WARNING: If the information in this
manual is not followed exactly, a fire or
explosion may result causing property
damage, personal injury or loss of life.
— Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your
building.
• Immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions.
• If you cannot reach your gas
supplier , call the fire department.
Should overheating occur or the gas supply fail to shut off, do
W ARNING
not turn off or disconnect the electrical supply to the pump.
Instead, shut off the gas supply at a location external to the
appliance.
W ARNING
Do not use this boiler if any part has been under water.
Immediately call a qualified service technician to inspect the
boiler and to replace any part of the control system and any
gas control which has been under water.
THE UNIT SHOULD NOT BE INSTALLED DIRECTLY ON A
CARPETED FLOOR. A FIRE HAZARD MAY RESULT. Instead,
the boiler must be installed on the A. O. Smith Combustible
Floor Kit Base or concrete blocks extending beyond the full width
and depth of the boiler by at least 3 (76.2mm) inches. If the
boiler is installed in a carpeted alcove, the entire floor must be
covered with concrete blocks, or use the A. O. Smith Combustible
Floor Kit Base.
Lighting Instructions for the G(B/W) 300 through 750 models
FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY
OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST
NEVER BE PLACED ON OR ADJACENT T O THE BOILER. OPEN
CONTAINERS OF FLAMMABLE MATERIAL SHOULD NOT BE
STORED OR USED IN THE SAME ROOM WITH THE BOILER.
Light the unit in accordance with the instructions on the lighting
and operating label attached to the boiler. These instructions
are repeated on the following two pages.
2
LIGHTING INSTRUCTIONS
These models have an automatic hot surface ignition system
mounted on the combustion chamber panel inside the front
jacket. This hot surface igniter ignites the main burner gas
whenever the system control calls for heat.
Before proceeding with operation of the unit, make sure the
boiler and system are filled with water and all air is expelled
from the boiler, radiator tank(s) and piping.
It is recommended that lower water temperatures be used to
avoid the risk of scalding. It is further recommended, in all cases,
that the water temperature be set for the lowest temperature
which satisfies the user's hot water needs. This will also provide
the most energy efficient operation of the water heater and
minimize scale formation.
SETTING THE WA TER HEATER TEMPERATURE A T 120°F WILL
REDUCE THE RISK OF SCALDS. Some states require settings
at specific lower temperatures. Table 1 below shows the
approximate time-to-burn relationship for normal adult skin.
WARNING
THE MAIN MANUAL GAS SHUT-OFF V A LVE MUST HA VE BEEN
CLOSED FOR A T LEAST FIVE (5) MINUTES BEFORE LIGHTING .
This waiting period is an important safety step. Its purpose is
to permit gas that might have accumulated in the combustion
chamber to clear. IF YOU DETECT GAS A T THE END OF THE
PERIOD DO NOT PROCEED WITH LIGHTING . RECOGNIZE THAT
GAS ODOR, EVEN IF IT SEEMS WEAK, MA Y INDICATE PRESENCE
OF ACCUMULA TED GAS SOMEPLACE IN THE AREA WITH A RISK
OF FIRE OR EXPLOSION.
WARNING
THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH
AS GAS WA TER BOILERS IN ROOMS, GARAGES OR OTHER
AREAS WHERE GASOLINE AND OTHER FLAMMABLE LIQUIDS
ARE USED OR STORED, OR ENGINE-DRIVEN EQUIPMENT OR
VEHICLES ARE STORED, OPERATED OR REPAIRED.
FLAMMABLE VAPORS ARE HEA VY AND TRA VEL ALONG THE
FLOOR AND MA Y BE IGNITED BY THE BOILER'S MAIN BURNER
FLAMES CAUSING FIRE OR EXPLOSION. Some local codes
permit operation of gas appliances if installed 18 inches or more
above the floor. This may reduce the risk if location in such an
area cannot be avoided.
TEMPERATURE REGULATION
DANGER
HOT WATER TEMPERATURES REQUIRED FOR AUTOMATIC
DISHWASHER AND LAUNDRY USE CAN CAUSE SCALD
BURNS RESULTING IN SERIOUS PERSONAL INJURY AND/
OR DEATH. THE TEMPERA TURE A T WHICH INJURY OCCURS
V ARIES WITH THE PERSON'S AGE AND TIME OF EXPOSURE.
THE SLOWER RESPONSE TIME OF CHILDREN, AGED OR
DISABLED PERSONS INCREASES THE HAZARDS TO THEM.
NEVER ALLOW SMALL CHILDREN TO USE A HOT WA TER T AP ,
OR TO DRAW THEIR OWN BATH WATER. NEVER LEAVE A
CHILD OR DISABLED PERSON UNATTENDED IN A BATHTUB
OR SHOWER.
THE WATER HEATER SHOULD BE LOCATED IN AN AREA
WHERE THE GENERAL PUBLIC DOES NOT HA VE ACCESS T O
SET TEMPERA TURES.
Table 1: Risk of Scalds
TemperatureTime to Produce 2nd & 3rd
SettingDegree Burns on Adult Skin
Over 170°FNearly instantaneous
160°FAbout 1/2 second
150°FAbout 1-1/2 seconds
140°FLess than 5 seconds
130°FAbout 30 seconds
120°F or lessMore than 5 minutes
BOILER LOCATION
Water heater life depends upon water quality, water pressure
and the environment in which the water heater is installed. Water
heaters are sometimes installed in locations where leakage
may result in property damage, even with the use of a drain pan
piped to a drain. However, unanticipated damage can be reduced
or prevented by a leak detector or water shutoff device used in
conjunction with a piped drain pan. These devices are available
from some plumbing supply wholesalers and retailers, and
detect and react to leakage in various ways:
• Sensors mounted in the drain pan that trigger an alarm or
turn off the incoming water to the water heater when leakage
is detected.
• Sensors mounted in the drain pan that turn off the water supply
to the entire home when water is detected in the drain pan.
• Water supply shutoff devices that activate based on the water
pressure differential between the cold water and hot water
pipes connected to the water heater.
• Devices that will turn off the gas supply to a gas water heater
while at the same time shutting off its water supply.
BLOCKED VENT SHUT-OFF SYSTEM
The Boiler is equipped with a blocked vent shut-off system which
will close the gas valve and shut off the main burner gas when
there is excessive pressure in the vent system due to a partially
or completely blocked vent system.
DO NOT ATTEMPT TO OPERATE THE BOILER if this situation
occurs. Shut the boiler off before performing all the steps shown
in "TO TURN OFF GAS TO APPLIANCE" section of the Lighting
and Operating Instructions.
Contact a qualified service agent to inspect the unit and vent
system and correct the problem.
VENT SYSTEM
The flue products are corrosive in nature and if the boiler is
vented horizontally the flue gases are at a higher pressure than
3
the surrounding air pressure. Inspection of the boiler and vent
system is necessary to insure that flue gas leakage to the
surrounding area does not occur.
Inspect the external surfaces of the vent system every 3 months
for corrosion and leakage. Inspect the vent terminations for
corrosion and foreign matter which may be blocking the
exhausting flue products. Call a qualified service agent to
replace or repair any corroded or leaking parts.
A qualified service agent must inspect the internal surfaces of
the vent system and the boiler at least once a year.
BURNER SYSTEM
To maintain safe operation and the greatest efficiency for the
boiler, observe the burner flame through the observation port on
the jacket panel, once a month for proper flame characteristics.
• The burners should display the following characteristics:
• Provide complete combustion of gas.
• Cause rapid ignition and carry over across all burners and
across the entire burner.
• Give quiet operation during ignition, burning and extinction.
• Cause no excessive lifting of flames from the burner ports.
If the preceding characteristics are not evident, check for
accumulation of lint or other foreign material that restricts the
inlet air or burner ports. Ensure there is the proper amount of air
to the burner. Flame lifting from the burner is caused by too
much air to the burner.
The burners must be inspected by a qualified service technician
at least once a year.
DO NOT STORE COMBUSTIBLE MATERIALS, GASOLINE, OR
OTHER FLAMMABLE VAPORS, LIQUIDS IN THE AREA OF THE
APPLIANCE. NONCOMPLIANCE MAY RESULT IN FIRE OR
EXPLOSION. DO NOT OBSTRUCT THE FLOW OF
COMBUSTION OR VENTILATION AIR TO THE APPLIANCE.
CHEMICAL VAPOR CORROSION
Boiler corrosion and component failure can be caused by
airborne chemical vapors. Spray can propellants, cleaning
solvents, refrigerants, calcium or sodium chloride (water softener
salts), waxes, and process chemicals are typical compounds
that are potentially corrosive. These materials are corrosive at
very low concentration levels with little or no odor to reveal their
presence. Products of this sort should not be stored near the
boiler. Air which is brought in contact with the boiler should not
contain any of these chemicals. The boiler should be provided
with air from outdoors when installed in environments having
corrosive atmospheres.
CIRCULATION PUMP
Refer to the pump manufacturer's schedule of maintenance for
frequency and method of lubricating the pump and motor. Inspect
the pump once a month for leaky mechanical seals and/or
O-rings and loose or damaged components. Contact a qualified
service agent to replace or repair parts as required.
ELECTRONIC HOT SURFACE
IGNITION CONTROL BOARD
The EMC5000 control system is a fully integrated, state of the art
electronic control system. It consists of sensors, output devices,
a power switch, a 24vac transformer, wiring, and the following
printed circuit boards:
Central Control Board (CCB).See Figure 1A.
Flame Control Board (FCB).See Figure 1B.
User Interface Board (UIB).This part of the User Interface
Module (UIM). See Figure 3.
Power Distribution Board (PDB). See Figure 1C.
Touch Sensor Board (TSB).This is part of the User
Interface Module (UIM). See
Figure 3.
The CCB contains circuitry for both master control and flame
control for the first stage. The FCB contains circuitry for flame
control on up to one additional stage. Dip switches on the CCB
and FCB are used to configure the system. The UIB and TSB
are included in the User Interface Module (UIM) along with a 4
line by 20-character LCD display . The PDB provides connection
points for input power, the water pump, and the transformer. It
also distributes power to the system and contains the system
fuses.
Dual stage control is accomplished by means of an internal
communication network and the FCB's. One FCB is required for
each stage beyond initial first stage. The CCB also contains an
external communications system to allow for connection to a
PC, a modem, or an EMS system. Through this connection
multiple boilers can also be linked together.
CAUTION
The internal communications cables should never be connected
to the external communications connectors and vice-versa.
There are several microcontrollers used on the board. Three on
the CCB, two on the FCB, and one on the UIB. These micros
control the temperature and ignition control functions for the
boiler. Inherent in the design are the normal operating sequences
and safety features associated with a gas ignition control system.
The system continuously performs various diagnostic tests to
verify proper appliance and control operation. Should an unsafe
condition occur, the control will shut down the burner and display
a red fault light as well as indicate the cause of the fault on the
display. The operating programs for the system are stored in
permanent memory inside the micros. User-selectable
operating parameters and a history of detected faults are stored
in re-writable memory in the micros. A loss of power does not
affect either of the memories.
Inputs T o CCB and FCB:
• Temperature Sensors:
• Temperature probes (CCB - outlet and either inlet or tank is
required): The CCB accepts analog temperature inputs from
up to three sensors (inlet, outlet and tank).
• ECO input (CCB - required):
The ECO (Energy Cut-Off) is a Hi-Limit switch, which is
located inside the output probe. It is a normally closed switch
that opens if the probe is exposed to a temperature higher
than the trip point.
• Thermostat input (CCB - optional):
This input is set up to work with an externally connected
thermostat that provides a contact closure. If this input is
4
Figure 1A. CCB (Drawing #211758)
5
Figure 1B. FCB (Drawing #211759)
6
Figure 1C. PDB (Drawing #211760)
7
closed and everything else is in the proper state, a "call for
heat" condition will be initiated. These leads should be
shorted together, when a thermostat is not being used. If it is
desired that the thermostat control the temperature of the
boiler, the operating setpoint of the system should be set
higher than the temperature that the thermostat is controlling
to. This will allow the thermostat to control the boiler. When
the thermostat closes, a call for heat will be generated until
the thermostat determines that the control temperature has
been reached.
• Air Pressure Sensors (open condition indicates fault):
• Blocked Flue (CCB - required)
• Normally closed switch that opens if the flue becomes
blocked during operation.
• Powered Vent (CCB - optional):
Normally open switch that closes when the powered vent is
operating properly. This input is enabled-disabled by a
dipswitch on the CCB.
• Blower Prover High (FCB - required on stages that have
blowers):
Normally open switch that closes when the air pressures
produced by the high-speed blower is above the trip level.
• Gas Pressure Sensors (open condition indicates fault):
• Low Gas (CCB - optional):
Normally open switch that closes when the gas pressure
rises above the trip level. This input is enabled/disabled by a
dipswitch on the CCB.
• Hi Gas (FCB - optional):
Normally closed switch that opens in the gas pressure
exceeds a set value. This input is enabled/disabled by a
dipswitch on the CCB and FCB's.
• Water Level Sensor (open conditions indicates fault):
• Low Water Cut Off (CCB - optional):
Normally closed switch opens if a low water condition occurs.
This input is enabled/disabled by a dipswitch on the CCB.
• Water Flow Sensor:
• Flow (CCB - required):
Normally open switch that closes when flow exceeds a set
value.
• IRI Gas Valve Sensor:
• IRI Gas Valve (CCB - optional):
Normally open switch that closes when the IRI Gas Valve is
operating correctly. This input is enabled/disabled by a
dipswitch on the CCB.
• Flame Sensor:
• Flame (FCB - required on stage 1 and on stage 2 of a 4 stage
system - optional on others):
Returns a signal to the microprocessor if flame is detected
in the burner. This input is enabled/disabled by a dipswitch
on the FCB.
Outputs from CCB and FCB's :
• Relay Contact Outputs:
• IRI Gas Valve (CCB - 120vac- optional):
Provides electrical power to operate an IRI Gas Valve device.
• Alarm (CCB - 24vac- optional):
Provides electrical power to operate on external alarm. This
can be an audio device (i.e. Sonalert), a visual device (lamp),
or any other device that will operate with the voltage and
current level provided.
• Pump (CCB - 120vac - required on systems that do not have
an external pump):
Provides electrical power to directly operate a pump or the
coil of an externally connected contactor.
• Powered Vent (CCB - 24vac - optional):
Provides electrical power to operate a powered vent.
• Low and High Speed Blowers (FCB - 120vac - required on
stage 1 and on stage 2 of a 4-stage system and optional on
others.):
Independent outputs that provide power to operate low and
high speed blower output. Dip switches on the FCB's enable/
disable the use of blowers on stages 2, 3 and 4.
• Igniter (FCB - 120vac - required on stage 1 and on stage 2 of
a 4-stage system and optional on others.):
Provides power to operate the Silicon Carbide igniter. Dip
switches on the FCB's enables/disables the use of an igniter
on stages 2, 3 and 4.
• Gas Valve (FCB - 24vac - required):
Provides power to activate the gas valve. The gas valve cannot
be activated when the ECO contacts are open.
• Direct Connection Output:
• Low Water Cut Off (CCB - 24vac - optional):
Directly connected to the 24 vac line to provide power to operate
an external LWCO device.
Line Polarity Indicator & Fuse Protection
CCB/FCB Indicator Lamps & Fuses
A green LED is mounted on the PDB to indicate when line voltage
is applied. (The PDB also contains a yellow LED, a red LED,
and a test-run jumper, that are used during installation to verify
proper power connections.) A red LED on the CCB is used to
indicate when the 24 vac input fuse has blown. The FCB's also
have fuses on their 24vac power line. (Recommended
replacement fuses are: Littlefuse p/n 29707.5 for the 7.5 amp
CCB fuse, and Littlefuse p/n 297003 for the 3 amp FCB fuses.)
Repeated failure of fuse is an indication of failure to some
part of the system.
Y ellow LED's are located near the micros on the CCB and FCB's.
These LED's are "heartbeat indicators" and blink approximately
twice per second to indicate that the micros are running.
Igniters
The Genesis 400 Series Boilers use a Silicon Carbide Igniter.
Appliance Operating Sequence
NOTE: The following sequence is based on a four-stage system
with all options and two-speed blowers. It is characteristic of
most system configurations.
1. The EMC5000 controller has four modes of operation:
Initialization, Standby, Running and Service. The internal
CCB and FCB micros control these modes through a
sequence of steps (or States) which are further described
in the "UIM Operating Procedures" section.
2. When power is applied to the system, it enters the
Initialization mode and the following automatic functions
are performed:
•A. O. Smith opening screen is displayed on the UIM.
•The system goes through a self-calibration indicated by the
green running LED blinking and then staying on: next the
red service LED and yellow standby LEDS come on; next
the stage 1 service and running LEDS blink on and off
followed by stage 2, stage 3, stage 4 and then back to stage
1,2,3,4 LEDS.
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.