TEXT PRINTED OR OUTLINED IN RED CONTAINS
INFORMATION RELATIVE TO YOUR SAFETY. PLEASE READ
THOROUGHLY BEFORE INSTALLING AND USING THIS
APPLIANCE.
PLACE THESE INSTRUCTIONS ADJACENT TO HEATER AND
NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.
PRINTED IN U.S.A. 1102 PART NO. 195091-000
1
FEATURES AND SPECIFICATIONS
The illustration shows a typical gas-fired commercial gas power burner, tank-type
water heater. The principal components of the heater are shown and identified
here. By referring to the plate on the heater jacket the unit may be identified in the
specifications presented in Table 1 and 2.
U.S. GALLONSBTU/HR.GPH@100°F RISEGPH@140°F RISE120V, 60Hz, 1Ø
***81-14081140,000136975
***81-19981199,0001931385
***81-27081270,0002621875
***81-37081370,0003592565
Model Designator: Sample ***81-140NEAN = Natural Gas
*** = Letter designatorE = 3 Year Warranty
81 = Gallon CapacityA = ASME Construction
140 = 140,000 BTU/HR imput
2
FOREWORD
These designs comply with the latest version of the American
National Standard for Gas Water Heaters, Volume III,
ANSI Z21.10.3 - CSA 4.3.
Detailed installation diagrams are found in this manual. These
diagrams will serve to provide the installer with a reference for
the materials and methods of piping necessary. It is highly
essential that all water, gas piping and wiring be installed as shown
on the diagrams.
Particular attention should be given to the installation of
thermometers at the locations indicated on the diagrams as these
are necessary for checking the proper functioning of the heater.
The ***81-140 through ***81-370 models are designed to
operate on either natural or propane gases. HOWEVER, MAKE
SURE the gas on which the heater will operate is the same as
that specified on the heater model and rating plate.
TABLE OF CONTENTS
PAGE
FEATURES AND SPECIFICATIONS ...........................................2
Gas Meter Size-City Gases Only ............................................8
Gas Pressure Regulation ........................................................8-9
Gas Piping ...............................................................................9
THESE HEATERS MUST NOT BE INSTALLED DIRECTLY ON
COMBUSTIBLE FLOORS.
In addition to these instructions, the equipment shall be installed
in accordance with those installation regulations in force in the
local area where the installation is to be made. These shall be
carefully followed in all cases. Authorities having jurisdiction
should be consulted before installations are made.
The installation must conform to these instructions and the local
code authority having jurisdiction. In the absence of local codes
the installation must comply with the latest editions of the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 and the National Electric
Code, NFPA 70. The former is available from the Canadian
Standards Association, 8501 Pleasant Valley Road, Cleveland,
OH 44131 and both documents are available from the National
Fire Protection Association, 1 Batterymarch Park, Quincy,
MA 02269.
Replacement Parts .................................................................23
PARTS LIST................................................................................ 24-27
GENERAL SAFETY INFORMATION
PRECAUTIONS
DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN
UNDERWATER. Immediately call a qualified service technician
to inspect the appliance and to replace any part of the control
system and any gas control which has been under water.
IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT
OPERATE HEATER UNTIL ALL CORRECTIVE STEPS HAVE
BEEN MADE BY A QUALIFIED SERVICEMAN.
1. EXTERNAL FIRE.
2. DAMAGE.
3. FIRING WITHOUT WATER.
4 SOOTING.
Heater must be protected from freezing downdrafts during
shutdown periods.
CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY
OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN
CHEMICAL VAPORS WHICH BREAK DOWN INTO ACIDS AT
HIGH TEMPERATURE. SUCH CORROSION MAY RESULT IN
FAILURE AND RISK OF ASPHYXIATION.
3
CHEMICAL VAPOR CORROSION
WARNING
Spray can propellants, cleaning solvents, refrigerator and air
conditioning refrigerants, swimming pool chemicals, calcium
and sodium chloride (water softener salt), waxes, and process
chemicals contain typical compounds which are potentially
corrosive. Do not store products of this sort near the heater.
Also, air which is brought in contact with the heater should not
contain any of these chemicals. If necessary, uncontaminated
air should be obtained from remote or outside sources. The
limited warranty is voided when failure of water heater is due to
a corrosive atmosphere. (Refer to the limited warranty for
complete terms and conditions).
IMPROPER COMBUSTION
WARNING
ATTIC AND/OR EXHAUST FANS OPERATING ON THE PREMISES
WITH A WATER HEATER CAN RESULT IN CARBON MONOXIDE
POISONING AND DEATH.
OPERATING THESE FANS CAN PRODUCE A NEGATIVE DRAFT
IN THE AREA OF THE WATER HEATER PREVENTING THE
PRODUCTS OF COMBUSTION FROM EXHAUSTING THROUGH
THE CHIMNEY OR VENT PIPE.
recommended that the hot water faucet be opened for several
minutes at the kitchen sink before using any electrical appliance
connected to the hot water system. If hydrogen is present, there
will probably be an unusual sound such as air escaping through
the pipe as the water begins to flow. THERE SHOULD BE NO
SMOKING OR OPEN FLAME NEAR THE FAUCET AT THE TIME
IT IS OPEN.
INSULATION BLANKETS
Insulation blankets available to the general public for external
use on gas water heaters are not approved for use on your water
heater. The purpose of an insulation blanket is to reduce the
standby heat loss encountered with storage tank water heaters.
Your water heater meets or exceeds the ASHRAE/IES
90.1b-1992 standards with respect to insulation and standby
loss requirements making an insulation blanket unnecessary.
WARNING
Should you choose to apply an insulation blanket to this heater,
you should follow these instructions. Failure to follow these
instructions can result in fire, asphyxiation, serious personal injury
or death.
The venting of the water heater should be inspected by a qualified
service technician at the time of installation and periodically
thereafter to ensure a down-draft condition does not exist.
DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND
VENTILATING AIR. ADEQUATE AIR FOR COMBUSTION AND
VENTILATION MUST BE PROVIDED FOR SAFE OPERATION.
LIQUID PETROLEUM MODELS
Water heaters for propane or liquefied petroleum gas (LPG) are
different from natural gas models. A natural gas heater will not
function safely on LP gas and no attempt should be made to
convert a heater from natural gas to LP gas.
LP gas must be used with great caution. It is highly explosive
and heavier than air. It collects first in the low areas making its
odor difficult to detect at nose level. If LP gas is present or even
suspected, do not attempt to find the cause yourself. Go to a
neighbor’s house, leaving your doors open to ventilate the house,
then call your gas supplier or service agent. Keep area clear
until a service call has been made.
At times you may not be able to smell an LP gas leak. One
cause is odor fade, which is a loss of the chemical odorant that
gives LP gas its distinctive smell. Another cause can be your
physical condition, such as having a cold or diminishing sense
of smell with age. For these reasons, the use of a propane gas
detector is recommended.
Only trained LP professionals should conduct the required safety
checks in accordance with industry standards.
EXTENDED NON-USE PERIODS
WARNING
HYDROGEN GAS CAN BE PRODUCED IN A HOT WATER
SYSTEM SERVED BY THIS HEATER THAT HAS NOT BEEN USED
FOR A LONG PERIOD OF TIME (GENERALLY TWO WEEKS OR
MORE). HYDROGEN GAS IS EXTREMELY FLAMMABLE. To
reduce the risk of injury under these conditions, it is
•
Do not apply insulation to the top of the water heater, as this
will interfere with safe operation of drafthood.
• Do not cover the temperature & pressure relief valve.
• Do not cover the instruction manual. Keep it on the side of the
water heater or nearby for future reference.
• Do obtain new labels from manufacturer for placement on
the blanket directly over the existing labels.
HIGH ALTITUDE INSTALLATIONS
WARNING
INSTALLATIONS ABOVE 2000 FEET REQUIRE REPLACEMENT
OF THE BURNER ORIFICE IN ACCORDANCE WITH SECTION
8.1.2 OF THE NATIONAL FUEL GAS CODE (ANSI Z223.1).
FAILURE TO REPLACE THE ORIFICE WILL RESULT IN
IMPROPER AND INEFFICIENT OPERATION OF THE APPLIANCE
RESULTING IN THE PRODUCTION OF INCREASED LEVELS
OF CARBON MONOXIDE GAS IN EXCESS OF SAFE LIMITS
WHICH COULD RESULT IN SERIOUS PERSONAL INJURY OR
DEATH.
As elevation above sea level is increased, there is less oxygen
per cubic foot of air. Therefore, the heater input rate should be
reduced at high altitudes for satisfactory operation with the
reduced oxygen supply. Failure to make this reduction would
result in an overfiring of the heater, causing sooting, poor
combustion and/or unsatisfactory heater performance.
Ratings specified by manufacturers for most appliances apply
for elevations up to 2000 feet. For elevations above 2000 feet,
ratings must be reduced at the rate of 4% for each 1000 feet
above sea level. For example, if a heater is rated at 120,000 Btu/
hr. at sea level, to rate the heater at 4000 feet, you subtract 4
(once for each thousand feet) x .04 (4% input reduction) x 120,000
(the original rating) from the original rating. Therefore, to calculate
the input rating at 4000 feet: 4 x .04 x 120,000 = 19,200 btu/hr.,
120,000 - 19,200 = 100,800 btu/hr. At 6000 feet elevation, the
heater rating would be 91,200 btu/hr.
4
The input reduction is primarily achieved by reducing the size of
the main burner orifices. To do this, the main burner orifices
require replacement with orifices sized for the particular installation
elevation. Correct orifice sizing and parts may be obtained from
the manufacturer. See the REPLACEMENT PARTS section of
this manual. When ordering, be sure to state the model number
and the altitude of the location where the heater is being
installed.
Refer to the piping diagrams at rear of manual for electrical
hookup information and install in accordance with the latest
version of the
Only all bronze circulators are used with commercial water heaters.
Although circulators are oiled and operated by the manufacturer
some circulators must be oiled again before operating. Please
refer to manufacturer’s instructions.
National Electric Code ANSI/NFPA No. 70.
Upon completion of derating of the heater, adjustment to the gas
pressure regulator may be required. See ADJUSTMENT
PROCEDURE in this manual for inlet and manifold pressure
requirements.
Also, due to the input rating reduction required at high altitudes,
the output rating of the appliance is also reduced and should be
compensated for in the sizing of the equipment for applications.
FEATURES
HIGH LIMIT SWITCH (E.C.O.)
The dual bulb controller ((fig. 1) contains the high limit (energy
cutoff) sensor. The high limit switch interrupts main burner gas
flow should the water temperature reach 205°F (96°C).
In the event of high limit switch operation, the appliance cannot
be restarted unless the water temperature is reduced by at least
20°F (11°C) and the high limit reset button on front of limit control
(fig.1) is depressed.
DISHWASHING MACHINE REQUIREMENT
All dishwashing machines meeting the National Sanitation
Foundation requirements are designed to operate with water flow
pressures between 15 and 25 pounds per square inch. Flow
pressures above 25 pounds per square inch, or below 15 pounds
per square inch, will result in improperly sanitized dishes. Where
pressures are high, a water pressure reducing or flow regulating
control valve should be used in 1800 line to the dishwashing
machine, and should be adjusted to deliver water between these
limits.
The National Sanitation Foundation also recommends circulation
of 1800F water. Where this is done, the circulation should be
very gentle so that it does not cause any unnecessary turbulence
inside the water heater. The circulation should be just enough to
provide 1800F water at the point of take-off to the dishwashing
machine. Adjust flow by means of the plug cock in the circulating
line.
INSTALLATION INSTRUCTIONS
REQUIRED ABILITY
INSTALLATION OR SERVICE OF THIS WATER HEATER
REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED
TRADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR
SUPPLY, VENTING, GAS SUPPLY AND ELECTRICAL WORK
ARE REQUIRED.
DUAL-BULB THERMOSTAT (COVER REMOVED)
FIGURE 1
Continued manual resetting of high limit control, preceded by
higher than usual water temperature is evidence of high limit switch
operation. The following is a possible reason for high limit switch
operation.
• A malfunction in the thermostatic controls would allow the gas
valve to remain open causing water temperature to exceed
the thermostat setting. The water temperature would continue
to rise until high limit switch operation.
Contact your dealer or servicer if continued high limit switch
operation occurs, to determine the reason for operation.
CIRCULATING PUMP
A circulating pump is used when a system requires a circulating
loop or there is a storage tank used in conjunction with the heater.
UNCRATING
Uncrate the heater by removing the outside mat and top locator.
The shipping pallet must be removed from the unit. It may be
possible to simply unbolt the base from the pallet and, with the
help of 2 or more persons, work the unit off the pallet. Some
units will be too heavy and will require the use of jacks or lifting
equipment to safely remove the pallet and move the unit into
position. Be careful when moving this heater. It will tip over
easily.
The heater is shipped with a burner and draft control. The burner
and draft control are shipped in separate cartons. They should
be installed as received without any alterations.
Discard the shipping crate and packaging cartons in an appropriate
manner.
LOCATING THE HEATER
WARNING
THERE IS A RISK IN USING FUEL BURNING APPLIANCES
SUCH AS GAS WATER HEATERS IN ROOMS, GARAGES OR
OTHER AREAS WHERE GASOLINE, OTHER FLAMMABLE
LIQUIDS OR ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE
STORED, OPERATED OR REPAIRED. FLAMMABLE VAPORS
5
ARE HEAVY AND TRAVEL ALONG THE FLOOR AND MAY BE
IGNITED BY THE HEATER’S IGNITION SYSTEM OR MAIN
BURNER FLAMES CAUSING FIRE OR EXPLOSION. SOME
LOCAL CODES PERMIT OPERATION OF GAS APPLIANCES
IN SUCH AREAS IF THEY ARE INSTALLED 18 INCHES OR
MORE ABOVE THE FLOOR. THIS MAY REDUCE THE RISK IF
LOCATION IN SUCH AN AREA CANNOT BE AVOIDED.
WARNING
FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY
OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST
NEVER BE PLACED ON OR ADJACENT TO THE HEATER.
OPEN CONTAINERS OF FLAMMABLE MATERIAL SHOULD
NOT BE STORED OR USED IN THE SAME ROOM WITH THE
HEATER.
THE HEATER SHALL BE LOCATED OR PROTECTED SO IT IS
NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING
VEHICLE.
THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE
IT WILL BE SUBJECT TO FREEZING.
When installing the heater, consideration must be given to proper
location. Location selected should be as close to a gas vent or
chimney as practicable, with adequate air supply and as
centralized with the piping system as possible.
CLEARANCES
These heaters are design certified by the Underwriter’s
Laboratories for installation on non-combustible flooring in an
alcove with clearances to combustible construction of 6" from
the sides and rear, and 6" minimum between vent pipe and ceiling.
Minimum clearance from barometric draft control to combustible
material is 6". A minimum of 21" from top of heater to the ceiling
is required, except for the ***81-370 which requires a minimum
of 24".
A clearance of 24" shall be maintained from serviceable parts,
such as the relief valve, power burner, thermostat and drain valve.
LOCATE HEATER NEAR A FLOOR DRAIN. THE HEATER
SHOULD BE LOCATED IN AN AREA WHERE LEAKAGE FROM
THE TANK OR CONNECTIONS WILL NOT RESULT IN DAMAGE
TO THE ADJACENT AREA OR TO LOWER FLOORS OF THE
STRUCTURE.
WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE
METAL DRAIN PAN, ADEQUATELY DRAINED, SHOULD BE
INSTALLED UNDER THE HEATER. Such pans should be
fabricated with sides at least 2" deep, with length and width at
least 2" greater than the diameter of the heater and must be piped
to an adequate drain. THE PAN MUST NOT RESTRICT
COMBUSTION AIR FLOW.
Units which are to be installed on combustible flooring must be
supported by a full layer of hollow concrete blocks, from 8" to 12"
thick and extending 12" (minimum) beyond the heater in all
directions. The concrete blocks must provide an unbroken
concrete surface under the heater with the hollows running
continuously and horizontally. A 3/16 inch steel plate must cover
the concrete blocks, see fig. 2.
NOTE: If electrical conduits run under the floor of the proposed
heater location, insulate the floor asrecommended
above.
PROPER INSTALLATION CLEARANCES
FIGURE 3
LEVELLING
The heater shall be installed plumb to the ground. If it is necessary
to adjust the heater, use metal shims under the channel type skid
base.
HARD WATER
Where hard water conditions exist, water softening or the threshold
type of water treatment is recommended. This will protect the
dishwashers, coffee urns, water heaters, water piping and other
equipment.
See MAINTENANCE section for details of tank cleanout
procedures.
AIR REQUIREMENTS
KEEP APPLIANCE AREA FREE FROM COMBUSTIBLE
MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS
AND LIQUIDS.
PROPER INSTALLATION ON COMBUSTIBLE FLOORING
FIGURE 2
For appliance installation locations with elevations above 2000
feet, refer to HIGH ALTITUDE INSTALLATIONS section of this
manual for input reduction procedure.
DO NOT OBSTRUCT THE FLOW OF COMBUSTION OR
VENTILATING AIR.
WARNING
FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR
COMBUSTION AND VENTILATION. AN INSUFFICIENT SUPPLY
OF AIR WILL CAUSE RECIRCULATION OF COMBUSTION
PRODUCTS RESULTING IN AIR CONTAMINATION THAT MAY
BE HAZARDOUS TO LIFE. SUCH A CONDITION OFTEN WILL
RESULT IN A YELLOW, LUMINOUS BURNER FLAME, CAUSING
6
CARBONING OR SOOTING OF THE COMBUSTION CHAMBER,
BURNERS AND FLUE TUBES AND CREATES A RISK OF
ASPHYXIATION.
MECHANICAL EXHAUSTING OF ROOM AIR
figure 4. The outlet of the draft control assembly may be rotated
to face in direction needed. The assembly must be fitted to the
jacket cover such that it is plumb and level to the ground. Fasten
the draft control assembly to the top cover using sheet metal
screws at three locations, or more, as required.
Where an exhaust fan is installed in the same room with a heater,
sufficient openings for air must be provided in the walls.
UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN
INTO THE ROOM THROUGH THE CHIMNEY, CAUSING POOR
COMBUSTION. SOOTING MAY RESULT IN SERIOUS DAMAGE
TO THE HEATER AND RISK OF FIRE OR EXPLOSION.
UNCONFINED SPACE
In buildings of conventional frame, brick or stone construction,
unconfined spaces may provide adequate air for combustion,
ventilation, and draft hood dilution.
If the unconfined space is within a building of tight construction
(buildings using the following construction: weather stripping,
heavy insulation, caulking, vapor barrier, etc.), air for combustion,
ventilation and draft hood dilution must be obtained from outdoors.
The installation instructions for confined spaces in tightly
constructed buildings must be followed to ensure adequate air
supply.
CONFINED SPACE
When drawing combustion and dilution air from inside a
conventionally constructed building to a confined space, such a
space shall be provided with two permanent openings, ONE IN
OR WITHIN 12 INCHES OF THE ENCLOSURE TOP AND ONE
IN OR WITHIN 12 INCHES OF THE ENCLOSURE BOTTOM.
Each opening shall have a free area of at least one square inch
per 1000 Btuh of the total input of all appliances in the enclosure,
but not less than 100 square inches.
If the confined space is within a building of tight construction, air
for combustion, ventilation and draft hood dilution must be
obtained from outdoors. When directly communicating with the
outdoors through vertical ducts, two permanent openings, located
in the above manner, shall be provided. Each opening shall have
a free area of not less than one square inch per 4000 Btuh of the
total input of all appliances in the enclosure. If horizontal ducts
are used, each opening shall have a free area of not less than
one square inch per 2000 Btuh of the total input of all appliances
in the enclosure.
Dampers or other obstructions must not be installed between the
heater and the barometric draft control assembly.
Do not adjust settings on gate. Counterweight washers are factory
adjusted and should result in breeching pressure measurements
at the combustion test hole (fig. 4) within the range shown in
table 6.
NOTE: A negative draft must be maintained in the vent piping.
When installed, the damper gate must pivot freely in the ring
guides. This gate will automatically adjust to regulate the chimney
draft imposed on the heater.
PROPER DRAFT CONTROLLER AND
VENT PIPE INSTALLATION
FIGURE 4
VENT CONNECTION
Vent connections must be made to an adequate stack or chimney.
Refer to the National Fuel Gas Code (latest version) or to the
vent pipe manufacturer’s gas vent and chimney sizing table to
properly design and size the venting system. Refer to Table 3 for
the vent pipe size required for installation to the barometric draft
control assembly outlet.
TABLE 3 - BAROMETRIC DRAFT CONTROL
ASSEMBLY OUTLET SIZE
VENTING
WARNING
THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST
BE FOLLOWED TO AVOID CHOKED COMBUSTION OR
RECIRCULATION OF FLUE GASES. SUCH CONDITIONS
CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION.
Type B venting may be used with these heaters. All local and
utility regulations on venting should be followed.
BAROMETRIC DRAFT CONTROL ASSEMBLY
A double-acting barometric draft control assembly is provided with
each unit. The draft control assembly must be installed without
alteration. This assembly is factory adjusted for horizontal
application only and must be attached to the heater as shown in
DRAFT CONTROL
MODELOUTLET DIAMETER
***81-1406”
***81-1996”
***81-2708”
***81-3708”
Where an existing chimney or vent is to be used, be sure that the
chimney or vent has adequate capacity for the number and sizes
of gas appliances being vented through it. Inspect the chimney
or vent and remove all soot or other obstructions which will retard
free draft.
Vent connectors making horizontal runs must have a minimum
upward slope toward the chimney or vent of 1/4 inch per foot.
Vent connector length should be kept as short as possible. Be
sure that the vent pipe does not extend beyond the inside wall of
a chimney.
7
In venting systems where a continuous or intermittent back
(positive) draft is found to exist, the cause must be determined
and corrected. In some cases, a special vent cap may be
required.
Do not install this unit on the positive draft side of a venting system
being served by a power exhauster.
Occasionally, some water seepage will occur at a cleanout port.
To correct this situation, slightly tighten the cleanout cover bolts
until the seepage is eliminated. Do not overly tighten the bolts or
the cleanout gasket will be damaged. Tighten each bolt gradually
and alternate between opposed bolts on the cleanout cover.
BURNER INSTALLATION
DRAIN VALVE AND ACCESS PANELS
The heaters are equipped with a 3/4" drain valve mounted above
and to the left of the burner. See page 2.
The combustion chamber observation access panel is located
above and to the left of the burner. A plug located under the
panel, see fig. 5, is inserted into the combustion chamber wall.
This plug should not be removed except, in rare cases, when the
combustion chamber requires cleaning or replacement.
WARNING
DO NOT REMOVE THIS PLUG WHILE THE HEATER IS IN
OPERATION. THE COMBUSTION CHAMBER IS UNDER
PRESSURE AND MAIN BURNER FLAMES WILL ESCAPE
THROUGH THE OPENING. THIS IS AN EXTREMELY
HAZARDOUS CONDITION WHICH MAY RESULT IN SERIOUS
INJURY.
Remove the factory-installed insulation covering the combustion
chamber opening. (A utility knife is useful for cutting out the
insulation). Cut the insulation back even with the jacket opening.
Install the flange gasket (which is usually taped to the heater
jacket) over the three bolts protruding from the tank at the
combustion chamber opening.
Remove the hardware (3 hex nuts, 3 flat washers, and 3 lock
washers) from the shipping bag attached to the heater’s electrical
conduit.
COMBUSTION CHAMBER ACCESS PORT
FIGURE 5
IMPORTANT
Before removing the access panel and observation plug, BE SURE
THAT THE ELECTRICAL POWER TO THE HEATER IS “OFF”.
This will prevent the heater from operating while servicing the
unit. Remember to install the plug and access cover BEFORE
restoring electrical power to the heater.
Another access panel is located above and to the right of the
burner, fig. 6. This panel covers the cleanout opening in the tank
which is sealed by a gasket and cover.
TANK CLEANOUT PORT
FIGURE 6
POWER BURNER INSTALLATION
FIGURE 7
Begin assembling the power burner to the tank by placing the
power burner nozzle in the combustion chamber opening. Slide
the nozzle into the tank and rotate the mounting flange to engage
the mounting bolts, refer to Figure 7. Then, place the flat washers
followed by the lock washers, and finally the hex nuts on the
mounting bolts. Hand tighten the nuts. Then gradually tighten
each nut alternating between the 3 mounting bolts. Do not over
tighten as damage to the flange gasket or to the tank may result.
Refer to figure 7.
GAS METER SIZE — CITY GASES ONLY
Be sure that the gas meter has sufficient capacity to supply the
full-rated gas input of the water heater as well as the
requirements of all other gas fired equipment supplied by the
meter. If gas meter is too small, request the gas company to
install a larger meter having adequate capacity.
GAS PRESSURE REGULATION
Main manual pressure to the water heater should be between
4.5" minimum and 10.5" maximum w.c. for natural gas and 11.0"
minimum and 13.0" maximum w.c. for propane gas. The inlet
gas pressure
regulator is necessary if higher gas pressures are encountered.
See Table 6.
8
must not exceed the maximum value. A service
WARNING
THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER
THAN 10.5" W.C. - NATURAL GAS, 13.0" W.C. - PROPANE GAS
(1/2 POUND PER SQUARE INCH GAUGE) SUPPLY GAS
PRESSURE. HIGHER GAS PRESSURES REQUIRE
SUPPLEMENTAL REDUCING SERVICE REGULATION.
EXPOSURE TO HIGHER GAS SUPPLY PRESSURE MAY CAUSE
DAMAGE TO THE GAS CONTROLS WHICH COULD RESULT IN
FIRE OR EXPLOSION. IF OVERPRESSURE HAS OCCURRED,
SUCH AS THROUGH IMPROPER TESTING OF GAS LINES OR
EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM, THE
GAS VALVE MUST BE CHECKED FOR SAFE OPERATION. MAKE
SURE THAT THE OUTSIDE VENTS ON THE SUPPLY
REGULATORS AND THE SAFETY VENT VALVES ARE
PROTECTED AGAINST BLOCKAGE. THESE ARE PARTS OF
THE GAS SUPPLY SYSTEM, NOT THE HEATER. VENT
BLOCKAGE MAY OCCUR DURING ICE STORMS.
DISCONNECT THE APPLIANCE AND ITS MAIN MANUAL GAS
SHUTOFF VALVE FROM THE GAS SUPPLY PIPING SYSTEM
DURING ANY SUPPLY PRESSURE TESTING EXCEEDING 1/2
PSIG. GAS SUPPLY LINE MUST BE CAPPED WHEN
DISCONNECTED FROM THE HEATER. FOR TEST
PRESSURES OF 1/2 PSIG OR LESS, THE APPLIANCE NEED
NOT BE DISCONNECTED, BUT MUST BE ISOLATED FROM
THE SUPPLY PRESSURE TESTING BY CLOSING THE MAIN
MANUAL GAS SHUT OFF VALVE.
GAS PIPING
Contact your local gas service company to ensure that adequate
gas service is available and to review applicable installation
codes for your area.
TABLE 4
MAXIMUM CAPACITY OF PIPE IN CUBIC FEET
OF GAS PER HOUR
(Based upon a Pressure Drop of 0.5 inch Water Column and
0.6 Specific Gravity Gas and max. gas pressure of .5 psig)
Apply joint compounds (pipe dope) sparingly and only to the male
threads of pipe joints. Do not apply compound to the first two
threads. Use joint compounds resistant to the action of liquefied
petroleum gases.
BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR
GAS LEAKAGE. USE SOAP AND WATER SOLUTION, OR
OTHER MATERIAL ACCEPTABLE FOR THE PURPOSE IN
LOCATING GAS LEAKS. DO NOT USE MATCHES, CANDLES,
FLAME OR OTHER SOURCES OF IGNITION FOR THIS
PURPOSE.
Size the main gas line in accordance with Table 4. The figures
shown are for iron pipe or equivalent at 0.5 in. w.c. pressure
drop, which is considered normal for low pressure systems.
Note that an excess number of fittings such as elbows and tees
will add to the pipe pressure drop. No additional allowance is
necessary for an ordinary number of fittings.
IF COPPER SUPPLY LINES ARE USED THEY MUST BE
INTERNALLY TINNED AND CERTIFIED FOR GAS SERVICE.
IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING
FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING
MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.
BEFORE ATTACHING THE GAS LINE, BE SURE THAT ALL GAS
PIPE IS CLEAN ON THE INSIDE.
TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS
SUPPLY LINE, A DRIP LEG (SOMETIMES CALLED DIRT LEG)
MUST BE INCORPORATED IN THE PIPING. SEE FIG. 8. THE
DRIP LEG MUST BE READILY ACCESSIBLE, REFER TO FIG. 8,
AND NOT SUBJECT TO FREEZING CONDITIONS. INSTALL IN
ACCORDANCE WITH RECOMMENDATIONS OF SERVICING
GAS SUPPLIERS. REFER TO THE
NATIONAL FUEL GAS CODE
(LATEST VERSION).
To prevent damage, care must be taken not to apply too much
torque when attaching gas supply pipe to gas valve inlet.
POWER BURNER ASSEMBLY, GAS MANIFOLD AND SUGGESTED
INLET PIPING - FIGURE 8
HEATER WIRING INSTRUCTIONS
The power burner should be wired to the heater as shown in
Figure 9. The model’s rating plate (or see Table 2) provides the
electrical information needed to size the complete heater branch
supply circuit.
All electrical work must be installed in accordance with the latest
version of the
When installed, the appliance must be electrically grounded in
accordance with local codes or, in the absence of local codes,
with the latest version of the National Electrical Code,
ANSI/NFPA 70.
National Electrical Code and local requirements.
9
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.