A.O. Smith 402, 401, 404, 403, 405 User Manual

...
COPPER BOILERS FOR
HYDRONIC HEATING AND
HOT WATER SUPPLY
Installation
Operation
Maintenance
Limited Warranty
WARNING: If the information in this manual is not followed exactly , a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Extinguish any open flame.
Do not try to light any appliance.
Do not touch any electrical switch; do
not use any phone in your building.
Immediately call your gas supplier
from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier,
call the fire department.
Installation and service must be
performed by a qualified installer, service agency or the gas supplier.
Instruction Manual
GB/GW MODELS:
1000, 1300, 1500, 1850, 2100, 2500
SERIES: 400, 401, 402, 403, 404, 405
CAUTION
TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY. PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE.
for buying this cost
Thank You
You should thoroughly read and understand this manual before installation and/or operation of this boiler. Please pay particular attention to the important safety and operating instructions as well as the WARNINGS and CAUTIONS.
CONTENTS P AG E
DIMENSIONS/CAPACITIES DA T A .......................... 2 - 3
FOREWORD......................................................... 4 - 5
FEATURES/CONTROLS..................................... 5 - 7
INSTALLA TION INSTRUCTIONS ....................... 7 - 9
VENTING ........................................................... 9 - 11
SYSTEM INSTALLATION ................................ 11 - 16
HYDRONIC INSTALLA TION ............................ 16 - 18
HOT WATER SUPPLY INSTALLATION ........... 18 - 31
GAS CONNECTIONS...................................... 18 - 23
OPERATION.................................................... 31 - 34
LIGHTING AND OPERATING .......................... 32 - 33
CONTROL SYSTEM ....................................... 34 - 44
PREVENTATIVE MAINTENANCE.................. 44 - 46
TROUBLE SHOOTING .................................... 42 - 44
WIRING DIAGRAM/SCHEMATIC ................... 24 - 27
LIMITED WARRANTY ............................................. 47
efficient, high recovery unit from
A. O. Smith Water Products Co.
PLACE THESE INSTRUCTIONS ADJACENT TO BOILER AND
NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.
PRINTED IN U.S.A. 0906
MC BEE, SC., RENTON, WA.,
STRATFORD-ONTARIO, VELDHOVEN-THE NETHERLANDS,
NANJING, CHINA
ww w.hotwater.com / email:parts@hotwater.com
1
212511-000
DIMENSIONS/CAP ACITIES DAT A
TOP VIEW
FRONT VIEW
IMPORT ANT!
Refer to "Installation Clearances" section of manual (page 7) for recommended service clearances prior to boiler placement.
LEFT SIDE
REAR VIEW
TABLE 1: GAS AND ELECTRICAL REQUIREMENT
Manifold Pressure Electrical Characteristics
MODEL Type of Gas Inches W.C. kPa Volts/Hz Amperes
GW/GB-1000
thru 2500 NATURAL 3.5 0.87 120/60 30
GW/GB-1000
thru 2500 PROPANE 10 2.49 120/60 30
All Models - Maximum Supply Pressure: 14.0 In. W.C. (3.49 kPa) Minimum Supply Pressure Natural Gas: 6.0 In. W.C. (1.22 kPa) Minimum Supply Pressure Propane Gas: 1 1.0 In. W.C. (2.74 kPa) Minimum Pressures must be maintained during operating conditions.
Figure 1.
T ABLE 2. DIMENSIONAL DA T A
ABCD EF
Model Inches c m Inches c m Inches cm Inches c m Inches cm Inches cm
GW/GB-1000 14.1 35.8 12.2 31.0 40.3 102.4 31.6 80.3 26.0 66.0 46.8 118.9 GW/GB-1300 24.8 63.0 12.2 31.0 40.3 102.4 31.6 80.3 39.3 99.8 57.3 145.5 GW/GB-1500 30.2 76.7 12.2 31.0 40.3 102.4 31.6 80.3 44.6 113.3 64.3 163.3 GW/GB-1850 27.7 70.4 11.2 28.4 43.0 109.2 32.3 82.0 44.0 111.8 78.3 198.9 GW/GB-2100 31.0 78.7 11.2 28.4 43.0 109.2 32.3 82.0 49.5 125.7 85.3 216.7 GW/GB-2500 38.1 96.8 10.5 26.7 43.0 109.2 32.3 82.0 56.5 143.5 99.3 252.2
Input Rating Exhaust Air Intake
Model Natural Gas Natural Gas Propane Gas Propane Gas Inches cm Inches c m Size
GW/GB-1000 990,000 289.95 990,000 289.95 10 25.4 8 20.3 2 1/2 NPT 2 NPT GW/GB-1300 1,300,000 380.74 1,300,000 380.74 12 30.5 10 25.4 2 1/2 NPT 2 NPT GW/GB-1500 1,500,000 439.31 1,500,000 439.31 12 30.5 10 25.4 2 1/2 NPT 2 NPT GW/GB-1850 1,850,000 541.82 1,850,000 541.82 14 35.6 10 25.4 2 1/2 NPT 2 1/2 NPT GW/GB-2100 2,100,000 615.04 2,100,000 615.04 14 35.6 12 30.5 2 1/2 NPT 2 1/2 NPT GW/GB-2500 2,490,000 729.26 2,490,000 729.26 16 40.7 12 30.5 2 1/2 NPT 2 1/2 NPT
BTU/Hr. KW BTU/Hr. KW Vent Diameter Diameter Water Conn. Gas Inlet
2
DIMENSIONS DA TA FOR OUTDOOR CONFIGURATION
REAR VIEW
FRONT VIEW
LEFT SIDE
TOP VIEW
Figure 2.
T ABLE 3. DIMENSIONAL DA TA
AB C D E F G HJ
Model Inches cm Inches cm Inches cm Inches cm Inches cm Inches cm Inches cm Inches cm Inches cm
GBO/GWO-1000 14 35.5 31.6 80.3 71.8 182.4 15.5 39.4 39.75 101 58.25 148 15.9 40.83 16 40.64 46.8 118.9 GBO/GWO-1300 24.75 62.9 31.6 80.3 82 208.3 15.5 39.4 39.75 101 58.25 148 15.9 40.83 16 40.64 57.3 145.5 GBO/GWO-1500 30 76.2 31.6 80.3 89 226 15.5 39.4 39.75 101 58.25 148 15.9 40.83 16 40.64 64.3 163.3 GBO/GWO-1850 27.5 69.9 32.3 82 103 261.6 18.9 48 43 109.2 61.5 156.2 23.9 60.7 20 50.8 78.3 198.9 GBO/GWO-2100 31 78.7 32.3 82 110 279.4 18.9 48 43 109.2 61.5 156.2 23.9 60.7 20 50.8 85.3 216.7 GBO/GWO-2500 38 96.5 32.3 82 124 315 18.9 48 43 109.2 61.5 156.2 23.9 60.7 20 50.8 99.3 252.2
3
TABLE 4: RECOVERY CAPACITIES
TEMPERATURE RISE - DEGREES °F (°C)
Input Rating Water 40°F 50°F 60°F 70°F 80°F 90°F 100°F 110°F 120°F 130°F
MODEL BTU/Hr. (kW) Flow (22.2°) (27.7°) (33.3°) (38.8°) (44.4°) (50°) (55.5°) (61.1°) (66.7°) (72.2°)
GW - 1000 990,000 (290.1) GPH 2520 2016 1680 1440 1260 1120 1008 916 840 775
LPH 9526 7620 6350 5443 4763 4234 3810 3462 3175 2930
GW - 1300 1,300,000 (380.9) GPH 3309 2647 2206 1891 1655 1471 1324 1203 1103 1018
LPH 12508 10006 8339 7148 6256 5560 5005 4547 4169 3848
GW - 1500 1,500,000 (439.5) GPH 3818 3055 2545 2182 1909 1697 1527 1388 1273 1175
LPH 14432 11548 9620 8248 7216 6415 5772 5247 4812 4442
GW - 1850 1,850,000 (542.0) GPH 4709 3767 3139 2691 2355 2093 1884 1712 1570 1449
LPH 17800 14239 11865 10172 8902 7912 7122 6471 5935 5477
GW - 2100 2,100,000 (615.3) GPH 5345 4276 3564 3055 2673 2376 2138 1944 1782 1645
LPH 20204 16163 13472 11548 10104 8981 8082 7348 6736 6218
GW - 2500 2,490,000 (729.6) GPH 6338 5071 4225 3622 3169 2817 2535 2305 2113 1950
LPH 23958 19168 15971 13691 11979 10648 9582 8713 7987 7371
TABLE 5: PUMPING PERFORMANCE GUIDE
GB MODELS-FLOW, HEAD LOSS AND TEMPERA TURE RISE
20 Deg. F Rise 30 Deg. F Rise 40 Deg. F Rise Maximum Flow Rate Minimum Flow Rate GPM PD-FT G PM PD-FT G PM PD-FT GPM PD-FT Deg. F GPM PD-FT Deg. F
MODEL Head Head Head Head Rise Head Rise GB - 1000 83 5.1 55 2.7 41.6 1.5 1 5 4 12.2 11 42 1.5 40 GB - 1300 109 7.2 72.8 4.2 54.6 3.2 154 14.5 1 4 55 3.2 40 GB - 1500 126 10.1 84 6.3 6 3 4.3 154 16.3 17 64 4.3 40 GB - 1850 154 18.5 103.6 10.1 77.7 6.4 15 4 18.5 20 78 6.4 40 GB - 2100 n/a n/a 117.6 14.5 88 8.3 154 21.3 2 3 89 8.3 40 GB - 2500 n/a n/a 139.4 18.5 104.6 11.6 154 23.2 28 105 11.6 40
Note: GW models (GB optional) are equipped with pumps capable of handling 50 equivalent feet
(15.2 m) of normal pipe fittings.
FOREWORD
Detailed installation diagrams are in this manual. These diagrams will provide the installer with a reference of materials needed and a suggested method of piping. IT IS NECESSARY THAT ALL W ATER AND GAS PIPING , AND THE ELECTRICAL WIRING BE INST ALLED AND CONNECTED AS SHOWN IN THE DIAGRAMS.
CHECK DIAGRAMS THOROUGHLY BEFORE STARTING INSTALLATION TO AVOID POSSIBLE ERRORS AND MINIMIZE TIME AND MA TERIALS COST. SEE FIGURES 1 THROUGH 5 AND TABLES 1, 2, AND 3.
This design complies with the current edition of ANSI Z21.13-CSA
4.9 for Gas-Fired Low-Pressure Steam and Hot Water Boilers.
MAKE SURE THE GAS ON WHICH THE BOILER WILL OPERATE IS THE SAME AS THAT SPECIFIED ON THE BOILER RATING PLATE.
The boiler installation must conform to these instructions and the local code authority having jurisdiction. In the absence of local codes, the installation must comply with the latest editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the National Electrical Code, NFPA 70 or CAN/CSA B149.1, and CSA 2 C22.1. The former is available from the Canadian Standards Association, 8501 East Pleasant Valley Road, Cleveland, OH 44131, and both documents are available from the National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269.
4
GROUNDING INSTRUCTIONS
This boiler must be grounded in accordance with the National Electrical Code, NFPA 70 or the Canadian Electrical Code CSA 2 C22.1
and/or local codes. The boiler is polarity sensitive, correct
wiring is imperative for proper operation.
This boiler must be connected to a grounded metal, permanent wiring system, or an equipment grounding conductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the boiler.
WARNING
YOUR BOILER IS NOT DESIGNED TO OPERA TE WITH A BOILER INLET WATER TEMPERATURE OF LESS THAN 120°F (49°C). COLDER INLET WATER TEMPERATURE WILL RESULT IN SIGNIFICANT CONDENSATION DEVELOPING ON THE HEAT EXCHANGER. THIS SITUATION CAN CAUSE A CORROSIVE ENVIRONMENT FOR THE HEAT EXCHANGER, BURNERS AND VENTING RESULTING IN PREMA TURE DAMAGE, WHICH COULD RESULT IN SERIOUS PERSONAL INJUR Y OR DEATH.
FOR SYSTEMS THAT USE LARGE VOLUMES OF COLD WATER OR SYSTEMS UTILIZING HEA VY WA TER DRAWS, CONDENSA TION CAN BE PREVENTED BY USING A BYP ASS LOOP.
CORRECT GAS
At times you may not be able to smell an LP gas leak. One cause is odor fade, which is a loss of the chemical odorant that gives LP gas its distinctive smell. Another cause can be your physical condition, such as having a cold or diminishing sense of smell with age. For these reasons, the use of a propane gas detector is recommended. IF YOU EXPERIENCE AN OUT OF GAS SITUATION, DO NOT TRY TO RELIGHT APPLIANCES YOURSELF . Call your local service agent. Only trained LP professionals should conduct the required safety checks in accordance with industry standards.
HIGH AL TITUDE INST ALLATION
WARNING
INSTALLATIONS ABOVE 4,500 FEET REQUIRE REPLACEMENT OF THE BURNER ORIFICES. FAILURE TO REPLACE THE ORIFICES WILL RESULT IN IMPROPER AND INEFFICIENT OPERATION OF THE APPLIANCE, PRODUCING CARBON MONOXIDE GAS IN EXCESS OF SAFE LIMITS, WHICH COULD RESULT IN SERIOUS PERSONAL INJURY OR DEATH.
GENESIS BOILERS ARE EQUIPPED WITH SELF-REGULATING PREJET ORIFICES WHICH AUT OMATICALL Y COMPENSATE FOR HIGHER ELEVATIONS AND ADJUST THE APPLIANCE'S INPUT RA TE ACCORDINGL Y, MAKING IT UNNECESSARY TO REPLACE ORIFICES FOR HIGH ALTITUDE (UP TO 4,500 FEET). CONSUL T THE FACTOR Y FOR HIGHER ALTITUDES.
Make sure the gas on which the boiler will operate is the same as that specified on the boiler rating plate. Do not install the boiler if equipped for a different type of gas, consult your gas supplier.
PRECAUTIONS
IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT OPERA TE UNTIL ALL CORRECTIVE STEPS HA VE BEEN MADE BY A QUALIFIED SERVICEMAN:
1. EXPOSURE TO FIRE.
2. IF DAMAGED.
3. FIRING WITHOUT WA TER.
4. SOOTING .
IF THE BOILER HAS BEEN EXPOSED TO FLOODING, IT MUST BE REPLACED.
LIQUID PETROLEUM MODELS
Boilers for propane or liquefied petroleum gas (LPG) are different from natural gas models. A natural gas boiler will not function safely on LP gas and no attempt should be made to convert a boiler from natural gas to LP gas.
LP gas must be used with great caution. It is highly explosive and heavier than air. It collects first in the low areas making its odor difficult to detect at nose level. If LP gas is present or even suspected, do not attempt to find the cause yourself. Leave the building, leaving doors open to ventilate, then call your gas supplier or service agent. Keep area clear until a service call has been made.
Some utility companies derate their gas for altitude. You should contact your gas supplier for any specific changes which may be required in your area. Call the local gas utility to verify BTU content of the gas supplied.
Input rating specified on the rating plate applies to elevations up to 4,500 feet (1350 m). For elevations above 4,500 feet (1350 m), ratings must be reduced, consult the factory.
FEATURES/CONTROLS
MUL TI-ST AGE FIRING AND CONTROL SYSTEM
ALL MODELS - The control system consists of four basic components: 1) Central Control Board 2) Flame Control Board 3) User Interface Module 4) Power Distribution Board; see Figures 17, 18, 19 and 21. The Central Control Board, Flame Control Boards and the Power Distribution Board are located in the control box and can be accessed through panels on the left side and top of the unit. The User Interface Module is attached to the front jacket panel. The control system is a multi-stage control capable of managing three or four firing stages. Models 1000, 1300, and 1500 operates with 3-stage fire. Models 1850, 2100 and 2500 operates with 4-stage fire. Every system will have one Central Control Board (CCB), one Power Distribution Board (PDB), one User Interface Module (UIM) and either two or three Flame Control Boards (FCB) depending on the model.
The Control Boards Figure 17 and 18, contain dipswitches which allow the user to control several system options. See Control System Section.
5
DIFFERENTIAL PRESSURE SWITCH
COMBUSTION AIR BLOWER
The differential pressure switch ensures that a sufficient differential exists between the air pressure in the pre-mix chamber and the inlet of the burner for safe, combustion and proper low NOx emission. The switch has two pressure taps marked "+" (positive) and "-" (negative). Silicone tubing is run from the positive pressure tap of the switch to a tap on the control panel to measure the air pressure in the pre-mix chamber. The negative pressure tap measures the pressure taken at the burner's auxiliary tube. Connections can be seen by removing the lower front jacket panel. It is important that this panel remain sealed at all times while the boiler is operating.
The differential pressure switch is normally open and closes when the combustion blower starts.
BLOCKED FLUE PRESSURE SWITCH
The blocked flue pressure switch ensures that the vent system is clear. This pressure switch is normally closed and only opens on fault conditions.
FLAME SENSOR
The flame sensor detects the flame presence on burner's ports. If no flame is sensed, the gas valve(s) will close automatically. If no flame is sensed on three ignition trials the boiler will lock out. In the event of a lockout, depress the SELECT button on the UIM to restart the boiler.
WA TER FLOW SWITCH
Provides air for combustion process. The blower settings are adjustable through the use of the air shutter, however, blowers are set at the factory and might require slight adjustment depending on site installation.
T ANK PROBE
FOR HOT WA TER SUPPLY SYSTEMS (GW models), a tank probe
is supplied with each hot water supply boiler. Note: The tank probe must be designated as the controlling probe
using dip switch "4" on Central Control Board (Figure 17) before it can be used for (GW) hot water supply applications.
"Pigtails" of field-supplied wires should be spliced to "pigtails" of tank probe and connected to terminal block in the 24VAC junction box. See Figure 12 for the tank probe installation. Follow the instructions in the "TANK PROBE INSTALLATION PROCEDURE". See page 18.
FOR HOT WA TER HEA TING SYSTEMS (GB models), a t ank probe is not supplied with the GB models due to the many various types of systems and operating conditions. A tank probe can be used as an option to control loop temperature and unit staging. Additionally, the inlet temperature probe can be used as the loop thermostat in some heating applications. The tank probe connects to designated wires in the junction box at the rear of the boiler. Do not operate this boiler using the internal
high limits only, use a tank probe or operating thermostat to control system temperatures.
The water flow switch is installed at the boiler outlet to prevent burner operation in the event of inadequate water flow through the boiler. It is a normally open switch that will close its contacts when increasing water flow rate is detected. The water flow switch is factory-set, but may require field adjustment. The contacts will open when the flow rate drops below the adjusted setting causing the gas valve(s) to close which will turn off the gas to the burners.
LIMIT CONTROLS
CAUTION
LIMIT CONTROLS ARE SAFETY DEVICES AND ARE NOT TO BE USED AS AN OPERATING CONTROL (THERMOSTA T).
The "G(B/W)" models incorporate an outlet water probe consisting of two limit controls:
1. An adjustable automatic reset limit control, that can be set as high as either 210°F (99°C) or 235°F (113°C) depending on the application.
2. A fixed manual reset limit (ECO) factory set at 244°F (118°C). If the manual reset should open due to high temperature, the gas valves will close and the unit will go into lockout. If lockout occurs, push the SELECTION button on the UIM to restart the boiler.
ON/OFF SWITCH
The ON/OFF switch is a single-pole, single-throw rocker switch. The switch provides 120VAC from the line source to the boiler.
Note: The tank probe or additional 24V AC devices must be identified using Dipswitches on Central Control Board before they are recognized as a part of the heating system; see Table 5. Refer to "Control System" section for more information about dipswitch settings.
CIRCULA TING PUMP
The pump flow rate should not exceed the maximum recommended flow rate; see Table 5.
FOR HOT WA TER SUPPLY SYSTEMS (GW models), ordered with the circulator as an integral part of the boiler; the pump has been lubricated at the factory, and future lubrication should be in accordance with the motor manufacturer's instructions provided as supplement to this manual.
FOR HOT WA TER HEA TING SYSTEMS (GB models or GW models ordered without circulator), the circulator is NOT provided and
must be field-installed.
LOW WA TER CUT OFF (Not Supplied)
If low water level protection is required by the authorities having jurisdiction, a low water cutoff switch should be installed next to the boiler in the outlet water line as shown in "HYDRONIC INSTALLATION" section; see page 16. The switch should receive periodic (every six months) inspection to assure proper operation. A low water cutoff device of the float type should
be flushed every six months.
6
DRAIN V ALVE (Not Supplied)
Additional drain valves must be obtained and installed on each boiler and tank for draining purposes.
SAFETY RELIEF V AL VES
side of the tank on a center line within the upper six (6) inches (15 cm) of the top of the tank. The tapping shall be threaded in accordance with the latest edition of the Standard for Pipe Threads, General Purpose (inch), ANSI/ASME B1.20.1. The location of, or intended location for, the T & P relief valve shall be readily accessible for servicing or replacement.
Your local code authority may have other specific relief valve requirements not covered below.
WARNING
THE PURPOSE OF A SAFETY RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE WHICH MAY CAUSE T ANK EXPLOSION, SYSTEM OR BOILER DAMAGE.
TO AVOID W A TER DAMAGE A DRAIN LINE MUST BE CONNECTED TO A SAFETY RELIEF V AL VE FOR DIRECT DISCHARGE TO A SAFE LOCATION. A DRAIN LINE MUST NOT BE REDUCED FROM THE SIZE OF THE V ALVE OUTLET AND IT MUST NOT CONT AIN ANY VALVES BETWEEN THE BOILER AND THE RELIEF VALVE OR THE RELIEF VAL VE AND THE DRAIN EXIT. IN ADDITION, THERE SHOULD NOT BE ANY RESTRICTIONS IN A DRAIN LINE NOR SHOULD IT BE ROUTED THROUGH AREAS WHERE FREEZING CONDITIONS MIGHT OCCUR. DO NOT THREAD OR CAP THE DRAIN LINE EXIT . RESTRICTING OR BLOCKING A DRAIN LINE WILL DEFEAT THE PURPOSE OF THE RELIEF VALVE AND MA Y CREATE AN UNSAFE CONDITION. INST ALL A DRAIN LINE WITH A DOWNWARD SLOPE SUCH THAT IT NATURALLY DRAINS ITSELF.
If any safety relief valve is replaced, the replacement valve must comply with the latest version of the ASME Boiler and Pressure Vessel Code, Section IV (HEATING BOILERS). Select a relief valve with a discharge rating NOT less than the boiler input, and a set pressure NOT exceeding the working pressure of any component in the system.
The storage tank temperature and pressure relief valve must comply with the applicable construction provisions of the Standard for Relief V alves for Hot W ater Supply Systems, ANSI Z21.22-CSA-
4.4 (current edition). The valve must be of the automatic reset type and not embody a single-use type fusible plug, cartridge or linkage.
FOR HOT WATER HEATING SYSTEMS, the boilers are shipped with a 50 psi pressure relief valve. This relief valve is factory installed on the water outlet header of the boiler.
FOR HOT WATER SUPPLY SYSTEMS, the boilers are shipped with a 125 psi pressure relief valve. This relief valve is factory installed on the water outlet header of the boiler. This ASME-rated valve has a discharge capacity that exceeds the maximum boiler input rating and a pressure rating that does not exceed the maximum working pressure shown on the boiler rating plate.
In addition, a CSA design-certified and ASME-rated temperature and pressure (T & P) relief valve must be installed on every water storage tank in the hot water supply system; see Figures 11 and 13.
The T & P relief valve should have a temperature rating of 210°F (99°C), a pressure rating NOT exceeding the lowest rated working pressure of any system component, and a discharge capacity exceeding the total input of the water boilers supplying water to the storage tank. Locate the T & P relief valve (a) in the top of the tank, or (b) in the
INST ALLATION INSTRUCTIONS
REQUIRED ABILITY
INST ALLATION OR SER VICE OF THIS BOILER REQUIRES ABILITY EQUIV ALENT TO THA T OF A LICENSED TRADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR SUPPL Y , VENTING, GAS SUPPLY AND ELECTRICAL WORK ARE REQUIRED.
LOCA TION
When installing the boiler, consideration must be given to proper location. The location selected should be as close to the stack or chimney as practical with adequate air supply and as centralized with the piping system as possible. The location should also be such that the gas ignition system components are protected from water (dripping, spraying, etc.) during appliance operation and service (circulator replacement, control replacement, etc.)
• THE BOILER MUST NOT BE INST ALLED ON CARPETING.
• THE BOILER SHOULD NOT BE LOCATED IN AN AREA WHERE IT WILL BE SUBJECT TO FREEZING.
• THE BOILER SHOULD BE LOCATED NEAR A FLOOR DRAIN.
• THE BOILER SHOULD BE LOCATED IN AN AREA WHERE LEAKAGE FROM THE BOILER OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE ADJACENT AREA OR T O LOWER FLOORS OF THE STRUCTURE.
WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE DRAIN PAN SHOULD BE INST ALLED UNDER THE BOILER. Such pans should be fabricated with sides at least 2-1/2" (6.5 cm) deep, with length and width at least 2" (5.1 cm) greater than the dimensions of the boiler and must be piped to an adequate drain. The pan must not restrict combustion air flow.
WARNING
THERE IS A RISK IN USING FUEL BURNING APPLIANCES IN ROOMS OR AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED, OPERA TED OR REP AIRED. FLAMMABLE VAPORS ARE HEAVY AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY THE IGNITER OR MAIN BURNER FLAMES CAUSING FIRE OR EXPLOSION. SOME LOCAL CODES PERMIT OPERA TION OF GAS APPLIANCES IF INSTALLED 18 INCHES (46.0 CM) OR MORE ABOVE THE FLOOR. THIS MA Y REDUCE THE RISK IF LOCA TION IN SUCH AN AREA CANNOT BE AVOIDED.
FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST NEVER BE PLACED ON OR ADJACENT TO THE BOILER.
OPEN CONTAINERS OF FLAMMABLE MATERIAL SHOULD NOT BE STORED OR USED IN THE SAME ROOM WITH THE BOILER.
A hot water boiler installed above radiation level or as required by
7
the authority having jurisdiction, must be provided with a low water cutoff device either as a part of the boiler or at the time of boiler installation.
WARNING
UNDER NO CIRCUMST ANCES SHOULD THE EQUIPMENT ROOM WHERE THE BOILER IS INSTALLED EVER BE UNDER NEGA TIVE PRESSURE. PARTICULAR CARE MUST BE TAKEN WHEN EXHAUST FANS, COMPRESSORS, AIR HANDLING EQUIPMENT, ETC., MAY INTERFERE WITH THE COMBUSTION AND VENTILA TION AIR SUPPLIES OF THIS BOILER.
CHEMICAL V APOR CORROSION
Heat exchanger corrosion and component failure can be caused by the heating and breakdown of airborne chemical vapors. Spray can propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, and process chemicals are typical compounds which are corrosive. These materials are corrosive at very low concentration levels with little or no odor to reveal their presence.
Products of this sort should not be stored near the boiler. Also, air which is brought in contact with the boiler should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outside sources. Failure to observe this
requirement will void the warranty.
INST ALLATION CLEARANCES
Sufficient area should be provided at the front and sides of the unit for proper servicing. For ease of service, minimum clearances of 24" (61.0 cm) in the front and 18" (46.0 cm) on the sides are recommended. It is important that the minimum clearances be observed to allow service to the control box and other controls. Observing proper clearances will allow service to
be performed without movement or removal of the boiler from its installed location. Failure to observe minimum clearances may require removal of the boiler in order to service such items as the heat exchanger and burners. In a utility room installation, the door shall be wide enough to allow the boiler to enter or to permit the replacement of another appliance.
Two inch (5.1 cm) clearance is allowable from combustible construction to hot water pipes. Sufficient clearance should be provided at one end of the boiler to permit access to heat exchanger tubes for cleaning.
Access to control box items such as the Central Control Board, Flame Control Boards, Power Distribution Board and wiring harnesses is provided through a panel on the left side of the unit. A minimum service clearance of 18" (46.0 cm) is required.
MODEL COMBUSTIBLE BASE KIT NUMBER
G(B,W) - 1000 211093 G(B,W) - 1300 211093-1 G(B,W) - 1500 211093-2 G(B,W) - 1850 211093-3 G(B,W) - 2100 211093-4 G(B,W) - 2500 211093-5
Figure 3. Boiler on Combustible Floor Base and Kit Numbers.
LEVELLING
Each unit must be checked after installation to be ce rtain that it is level.
AIR REQUIREMENTS
WARNING
FOR SAFE OPERATION, AN AMPLE SUPPLY OF AIR MUST BE PROVIDED FOR PROPER COMBUSTION AND VENTILATION IN ACCORDANCE WITH THE NATIONAL FUEL GAS CODE, ANSI Z223.1 OR CAN/CSA-B149.1 CURRENT EDITION OR APPLICABLE PROVISIONS OF THE LOCAL BUILDING CODES. AN INSUFFICIENT SUPPLY OF AIR MAY RESULT IN A YELLOW, LUMINOUS BURNER FLAME, CARBONING OR SOOTING OF THE FINNED HEAT EXCHANGER, OR CREATE A RISK OF ASPHYXIATION. DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATION AIR.
UNCONFINED SP ACE
In buildings of conventional frame, brick or stone construction, unconfined spaces may provide adequate air for combustion.
If the unconfined space is within a building of tight construction (buildings using the following construction: weather stripping, heavy insulation, caulking, vapor barrier, etc.), air for combustion, ventilation, must be obtained from outdoors or spaces freely communicating with the outdoors. The installation instructions for confined spaces in tightly constructed buildings must be followed to ensure adequate air supply.
These boilers are approved for installation on noncombustible flooring in an alcove with minimum clearance to combustibles of: 3 inches (7.6 cm) Right Side, and Back; 6 inches (15.2 cm) Top; Front, Alcove; 12 inches (30.5 cm) Left Side; and 6 inches (15.2 cm) surrounding the Vent.
For installation on combustible flooring use the Combustible Floor Kit. The combustible floor kit base adds 4" (10.1 cm) to the overall height of the boiler. See Figure 3.
CONFINED SP ACE
(a) U. S. INST ALLATIONS
When drawing combustion and dilution air from inside a conventionally constructed building to a confined space, such a space shall be provided with two permanent openings, ONE WITHIN 12 INCHES OF THE ENCLOSURE TOP AND ONE WITHIN 12 INCHES OF THE ENCLOSURE BOTTOM. Each opening shall have a free area of at least one square inch per 1000 Btu/hr (22 cm2/k W) of the total input of all appliances in the enclosure.
8
If the confined space is within a building of tight construction, air for combustion, ventilation, and draft hood dilution must be obtained from outdoors. When directly communicating with the outdoors or communicating with the outdoors through vertical ducts, two permanent openings, located in the above manner, shall be provided. Each opening shall have a free area of not less than one square inch per 4000 Btuh (5.5 cm
2
/kW) of the total input of all appliances in the enclosure. If horizontal ducts are used, each opening shall have a free area of not less than one square inch per 2000 Btuh (11 cm
2
/kW) of the total input of all appliances in the
enclosure.
(b) CANADIAN INSTALLA TIONS
Ventilation of the space occupied by the boiler(s) shall be provided by an opening for ventilation air at the highest practical point communicating with outdoors. The total cross-sectional area shall be at least 10% of the area of the combustion air opening but in no case shall the cross-sectional area be less than 10 square inches (64.5 cm
2
).
In addition to the above, there shall be permanent air supply opening(s) having a cross-sectional area of not less than 1 square inch per 7,000 BTUH (3.2 cm
2
/kW) up to and including 1,000,000 BTUH plus 1 square inch per 14,000 BTU (1.6 cm2/kW) in excess of 1,000,000 BTUH. This opening(s) shall be located at, or ducted to, a point neither more than 18" (46.0 cm) nor less than 6 inches (15.2 cm) above the floor level.
Where power vented equipment is used in the same room as the boiler, sufficient air openings must be supplied. UNDERSIZED OPENINGS MAY RESULT IN INSUFFICIENT AIR FOR COMBUSTION.
Where an exhaust fan is installed in the same room with a boiler, sufficient openings for air must be provided in the walls. UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRA WN INTO THE ROOM THROUGH THE CHIMNEY, CAUSING POOR COMBUSTION. SOOTING MAY RESULT WITH AN INCREASED RISK OF ASPHYXIA TION.
SEE FIGURE 6). AT LEAST TYPE B VENTING MUST BE USED WITH THE STANDARD VENTING OPTION (thru-the-roof) USING THE NA TIONAL FUEL GAS CODE VENT TABLES. TYPE B VENT
CANNOT BE USED IF THE BOILER IS VENTED
PIPE HORIZONTALLY OR AS A DIRECT VENT (SEE PAGES 12 THROUGH 15). ALL LOCAL UTILITY, STATE/ PROVINCIAL, REGULATIONS ON VENTING MUST BE FOLLOWED.
VENT SIZING, VENT CONNECTORS, INSTALLATION AND TERMINATION SHALL BE IN ACCORDANCE WITH THE CURRENT EDITION OF
NATIONAL FUEL GAS CODE, ANSI Z223.1 OR CAN/ CSA-B149.1 or applicable provisions of the local building codes. Size and install proper size vent pipe; refer to Table 6.
Horizontal runs of vent pipe shall be securely supported by adequately placed (approximately every 4 feet [1.2 m]), noncombustible hangers suitable for the weight and design of the materials employed to prevent sagging and to maintain a minimum upward slope of 1/4" per foot (2 cm/m) from the boiler to the vent terminals. Dampers or other obstructions must not be installed in the vent. Be sure that the vent connector does not extend beyond the inside wall of the chimney.
TABLE 6: VENT CONNECTION
MODEL NUMBER VENT CONNECTOR
G(B,W) 1000 10" (25.4 cm) G(B,W) 1300 12" (30.5 cm) G(B,W) 1500 12" (30.5 cm) G(B,W) 1850 14" (35.6 cm) G(B,W) 2100 14" (35.6 cm) G(B,W) 2500 16" (40.6 cm)
For vent arrangements other than Table 10 and for proper boiler operation, a barometric damper is required to maintain draft between -0.02" W.C.. and -0.04" W.C. at 2 feet (0.6 m) above the boiler vent collar.
VENTING
CAUTION
WHEN VENTING THE GENESIS BOILER THROUGH AN OVERSIZED CHIMNEY (INCLUDING MASONRY CHIMNEYS), ADDITIONAL CARE MUST BE EXERCISED T O ASSURE PROPER DRAFT . FOR PROPER OPERA TION, A MINIMUM DRAFT OF -0.02"
W.C. AND A MAXIMUM DRAFT OF -0.04" W .C. MUST BE MAINTAINED. IN INSTANCES OF EXCESSIVE DRAFT, A BAROMETRIC DAMPER MA Y BE REQUIRED T O ASSIST IN MAINTAINING THE PROPER DRAFT. DRAFT SHOULD BE MEASURED 2 FEET (0.6 M) ABOVE
THE BOILER VENT COLLAR.
WARNING
THE INSTRUCTIONS IN THIS SECTION ON VENTING THE BOILER MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIA TION.
This boiler is approved to be vented as a Category I, Category III (horizontal venting), or a Direct V ent appliance. The Horizont al and Direct Venting options require a special vent kit.
STANDARD (VERTICAL) VENTING , CA TEGOR Y I
THIS BOILER MAY BE VENTED ACCORDING TO T ABLE 10 (ALSO
STANDARD (HORIZONT AL) VENTING , CA TEGORY III
Vent sizing, installation and termination shall be in accordance with the
NATIONAL FUEL GAS CODE, ANSI Z223.1 OR CAN/CSA-B149.1 (Current Editions). If applicable, all local, utility, state/provincial regulations on venting must be followed. See Table 1 1, Figure 7 for venting specifications. The exhaust vent pipe must be of a type listed for use with Category III gas burning heaters such as "Saf-T-Vent" manufactured by Heat-Fab Inc.
For Category III installations, it is important that the Installed vent be airtight. Please insure that all joints are sealed properly during installation. For Horizontal Vent Kit part numbers, see Table 7.
T ABLE 7: HORIZONTAL VENT KITS.
HORIZONT AL VENT KIT MODEL
211426 G(B,W) 1000 211426-1 G(B,W) 1300 211426-1 G(B,W) 1500 211426-2 G(B,W) 1850 211426-2 G(B,W) 2100 211426-3 G(B,W) 2500
DIRECT VENT VERTICAL AND HORIZONT AL VENTING
For direct vent applications, this boiler may be vented according to T ables 12 and 13; see Figures 8 and 9. For category III applications,
9
the exhaust vent pipe must be listed for use with category III gas burning heaters such as "Saf-T-Vent" manufactured by Heat-Fab Inc. This vent system must be 100% sealed with a condensate trap located as close to the boiler as possible. When sizing exhaust piping and intake air piping, 90-degree elbows are equivalent to 10 feet (3.1 m) of straight pipe and 45-degree elbows are equal to 5 feet (1.5 m) of straight pipe.
The intake air piping can be PVC, CPVC, ABS, Galvanized steel or any suit able intake air piping that can be sealed. See Table 8 for Direct Vent Kit number s.
T ABLE 8: DIRECT VENT KITS.
HORIZONT AL DIRECT VENT KIT NO. MODEL
211090 G(B,W) 1000 211090-1 G(B,W) 1300 211090-1 G(B,W) 1500 211090-4 G(B,W) 1850 211090-2 G(B,W) 2100 211090-3 G(B,W) 2500
VERTICAL DIRECT VENT KIT NO. MODEL
211089 G(B,W) 1000 211089-1 G(B,W) 1300 211089-1 G(B,W) 1500 211089-4 G(B,W) 1850 211089-2 G(B,W) 2100 211089-3 G(B,W) 2500
AIR INTAKE TERMINAL MODEL
191965-2 G(B/W) 1000
211336 G(B/W) 1300,1 500,1850 211336-1 G(B/W) 2100, 2500
HORIZONTAL VENT INST ALLATION
This boiler can be vented through the rear of the cabinet with the use of the fluebox and vent adaptor. Any of the previous venting configurations can be installed with rear connections.
To change the unit to rear exhaust:
1. The vent collar and cover plates must be removed from the top and rear of the unit.
POWER VENT (OPTIONAL)
The length of vent used in horizontally vented installations can be extended beyond the lengths shown in Tables 11 and 13 by implementing the kits listed below:
TABLE 9: POWER VENT KITS.
POWER VENT KIT NO. MODEL MAX. LENGTH
211499 G(B,W) 1000 110' (33.5 m) 211499-1 G(B,W) 1300 100' (30.5 m) 211499-1 G(B,W) 1500 100' (30.5 m) 211499-2 G(B,W) 1850 100' (30.5 m) 211499-3 G(B,W) 2100 100' (30.5 m) 211499-4 G(B,W) 2500 100' (30.5 m)
CONNECTING BOILER TO A COMMON VENT
Do not connect the boiler to a common vent or chimney with solid fuel burning equipment. This practice is prohibited by most local building codes as is the practice of venting gas fired equipment to the duct work of ventilation systems.
Where a separate vent connection is not available and the vent pipe from the boiler must be connected to a common vent with an oil burning furnace, the vent pipe should enter the common vent or chimney at a point ABOVE the flue pipe from the oil furnace.
UL/ULC listed double wall type B-1 gas vents, through 16" diameter, can be installed in heated and unheated areas and can pass through floors, ceilings, partitions, walls and roofs, provided the required clearance is observed.
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system. Perform these steps while the other appliances remaining connected to the common venting system are not in operation.
1. Seal any unused opening in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other unsafe condition.
2. Trim the insulation from around the rear flue hole in the jacket and the fluebox. Support insulation from inside the fluebox to facilitate cutting. Use safety precautions such as gloves. Place the gasket and vent adaptor in the horizontal position. Place the gasket and flue plate in the vertical position as shown in Figure 4.
Figure 4. Switching from Vertical to Horizontal Venting.
3. Insofar as is practical, close all building doors, windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Test fire the appliance(s) being inspected, making sure to follow the manufacturers lighting and operating instructions. Appliance(s) operating controls should be adjusted to provide continuous service.
5. Check vent pressure of the appliance 24 inches (61.0 cm) above boiler vent collar. Vent pressure should be maintained between
-0.02" W. C. and -0.04" W.C. to assure proper operation. For appliances with a draft hood, check for spillage with mirror, smoke or other device five minutes after placing appliance in operation.
6. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans,
10
fireplace dampers and other gas burning appliances to their previous conditions of use.
All boiler venting systems shall be installed in accordance with the National Fuel Gas Code, ANSI Z223.1 or CAN/CSA-B149.1 (current edition), or applicable provisions of the local building codes.
7. Avoid areas where condensate drainage may cause problems such as above planters, patios, or adjacent to windows where the steam from the flue gases may cause fogging.
8. Select the point of wall penetration where the minimum 1/4" per foot (2 cm/m) of slope up can be maintained.
INT AKE/EXHAUST INST ALLA TION REQUIREMENTS
1. The termination must be 12 inches (30.5 cm) above snow or grade level whichever is higher.
2. Due to normal formation of water vapor in the combustion process, horizontal terminations must not be located over areas of pedestrian or vehicular traffic, i.e. public walkways or over areas where condensate could create a nuisance or hazard. This is especially true in colder climates where ice buildup is likely to occur. A.O. Smith Corporation will not be held liable for any personal injury or property damage due to any dislodging of ice.
3. The exhaust terminal of the venting system must maintain a minimum clearance of 4 feet (1.22 m) horizontally from, and in no case above or below, unless a 4-foot horizontal distance is maintained, from electric meters, gas meters, regulators and relief equipment.
4. The minimum distance from inside corner formed by two exterior walls is 6 feet (1.8 m) but 10 feet (3.1 m) is recommended where possible.
5. Maintain a minimum distance of 4 feet (1.2 m) from any soffit or eve vent to the exhaust terminal.
6. Maintain a minimum distance of 10 feet (3.1 m) from any forced air inlet. Fresh air or make up air inlet such as a dryer or furnace area is considered to be a forced air inlet.
9. The through the wall termination kit is suitable for zero clearance to combustible materials.
10. The mid point of the termination elbow must be a minimum of 12 inches (30.5 cm) from the exterior wall.
SYSTEM INST ALLA TION
GENERAL
If the system is to be filled with water for testing or other purposes during cold weather and before actual operation, care must be taken to prevent a down draft entering the boiler or freezing air from contacting the system. Failure to do so may cause the water in the system to freeze with resulting damage to the system. Damage due to freezing is not covered by the warranty .
Good practice requires that all piping, etc., be properly supported. The boilers described in this manual may be used for space (hydronic)
heating or for the heating of potable water . If the heater is to be used for hydronic space heating, follow the instructions on pages 16-17 given for equipment required for installation as in Figure 10. However, if units are to be used for heating potable water, the information describing specific systems is found on pages 18-20; see Figures 11 and 13. Installations must comply with all local codes.
INST ALLA TION AS BOILER REPLACEMENT
Installation as boiler replacement on an old system with large water
DIRECT VENTING INTO DEAD AIR SPACES SUCH AS ALLEYS, ATRIUMS AND INSIDE CORNERS CAN CAUSE RECIRCULATION OF FLUE GASES. RECIRCULATION OF FLUE GASES WILL CAUSE SOOTING , PREMA TURE FAILURE OF THE HEAT EXCHANGER AND ICING OF THE COMBUSTION AIR INTAKE DURING SEVERE COLD WEATHER. TO PREVENT THE RECIRCULATION OF FLUE GASES, MAINTAIN AS MUCH DISTANCE AS POSSIBLE BETWEEN THE COMBUSTION AIR INTAKE AND THE EXHAUST VENT TERMINAL.
Note: Venting system of other than direct-vent appliance shall terminate at least 4 ft. (1.2 m) below, 4 ft. (1.2 m) horizontally from, or 1 ft. (30.0 cm) above any door window or gravity air inlet.
CAUTION
Figure 5. Vent Termination Installation Clearances
STANDARD VENTING DIRECT VENT APPLICA TIONS
11
STANDARD VENT - VERTICAL (CATEGORY I)
IMPORT ANT!
VENT PRESSURE MUST BE MAINT AINED
BETWEEN -0.02" W.C. AND -0.04" W.C. AT 24"
(61.0 cm) ABOVE BOILER COLLAR.
Figure 6.
T ABLE 10. STANDARD VERTICAL VENTING (CA TEGOR Y I)
APPLIANCE CERTIFIED EXHAUST MAXIMUM LENGTH
MODEL CA TEGOR Y VENTING VENT SIZE WITHOUT BAROMETRIC DAMPER
MATERIAL INCHES (cm) FEET (m)
I000 1300 TYPE B OR 35 Feet (10.7 m) without damper
1500 EQUIVALENT 12" (30.5 cm) *70 Feet (21.3 m) max. with damper 1850 TYPE B OR 14"(35.6 cm) 35 Feet (10.7 m) without damper
2100 EQUIVALENT *70 Feet (21.3 m) max. with damper
2500
* Extending venting over 70 feet (21.3 m) may require special considerations.
• Connection for the appliance exhaust vent to the stack must be as direct as possible. Maximum and minimum venting length for Category I appliances shall be determined per the latest edition of the National Fuel Code (U.S.) and CAN/CSA-B149.1 Installation Code (Canada).
• The horizontal breaching of a vent must have an upward slope of not less than 1/4 inch per linear foot (2 cm/m) from the boiler to the vent terminal. The horizontal portion of the vent shall be supported to maintain clearances and to prevent physical damage or separation of joints.
I
I
I
I
TYPE B OR 10”(25.4 cm) 35 Feet (10.7 m) without damper
EQUIV ALENT *70 Feet (21.3 m) max. with damper
TYPE B OR 16" (40.6 cm) 35 Feet (10.7 m) without damper
EQUIV ALENT *70 Feet (21.3 m) max. with damper
12
ST ANDARD VENT - HORIZONTAL (CA TEGOR Y III)
Figure 7.
T ABLE 11. ST ANDARD HORIZONT AL VENTING (CA TEGOR Y III)
APPLIANCE CERTIFIED EXHAUST MAXIMUM
MODEL CATEGORY VENTING VENT SIZE VENT LENGTH
MA TERIAL INCHES (cm) FEET (m)
I000
1300 STAINLESS 1500 STEEL
1850 STAINLESS 2100 STEEL
2500
WARNING: No substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the safety and health of inhabitants.
• A maximum of two elbows can be used on inlet and outlet vent piping respectively. Each elbow is equal to 10 feet (3 m) of straight pipe.
III
III
III
III
STAINLESS
STEEL
STAINLESS
STEEL
10”(25.4 cm)
12" (30.5 cm)
14"(35.6 cm)
16" (40.6 cm)
70' (21.3 m)
70' (21.3 m)
35' (10.7 m)
35' (10.7 m)
• Use only special gas vent pipes listed for use with Category III gas burning heaters, such as stainless steel Saf-T-Vent by Heat Fab, Inc., available from A.O. Smith, 500 T ennessee W altz Parkway , Ashland City , TN 37015 Phone: 1-800-433-2545 or Fax: 1-800-433-2515. Pipe joints must be positively sealed.
13
DIRECT VENT - VERTICAL (CATEGORY I)
Figure 8.
T ABLE 12. DIRECT VENT (VERTICAL EXHAUST CONFIGURA TIONS)
APPLIANCE CERTIFIED EXHAUST VENT MAXIMUM AIR INTAKE AIR INT AKE MAXIMUM
MODEL CATEGORY EXHAUST VENT SIZE EXHAUST VENT MATERIAL SIZE AIR INTAKE
MATERIAL INCHES (cm) LENGTH FT (m) INCHES (cm) LENGTH FT (m)
GAL. STEEL
CPVC
GAL.STEEL
CPVC
GAL. STEEL
CPVC
GAL. STEEL
CPVC
GAL. STEEL
CPVC
8"
(20.3 cm)
10"
(25.4 cm)
10"
(25.4 cm)
12"
(30.5 cm)
12"
(30.5 cm)
(10.7 m)
(10.7 m)
I000
1300 1500
1850
2100
2500
I PVC, ABS OR
I PVC, ABS CR
I PVC, ABS OR
I PVC, ABS OR
I PVC, ABS OR
TYPE B OR
EQUIVALENT
TYPE B OR
EQUIV ALENT
TYPE B OR
EQUIV ALENT
TYPE B OR
EQUIVALENT
TYPE B OR
EQUIV ALENT
10"
(25.4 cm)
12"
(30.5 cm)
14"
(35.6 cm)
14"
(35.6 cm)
16"
(40.6 cm)
35'
(10.7 m)
35'
(10.7 m)
20'
(6.1 m)
20'
(6.1 m)
20'
(6.1 m)
35'
35'
20'
(6.1 m)
20'
(6.1 m)
20'
(6.1 m)
• Connection for the appliance exhaust vent to the stack must be as direct as possible. Maximum and minimum venting length for Category I appliances shall be determined per the latest edition of the National Fuel Code (U.S.) and CAN/CSA-B149.1 Installation Code (Canada).
• The vent should be installed so as to prevent the accumulation of condensate and, where necessary , have means provided for drainage of condensate. The horizontal breaching of a vent must have an upward slope of not less than 1/4 inch per linear foot (2 cm/m) from the boiler to the vent terminal. The horizontal portion of the vent shall be supported to maintain clearances and to prevent physical damage or separation of joints.
14
DIRECT VENT - HORIZONT AL (CATEGORY III)
Figure 9.
T ABLE 13. DIRECT VENT (HORIZONT AL EXHAUST CONFIGURA TIONS)
APPLIANCE CERTIFIED EXHAUST MAXIMUM AIR INTAKE AIR INT AKE MAXIMUM
MODEL CATEGOR Y EXHAUST VENT VENT SIZE EXHAUST VENT MA TERIAL SIZE AIR INTAKE
MATERIAL INCHES (cm) LENGTH FT (m) INCHES (m) LENGTH FT (m)
GAL. STEEL
CPVC
GAL.STEEL
CPVC
GAL. STEEL
CPVC
GAL. STEEL
CPVC
GAL. STEEL
CPVC
8"
(20.3 cm)
10"
(25.4 cm)
10"
(25.4 cm)
12"
(30.5 cm)
12"
(30.5 cm)
I000
1300 1500
1850
2100
2500
III PVC, ABS OR
III PVC, ABS CR
III PVC, ABS OR
III PVC, ABS OR
III PVC, ABS OR
STAINLESS
(SEALED)
STAINLESS
(SEALED)
STAINLESS
(SEALED)
STAINLESS
(SEALED)
STAINLESS
(SEALED)
10"
(25.4 cm)
12"
(30.5 cm)
14"
(35.6 cm)
14"
(35.6 cm)
16"
(40.6 cm)
35'
(10.7 m)
35'
(10.7 m)
20'
(6.1 m)
20'
(6.1 m)
20'
(6.1 m)
35'
(10.7 m)
35'
(10.7 m)
20'
(6.1 m)
20'
(6.1 m)
20'
(6.1 m)
WARNING: No substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the safety and health of inhabitants.
• A maximum of two elbows can be used on inlet and outlet vent piping respectively. Each elbow is equal to 10 feet (3 m) of straight pipe.
• Use only special gas vent pipes listed for use with Category III gas burning heaters, such as stainless steel Saf-T -Vent by Heat Fab, Inc. Inc., available from A.O. Smith, 500 Tennessee Waltz Parkway, Ashland City, TN 37015 Phone: 1-800-433-2545 or Fax: 1-800-433-2515. Pipe joints must be positively sealed.
15
Loading...
+ 33 hidden pages