A.O. Smith DVE-150A, DVE-200A, DVE-250A, DVE-300A, DVE-400A User Manual

...
DURA-POWER™ XI
COMMERCIAL ELECTRIC
COMMERCIAL
ELECTRIC WATER HEATERS
ADVANCED ELECTRONIC CONTROL
A. O. Smith’s new propriety electronic water heater control, provides precise + or - 1ºF temperature control, that is ideal for industrial and food service applications where accurate hot water temperatures are needed.
EASY-TO-READ TEXT
• Animated icons display detailed operational and diagnostic information. Fault or alert messages appear if an operational issue occurs.
LOW WATER CUT OFF
• Factory standard on board low water cut-off uses a remote electronic immersion type probe to prevent energizing of the elements in the event of low water condition and eliminates accidental dry firing.
PROGRESSIVE MODULATING
• Matches number of elements to current load conditions. Rotates and lead lags element loads to provide long life and equal wear.
ECONOMY MODE OPERATION
• Control system automatically lowers the operating set point by a programmed value during user defined time periods. Seven-day clock may be programmed for night set back and or weekend shutdown to reduce operating cost and save money.
BMS COMPATIBLE
• Modbus/BACnet compatible with optional Gateway interface. Call 888 WATER02 for more information.
PERMAGLAS® GLASS LINING IS STANDARD
• Exclusive process provides superior protection against corrosion in varying water conditions. Cement and Epoxy linings are optional.
ASME CODE CONSTRUCTION
• All models are constructed to the requirements of ASME and are available in 125, 150 and 160 psi working pressures (125 psi working pressure - standard). Consult factory for ASME code tanks with greater or lesser working pressures and special configurations or materials.
INCOLOY IMMERSION HEATERS
• Heavy-duty elements have incoloy sheathing: provide excellent protection against oxidation and scaling. The input ranges from 15kW to 900kW (see accompanying chart).
FUSING
• Control and power circuit fusing to meet N.E.C.
COMPLIANCE
• Meets the standby loss requirements of the U.S. Department of Energy, NRCan and current edition of ASHRAE/IES 90.1.
MAGNETIC CONTACTOR(S)
• Heavy duty UL rated for 100,000 cycles.
OTHER STANDARD FEATURES
• Color-coded circuitry for easier servicing
• Anode rods for maximum corrosion protection
• Standard voltages include 208, 240, 380, 400, 415, 480, 600 volt single or three­phase
• International voltages available (consult factory)
• Factory-installed terminal block(s)
• Temperature and pressure relief valve, supplied but not installed
OPTIONAL DUAL-ENERGY SOURCE CAPABILITY
• Provides emergency back up energy source or winter/summer boiler operation. Can be specified with optional water to water or steam to water heat exchangers. Both single and double-wall heat exchangers are available. Complete control packages can be factory-installed for hook-up and run capability.
THREE YEAR LIMITED WARRANTY
• For complete warranty information consult written warranty or go to hotwater.com
Attention: Significant changes have been made to some models. Please note that this spec sheet refers specifically to models manufactured in Lebanon, TN
DVE-150 THRU 2500
DHE-150 THRU 2500
© October 2018 A. O. Smith Corporation. All rights reserved.
www.hotwater.com | 800-527-1953 Toll-Free USA | A. O. Smith Corporation | 500 Tennessee Waltz Parkway | Ashland City, TN 37015
Page 1 of 4
AOSCE15500
COMMERCIAL
ELECTRONIC CONTROL
LOCATION OF ADDITIONAL BOX FOR DUAL BOX MODELS
ELECTRONIC CONTROL
ADDITIONAL HEIGHT IF REQUIRED
(2" Channel on 150 gallon and higher. Optional on smaller sizes.)
LOCATION OF ADDITIONAL CONTROL BOX IF NEEDED
ELECTRIC WATER HEATERS
Vertical Round Models 150-1000
*An oversized control panel may be required on models with inputs above 72 kW. Consult the factory for specific details.
Vertical Square Models 1250-2500
TOP VIEWTOP VIEW
Horizontal Models
ADDITIONAL HEIGHT IF REQUIRED
ELECTRONIC CONTROL
*An oversized control panel may be required on models with inputs above 72 kW. An oversized control panel may increase the width and depth of the square jacket by up to 2”.
ADDITIONAL HEIGHT IF REQUIRED