCEPT ANY RESPONSIBILITY FOR GUARANTEE,
SERVICE AND/OR PRODUCT LIABILITY IN THE EVENT OF UNAUTHORIZED
CHANGES, PRODUCT MODIFICATIONS OR REPAIRS.
1
CONTENTS
1. GENERAL
1.1 Description of the heater 3
1.2 Controls 3
1.3 Dimensions 3
1.4 Technical data 5
2. FOR THE INSTALLER
2.1 Installation 5
2.2 Water connections 6
2.3 Commissioning 7
2.3.1 Filling the heater 7
2.3.2 Heater start-up 7
2.4 Shutting down 7
2.5 Maintenance 7
2.5.1 Anode 7
2.5.2 Descaling 7
2.6 Spare parts 8
3. FOR THE END - USER
3.1 Filling the heater 8
3.2 Start-up of the water heater 8
3.3 Shutting down 8
3.4 Maintenance 8
4. WARRANTY
4.1 Warranty in general 9
4.2. Warranty of the tank 9
4.3 Conditions for installation and use 9
4.4 Exclusions. 10
4.5 Scope of the warranty 10
4.6 Claims 10
4.7 No other obligations for A.O. Smith
than those stated in this manual 10
2
8
1. GENERAL
1.1 Description of the heater
Construction of the heater is in accordance with the European standard for water heaters
or sanitary use. The heaters are suitable for use with a working pressure of up to 7 bar.
The cylindrical tank is made from sheet steel. For protection against corrosion, the inside
of the tank is glass-lined. The tank is also fitted with magnesium anodes for extra
protection against corrosion. A thick, replaceable insulation jacket minimizes heat loss.
1.2 Controls.
ST models are supplied without controls.
1.3 Dimensions
2 Hot water outlet 2”
”
Clean out flange
1 Cold water inlet/drain 2”
ST 1500/2000 ST 2500/3000
Connection sizes
1 Inlet
2 Outlet
3
4
5 Anode
Recirculation
6
connection
7
8 T&P connection
A Tank diameter
B Overall diameter
C Height
D Height alt inlet
Distance
between 2 “
E
connections
Height
F
circulation conn.
height clean out
G
opening
H Height inlet
Clean out
F
diameter
2" 2"
2" 2"
3/4 3/4
1¼" 1¼"
3/4 3/4
1100 1400
1200 1500
1930/2118 1990/2118
400 480
550/644 500/565
710 690
450 530
135 183
110 110
3
1.4 Technical specifications
1 Storage capacity ltr
2 Tank heat loss kWh/24h
3 Maximum working pressure bar
4 Test pressure tank bar
5 Maximum allowed tank temperature °C
6 Weight empty kg
ST 1500/2000 ST 2500/3000
1500/2000 2500/3000
8.5 10.1
7 7
12 12
95 95
374/506 637/739
2. FOR THE INSTALLER
2.1 Installation
A qualified, competent installer must install the hot water storage tanks in accordance
with local valid regulations and codes.
Location needs to be chosen to prevent damage in case of tank leakage (e.g. place tank in
a drain pan or near a floor drain of sufficient capacity). For mounting of the jacket see
separate attached Kit installation sheet.
2.2 Water connections
The water heater is suitable for connection to vented, un-vented and pumped pressurized
systems. In each case appropriate valves and fittings should be used to ensure the system
complies with the governing codes and appropriate building requirements. The maximum
working pressure is 7 bars. A typical installation diagram for an un-vented installation is
as follows:
4