A.O. Smith 3400 User Manual

Page 1
Instruction Manual
XP BOILER
MODELS: XB/XW
1000, 1300, 1700 2000, 2600, 3400
25589 Highway 1
McBee, SC 29101
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
MAINTENANCE - LIMITED WARRANTY
INSTALLATION - OPERATION -
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do
not use any phone in your building.
Immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier,
call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Thank you for buying this energy efcient boiler. We appreciate your condence in our products.
PRINTED IN THE U.S.A. 0711 320741-002
Page 2

TABLE OF CONTENTS

TABLE OF CONTENTS ..........................................................................2
SAFE INSTALLATION, USE AND SERVICE.......................................... 3
GENERAL SAFETY................................................................................ 4
INTRODUCTION .................................................................................... 5
Model Identication ............................................................................ 5
Abbreviations Used ........................................................................... 5
Qualications ..................................................................................... 5
DIMENSIONS AND CAPACITY DATA .................................................... 6
FEATURES AND COMPONENTS ....................................................... 10
Component Description ................................................................... 12
CONTROL COMPONENTS ................................................................. 13
BOILER INSTALLATION CONSIDERATIONS ..................................... 15
Hydronic System ............................................................................. 15
Hot water boiler system - general water line connections ............... 16
GENERAL REQUIREMENTS .............................................................. 21
Location ........................................................................................... 21
Fresh air openings for conned spaces ........................................... 23
VENTING .............................................................................................. 25
Vent Installation Considerations ...................................................... 25
Venting Supports ............................................................................. 27
CONDENSATE DISPOSAL .................................................................. 37
GAS SUPPLY CONNECTIONS ........................................................... 38
BOILER START UP AND OPERATIONS ............................................. 40
LIGHTING AND OPERATING INSTRUCTIONS .................................. 42
CONTROL SYSTEM ............................................................................ 45
Burner Control System .................................................................... 45
Burner control operation .................................................................. 46
General operational sequence ........................................................ 47
Local operator interface: display system ......................................... 49
Installation instructions (S7999B OI Display) .................................. 50
Starting up the S7999B OI Display .................................................. 51
Page Navigation .............................................................................. 51
TROUBLESHOOTING ......................................................................... 61
MAINTENANCE PROCEDURES ......................................................... 76
Maintenance schedules ................................................................... 76
General maintenance ...................................................................... 76
Burner maintenance ........................................................................ 77
Venting maintenance ....................................................................... 78
Heat exchanger maintenance .......................................................... 78
Handling ceramic ber materials ..................................................... 79
Replacement parts .......................................................................... 79
PIPING DIAGRAMS ............................................................................. 80
LIMITED WARRANTY .......................................................................... 82
2
Page 3

SAFE INSTALLATION, USE AND SERVICE

The proper installation, use and servicing of this boiler is extremely important to your safety and the safety of others.
Many safety-related messages and instructions have been provided in this manual and on your boiler to warn you and others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important that the meaning of each safety message is understood by you and others who install, use, or service this boiler.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates an imminently
DANGER
WARNING
CAUTION
hazardous situation which, if not avoided, will result in injury or death.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in injury or death.
CAUTION indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury.
CAUTION used without the safety alert
CAUTION
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message, and how to avoid the risk of injury.
The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of substances known to the State of California to cause cancer, birth defects, or other reproductive harm, and requires businesses to warn of potential exposure to such substances.
This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm. This boiler can cause low level exposure to some of the substances listed in the Act.
symbol indicates a potentially hazardous situation which, if not avoided, could result in property damage.
IMPORTANT DEFINITIONS
Gas Supplier: The Natural Gas or Propane Utility or service who supplies gas for utilization by the gas burning
appliances within this application. The gas supplier typically has responsibility for the inspection and code approval of gas piping up to and including the Natural Gas meter or Propane storage tank of a building. Many gas suppliers also offer service and inspection of appliances within the building.
APPROVALS
3
Page 4

GENERAL SAFETY

GROUNDING INSTRUCTIONS
This boiler must be grounded in accordance with the National Electrical Code, Canadian Electrical Code and/or local codes. Boiler is polarity sensitive; correct wiring is imperative for proper
operation.
This boiler must be connected to a grounded metal, permanent wiring system, or an equipment grounding conductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the boiler.
INLET WATER CONSIDERATIONS
Circulating water through the boiler and to the remote storage tank (if applica ble) is accomplished by a pump on XW models only. For hot water heating systems using the XB model, the circulating pump is NOT provided on standard models (optional) and must be eld installed.
CORRECT GAS
Make sure the gas on which the boiler will operate is the same as that speci ed on the boiler rating plate. Do not install the boiler if equipped for a different type of gas; con sult your supplier.
PRECAUTIONS
If the unit is exposed to the following, do not operate until all corrective steps have been made by a qualied service agent:
1. Exposure to re.
2. If damaged.
3. Firing without water.
4. Sooting.
If the boiler has been exposed to ooding, it must be replaced.
LIQUEFIED PETROLEUM GAS MODELS
HIGH ALTITUDE INSTALLATIONS
Rated inputs are suitable up to 2000 feet (610 m) elevation. Consult the factory for installation at altitudes over 2000 feet (610 m).
FIELD INSTALLED COMPONENTS
When installing the boiler, the follow ing compo nents must be installed:
Circulating Pump (Hyd ronic)
• Remote Temperature Sensor/Header Sensor
• Storage Tank (Temperature & Pressure Relief Valve)
Boilers for propane or liqueed petroleum gas (LPG) are different from natural gas models. A natural gas boiler will not function safely on LP gas and no attempt should be made to convert a boiler from natural gas to LP gas.
LP gas must be used with great caution. It is highly explosive and heavier than air. It collects rst in the low areas making its odor difcult to detect at nose level. If LP gas is present or even suspected, do not attempt to nd the cause yourself. Leave the building, leaving doors open to ventilate, then call your gas supplier or service agent. Keep area clear until a service call has been made.
At times you may not be able to smell an LP gas leak. One cause is odor fade, which is a loss of the chemical odorant that gives LP gas its distinctive smell. Another cause can be your physical condition, such as having a cold or diminishing sense of smell with age. For these reasons, the use of a propane gas detector is recommended.
If you experience an out of gas situation, do not try to relight appliances yourself. Call your local service agent. Only trained LP professionals should conduct the required safety checks in accordance with industry standards.
4
Page 5

INTRODUCTION

This Instruction Manual covers XP Boiler models XB/XW 1000, 1300, 1700, 2000, 2600, 3400 - Series 100/101. The instructions and illustrations contained in this Instruction manual will provide you with troubleshooting procedures to diagnose and repair common problems and verify proper operation.

MODEL IDENTIFICATION

Check the rating plate afxed to the Boiler. The following information describes the model number structure:
SERIES-100/101 DESIGNATION:
• XP = Extreme Performance
MODEL (APPLICATION):
• XB = Hydronic Heating Boiler
• XW = Domestic Hot Water Supply Boiler
SIZE:
• 1000 = 920,000 Btu/hr input
• 1300 = 1,300,000 Btu/hr input
• 1700 = 1,700,000 Btu/hr input
• 2000 = 2,000,000 Btu/hr input
• 2600 = 2,600,000 Btu/hr input
• 3400 = 3,400,000 Btu/hr input
FUEL:
N = Natural gas P = Propane
NOTE:
XB models are equipped with 50 psi pressure relief valve. (pump is optionally installed) XW models are factory installed circulating pump (standard), with 125 psi pressure relief valve.
XB models can be special ordered with a factory installed pump and XW models can be special ordered without the factory installed pump. These factory congurations can also be changed in the eld by installing circulation pumps and changing pressure relief valves to accommodate domestic and hydronic hot water system requirements.
Properly installed and maintained, it should give you years of trouble free service.

ABBREVIATIONS USED

QUALIFICATIONS

QUALIFIED INSTALLER OR SERVICE AGENCY
Installation and service of this boiler requires ability equivalent to that of a Qualied Agency, as dened by ANSI below. In the eld involved. Installation skills such as plumbing, air supply, venting, gas supply and electrical supply are required in addition to electrical testing skills when performing service.
ANSI Z21.13 - CSA 4.9: “Qualied Agency” - “Any individual, rm, corporation or company that either in person or through a representative is engaged in and is responsible for (a) the installation, testing or replacement of gas piping or (b) the connection, installation, testing, repair or servicing of appliances and equipment; that is experienced in such work; that is familiar with all precautions required; and that has complied with all the requirements of the authority having jurisdiction.”
If you are not qualied (as dened by ANSI above) and licensed or certied as required by the authority having jurisdiction to perform a given task do not attempt to perform any of the procedures described in this manual. If you do not understand the instructions given in this manual do not attempt to perform any procedures outlined in this manual.
This product requires a formal Start-Up by an authorized service/ start-up provider that has been approved by the manufacturer for this specic product. Call 1-800-527-1953 to locate the nearest authorized start-up provider and arrange a factory start-up. Please provide as much notice as possible, preferably 2 weeks. Please have the model and serial number ready when you call. This start-up is required to activate the warranty and ensure safe, efcient operation.
Warranty on this product is limited and could be void in the event the unit is not installed per the instructions in this manual and/or not started up by an authorized factory trained service/start-up provider.
Abbreviations found in this Instruction Manual include :
• ANSI - American National Standards Institute
• ASME - American Society of Mechanical Engineers
• NEC - National Electrical Code
• NFPA - National Fire Protection Association
• UL - Underwriters Laboratory
• CSA - Canadian Standards Association
• AHRI - Air-Conditioning, Heating and Refrigeration Institute
5
Page 6

DIMENSIONS AND CAPACITY DATA

FIGURE 1. SINGLE HEAT EXCHANGER BOILER
TABLE 1. ROUGH IN DIMENSIONS (SINGLE)
Models XB/XW-1000 XB/XW-1300 XB/XW-1700
Dimensions inches mm inches mm inches mm
Flue Outlet Diameter 6 152 8 152 8 203
Air Intake Diameter 6 152 6 152 8 203
Water Inlet 2 inch NPT 2 1/2 inch NPT
Water Outlet 2 inch NPT 2 1/2 inch NPT
Gas Inlet 2 inch NPT 2 inch NPT
A 47 1199 49 1245 57 1448
B 67 1702 68 1727 76 1930
C 29 737 29 737 29 737
D 37 940 38 965 37 940
E 23 584 23 584 24 610
F 9 229 9 229 9 229
G 34 864 34 864 34 864
H 44 111 8 45 1143 45 1143 J 6 152 6 152 6 152
K 11 279 11 279 11 279
L 12 305 11 279 12 305
TABLE 2. OPERATING CHARACTERISTICS
Models
(XB/XW)
1000, 1300, 1700 2000, 2600, 3400
Type of Gas Inches W.C. kPa Inches W.C. kPa Inches W.C. kPa
Natural
Propane
Manifold Pressure Maximum Supply Pressure Minimum Supply Pressure
Min Fire -0.2 to - 0.3 -0.05 to - 0.07
14.0 3.49 4.0 1.0
Max Fire -3.0 to -3.9 -0.75 to -0.97
Min Fire -0.1 to - 0.3 -0.025 to -0.07
14.0 3.49 4.0 2.0
Max Fire -3.6 to -4.9 -0.90 to -1.22
6
Page 7
FIGURE 2. DOUBLE HEAT EXCHANGER BOILER
TABLE 3. ROUGH IN DIMENSIONS (DOUBLE)
Models XB/XW-2000 XB/XW-2600 XB/XW-3400
Dimensions inches mm inches mm inches mm
Flue Outlet Diameter 8 203 8 203 10 254
Air Intake Diameter 8 203 8 203 10 254
Water Inlet 3 inch NPT 4 inch NPT
Water Outlet 3 inch NPT 4 inch NPT
Gas Inlet 2 inch NPT 3 inch NPT
A 47 1194 49 1245 57 1448
B 78 1981 80 2032 91 2311
C 36 914 37 940 37 940
D 22 559 22 559 22 559
E 40 1016 41 1041 41 1041
F 7 178 6 152 6 152
G 10 254 10 254 10 254
H 4 102 4 102 4 102
J 20 508 19 483 19 483
K 12 305 12 305 13 330
TABLE 4. RECOVERY CAPACITIES
Models
XW-1000 920,000 854,680
XW-1300 1,300,000 1,207,700
XW-1700 1,700,000 1,579,300
XW-2000 2,000,000 1,858,000
XW-2600 2,600,000 2,415,400
XW-3400 3,400,000 3,158,600
Input Rating
(Btu/hr)
Output Rating
(Btu/hr)
Temperature Rise - ΔT °F (°C)
Water
Flow
GPH 2,593 1,728 1,482 1,296 1,152 1,037 864 741
LPH 9,815 6,543 5,608 4,907 4,362 3,926 3,272 2,804
GPH 3,664 2,442 2,094 1,832 1,628 1,465 1,221 1,047
LPH 13,868 9,246 7,925 6,934 6,164 5,547 4,623 3,962
GPH 4,791 3,194 2,738 2,395 2,129 1,916 1,597 1,369
LPH 18,136 12,090 10,363 9,068 8,060 7,254 6,045 5,182
GPH 5,636 3,758 3,221 2,818 2,505 2,255 1,879 1,610
LPH 21,336 14,224 12,192 10,668 9,483 8,534 7,112 6,096
GPH 7,327 4,885 4,187 3,664 3,257 2,931 2,442 2,094
LPH 27,737 18,491 15,850 13,868 12,327 11,095 9,246 7,925
GPH 9,582 6,388 5,475 4,791 4,259 3,833 3,194 2,738
LPH 36,271 24,181 20,726 18,136 16,121 14,508 12,090 10,363
40
(22)
60
(33)
7
70
(39)
80
(44)
90
(50)
100
(56)
120
(67)
140
(78)
Page 8
RATINGS
TABLE 5. IBR RATINGS
MODELS
(XB/XW)
1000 920 100 856 744
1300 1300 130 1209 1051
1700 1700 170 1581 1375
2000 2000 100 1860 1617
2600 2600 130 2418 2103
3400 3400 212 3162 2750
Notes:
1. The ratings are based on standard test procedures prescribed by the United States Department of Energy.
2. Net I=B=R ratings are based on net installed radiation of sufcient quantity for the requirements of the building and nothing need
be added for normal piping and pickup. Ratings are based on a piping and pickup allowance of 1.15.
3. Ratings have been conrmed by the Hydronics Institute, Section of AHRI.
INPUT
MBH
MAX MIN
GROSS
OUTPUT MBH
(NOTE 1)
NET I=B=R RATINGS WATER MBH
(NOTE 2)
ELECTRICAL REQUIREMENTS
TABLE 6. ELECTRICAL REQUIREMENTS
MODELS
(XB/XW)
1000 120 60 30 A dedicated, single phase, 30/60 amp circuit breaker
1300 120 60 30
1700 120 60 30
2000 120 60 60 A dedicated, single phase, 60/60 amp circuit breaker
2600 120 60 60
3400 120 60 60
SUPPLY VOLTAGE
(VOLTS)
FREQUENCY
(HZ)
CURRENT
(AMPS)
ELECTRICAL NOTES
with a grounded neutral should be provided to supply power to the boiler.
with a grounded neutral should be provided to supply power to the boiler.
8
Page 9
FLOW, HEAD AND TEMPERATURE RISE
TABLE 7. XB MODELS - FLOW, HEAD AND TEMPERATURE RISE
Models
XB-1000 920,000 855,600
XB-1300 1,300,000 1,209,000
XB-1700 1,700,000 1,581,000
XB-2000 2,000,000 1,860,000
XB-2600 2,600,000 2,418,000
XB-3400 3,400,000 3,162,000
Input
(Btu/hr)
Output
(Btu/hr)
Temperature Rise - ΔT °F Flow Rate
Water
Flow
GPM 86 56 43 86 43
LPM 325 211 162 325 162
ΔP FT 26 12 7 26 7
ΔP M 7.9 3.7 2.1 7.9 2.1
GPM 120 80 60 120 60
LPM 453 302 226 453 226
ΔP FT 32.5 15 8 32.5 8
ΔP M 9.9 4.6 2.4 9.9 2.4
GPM 156 104 78 156 78
LPM 592 395 296 592 296
ΔP FT 35 14 8 35 8
ΔP M 10.7 4.3 2.4 10.7 2.4
GPM 184 123 92 184 92
LPM 696 464 348 696 348
ΔP FT 26 12 7 26 7
ΔP M 7.9 3.7 2.1 7.9 2.1
GPM 239 159 120 239 120
LPM 905 604 453 905 453
ΔP FT 32.5 15 8 32.5 8
ΔP M 9.9 4.6 2.4 9.9 2.4
GPM 313 209 156 313 156
LPM 1184 789 592 1184 592
ΔP FT 35 14 8 35 8
ΔP M 10.7 4.3 2.4 10.7 2.4
20 30 40 Maximum Minimum
Note: Head Loss shown is through the boiler only and allows for no additional piping.
9
Page 10

FEATURES AND COMPONENTS

FIGURE 3. SINGLE HEAT EXCHANGER BOILER COMPONENTS
10
Page 11
FIGURE 4. DOUBLE HEAT EXCHANGER BOILER COMPONENTS
11
Page 12

COMPONENT DESCRIPTION

1. Front access door: Provides access to the gas train, burner controllers and the heat exchanger.
2. Air Filter Box: Allows for the connection of the PVC air intake pipe to the boiler through a standard PVC adapter. It uses a lter to prevent dust and debris from entering the boiler.
3. Automatic air vents: Designed to remove trapped air from the heat exchanger coils.
4. Blowers: The blowers pull in air and gas through the venturis. Air and gas mix inside the venturi and are pushed into the burners, where they burn inside the combustion chamber.
5. Boiler inlet temperature sensors These sensors monitor system return water temperature.
6. Boiler outlet temperature sensors/High Limits These sensors monitor boiler outlet water temperature. The boiler modulates based on the Lead Lag Sensor connected to the tank.
7. Burners Made with metal ber and stainless steel construction, the burners use pre-mixed air and gas and provide a wide range of ring rates.
8. Condensate Trap Disposes the condensate produced from heat exchanger and houses a switch that detects in case of blockage.
9. Control modules The control modules respond to internal and external signals and control the blowers, gas valves, and pumps to meet the heating demand.
10. Touch Screen Display Digital controls with touch screen technology and full color display.
11. Sight glass The quartz sight glass provides a view of the ame for inspection
purposes.
12. Flame sensors
Used by the control module to detect the presence of burner ame.
13. Flap valves Prevents recirculation of ue products when only one burner is
running.
14. Flue gas sensors (not visible)
These sensors monitor the ue gas exit temperature. The control modules will modulate and shut down the boiler if the ue gas temperature gets too hot. This protects the ue pipe from
overheating.
15. Flue pipe adapter (not visible)
Allows for the connection of the PVC vent pipe system to the boiler.
16. Gas shutoff valves (Internal unit) Manual valves used to isolate the gas valves from the burners.
17. Main gas shutoff valve (External unit) Manual valve used to isolate the boiler from the gas supply.
18. Automatic modulating gas valve The gas valve with the addition of venturi and blower are used for modulating premix appliances.
19. Heat exchanger access covers Allows access to the combustion side of the heat exchanger coils.
20. High gas pressure switch Switch provided to detect excessive supply gas pressure.
21. Spark Igniter
Provides direct spark for igniting the burners.
22. Boiler power supply terminals (not visible) The main power to the boiler is supplied through the terminals housed inside the high voltage junction box.
23. Low gas pressure switch Switch provided to detect low gas supply pressure.
24. High voltage connection box This box has terminals for connecting the main power supply (120V) to the boiler and outputs power supply (120V) for the pumps from the boiler control. This box has terminals for low voltage devices such as condensate trap and ow switch.
25. Sensors/Communication Box Connects sensors to tank sensor/header sensor and external connections to building managements systems through MODBUS.
26. Low water cutoff board and sensor probe (LWCO) Device used to ensure adequate water is supplied to the boiler. In the event of inadequate water levels, LWCO will ensure boiler shut down. LWCO board is connected to the electronic panel, whereas the sensor probe is connected to the heat exchanger.
27. Main power supply switch Turns 120 VAC ON/OFF to the boiler.
28. Pump relay The pump relays are used tfor providing power to the XW Boiler models.
29. Pressure relief valve Protects the heat exchangers from an over pressure condition. The relief valve will be set at particular PSI, depending on models.
30. Reset switch (optional) (not visible) Reset switch for the low water cutoff.
31. Stainless steel heat exchangers Allows system water to ow through specially designed coils.
32. Venturi The venturi is a gas/air mixing unit that allows modulation of a premix burner with constant gas/air ratio.
33. Water inlet Water connection that return water from the system to the heat exchangers.
34. Water outlets A NPT water connection that supplies hot water to the system.
35. Enable/Disable Switch This is an emergency boiler turn off switch which disconnects the interlock voltage to the control board, hence turning off the power supply to the gas valves. Do not use this switch for
turning off the boiler, this should be done from the touch screen display, using the Operational Switch on the Lead Lag screen.
36. Vent outlet Provides an outlet for combustion gases to outdoor.
12
Page 13

CONTROL COMPONENTS

THE CONTROL SYSTEM
The R7910A1138 is a burner control system that provides heat control, ame supervision, circulation pump control, fan control, boiler control sequencing, and electric ignition function. It will also provide status and error reporting.
FIGURE 5. BURNER CONTROL SYSTEM
SPARK IGNITER
The spark igniter is a device that ignites the main burner. When power is supplied to the igniter electrode, an electric arc is created between the electrode and the ground terminal which ignites the main burner.
FIGURE 7. LOW/HIGH GAS PRESSURE SWITCH
GAS VALVE
The gas valve is a normally closed servo regulated gas valve. The valve opens only when energized by the burner control and closes when the power is removed. The burner control supplies 24 volts to the gas valve during operation.
FIGURE 6. SPARK IGNITER
LOW/HIGH GAS PRESSURE SWITCH
This XP boiler is equipped with a low gas pressure switch which meets the CSD-1 code requirements.
The Low Gas Pressure Switch is normally open and remains open unless the pressure falls below the preset pressure.
The High Gas Pressure Switch is normally closed and is used to detect excessive gas pressure.
FIGURE 8. GAS VALVE
WATER FLOW SWITCH
The water ow switch activates when sufcient water ow has been established. Switch will not close when water ow is not
present.
FIGURE 9. WATER FLOW SWITCH
13
Page 14
FLAME SENSOR
Each burner is equipped with a ame sensor to detect the presence of the burner ames at high and low re conditions. If no ame is sensed, the gas valve will close automatically. The voltage sensed by the ame sensor will also be displayed on the Burner Screen.
FIGURE 10. FLAME SENSOR
WATER TEMPERATURE LIMIT CONTROLS
The “XB/XW” models incorporate an outlet water sensor having dual sensors, that are factory set at 210°F (99°C).
MAIN POWER SUPPLY SWITCH
The main power supply switch is a padlockable switch. This switch pro vides 120V from the power supply to the boiler.
This switch needs to be turned off when servicing the boiler. Note: The Enable/Disable Switch on the front of the boiler does not interrupt electrical power to the boiler.
WATER TEMPERATURE SENSORS
FIGURE 12. WATER TEMPERATURE SENSORS
Temperature sensors are threaded immersion probes. Temperature probes have embedded temperature sensors (thermistors). The boiler’s control system monitors these sensors to determine water temperature at various points in the system.
INLET AND OUTLET TEMPERATURE SENSORS
All models have two inlet and two outlet temperature sensors for each heat exchanger, factory installed to monitor the water temperature entering and leaving the boiler. The Inlet Probe is a temperature sensor only and has two leads. The Outlet probe also contains the manual reset high temperature limit switch and has four leads. The control system displays the Inlet and Outlet water temperatures sensed from these two sensors on the default Temperatures screen.
REMOTE SENSORS
All models are supplied from the factory with a remote sensor. The remote sensor is used to control system water temperature for a single boiler in a domestic hot water storage tank or in the return line from a primary/secondary hydronic heating system.
The boiler will modulate its ring rate in response to the actual system temperature and load conditions. The control system displays the temperature sensed from the remote sensor as the “Lead Lag” temperature on the default Temperatures screen.
FIGURE 11. MAIN POWER SUPPLY SWITCH
LOW WATER CUTOFF DEVICE (LWCO)
Low water cutoff device is normally a closed switch that opens when water drops below a preset level. Each model is equipped with a factory installed LWCO. LWCO board is connected to the electronic panel, whereas the sensor probe is connected to the heat exchanger.
FIGURE 13. LWCO BOARD AND PROBE
14
Page 15

BOILER INSTALLATION CONSIDERATIONS

GENERAL
If the system is to be lled with water for testing or other purposes during cold weather and before actual operation, care must be taken to prevent freezing of water in the system. Failure to do so may cause the water in the system to freeze with resulting damage to the system.
Damage due to freezing is not covered by the warranty.
Figure 78 on Page 80 shows a typical primary, secondary piping method. This is the preferred piping method for most stainless steel boilers. Other piping methods, however, may provide good system operation. A prime concern when designing heating systems is the maintenance of proper ow through the unit during boiler operation. The secondary pump should be sized per the recommended ow rate of the boiler, see Dimension and Capacity Data section in this manual.
Before locating the boiler:
1. Check for nearby connection to:
• System water piping
• Venting connections
• Gas supply piping
• Electrical power
2. Locate the boiler so that if water connections should leak,
water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. The pan must not restrict combustion air ow. Under no circumstances is the manufacturer to be held responsible for water damage in connection with this appliance, or any of its components.
3. Check area around the boiler. Remove any combustible
materials, gasoline and other ammable liquids.
4. Make sure the gas control system components are protected
from dripping or spraying water or rain during operation or service.
5. If a new boiler will replace an existing boiler, check for and
correct system problems, such as:
• System leaks causing oxygen corrosion or heat exchanger cracks from hard water deposits.
• Lack of freeze protection in boiler water causing system and boiler to freeze and leak.

HYDRONIC SYSTEM

The following is a brief description of the equipment required for the installations noted in this manual. All installations must comply with local code.
WATER SUPPLY LINE
These boilers can be used only in a forced circulation hot water heating system. Since most forced circulation systems will be of the closed type, install the water supply line as shown on piping
diagram.
Fast lling of large pipe, old radiator installations and pressure purging of series loop systems (where high pressures are not available) requires bypassing of the pressure reducing valve.
Gener ally, pressure purging is not possible with a well pump system. High point air venting is essential.
If the system is of the open type, a pressure reducing valve will not be required as the water supply to the system will be controlled by a manu ally operated valve. An overhead surge tank is required. A minimum pressure of 15 psi (100 kPa) must be maintained on the boiler at all times to ensure avoidance of potential damage to the boiler which may not be covered by the warranty.
EXPANSION TANK
If the system is of the closed type, install an expansion tank. The sizing of the expansion tank for a closed system is very important and is directly related to the total water volume of the system.
An air separator as shown in the piping diagrams is recommended especially for modern commercial hydronic systems. See Figure 78
on Page 80.
VENT VALVES
It is recommended that automatic, loose key or screw-driver type vent valves be installed at each convector or radiator.
SYSTEM HEADERS
Split systems with individual supply and return lines from the boiler room should normally have this piping connected to supply and return manifold headers near the boiler. To achieve good water distribution with maximum pressure drop for sever al circuits, manifolds should be larger than system mains.
The circuits should be spaced on the heater at a minimum of 3” (76 mm) center to center. Install a balancing cock in each return line.
Manifold headers are recommended for split systems with or without zone valves and also those installations with zone circulators. If the system is to be split at remote points, good practice requires special attention be given to main pipe sizing to allow balancing of water ow.
CHECK VALVES
Check valves must be installed to isolate each boiler in installations where multiple boilers/pumps are installed in the same zone.
COOLING PIPING
When the boiler is used in conjunction with a refrigeration system it must be installed so that the chilled medium is piped in parallel with the boiler. Appropriate ow control valves, manual or motorized, must be provided to prevent the chilled medium from entering the boiler.
If the boiler is connected to chilled water piping or its heating coils are exposed to refrigerated air, the boiler piping system must be equipped with ow valves or other automatic means to prevent gravity circulation through the boiler during the cooling cycle.
Primary/secondary pumping of both the chiller(s) and the boiler(s) is an excellent winter-summer change-over method, because cooling ow rates are so much more than heating ow rates. In this way each system (heating or cooling) is circulated independently.
15
Page 16
CIRCULATING PUMP
A circulating pump is used when a system requires a circulating loop or there is a storage tank used in conjunction with the boiler. Install in accordance with the current edition of the National Electrical Code, NFPA 70 or the Canadian Electrical Code, CSA C22.1. All bronze circulating pumps are recommended for use with commercial boilers. Some circulating pumps are manufactured with sealed bearings and do not require further lubrication. Some circulating pumps must be periodically oiled. Refer to the pump manufacturer’s instructions for lubrication requirements.
XB HYDRONIC BOILERS: The circulating pump is not provided on standard models (optional) and must be obtained and installed in the eld.
XW HOT WATER BOILERS: The circulating pump is integral to the XW models. This pump has been lubricated at the factory, and future lubrication should be in accordance with the motor manufacturer’s instructions provided as a supplement to this manual.
PRIMARY SYSTEM CONTROL
All XP boiler installations require a “Primary System Control” that senses and reacts to water temperature inside the storage tank on domestic water applications or in the return line on primary/ secondary hydronic heating systems. The Primary System Control will activate and deactivate boiler heating cycles based on its setpoint and current system water temperature. There are three suitable methods to congure a Primary System Control. One of these three methods must be used.
1. The Primary System Control can be the boiler’s control system working with the factory supplied Header Sensor, installed inside the storage tank on domestic water applications or in the return line on primary/secondary hydronic heating systems.
2. Alternatively, the Burner Control system can be used as a Primary System Control. It will also provide boiler status and error reporting. Multiple boilers can be joined together to heat a system instead of a single, larger burner or boiler. Using boilers in parallel is more efcient, costs less, reduces emissions, improves load control, and is more exible than the traditional large boiler.
3. MB2 and COM2 ports can be used for Building Management Systems.
INTERNAL CONTAMINANTS
The hydronic system must be internally cleaned and ushed after a new or replacement boiler has been installed, to remove contaminants that may have accumulated during installation. This is extremely important when a replacement boiler is installed into an existing system where Stop Leak or other boiler additives have been used.
Failure to clean and ush the system can produce acid concentrations that become corrosive, and leads to heat exchanger failure.
All hot water heating systems should be completely ushed with a grease removing solution to assure trouble-free opera tion. Pipe joint compounds, soldering paste, grease on tubing and pipe all tend to contaminate a system
Failure to ush contaminants from a system can cause solids to form on the inside of boiler exchangers, create excessive blockage of water circulation, deterioration of the pump seals and impellers.

HOT WATER BOILER SYSTEM - GENERAL WATER LINE CONNECTIONS

Piping diagrams will serve to provide the installer with a reference for the materials and methods of piping necessary for installation. It is essential that all water piping be installed and connected as shown on the diagrams. Check the diagrams to be used thoroughly before starting installation to avoid possible errors and to minimize time and material cost. It is essential that all water piping be installed and connected as shown on the diagrams. See Figure 78 on Page 80 and Figure 79 on Page 81.
CLOSED WATER SYSTEMS
Water supply systems may, because of code requirements or such conditions as high line pressure, among others, have installed devices such as pressure reducing valves, check valves, and back ow preventers. Devices such as these cause the water system to be a closed system.
THERMAL EXPANSION
As water is heated, it expands (thermal expansion). In a closed system the volume of water will increase when it is heated. As the volume of water increases there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent Temperature-Pressure Relief Valve operation: water discharged from the valve due to excessive pressure build up. This condition is not covered under the limited warranty. The Temperature-Pressure Relief Valve is not intended for the constant relief of thermal expansion.
A properly sized thermal expansion tank must be installed on all closed systems to control the harmful effects of thermal expansion. Contact a local plumbing service agency to have a thermal expansion tank installed.
PRESSURE RELIEF VALVE
An ASME rated pressure relief valve is furnished with the boiler. A tting for the relief valve is provided in the top of the boiler. Never operate the heating elements without being certain the boiler is lled with water and a properly sized pressure relief valve is installed in the relief valve opening provided.
The pressure rating of the relief valve should be equal to or less than the rated pressure capacity of any component in the system including the boiler. Should the valve need to be replaced, call the toll free phone number listed on the back of this manual for further technical assistance
16
Page 17
CAUTION
Pressure Relief Valve discharge pipe must
terminate at adequate drain.
Water Damage Hazard
Explosion Hazard
Relief Valve must comply with ASME code.
Properly sized Relief Valve must be installed in opening provided.
Can result in overheating and excessive tank pressure.
Can cause serious injury or death.
A discharge pipe from the relief valve should terminate at an adequate oor drain. Do not thread, plug, or cap the end of drain line.
In addition, a CSA design-certied and ASME-rated tempera ture and pressure (T&P) relief valve must be installed on each and every water storage tank in hot water supply system. The T&P relief valve must comply with appli cable construction provisions of Standard for Relief Valves for Hot Water Supply Systems, ANSI Z21.22 or CSA 4.4. T&P re lief valve must be of automatic reset type and not embody a single-use type fusible plug, cartridge or linkage.
T&P relief valve should have a temperature rating of 210°F (99°C), a pressure rating not exceeding lowest rated working pressure of any system compo nent, and a discharge capacity exceeding total input of water boilers supply ing water to storage
tank.
Locate the T&P relief valve (a) in the top of the tank, or (b) in the side of the tank on a centerline within the upper 6 inches (152 mm) of the top of the tank, see Figure 78 and Figure 79. The tapping should be threaded in accordance with the current edition of the Standard for Pipe Threads, General Purpose (inch), ANSI/A SME B1.20.1. The location of, or in tended location for, the T&P relief valve should be readily accessible for servicing or replacement.
GAS CONNECTIONS
The Discharge Pipe:
• Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions.
• Shall not be plugged or blocked.
• Shall not be exposed to freezing temperatures.
• Shall be of material listed for hot water distribution.
• Shall be installed so as to allow complete drainage of both the relief valve and the discharge pipe.
• Must terminate a maximum of six inches above a oor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building.
• Shall not have any valve or other obstruction between the relief valve and the drain.
Once the boiler is installed and lled with water and the system is pressurized, manually test the operation of the pressure relief valve. See the Maintenance Procedures section of this manual for instructions.
Your local code authority may have other specic safety relief valve requirements not covered below. If any pressure relief valve is re placed, the replace ment valve must com ply with the current version of the ASME Boiler and Pressure Vessel Code, Section IV (“HEATING BOILERS”).
XB HYDRONIC BOILERS, are shipped with a 50 psi (345 kPa) pressure relief valve. This relief valve must be in stalled in the water outlet as near to the boiler as possi ble.
XW HOT WATER BOILERS, are shipped with a 125 psi (860 kPa) pressure relief valve that must be in stalled in the water out­let as near to the boil er as possi ble.
This ASME-rated valve has a discharge capacity that exceeds maximum boiler input rating and a pres sure rating that does not exceed maxi mum working pres sure shown on boiler rating plate.
Make sure the gas on which boiler is to operate is same as that specied on the rating plate. Do not install boiler if equipped for a different type of gas. Consult your gas supplier.
This boiler is not intended to operate at gas supply pressure other than shown on the rating plate. A lock-up or positive shut­off type regulator must be installed in gas supply line. For proper gas regulation the lock-up style regulators must be installed no closer than a minimum of 3 feet from the boiler and a maximum of 8 feet away from the boiler. Exposure to higher gas supply pressure may cause damage to gas valves which can result in re or explosion. If overpressure has occurred such as through improper testing of gas lines or emergency malfunction of supply system, the gas valves must be checked for safe operation. Make sure that the outside vents on supply regulators and the safety vent valves are protected against blockage. These are parts of the gas supply system, not boiler. Vent blockage may occur during ice build-up or snowstorms.
The boiler must be isolated from the gas supply piping system by closing its main manual gas shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig.
Disconnect the boiler and its main manual gas shut-off valve from the gas supply piping during any pressure testing of the gas supply system over 1/2 psig. The gas supply line must be capped when not connected to the boiler.
17
Page 18
It is important to guard against gas valve fouling from contaminants in the gas ways. Such fouling may cause improper operation, re or explosion. If copper supply lines are used they must be approved for gas service.
When local codes require a main manual shut-off valve outside the boiler jacket, a suitable main manual shut-off valve must be installed in a location complying with those codes.
Before attaching gas line be sure that all gas pipe is clean on inside. To trap any dirt or foreign material in the gas supply line, a drip leg (or sediment trap) must be incorporated in piping. The drip leg must be readily accessible and not subject to freezing conditions. Install in accordance with recommendations of serving gas supplier. Refer to the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the Natural Gas and Propane Installation Code, CAN/CSA B149.1
Size of gas supply piping may be larger than heater connection on installations where a signicant run of piping is required.
To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to boiler gas inlet. When installing and tightening gas piping use a second wrench to hold the gas valve to keep the valve from turning. To prevent damage to the gas valve do not use pipe wrench on the valve body.
Fittings and unions in gas line must be of metal to metal type. Apply joint compounds (pipe dope) sparingly and only to the male threads of pipe joints. Do not apply compound to the rst two threads. Use compounds resistant to the action of liqueed petroleum gases. The boiler and its gas connection must be leak tested before placing the boiler in operation.
GAS SUPPLY LINE SIZING
The gas piping installation must be capable of supplying the maximum probable gas demand without excessive pressure loss. Depending on local practices, the ALLOWABLE PRESSURE LOSS between the gas meter, or service regulator and each appliance is generally 0.3 or 0.5 inches of water column (0.075 or 0.124 kPa).
For single boiler installation, refer to Table 8 and Table 9 to size iron pipe or equivalent gas supply line size to be used with single
unit.
For multiple boiler installation or installations of a single boiler with other gas appliances, please refer to Table 10 and Table 11 on Page 20 to size iron pipe or equivalent gas supply line. These tables are taken from the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the Natural Gas and Propane Installation Code, CAN/CSA B149.1.
• Table 10 is based on a pressure drop of 0.5 inches water column (0.124 kPa), and a gas with a specic gravity of
0.60 and a heating value of 1,000 BTU/ft3, approximately that of Natural Gas.
• Table 11 is based on a pressure drop of 0.5 inches water column (0.124 kPa), and a gas with a specic gravity of
1.53 and a heating value of 2,500 BTU/ft3, approximately
that of Propane Gas.
Where it is necessary to use more than the average number of ttings (i.e., elbows, tees and valves in gas supply line) use a pipe larger than specied to compensate for increased pressure drop.
Table 8 and Table 9 shows the maximum equivalent gas pipe length for a single unit installation. It does not take into account other appliances that may be connected to the gas line. For installation of multiple units, or instances where several appliances are connected to the same line, use Table 10 and Table 11 for proper sizing.
SINGLE UNIT INSTALLATION, SUGGESTED GAS PIPE
TABLE 8.
SIZING. MAXIMUM EQUIVALENT PIPE LENGTH (IN FEET).
BTU
Input
920,000 70 150 175 ----- ----- ----- ----- -----
1,300,000 40 100 100 200 ----- ----- ----- -----
1,700,000 20 60 70 150 200 ----- ----- -----
2,000,000 20 50 50 100 150 ----- ----- -----
2,600,000 10 30 30 70 90 200 ----- -----
3,400,000 ----- ----- 20 40 50 125 200 -----
Natural gas 1000 Btu/ft^3, 0.60 specic gravity @ 0.3 in. w.c. pressure drop. Propane gas 2500 Btu/ft^3, 1.50 specic gravity @ 0.3 in. w.c. pressure drop.
2” 2-1/2” 3” 4”
Nat Pro Nat Pro Nat Pro Nat Pro
TABLE 9.
SINGLE UNIT INSTALLATION, SUGGESTED GAS PIPE
SIZING. MAXIMUM EQUIVALENT PIPE LENGTH (IN FEET).
BTU
Input
920,000 125 200 200 ----- ----- ----- ----- -----
1,300,000 80 175 175 ----- ----- ----- ----- -----
1,700,000 40 100 100 ----- ----- ----- ----- -----
2,000,000 30 80 80 200 200 ----- ----- -----
2,600,000 20 50 50 125 150 ----- ----- -----
3,400,000 10 30 30 70 90 200 ----- -----
Natural gas 1000 Btu/ft^3, 0.63 specic gravity @ 0.5 in. w.c. pressure drop. Propane gas 2500 Btu/ft^3, 1.50 specic gravity @ 0.5 in. w.c. pressure drop.
2” 2-1/2” 3” 4”
Nat Pro Nat Pro Nat Pro Nat Pro
CORROSIVE MATERIALS AND CONTAMINATION SOURCES
Products to avoid:
• Spray cans containing chloro/uorocarbons
• Permanent wave solutions
• Chlorinated waxes/cleaners
• Chlorine-based swimming pool chemicals
• Calcium chloride used for thawing
• Sodium chloride used for water softening
• Refrigerant leaks
• Paint or varnish removers
• Hydrochloric acid/muriatic acid
• Cements and glues
• Antistatic fabric softeners used in clothes dryers
• Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
• Adhesives used to fasten building products and other similar products
Areas likely to have contaminants:
• Dry cleaning/laundry areas and establishments
• Swimming pools
• Metal fabrication plants
• Beauty shops
Refrigeration repair shops
• Photo processing plants
18
Page 19
• Auto body shops
• Plastic manufacturing plants
• Furniture renishing areas and establishments
• New building construction
• Remodeling areas
Common household products, pool and laundry products may contain uorine or chlorine compounds. When these chemicals come in contact with the boiler, they react and can form strong acids. The acid can spoil the boiler wall, causing serious damage and may result in ue gas spillage or boiler water leakage into the building.
If the above mentioned contaminants and corrosive materials chemicals are present near the location of the boiler, make sure to remove the boiler permanently or relocate air inlet and vent terminations to other areas.
FIELD WIRING
120 VAC POWER SUPPLY WIRING
A dedicated, single phase, 30-60 amp (refer to Table 6 on Page
8) circuit breaker with a grounded neutral should be provided to supply power to the boilers. Use #10 AWG wire for the 120 VAC power supply to the boiler. All 120 VAC power supply connections must be made as shown in Figure 14. These connections should be made at the rear of the unit where a wiring junction box is provided. Field installed power supply wiring to the boiler should be installed in conduit. This conduit and wiring should be separate from any other conduit/wiring to guard against EMI (electromagnetic interference).
POWER SUPPLY CHECK
To reduce the possibility of electrical interference with the boiler’s control system the power supply voltage, polarity and ground must be checked. Using an AC volt meter check the 120 VAC power supply wiring from the breaker prior to making power supply connections at the boiler. Conrm the power supply voltage & polarity are correct and that an adequate ground connection is present by performing the three voltage tests below. See Figure 14 for wiring references.
Conrm RMS voltage between:
H and GND = 108 VAC minimum, 132 VAC maximum.
N and H = 108 VAC minimum, 132 VAC maximum.
N and GND = < 1 VAC maximum.
LOW VOLTAGE CONTROL WIRING
1. Header Terminals: In case of Hydronic Boilers, the header
terminals are connected to the hydronic loop header sensor. Whereas in case of Hot water Boilers the header terminals are connected to the tank sensor where the temperature can be sensed. See Figure 15.
2. Outdoor Terminals: In case of Hydronic Boilers, they are
connected to the outdoor sensors. But in case of Hot water Boilers, they are not connected. See Figure 15. The outdoor sensors must be mounted with cable inlet facing down as shown in Figure 16. The maximum length of the wire connecting from the boiler to the outdoor sensor must be no more than 50 feet.
3. MB2 and COM2 terminals are meant for building
management systems.
FIGURE 15. LOW VOLTAGE CONTROL WIRING
All low voltage control wiring connections must be made as shown in Figure 14. These connections should be made at the rear of the unit where a wiring junction box is provided. Field installed wiring inside 1/2 inch conduit is installed between the junction box on the back of the boiler and the temperature probe and/or eld supplied external control being used. This conduit and wiring should be separate from any other conduit/wiring to guard against EMI (electromagnetic interference).
FIGURE 14. FIELD WIRING
FIGURE 16. OUTDOOR SENSOR
The outdoor sensor must be mounted in a shaded location, to avoid direct sunlight. It must be atleast 3 feet away from any exhaust, dryer, bathroom or other building vents. It must be located on the north side of th building, above the expected snow line where ice and debris cannot cover it.
19
Page 20
TABLE 10. SUGGESTED PIPE SIZE FOR MULTIPLE GAS APPLIANCES (NATURAL GAS)
Nominal Maximum Capacity of Pipe in BTU/hr and kW for Gas Pressures of 14 in. W.C. (0.5 psi) or Less and
Iron Pipe a Pressure Drop of 0.5 in. W.C. (based on 0.60 Specic Gravity Gas w/Heating Value of 1,000 BTU’s/Ft3)
Size Length of Pipe in Feet (Meters)
(Inches) 10 (3.05) 20 (6.1) 30 (9.14) 40 (12.19) 50 (15.24) 60 (18.29) 70 (21.34) 80 (24.38) 90 (27.43) 100 (30.48) 125 (38.1) 150 175 200
1 1/2 BTU/hr 2,100,000 1,460,000 1,180,000 990,000 900,000 810,000 750,000 690,000 650,000 620,000 550,000 500,000 460,000
kW 615 428 346 290 264 237 220 202 190 182 161 146 135
2 BTU/hr 3,950,000 2,750,000 2,200,000 1,900,000 1,680,000 1,520,000 1,400,000 1,300,000 1,220,000 1,150,000 1,020,000 950,000 850,000 800,000
kW 1,157 805 644 556 492 445 410 381 357 337 299 278 249 234
2 1/2 BTU/hr 6,300,000 4,350,000 3,520,000 3,000,000 2,650,000 2,400,000 2,250,000 2,050,000 1,950,000 1,850,000 1,650,000 1,500,000 1,370,000 1,280,000
kW 1,845 1,274 1,031 879 776 703 659 600 571 542 483 439 401 375
3 BTU/hr 11,000,000 7,700,000 6,250,000 5,300,000 4,750,000 4,300,000 3,900,000 3,700,000 3,450,000 3,250,000 2,950,000 2,650,000 2,450,000 2,280,000
kW 3,222 2,255 1,830 1,552 1,391 1,259 1,142 1,084 1,010 952 864 776 718 668
4 BTU/hr 23,000,000 15,800,000 12,800,000 10,900,000 9,700,000 8,800,000 8,100,000 7,500,000 7,200,000 6,700,000 6,000,000 5,500,000 5,000,000 4,600,000
kW 6,736 4,627 3,749 3,192 2,841 2,577 2,372 2,197 2,109 1,962 1,757 1,611 1,464 1,347
20
TABLE 11. SUGGESTED PIPE SIZE FOR MULTIPLE GAS APPLIANCES (PROPANE GAS)
Nominal Maximum Capacity of Pipe in BTU/hr and kW for Gas Pressures of 14 in. W.C. (0.5 psi) or Less and
Iron Pipe a Pressure Drop of 0.5 in. W.C. (based on 0.60 Specic Gravity Gas w/Heating Value of 1,000 BTU’s/Ft3)
Size Length of Pipe in Feet (Meters)
(Inches) 10 (3.05) 20 (6.1) 30 (9.14) 40 (12.19) 50 (15.24) 60 (18.29) 70 (21.34) 80 (24.38) 90 (27.43) 100 (30.48) 125 (38.1) 150 175 200
1 1/2 BTU/hr 3,276,000 2,277,600 1,840,800 1,544,400 1,404,000 1,263,600 1,170,000 1,076,400 1,014,000 967,200 858,000 780,000 717,600 670,800
kW 959 667 539 452 411 370 343 315 297 283 251 228 210 196
2 BTU/hr 6,162,000 4,290,000 3,432,000 2,964,000 2,620,800 2,371,200 2,184,000 2,028,000 1,903,200 1,794,000 1,591,200 1,482,000 1,326,000 1,248,000
kW 1,805 1,256 1,005 868 768 694 640 594 557 525 466 434 388 366
2 1/2 BTU/hr 9,828,000 6,786,000 5,491,200 4,680,000 4,134,000 3,744,000 3,510,000 3,198,000 3,042,000 2,886,000 2,574,000 2,340,000 2,137,200 1,999,800
kW 2,878 1,987 1,608 1,371 1,211 1,097 1,028 937 891 845 754 685 626 585
3 BTU/hr 17,160,000 12,012,000 9,750,000 8,268,000 7,410,000 6,708,000 6,084,000 5,772,000 5,382,000 5,070,000 4,602,000 4,134,000 3,822,000 3,556,800
kW 5,026 3,518 2,856 2,421 2,170 1,965 1,782 1,690 1,576 1,485 1,348 1,211 1,119 1,042
4 BTU/hr 35,880,000 24,648,000 19,968,000 17,004,000 15,132,000 13,728,000 12,636,000 11,700,000 11,232,000 10,452,000 9,360,000 8,580,000 7,800,000 7,176,000
kW 10,508 7,219 5,848 4,980 4,432 4,021 3,701 3,427 3,290 3,061 2,741 2,513 2,284 2,102
Page 21

GENERAL REQUIREMENTS

REQUIRED ABILITY
Installation or service of this boiler requires ability equivalent to that of a licensed trades man in the eld involved. Plumbing, air supply, venting, gas supply, and electrical work are re quired.

LOCATION

When installing the boiler, consideration must be given to proper location. The location selected should provide ade quate air supply and be as centralized with the piping system as possible.
REPLACING EXISTING COMMON VENTED BOILER
NOTE: This section does not describe a method for common venting XP units. It describes what must be done when a unit is removed from a common vent system. The XP units require special vent systems and fans for common vent. Contact the factory if you have questions about common venting XP units.
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it. At the time of removal of an existing boiler, the following steps should be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system
are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and deciencies which could cause an unsafe condition.
3. In so far as it is practical, close all building doors and
windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close replace dampers.
4. Place in operation the appliance being inspected. Follow the
lighting instructions. Adjust thermostat so the appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after 5
minutes of main burner operation. Use the ame of a match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining
connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, replace dampers and any other gas-burning appliance to their previous condition of use.
7. Any improper operation of the common venting system
should be corrected so that the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/ or CSA B149.1, Installation Codes. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables and guidelines in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Installation Codes.
This boiler is intended for Indoor Installation only, and should not be installed where freezing temperatures or any moisture could damage the external components of the boiler.
21
Page 22
PANELS AND COVERS
All panels and covers (e.g. control and junction box covers; front, side and rear panels of boiler) must be in place after service and/ or before opera tion of boiler. This will ensure that all gas ignition components will be protected from water.
The XP is a low-pressure boiler (Category IV) to be used as either hot water supply (domestic/commercial water heating) or hot water heating (hydronic) application. Category IV appli ances are often termed “High Ef ciency” appliances.
CHEMICAL VAPOR CORROSION
Boiler corrosion and component failure can be caused by the he a ting an d br eakd own of air b o r ne chemic a l vapors. Spr ay can propellants, cleaning sol vents, refrigerator and air conditioning refrig erants, swimming pool chemicals, calcium and sodium chloride (water softener salt), waxes, and process chemicals are typical compounds which are potentially corrosive. These materials are corrosive at very low concentration levels with little or no odor to reveal their presence.
Products of this sort should not be stored near boiler. Also, air which is brought in contact with boiler should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outside sources. Failure to observe this requirement will void warranty.
LEVELING
Because this unit is a Category IV appliance it produces some amounts of condensation. The unit has a condensation disposal system that requires this unit to be level to properly drain. Each unit should be checked to be certain that it is level prior to starting
the unit.
If the unit is not level, obtain and insert shims under the feet at the frame base to correct this condition.
AIR REQUIREMENTS
Breathing Hazard - Carbon Monoxide Gas
Install appliance in accordance with the Instruction Manual and NFPA 54 or CAN/CSA-B149.1.
To avoid injury, combustion and ventilation air must be taken from outdoors.
Do not place chemical vapor emitting products near water heater.
Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.
INSTALLATION CLEARANCES
This boiler is approved for installation in an alcove with minimum clearances to combustibles.
TABLE 12. INSTALLATION CLEARANCES
RECOMMENDED
SERVICE
CLEARANCES
Front 30" (762 mm) 8" (203 mm)
Rear 36" (610 mm) 24" (610 mm)
Left 24 " (610 mm) 1" (25.4 mm)
Right 24 " (610 mm) 2" (51 mm)
Top 24" (610 mm) 6" (152 mm)
2” (51 mm) clearance is allowable from combustible construction
for hot water pipes.
Sufcient area should be provided at the front and rear of the unit for prop er servicing. In a utility room installa tion, the door opening should be wide enough to allow the boiler to enter or to permit the replacement of another appli ance such as a boiler.
FLOORING AND FOUNDATION:
All models are approved for installation on combustible ooring, but must never be installed on carpeting. Do not install the boiler on carpeting even if foundation is used. Fire can result, causing severe personal injury, death, or substantial property damage.
If ooding is possible, elevate the boiler sufciently to prevent water from reaching the boiler.
CLEARANCES FROM
COMBUSTIBLE
MATERIALS
For safe operation an adequate supply of fresh uncontaminated air for combustion and ventilation must be provided.
An insufcient supply of air can cause recirculation of combustion products resulting in contamination that may be hazardous to life. Such a condition often will result in a yellow, luminous burner ame, causing sooting of the combustion chamber, burners and ue tubes and creates a risk of asphyxiation.
Do not install the boiler in a conned space unless an adequate supply of air for combustion and ventilation is brought in to that space using the methods described in the Conned Space section that follows.
Never obstruct the ow of ventilation air. If you have any doubts or questions at all, call your gas supplier. Failure to provide the proper amount of combustion air can result in a re or explosion and cause property damage, serious bodily injury or death.
UNCONFINED SPACE
An unconned space is one whose volume is not less than 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating of all appliances installed in the space. Rooms communicating directly with the space, in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconned space.
Makeup air requirements for the operation of exhaust fans, kitchen ventilation systems, clothes dryers and replaces shall also be considered in determining the adequacy of a space to provide combustion, ventilation and dilution air.
UNUSUALLY TIGHT CONSTRUCTION
In unconned spaces in buildings, inltration may be adequate to provide air for combustion, ventilation and dilution of ue gases. However, in buildings of unusually tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.) additional air must be provided using the methods described in the Conned Space section that follows.
22
Page 23
CONFINED SPACE
A conned space is one whose volume is less than 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating of all appliances installed in the space.
Openings must be installed to provide fresh air for combustion, ventilation and dilution in conned spaces. The required size for the openings is dependent on the method used to provide fresh air to the conned space and the total Btu/hr input rating of all appliances installed in the space.
DIRECT VENT APPLIANCES
Appliances installed in a direct vent conguration that derive all air for combustion from the outdoor atmosphere through sealed intake air piping are not factored in the total appliance input Btu/ hr calculations used to determine the size of openings providing fresh air into conned spaces.
EXHAUST FANS
Where exhaust fans are installed, additional air shall be provided to replace the exhausted air. When an exhaust fan is installed in the same space with a water heater, sufcient openings to provide fresh air must be provided that accommodate the requirements for all appliances in the room and the exhaust fan. Undersized openings will cause air to be drawn into the room through the water heater’s vent system causing poor combustion. Sooting, serious damage to the water heater and the risk of re or explosion may result. It can also create a risk of asphyxiation.
LOUVERS AND GRILLES
The free areas of the fresh air openings in the instructions that follow do not take in to account the presence of louvers, grilles or screens in the openings.
The required size of openings for combustion, ventilation and dilution air shall be based on the “net free area” of each opening. Where the free area through a design of louver or grille or screen is known, it shall be used in calculating the size of opening required to provide the free area specied. Where the louver and grille design and free area are not known, it shall be assumed that wood louvers will have 25% free area and metal louvers and grilles will have 75% free area. Non motorized louvers and grilles shall be xed in the open position.
OUTDOOR AIR THROUGH TWO OPENINGS
FIGURE 17. OUTDOOR AIR THROUGH TWO OPENINGS
The conned space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The openings shall communicate directly with the outdoors. See Figure 17.
Each opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm2).
OUTDOOR AIR THROUGH ONE OPENING

FRESH AIR OPENINGS FOR CONFINED SPACES

The following instructions shall be used to calculate the size, number and placement of openings providing fresh air for combustion, ventilation and dilution in conned spaces. The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into conned spaces only. Do not refer to these illustrations for the purpose of vent installation. See Venting section on Page 25 for complete venting installation instructions.
FIGURE 18. OUTDOOR AIR THROUGH ONE OPENING
Alternatively a single permanent opening, commencing within 12 inches (300 mm) of the top of the enclosure, shall be provided. See Figure 18. The water heater shall have clearances of at least 1 inch (25 mm) from the sides and back and 6 inches (150 mm) from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors and shall have a minimum free area of the following:
1. 1 square inch per 3000 Btu/hr (700 mm2 per kW) of the total
input rating of all appliances located in the enclosure, and
2. Not less than the sum of the areas of all vent connectors in
the space.
23
Page 24
OUTDOOR AIR THROUGH TWO HORIZONTAL DUCTS
FIGURE 19. OUTDOOR AIR THROUGH TWO HORIZONTAL
DUCTS
The conned space shall be provided with two permanent horizontal ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The horizontal ducts shall communicate directly with the outdoors. See Figure 19.
Each duct opening shall have a minimum free area of 1 square inch per 2,000 Btu/hr (1100 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure.
When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches.
OUTDOOR AIR THROUGH TWO VERTICAL DUCTS
The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into conned spaces only.
Do not refer to these illustrations for the purpose of vent installation.
The conned space shall be provided with two permanent vertical ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The vertical ducts shall communicate directly with the outdoors. See Figure 20.
Each duct opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure.
When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches.
AIR FROM OTHER INDOOR SPACES
FIGURE 21. AIR FROM OTHER INDOOR SPACES
The conned space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. See Figure 21.
Each opening shall communicate directly with an additional room(s) of sufcient volume so that the combined volume of all spaces meets the criteria for an Unconned Space.
Each opening shall have a minimum free area of 1 square inch per 1,000 Btu/hr (1100 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm2).
FIGURE 20. OUTDOOR AIR THROUGH TWO VERTICAL
DUCTS
24
Page 25

VENTING

Vent sizing, installation and termination should be in accordance with this installation manual. This boiler must be vented using PVC/CPVC or Stainless Steel materials.
All electrical power and gas must be turned off prior to any installation of the venting system.

VENT INSTALLATION CONSIDERATIONS

This boiler is a category IV appliance that can be vented using room air for intake combustion air, or direct vented so that all intake air for combustion comes from the outside through a sealed pipe. When installing this appliance as direct vent, special vent kits are required.
In cold climates any water vapor remaining in the ue gases will condense into a cloud of vapor at the point where the vent system exits the building. Special consideration is recommended, before locating the vent termination near walkways, windows and building entrances.
Direct venting into dead spaces such as alleys, atriums, and inside corners can cause recirculation of ue gases. Recirculation of ue gases will cause sooting, premature failure of the heat exchanger, and icing of the combustion air intake during severe cold weather. To prevent the recirculation of ue gases, maintain as much distance as possible between the combustion air intake and the exhaust vent terminal. Due to large volumes of ue gases, multiple boiler applications also require additional distance between the intake and the exhaust terminals.
This boiler can be vented with PVC/CPVC or an UL approved AL 29-4C Stainless Steel venting material which are explained in the following pages.
PVC/CPVC INSTALLATION:
STAINLESS STEEL INSTALLATION:
Installations must comply with applicable national, state, and local codes. Stainless steel vent systems must be listed as a UL­1738 approved system for the United States and a ULC-S636 approved system for Canada.
Installation of the approved AL 29-4C stainless steel venting material should adhere to the stainless steel vent manufacturer’s installation instructions supplied with the vent system.
Refer to Table 14 and Table 15 on Page 36 for air intake and vent pipe sizes.
AIR INTAKE/VENT CONNECTIONS
1. Air Intake Adapter: Provides an inlet for combustion air
directly to the unit from outdoors.
2. Vent Outlet: Provides an outlet for combustion gases to
outdoors.
VENTING SYSTEM
This boiler may be installed in six separate orientations depending on the require ments of the building and the appliance. The installer must decide which method is most appro priate for each installation. These orientations are:
1. Vertical Termination - vertical vent termi na tion through
un-enclosed or en closed areas with roof penetration, see Figure 25 on Page 28.
2. Through-the-Wall Termination (TWT) - hori zontal vent
termination directly through an outside wall, see Figure 26
on Page 28.
3. Horizontal Direct Vent - using TWT to exhaust ue
prod ucts and PVC piping to bring combus tion air to the boiler from the outside. See Figure 27 on Page 29 and Figure 30
on Page 30.
4. Vertical Direct Vent - using a vertical vent termination to
exhaust ue products and PVC piping to bring combustion air to the boiler from outside, see Figure 28 on Page 29 and Figure 29 on Page 30.
GENERAL VENT INSTALLATION PROCEDURE
Prior to beginning the installation of the vent system, deter mine and obtain all parts re quired for the installa tion. Proper operation of the boiler and vent ing system is depen­dent upon use of all speci ed parts and installa tion tech niques; both safety and proper perfor mance of the system may suffer if in structions are not followed.
Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 for Canadian installations.
Refer to Table 13 on Page 36 for PVC/CPVC piping materials.
All PVC vent pipes must be glued, properly supported, and the exhaust must be pitched a minimum of a 1/4 inch per foot back to the boiler (to allow drainage of condensate).
This appliance requires a special venting system. Use only the vent materials, primer, and cement specified in this manual to make the vent connections. Failure to follow this warning could result in fire, personal injury, or death.
Note: Make sure that for PVC venting installation, the first 10 feet of vent must be CPVC or stainless steel and the set point temperature of the boiler must not exceed
200 °F.
25
Page 26
AIR INLET PIPE MATERIALS
VENT AND AIR PIPE INSTALLATION
Make sure the air inlet pipe(s) are sealed. The acceptable air inlet pipe materials are:
• PVC/CPVC
• AL 29-4C
An adapter is provided for transition between the air inlet connection on the boiler and the plastic air inlet pipe.
Seal all joints and seams of the air inlet pipe using either Aluminum Foil Duct Tape meeting UL Standard 723 or 181A-P or a high quality UL Listed silicone sealant. Do not install seams of vent pipe on the bottom of horizontal runs.
Secure all joints with a minimum of 3 sheet metal screws or pop rivets. Apply Aluminum Foil Duct Tape or silicone sealant to all screws or rivets installed in the vent pipe.
Make sure that the air inlet pipes are properly supported.
The PVC/ CPVC air inlet pipe must be cleaned and sealed with the pipe manufacturer’s recommended solvents and standard commercial pipe cement for the material used. The PVC, CPVC, air inlet pipe should use a silicone sealant to ensure a proper seal at the boiler connection and the air intake adapter connection. Proper sealing of the air inlet pipe ensures that combustion air will be free of contaminants and supplied in proper volume.
1. Measure from the boiler level to vent. Refer to the Table 14
on Page 36 for the allowable lengths.
2. Prepare pipes to the required lengths and deburr the inside
and outside of the pipe ends. Chamfer outside the pipe end to ensure even cement distribution when joining.
3. Clean all pipe ends and ttings using a clean dry rag.
(Moisture will retard curing and dirt or grease will prevent adhesion.)
4. Dry t vent or air piping to ensure proper t before assembling
any joint. The pipe should go a third to two-thirds into the tting to ensure proper sealing after cement is applied.
5. Priming and Cementing:
• Handle pipes and ttings carefully to prevent contamination of surfaces.
• Apply an even coat of primer to the tting socket.
• Apply an even coat of primer to the pipe end to approximately 1/2" beyond the socket depth.
• Apply a second primer coat to the tting socket.
• While primer is still wet, apply an even coat of approved cement to the pipe equal to the depth of the tting socket.
• While primer is still wet, apply an even coat of approved cement to the tting socket.
• Apply a second coat of cement to the pipe.
• While the cement is still wet, insert the pipe into the tting, if possible twist the pipe a 1/4 turn as you insert it.
Note: If voids are present, sufcient cement was not applied and joint could be defective.
• Clear excess cement from the joint removing ring or beads as it will needlessly soften the pipe.
When a sidewall or vertical rooftop combustion air supply system is disconnected for any reason, the air inlet pipe must be resealed to ensure that combustion air will be free of contaminants and supplied in proper volume.
Failure to properly seal all joints and seams may result in ue gas recirculation, spillage of ue products and carbon monoxide emissions causing severe personal injury or death.
FIGURE 22. PVC/CPVC VENTING WITH ADAPTER
REQUIREMENTS FOR INSTALLATION IN CANADA
1. Installations must be made with a vent pipe system certied
to ULC-S636. IPEX is an approved vent manufacturer in Canada supplying vent material listed to ULC-S636.
2. The initial 3 feet of plastic vent pipe from the appliance ue
outlet must be readily accessible for visual inspection.
3. The components of the certied vent system must not be
interchanged with other vent systems or unlisted pipe/ ttings.
FIGURE 23. PVC/CPVC VENTING - HORIZONTAL
26
Page 27
FIGURE 24. PVC/CPVC VENTING - VERTICAL

VENTING SUPPORTS

Care must be taken in the installation of the venting system that adequate support is maintained throughout the installation process. When extending more than 10 feet (3.0 m) vertically, vertical support kits are required once every 10 feet (3.0 m) of vertical run. Vertical support is also re quired immedi ately after any transi tion (elbow, tee, etc.) to vertical of over 10 feet (3.0 m) of run and after any offset in the vertical run.
The support brackets (supplied in the Vertical Support Kit) are to be secure ly fastened to a solid vertical member of the building using the appropriate fasteners; i.e., wood screws for wood framing, machine or tapping screws for structural steel or masonry anchors for solid masonry. The bracket should be located so that it will not interfere with any joints of the venting system. The bottom most support bracket should be located directly above the rst transition from horizontal to vertical.
If a means of support for the brackets is not available and horizontal vent sections are present, install hanger straps (made from non-combustible material) as close to the points of transition as possible. If the horizontal portions of the vent and/or vent connector are longer than 6 feet (2.0 m), then install hanger straps every 6 feet (2.0 m) to support the connector.
Do not rivet or screw the straps to the conduit or other wise puncture the conduit wall. Instead, wrap an extra loop of strap around the conduit to hold it in position, or attach the strap to the center screw of the double wall AL 29-4C® vent coupling, if applica ble.
VERTICAL INSTALLATION REQUIREMENTS
1. The vent system must terminate at least 3 feet (1.0 m) and
no more than 6 feet (2.0 m) above the roof line and no closer than 10 feet (3.0 m) from any wall or verti cal structure. If the exhaust vent terminal is within 10 feet (3.0 m) of a wall or parapet, it must extend a minimum of 2 feet (610 mm) above the wall or parapet, see Figure 25 on Page 28 and Figure
28 on Page 29.
2. For direct vent installations, the total distance of the vent
system from the boiler vent connector to the vertical vent termination should not exceed 100 equivalent feet
(30.5 m). A maximum of three 90° elbows can be used. Minimum vertical vent is 7 equivalent feet (2.1 m) for direct vent installations. Standard minimum vertical vent length is 7 feet (2.1 m). See Figure 25, Figure 28 thru Figure 30 for differences between standard and direct vent installations.
3. An AL 29-4C® Vent Vertical Vent Terminal must be used at
the termina tion.
4. Maintain a minimum of 6 feet (2.0 m) separation between
the air intake and the exhaust terminals.
HORIZONTAL INSTALLATION REQUIREMENTS
1. The vent system must terminate with the Through-the-Wall
Termination (TWT) kits. Do not locate the terminal within 8 feet (2.5 m) of an inside corner of a building or adjacent to outside walls, shrubs or other such objects that may cause adverse wind conditions in the immediate area.
2. The TWT should be located not less than 12 inches (305
mm) above grade or, in geographical areas where snow accumulates, no less than 12 inches (305 mm) above antici­pated snow line. Ensure that TWT is protected against blockage which may occur during ice build up or snowstorms. The TWT should terminate at least 3 feet (1.0 m) above any forced air inlet within 10 feet (3.0 m), except when the forced air inlet is the combustion air intake of a direct vent appliance. The TWT should terminate at least 4 feet (1.2 m) below, 4 feet (1.2 m) horizontally from or 1 foot (305 mm) above any door, window or gravity air inlet into any building as provided in the current edition of the nation al fuel gas code ANSI Z223.1. In addition, a minimum clearance of 4 feet (1.2 m) horizontally from, and in no case above or below, unless the 4 feet (1.2 m) of horizontal distance is main tained from electric meters, gas meters, regulators and relief equip ment.
3. This horizontal exhaust vent system must pitch upward toward
the termination at 1/4 inch per foot (21 mm per meter).
4. The TWT is designed such that the building is protected from
degradation by ue gas and condensate. Howev er, if additional protection is desired, install against the wall a non-corrosive metal sheet under the TWT.
5. Due to the normal formation of water vapor in the combustion
process, horizon tal terminations must not be located over areas of pedestrian or vehicular trafc, (i.e., public walkways or over areas where condensate could create a nuisance or hazard). This is especially true in colder climates where ice buildup is likely to occur. A.O. Smith Corporation will not be held liable for any personal injury or property damage due to any dislodg ing of ice.
DIRECT VENT INSTALLATION REQUIREMENTS
The labels in the Direct Vent Kit must be afxed to the boiler in locations specied by the instruction sheet provided in the kit. The following are requirements for the Air-Intake Terminal (AIT):
1. The Air-Intake System (AIS) must ter minate with the venting
equipment pro vided with the boiler.
2. The AIT should not be located less than 3 feet (1.0 m) below
any exhaust vent within 10 feet (3.0 m).
3. The total horizontal distance of the AIS from the boiler’s
Blower Adapter to the outside of the “AIT” should not be greater than 100 equivalent feet (30.5 m) of vent pipe nor less than 3 feet (1.0 m), excluding elbows. A maximum of 3 elbows, equiva lent to 10 feet (3.0 m) each of pipe may be used.
27
Page 28
MODELS
(XB/XW)
1000 320884-000
1300 320884-001
1700 320884-001
2000 320884-001
2600 320884-001
3400 320884-002
VENT KIT NUMBERS
(RAIN CAP)
FIGURE 25. VERTICAL VENTING
MODELS
(XB/XW)
1000 321765-000
1300 321765-001
1700 321765-001
2000 321765-001
2600 321765-001
3400 321765-002
VENT KIT NUMBERS
(TEE)
FIGURE 26. HORIZONTAL VENTING
28
Page 29
MODELS
(XB/XW)
1000 321765-000 321764-000
1300 321765-001 321764-000
1700 321765-001 321764-001
2000 321765-001 321764-001
2600 321765-001 321764-001
3400 321765-002 321764-002
VENT
KIT NUMBERS
(TEE)
AIR INTAKE
KIT NUMBERS
(ELBOW)
FIGURE 27. DIRECT VENT HORIZONTAL
MODELS
(XB/XW)
1000 320884-000 321764-000
1300 320884-001 321764-000
1700 320884-001 321764-001
2000 320884-001 321764-001
2600 320884-001 321764-001
3400 320884-002 321764-002
VENT
KIT NUMBERS
(RAIN CAP)
AIR INTAKE
KIT NUMBERS
(ELBOW)
FIGURE 28. DIRECT VENT VERTICAL
29
Page 30
MODELS
(XB/XW)
1000 320884-000 321764-000
1300 320884-001 321764-000
1700 320884-001 321764-001
2000 320884-001 321764-001
2600 320884-001 321764-001
3400 320884-002 321764-002
VENT
KIT NUMBERS
(RAIN CAP)
FIGURE 29. DIRECT VENT, VERTICAL VENT HORIZONTAL INTAKE
AIR INTAKE
KIT NUMBERS
(ELBOW)
MODELS
(XB/XW)
1000 321765-000 321764-000
1300 321765-001 321764-000
1700 321765-001 321764-001
2000 321765-001 321764-001
2600 321765-001 321764-001
3400 321765-002 321764-002
VENT
KIT NUMBERS
(TEE)
FIGURE 30. DIRECT VENT, HORIZONTAL VENT VERTICAL INTAKE
AIR INTAKE
KIT NUMBERS
(ELBOW)
30
Page 31
TERMINATION CLEARANCES SIDEWALL POWER VENT
POWER VENT
EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION
D
E
v
(using room air for combustion)
G
V
A
H
L
B
v
C
FIX ED
V
CLOSED
OPERABLE
V
F
B
OPERABLE
V
B
B
B
V
FIX ED
CLOSED
X
V
J
A
M
X
V
K
B
VENT TERMINAL AIR SUPPLY INLETAREA WHERE TERMINAL IS NOT PERMITTED
V X
FIGURE 31. POWER VENT
Vent terminal clearances for “Power Vent” installations. Power Vent congurations use room air for combustion.
2
Clearance to each side of center line extended
H
above meter/regulator assembly
Clearance to service regulator vent outlet
I
CANADIAN INSTALLATIONS 1US INSTALLATIONS
3 feet (91 cm) within a height 15 feet (4.5 m) above the meter/ regulator assembly
3 feet (91 cm) 3 feet (91 cm)*
3 feet (91 cm) within a height 15 feet (4.5 m) above the meter/regulator assembly*
Clearance above grade, veranda, porch, deck or
A
balcony
Clearance to window or door that may be
B
opened
CANADIAN INSTALLATIONS 1US INSTALLATIONS
12 inches (30 cm) 12 inches (30 cm)
6 inches (15 cm) for appliances up to 10,000 Btu/hr (3 kW), 12 inches (30 cm) for appliances between 10,000 Btu/hr (3 kW) and 100,000 Btu/hr (30 kW), 36 inches (91 cm) for appliances above 100,000 Btu/hr (30 kW)
4 feet (1.2 m) below or to side of opening; 1 foot (30 cm) above
opening
2
6 inches (15 cm) for appliances up to 10,000 Btu/hr (3 kW), 12 inches (30 cm) for appliances between 10,000 Btu/hr (3 kW) and 100,000 Btu/hr (30kW), 36 inches (91cm) for appliances above 100,000 Btu/ hr (30 kW)
6 feet (1.83 m)
7 feet (2.13 m)†
12 inches (30 cm) ‡ 12 inches (30 cm) ‡
4 feet (1.2 m) below or to side of opening; 1 foot (30 cm) above opening.
3 feet (91 cm) above if
within
10 feet (3 m) horizontally
7 feet (2.13 m)
Clearance to permanently closed
C
window
Vertical clearance to ventilated soft located above the terminal within a horizontal
D
distance of 2 feet (61 cm) from the center line of the terminal
Clearance to
E
unventilated soft
Clearance to outside
F
corner
Clearance to inside
G
corner
12 inches (30 cm)* 12 inches (30 cm)*
12 inches (30 cm)* 12 inches (30 cm)*
12 inches (30 cm)* 12 inches (30 cm)*
2 feet (60 cm)* 2 feet (60 cm)*
8 feet (2.44 m)* 8 feet (2.44 m)*
Clearance to a non mechanical air supply inlet into building or
J
combustion air inlet to any other appliance
Clearance to a mechanical air supply
K
inlet
Clearance above paved sidewalk or paved
L
driveway located on public property
Clearance under veranda, porch, deck, or
M
balcony
1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.
31
Page 32
TERMINATION CLEARANCES SIDEWALL DIRECT VENT
(using outdoor air for combustion)
G
V
A
C
FIX ED
V
CLOSED
OPERABLE
V
F
B
V
B
B
B
OPERABLE
V
A
B
FIX ED CLOSED
J
H
V
M
X
X
V
K
D
E
v
L
B
v
VENT TERMINAL AIR SUPPLY INLETAREA WHERE TERMINAL IS NOT PERMITTED
V X
EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION
FIGURE 32. DIRECT VENT
Vent terminal clearances for “Direct Vent” installations. Direct Vent congurations use outdoor air for combustion.
DIRECT VENT
CANADIAN INSTALLATIONS 1US INSTALLATIONS
2
CANADIAN INSTALLATIONS
1
US INSTALLATIONS
2
Clearance above grade, veranda, porch, deck or
A
balcony
Clearance to window or
B
door that may be opened
Clearance to permanently closed
C
window
Vertical clearance to ventilated soft located above the terminal within
D
a horizontal distance of 2 feet (61 cm) from the center line of the terminal
Clearance to unventilated
E
soft
Clearance to outside
F
corner
Clearance to inside
G
corner
12 inches (30 cm) 12 inches (30 cm)
6 inches (15 cm)
6 inches (15 cm) for appliances up to 10,000 Btu/hr (3 kW), 12 inches (30 cm) for appliances between 10,000 Btu/hr (3 kW) and 100,000 Btu/hr (30 kW), 36 inches (91 cm) for appliances above 100,000 Btu/hr (30 kW)
6 inches (15 cm)* 6 inches (15 cm)*
12 inches (30 cm)* 12 inches (30 cm)*
12 inches (30 cm)* 12 inches (30 cm)*
2 feet (60 cm)* 2 feet (60 cm)*
8 feet (2.44 m)* 8 feet (2.44 m)*
for appliances up to 10,000 Btu/hr (3 kW), 9 inches (23 cm) for appliances between 10,000 Btu/hr (3 kW) and 50,000 Btu/hr (15 kW), 12 inches (30 cm) for appliances above 50,000 Btu/hr (15 kW)
Clearance to each side of center line extended
H
above meter/regulator assembly
Clearance to service
I
regulator vent outlet
Clearance to a non mechanical air supply inlet into building or
J
combustion air inlet to any other appliance
Clearance to a mechanical air supply
K
inlet
Clearance above paved sidewalk or
L
paved driveway located on public property
Clearance under veranda, porch, deck,
M
or balcony
3 feet (91 cm) within a height 15 feet (4.5 m) above the meter/ regulator assembly
3 feet (91 cm) 3 feet (91 cm)*
6 inches (15 cm) for appliances up to 10,000 Btu/hr (3 kW), 12 inches (30 cm) for appliances between 10,000 Btu/hr (3 kW) and 100,000 Btu/hr (30 kW), 36 inches (91 cm) for appliances above 100,000 Btu/ hr (30 kW)
6 feet (1.83 m)
7 feet (2.13 m)† 7 feet (2.13 m)†*
12 inches (30 cm) ‡ 12 inches (30 cm) ‡*
3 feet (91 cm) within a height 15 feet (4.5 m) above the meter/regulator assembly*
6 inches (15 cm) for appliances up to 10,000 Btu/hr (3 kW), 9 inches (23 cm) for appliances between 10,000 Btu/hr (3 kW) and 50,000 Btu/hr (15 kW), 12 inches (30 cm) for appliances above 50,000 Btu/hr (15 kW)
3 feet (91 cm) above if within 10 feet (3 m) horizontally
1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.
32
Page 33
INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above nished grade in the area of the venting, including but not limited to decks and porches, the following requirements should be satised:
INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gastter should observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the oor level where the gas equipment is to be installed. In addition, the installing plumber or gastter should observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the sidewall horizontal vented gas fueled equipment. It should be the responsibility of the property owner to secure the services of qualied licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent oor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner should have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm should be installed.
APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance with the above provisions should comply with NFPA 720 and be ANSI/UL 2034 listed and CSA certied.
SIGNAGE A metal or plastic identication plate should be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign should read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment should not approve
the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building, or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system should include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the ue gases, but identies “special venting systems,” the following requirements should be satised by the manufacturer:
1. The referenced “special venting system” instructions should be included with the appliance or equipment installation instructions; and
2. The “special venting systems” should be Product Approved by the Board, and the instructions for that system should include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions should remain with the appliance or equipment at the completion of the installation.
33
Page 34
DIRECT VENT: HORIZONTAL TERMINATION
Gas vent extending through an exterior wall must not terminate adjacent to a wall or below building extensions such as eaves, parapets, balconies, or decks. Failure to comply could result in severe personal injury, death, or substantial property damage.
Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 for Canadian installations.
VENT/AIR TERMINATION LOCATIONS:
Follow these guidelines for locating the vent/air terminations:
1. Make sure the total length of piping for vent or air do not
exceed the limits mentioned in Table 14 and Table 15 on
Page 36.
2. Consider the surroundings when terminating the vent and
air:
• While positioning the vent termination, ensure vapors will not damage nearby shrubs, plants or air conditioning equipment.
• The ue products will form a noticeable plume as they condense in cold air. Avoid areas where the plume could obstruct window views.
• Prevailing winds could cause freezing of condensate and water/ice buildup where ue products impinge on building surfaces or plants.
• Do not allow accidental contact of ue products with people or pets.
• Do not locate the terminations near building corners, near adjacent buildings or surfaces, window wells, stairwells, alcoves, courtyards, or other recessed areas, where wind eddies could affect performance or cause recirculation .
• Sidewall vent and air inlet terminations must terminate in the same pressure zone.
• Do not terminate above any door or window, where condensate can freeze, causing ice formations.
• Locate or monitor the vent to prevent condensate damage to exterior nishes.
3. The air piping must terminate in a down-turned elbow, using
a mesh screen. This setup will avoid recirculation of ue products into the combustion air stream. See Figure 33.
4. The vent piping must terminate with a Tee pointed upwards
and away from the air inlet. See Figure 33.
5. Maintain clearances as shown in Figure 33 and Figure 34.
Vent must terminate:
• At least 6 feet (1.8 m) from adjacent walls.
• No closer than 12 inches (305 mm) below roof overhang.
• At least 7 feet (2.1 m) above any public walkway.
• At least 3 feet (0.9 m) above any forced air intake within 10 feet (3 m).
• No closer than 12 inches (305 mm) below or horizontally from any door or window or any other gravity air inlet.
Air inlet must terminate at least 12 inches (305 m) above grade or snow line; at least 12 inches (305 mm) below the vent termination; and the vent pipe must not extend more than 24 inches (610 mm) vertically outside the building as shown in Figure 33 and Figure
34.
Do not terminate closer than 4 feet (1.2 m) horizontally from any electric meter, gas meter, regulator, relief valve, or other equipment. Never terminate above or below any of these within 4 feet (1.2 m) horizontally.
6. Locate terminations so they are not likely to be damaged by
foreign objects, such as stones or balls, or subject to buildup of leaves or sediment.
FIGURE 33. AIR/VENT TERMINATION - HORIZONTAL
FIGURE 34. HORIZONTAL CLEARANCES - AIR/VENT
TERMINATION
34
Page 35
DIRECT VENTING: VERTICAL TERMINATION
Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 for Canadian installations.
VENT/AIR TERMINATION LOCATIONS:
Follow these guidelines for locating the vent/air terminations:
1. Make sure the total length of piping for vent or air do not
exceed the limits mentioned in Table 14 and Table 15 on
Page 36.
2. The vent must terminate at least 3 feet above the highest
place in which the vent penetrates the roof and at least 2 feet above any part of a building within 10 feet horizontal.
3. The air piping must terminate in a down-turned 180° elbow,
using a mesh screen, no further than 2 feet (0.6 m) from the center of the vent pipe. This placement avoids recirculation of ue products into the combustion air stream.
4. The vent piping must terminate in an up-turned rain cap as
shown in Figure 35. When the vent termination uses a rain cap as illustrated in Figure 35, maintain at least 36" (914 mm) above the air inlet. The air inlet pipe and vent pipe can be located in any desired position on the roof, but must always be no further than 2 feet (0.6 m) apart and with the vent termination at least 1 foot above the air intake.
5. Locate terminations so they are not likely to be damaged by
foreign objects, such as stones or balls, or subject to buildup of leaves or sediment and also not blocked or restricted by snow accumulation.
6. If installing both intake air and vent piping in a Direct Vent
conguration vertically through the roof; ensure that all exterior vertical clearance requirements shown in Figure 35 are being maintained. These clearances and those cited by local and national codes must be maintained.
Note: On at roof installations the intake air and the vent terminations must be a minimum of 24 inches (60 cm) above any parapet, vertical wall or structure within 10 feet (3 m) horizontally. See Figure 37.
FIGURE 36. STAINLESS STEEL AIR/VENT TERMINATION -
VERTICAL
FIGURE 37. VERTICAL TERMINATION - FLAT ROOF
CLEARANCES
FIGURE 35. PVC/CPVC AIR/VENT TERMINATION -
VERTICAL
PREPARE ROOF/WALL PENETRATIONS
1. Air pipe penetration:
Cut a hole for the air pipe. Size the air pipe hole as close as desired to the air pipe outside diameter.
2. Vent pipe penetration:
Cut a hole for the vent pipe. For either combustible or noncombustible construction, size the vent pipe hole with at least a 1/2 inch clearance around the vent pipe outer diameter:
• 7½ inch (178 mm) hole for 6 inch (152 mm) vent pipe
• 8½ inch (203 mm) hole for 7 inch (178 mm) vent pipe
Insert a galvanized metal thimble in the vent pipe hole (when required by local codes).
3. Space the air and vent holes to provide the minimum spacing
shown in Figure 35 and Figure 36.
4. Follow all local codes for isolation of vent pipe when passing
through oors, ceilings, and roofs.
5. Provide ashing and sealing boots sized for the vent pipe
and air pipe.
35
Page 36
TABLE 13. PVC, VENT PIPE, AND FITTINGS
ALL VENT PIPE MATERIALS AND FITTINGS MUST COMPLY WITH THE FOLLOWING:
ITEM MATERIAL STANDARDS FOR INSTALLATION IN:
UNITED STATES CANADA
Vent pipe and ttings PVC schedule 40 ANSI/ASTM D1785 CPVC and PVC venting must be ULC-S636 Certied.
CPVC schedule 40/80 ANSI/ASTM F441
Pipe cement/primer PVC ANSI/ASTM D2564 ULC-S636 Certied.
CPVC ANSI/ASTM F493
NOTICE: DO NOT USE CELLULAR (FOAM) CORE PIPE
TABLE 14. DIRECT VENT ALLOWABLE AIR/VENT LENGTHS
MODEL AIR INTAKE
DIAMETER
(INCH)
XP 1000 6 12 100 6 12 100
XP 1300 6 12 100 8 12 100
XP 1700 8 12 100 8 12 100
XP 2000 8 12 100 8 12 100
XP 2600 8 12 100 8 12 100
XP 3400 10 12 100 10 12 100
When determining equivalent combustion air and vent length, add 5 feet (1.5 m) for each 90° elbow and 3 feet (0.9 m) for each 45° elbow.
EXAMPLE: 20 feet (6 m) of PVC pipe + (4) 90° elbows + (3) 45° elbows = 49 equivalent feet (15 m) of piping.
MODEL VENT DIAMETER
XP 1000 6 12 100
XP 1300 8 12 100
XP 1700 8 12 100
XP 2000 8 12 100
XP 2600 8 12 100
XP 3400 10 12 100
AIR INTAKE
MIN. LENGTH
(FT)
TABLE 15. ROOM AIR ALLOWABLE VENT LENGTHS
AIR INTAKE
MAX. LENGTH
(FT)
VENT
DIAMETER
(INCH)
VENT MIN. LENGTH
(INCH)
(FT)
VENT MIN.
LENGTH
(FT)
VENT MAX. LENGTH
VENT MAX.
LENGTH
(FT)
(FT)
36
Page 37

CONDENSATE DISPOSAL

FIGURE 38. CONDENSATE DISPOSAL SYSTEM
CONDENSATE NEUTRALIZER
FIGURE 40. CONDENSATE NEUTRALIZER
The condensate drains from the boiler have pH levels between
4.3 and 5.0. The pH measurement of a uid is an indicator of the acidity or alkalinity. Neutral uids have pH of 7.0. Acid uids have pH below 7. Some local codes may require the use of a condensate neutralizer to raise the pH level of the condensate leaving the boiler. The condensate neutralizer be must installed between the boiler and the drain and must be installed lower than the outlet of the condensate trap as shown in Figure 38. The Condensate Neutralizer Kit model must be selected with respect to the boiler's output as mentioned in the Table 16.
TABLE 16. CONDENSATE NEUTRALIZER KIT MODELS
FIGURE 39. CONDENSATE TRAP
CONDENSATE TRAP
Installation of the Condensate Trap must conform with the instructions in this manual and local building codes. Condensate Neutralizer Kits are available. Contact your distributor or Service Agency. Do not remove, modify or alter the factory installed condensate trap. Install a commercially available neutralizing kit if required by the local codes.
The boiler is factory tted with a 24V condensate trap connected to the controller. For safety reasons, if the condensate drain is blocked, the control system will turn off all the ring burners and bring the boiler to a safe shut down. If there is an air blockage in the line, vent out the air by removing the cap. Cap acts as an air vent for releasing any air block on down stream condensate line. Flexible silicon hose connect from the trap through the Condensate Neutralizer to the drain.
Due to the highly efcient operation of this unit, condensate is formed during operation and must be removed by the conden­sate drain systems. Inspect the condensate drains and tubes at least once a month and insure they will allow the free ow of condensate at all times. The system must be inspected more frequently in cold weather if the drain system is located in an area, such as along the oor, where freezing tempera tures are likely to occur. The conden sate drain system must be protected against freezing. Contact a qualied service agent to inspect and correct the condition if freezing of the conden sate lines is a problem.
XP MODELS AO SMITH CONDENSATE
NEUTRALIZER KIT NUMBERS
XP 1000 9007961005
XP 1300 9007962005
XP 1700 9007962005
XP 2000 9007962005
XP 2600 9007963005
XP 3400 9007963005
37
Page 38

GAS SUPPLY CONNECTIONS

GAS SUPPLY PIPE CONNECTIONS
FIGURE 41. GAS SUPPLY PIPING
1. Make sure to install ground joint union for servicing.
In Canada – When using manual main shutoff to support the weight of the piping with valves, ensure that it is identied by the installer.
2. Install drip leg (sediment trap) per NFPA 54 for US and CAN
B149.1 for Canada.
3. Support the piping with hangers, not by the boiler or its
accessories. The gas valve and blower will not support the weight of the piping. Failure to comply could result in severe personal injury, death, or substantial property damage.
4. Purge all air from the gas supply piping.
5. Before setting the boiler in operation, check the boiler and its
gas connection for leaks.
• Disconnect the boiler from the gas supply piping system during any pressure testing, at a test pressure in excess of 1/2 PSIG (3.5 kPa)
• The boiler must be isolated from the gas supply piping system by closing a manual shutoff valve during any pressure testing, at test pressures equal to or less than 1/2 PSIG (3.5 kPa).
Do not check for gas leaks with an open ame, instead use the bubble test. Failure to use the bubble test or check for gas leaks can cause severe personal injury, death, or substantial property damage.
6. Use pipe sealing compound compatible with propane gases.
Apply sparingly only to male threads of the pipe joints so that pipe dope does not block gas ow.
Failure to apply pipe sealing compound as detailed in this manual can result in severe personal injury, death, or substantial property damage.
7. Make sure the maximum inlet gas pressure do not exceed
the value specied. Minimum value specied is for input adjustment only.
Make sure to use two wrenches when tightening gas piping at the boiler, using one wrench to prevent the boiler gas line connection from turning. Failure to support the boiler gas connection pipe to prevent it from turning could damage gas line components. Do not use wrench on valve body as damage would occur.
GAS PRESSURE REQUIREMENTS
The maximum allowable gas supply pressure for this boiler is 14 inches w.c. (3.5 kPa). Install a positive lock-up gas pressure regulator in the gas supply line if inlet gas pressure can exceed 14 inches w.c. (3.5 kPa) at any time.
If a positive lock-up regulator is required follow these instructions:
1. Positive lock-up gas pressure regulators must be rated at or
above the input Btu/hr rating of the boiler they supply.
2. Positive lock-up gas pressure regulator(s) should be
installed no closer than 3 feet (1 meter) and no farther than 8 feet (2.4 meters) from the boiler’s inlet gas connection.
3. After installing the positive lock-up gas pressure regulator(s),
an initial nominal supply pressure setting of 7 inches w.c. (1.7 kPa) while the boiler is operating is recommended and will generally provide good boiler operation. Some addition adjustment maybe required later to maintain a steady gas supply pressure.
4. When installing multiple boilers in the same gas supply
system it is recommended that individual positive lock-up gas pressure regulators be installed at each unit.
38
Page 39
PIPE SIZES FOR PROPANE GAS
Make sure to contact the gas supplier for pipe sizes, tanks, and 100% lockup gas pressure regulator.
PURGING GAS LINE
Gas line purging is required with new piping or systems in which air has entered. Gas purging should be performed per NFPA 54 for US and CAN B149.1 for Canada.
CHECK GAS SUPPLY INLET PRESSURE
CSA or UL listed exible gas connections are acceptable, but make sure that the line has adequate capacity to allow your boiler to re at full rate. Consult with local codes for proper installation or service procedures.
Do not adjust or attempt to measure gas valve outlet pressure. Attempting to alter or measure the gas valve outlet pressure could result in damage to the valve, causing potential severe personal injury, death, or substantial property damage.
Make sure the gas piping are sized for the proper ow and length of pipe, to avoid excessive pressure drop. The gas meter and the gas regulator must be properly sized for the total gas load.
Perform the below steps when checking inlet gas supply:
1. Turn the main power switch to the “OFF” position.
2. Shut off gas supply.
3. Remove the 1/8" pipe plug on the main gas shutoff valve
and install a suitable 1/8" tting (eld supplied) for the manometer tubing. Place the tubing of the manometer over the tap once the 1/8" tting is installed.
4. Slowly turn on the gas supply.
5. Ensure inlet pressure is within specied range.
6. If the gas pressure is out of range, contact the gas utility, gas
supplier, qualied installer or service agency to determine the necessary steps to provide proper gas pressure to the control.
CHECK FOR GAS LEAKS
Before operating the boiler, make sure to check the oor near and around the boiler for gas odorant or any unusual odor. Remove the top access panel and check for odor in the interior of the boiler enclosure. Do not start the boiler if there is any indication of a gas leak. Use an approved leak detection solution and repair any leaks at once.
In the case of propane boilers, the supplier mixes an odorant with the propane to make its presence detectable. But in some instances, the odorant can fade, and the gas may no longer have an odor. Before operating the boiler, make sure the propane supplier verify the correct odorant level in the gas.
Do not adjust or attempt to measure gas valve outlet pressure. The gas valve is factory set for the correct outlet pressure. This setting is suitable for natural gas and propane, requiring no eld adjustment. Attempting to alter or measure the gas valve outlet pressure could result in damage to the valve, causing potential severe personal injury, death, or substantial property damage.
39
Page 40

BOILER START UP AND OPERATIONS

IMPORTANT
Only an A.O. Smith Certied Start-up agent must perform the initial ring of the boiler. At this time the user should not hesitate to ask the start-up agent any questions regarding the operation and maintenance of the unit. If you still have questions, please contact the factory or your local A.O. Smith representative. Contact Technical Support noted on the back cover for the name of your closest Certied Start-Up agent.
Lighting and Operating instructions are included with this manual. By using these instructions, the user may be able to make minor operational adjustments and save unnecessary service calls. However the user should not attempt repairs, but should contact a service technician or gas supplier.
GENERAL
Never operate the boiler without rst making sure the boiler and system are lled with water, in addition:
• Make sure a temperature and pressure relief valve is installed in the storage tank for hot water supply installations.
• Make sure that the boiler and system have been purged of air and checked for leaks.
Also ensure to check the gas piping for leaks before beginning the initial ring of the boiler.
FIGURE 42. GAS TRAIN ASSEMBLY
MANIFOLD PRESSURE CONNECTIONS
Take the manifold pressure, refer to Table 2, by removing the pipe plug and inserting a suitable 1/8” NPT hose barb for connection to the manometer/pressure gauge. Upon completion of measurements and adjustments, remove the hose barb and replace the pipe plug. Check for gas leaks and insure all connections are gas tight, see Figure 42.
FILLING AND PURGING OF HEATING BOILER INSTALLATION
1. Fast ll system through bypass until pressure approaches desired system pressure. Close bypass valve and permit pressure to be established by the pressure reducing valve.
2. Vent all high points in system to purge system of air.
Provisions should be made to permit manual venting of radiators or convectors.
FILLING HOT WATER SUPPLY BOILER INSTALLATION
1. Close the system’s drain valve by turning handle clockwise.
2. Open a nearby hot water faucet to permit the air to escape
3. Fully open the cold water inlet pipe valve allowing the boiler
and piping to be lled.
4. Close the hot water faucet as water starts to ow.
PURGING GAS LINE
Gas line purging is required with new piping or systems in which air has entered.
INLET GAS PRESSURE
The inlet gas pressure is measured by removing the 1/8” NPT Plug located on the upstream side of the supply gas valve, and insert a 1/8” NPT hose barb tting to be connected to a manometer or pressure gauge. Once pressure has been checked and/or adjusted, replace the plug and check for leaks. The maximum value specied in Table 2 on Page 6 must not be exceeded. The minimum values, shown in Table 2, must be maintained under both load and no load conditions (static and ring conditions). The combination gas valves supplied with the boiler are for low pressure service. If upstream pressure exceeds 14.0” W.C., an intermediate gas pressure regulator of the lockup type must be installed.
WATER TEMPERATURE REGULATION
40
Page 41
HOT WATER CAN SCALD: Boilers are intended to produce hot water. Water heated to a temperature which will satisfy space heating, clothes washing, dish washing and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the inrm or physically/mentally disabled. If anyone using hot water in your home ts into one of theses groups or if there is a local code or state law requiring a specic temperature water at the hot water tap, then you must take special precautions. In addition to using the lowest possible temperature setting that satises your hot water needs, a means such as a mixing valve should be used at the hot water taps used by these people or at the hot water supply tank. Mixing valves are available at plumbing supply or hardware stores. Follow the manufacturer’s instructions for installation of the valves. Before changing the thermostat setting on the hot water system controller, refer to Table 17.
Hot water temperatures required for automatic dishwasher and laundry use can cause scald burns resulting in serious personal injury and/or death. The temperature at which injury occurs varies with the person’s age and time of exposure. The slower response time of children, aged or disabled persons increases the hazards to them. Never allow small children to use a hot water tap, or to draw their own bath water. Never leave a child or disabled person unattended in a bathtub
or shower.
The boiler should be located in an area that is inaccessible to the general public.
TABLE 17. RISK OF SCALDS
Water Temperature
180°F (82°C) Nearly instantaneous 170°F (77°C) Nearly instantaneous 160°F (71°C) About 1/2 second 150°F (66°C) About 1-1/2 seconds 140°F (60°C) Less than 5 seconds 130°F (54°C) About 30 seconds 120°F (49°C) More than 5 minutes
Time to Produce 2nd & 3rd
Should overheating occur or the gas supply fail to shut off, turn off the main manual gas shutoff valve to the boiler.
CHECK/CONTROL WATER HARDNESS
XW Model XP Boilers are approved for use in Domestic Water Heating Systems with a water supply hardness of 0 grains per gallon to a maximim of 12 grains per gallon. Refer to Table 18 for recommend ow rate to maintain scale free operation with up to a medium water hardness. For scale free operation in hard water systems with a water hardness greater than 12 grains per gallon, a water softener must be installed and maintained.
TABLE 18.
WATER HARDNESS MEDIUM (0-12 GRAINS PER GALLON)
XW MODEL
∆T ºF GPM ∆P FEET
NO.
1000 25 76 17.5
1300 25 99 22
1700 25 129 23
2000 25 152 17.5
2600 25 198 22
3400 25 258 23
∆T ºF = Temperature rise ºF at the specied GPM. GPM = Flow rate in gallons per minute. ∆P = Pressure loss through the heat exchanger in feet of head. For systems over 5 grains per gallon; and for scale free operation, boiler setpoint should not exceed 140 ºF.
Note: The factory installed/supplied pump on the above listed model boilers is sized to maintian a 25 ºF ∆T through the boiler when the boiler is ring at 100% re.
In addtion to the pressure loss through the heat exchanger, the factory supplied pump is sized for an additional 50 feet of equivalent feet of piping between the boiler and a storage tank. All piping between the boiler and the storage tank must be of a pipe size equal to the inlet/outlets of the boiler. Installation differences may slightly change these parameters.
FREEZE PROTECTION (HYDRONIC HEATING INSTALLATION)
1. Determine freeze protection uid quantity using system
water content, following uid manufacturer’s instructions.
2. Local codes may require a backow preventer or actual
disconnect from city water supply.
3. When using freeze protection uid with automatic ll, install
a water meter to monitor water makeup. Freeze protection uid may leak before the water begins to leak, causing concentration to drop, reducing the freeze protection level.
INSPECT/FILL CONDENSATE SYSTEM
Inspect/check condensate lines and ttings:
1. Inspect the condensate drain line, condensate PVC ttings
and condensate trap.
Fill condensate trap with water:
1. Remove the 2 inch PVC cap with the switch located at the top of the trap.
2. Fill with fresh water until the water begins to pour out of the
drain.
3. Replace the cap. Press the cap onto the trap until the cap makes contact with the drain.
The condensate trap must be lled with water during all times of boiler operation to avoid ue gas emission from the condensate drain line. Failure to ll the trap could result in severe personal injury or death.
41
Page 42

LIGHTING AND OPERATING INSTRUCTIONS

42
Page 43
ADJUSTMENT
There must be sufcient load to operate the boiler at high re to perform the following adjustments. Start the boiler and observe proper operating parameters for the system.
Required Tools:
• TORX® T40 or 5 mm hex wrench
• 3 mm or 7/64 inch hex wrench
• Combustion analyzer
These boilers are equipped with a combined gas/air control and gas safety shut off control valves. The valve functions in parallel with the variable speed combustion blower to supply the correct gas air ratio for optimum performance and efciency. The combustion blower speed is controlled automatically and determines the amount of negative pressure experienced by the gas safety shut off/control valves. The gas/air regulator adjusts gas ow to maintain the proper pressure at the outlet nozzle of the associated valve.
SETTING OF THE TEST MODE
FIGURE 44. BURNER INFORMATION SCREEN
Click on Operation button, and under the Modulation Menu, set the required Firing rate (High/Low) by setting the RPM.
On the Burner Home screen, select any individual boiler which will guide to Burner Information screen.
FIGURE 43. BURNER HOME SCREEN
FIGURE 45. OPERATION SCREEN
On the Firing Rate page, set the Firing rate RPM by selecting the Manual in Run check box.
43
FIGURE 46. FIRING RATE PAGE
Page 44
HIGH FIRING RATE SETTING
Set the boiler to the high ring rate by setting the High Firing Rate RPM as described below. Check combustion readings using a combustion analyzer. If combustion readings are not in accordance with the chart below adjust the gas valve as follows: remove the at, round, blue plastic cap from the cover. Using a 3 mm (7/64”) hex wrench, turn the adjustment screw counterclockwise to increase or clockwise to decrease gas ow and achieve the desired CO2 level. Refer to the Table 19 for correct settings. There will be a slight time delay between the adjustment and the response of the CO2 measuring instrument. Adjust the settings in small increments and allow the combustion readings to stabilize before readjusting. When desired adjustments are complete, reinstall the blue plastic cap on the cover. Combustion samples should be taken in the stack within two feet of the boiler. The carbon monoxide (CO) values in the combustion sample should not exceed 150 PPM under any circumstances. Contact OEM for any abnormal conditions leading to excessive CO above 150 PPM.
TABLE 19. HIGH FIRE RATE
MODELS (XB/XW)
RPM
(APPROXIMATE FACTORY SET)
NATURAL
PROPANE NATURAL
GAS
GAS
CO
2
*MANIFOLD PRESSURE
INCHES W.C
PROPANE NATURAL GAS PROPANE
1000 (920,000) 4450 4750 8.5 - 9.2% 9.3 - 10.2% -3.5 -4.7
1300 4850 5100 8.5 - 9.2% 9.3 - 10.2% -3.0 -3.6
1700 5700 5700 8.5 - 9.2% 9.3 - 10.2% -3.6 -4.4
2000 4700 4750 8.5 - 9.2% 9.3 - 10.2% -3.9 -4.9
2600 5700 5100 8.5 - 9.2% 9.3 - 10.2% -3.3 -3.6
3400 5700 5700 8.5 - 9.2% 9.3 - 10.2% -3.5 -4.4
LOW FIRING RATE SETTING
Set the boiler to the low ring rate by setting the Low Firing Rate RPM as described below. Check combustion readings using a combustion analyzer. If combustion readings are not in accordance with the chart shown below adjust as follows: remove the cap on the gas regulator using a slotted screwdriver. This will expose the offset adjustment screw. Using a TORX® T40 or a 5 mm hex wrench, carefully adjust the low re gas setting to achieve the CO2 level prescribed in Table 20.
Note: The rotation of the Low Fire adjustment is opposite of the High Fire as follows: Clockwise rotation increases gas ow, counterclockwise rotation decreases gas ow.
Adjustments to the offset pressure regulators should not exceed 1/4 turn at a time before allowing the readings to respond and stabilize.
After proper low re offset adjustment is made, reinstall the slotted cap on the regulator.
Following all gas valve adjustments, check for proper light-off and verify correct fuel/air mix and combustion quality throughout the entire ring range (from lowest to highest fan speed).
Note: Make sure the Manual Mode is set back to Automatic Mode to each of the burners, once the required settings are done. Turn off the individual burner before proceeding to the next burner settings.
TABLE 20. LOW FIRE RATE
MODELS (XB/XW)
RPM
(APPROXIMATE FACTORY SET)
NATURAL
PROPANE NATURAL
GAS
GAS
CO
2
*MANIFOLD PRESSURE
INCHES W.C
PROPANE NATURAL GAS PROPANE
1000 (920,000) 1650 1540 7.3 - 8.2% 8.4 - 8.8% -0.3 -0.25
1300 1650 1600 7.3 - 8.2% 8.4 - 8.8% -0.2 -0.14
1700 1700 1700 7.3 - 8.2% 8.4 - 8.8% -0.2 -0.23
2000 1550 1540 7.3 - 8.2% 8.4 - 8.8% -0.3 -0.31
2600 1700 1600 7.3 - 8.2% 8.4 - 8.8% -0.2 -0.14
3400 1700 1700 7.3 - 8.2% 8.4 - 8.8% -0.2 -0.23
* NOTE: Values listed in Table 19 and Table 20 are tested under laboratory conditions with minimum vent length. Values may slightly vary depending on
ambient conditions and eld equipment accuracy.
44
Page 45

CONTROL SYSTEM

BURNER CONTROL SYSTEM

FIGURE 47. R7910A1138 CONTROL SYSTEM
The R7910A1138 is a burner control system that provide heat control, ame supervision, circulation pump control, fan control, boiler control sequencing, and electric ignition function. It will also provide boiler status and error reporting. Multiple boilers can be joined together to heat a system instead of a single, larger burner or boiler. Using boilers in parallel is more efcient, costs less, reduces emissions, improves load control, and is more exible than the traditional large boiler. Control System consists of:
• R7910A1138 Control Device.
• S7999B Touchscreen Display—required for setup and ModBus communication but not required for the system to operate once the R7910A1138 is programmed.
• S7910A Local Keyboard Display Module.
• Flame Rod .
• Temperature Sensor, NTC Type 10KΩ at 77°F (25°C) or 12KΩ at 77°F (25°C).
• Limit Sensor, NTC Type 10KΩ at 77°F (25°C).
• 24V Digital I/O.
3. Three Pump Outputs with 5 selectable operation modes.
4. 24VAC:
• Output control of gas valve (Pilot and Main) and External Ignition Transformer.
• Digital inputs for room limit control, high limit control, Gas pressure switch, low water cutoff.
5. External spark transformer.
6. Flame Sensor.
7. Test jacks for ame signal measurement from either a ame
rod or UV ame sensor.
8. Alarm Output.
FIGURE 48. GENERAL R7910A1138 BOILER SCHEMATIC
The above gure shows two loops of heat control: Central Heating (CH), and an optional second loop for Domestic Hot Water (DHW) can be congured on each R7910A. The DHW loop transfers heat from the boiler outlet to hot water appliances in conjunction with the primary system heat loop. Priority assignment to each heat loop can be congured to specify which loop gets serviced rst.
OVERVIEW
Functions provided by the R7910A1138 include automatic boiler sequencing, ame supervision, system status indication, ring rate control, load control, CH/DHW control, limit control, system or self-diagnostics and troubleshooting. The R7910 maximum version of the controller offers:
1. NTC-temperature sensor for:
• Outlet Limit And Temperature.
• Stack Temperature Limit and Temperature.
• Inlet Temperature.
• Outdoor Temperature (R7910 only).
2. Modulating output PWM-driven rotation speed controlled
DC-fan for optimal modulation control.
45
Page 46
COMMUNICATIONS AND DISPLAYS
Two modes of communications are available to the R7910.
1. The R7910 has two RS485 communication ports for
ModBus that allows for interfacing to one or all R7910s of a system and presents them individually to the user. The S7999B System Operator interface is a color touchscreen displays used for conguration and monitoring of the R7910A. Control Operation and display status in both test and graphical modes can be shown along with the ability to setup. The R7910 can also be remotely reset through the S7999B display.
2. Either ModBus RS485 communication port can be used to
allow conguration and status data to be read and written to the R7910. Support a Master S7999B or a Building Automation master to control the R7910 to respond to a single ModBus address to service the requests of the ModBus master in a Lead/Lag arrangement.
The local S7910 Keyboard display, the S7999B System Operator interface, and the S7999C Local Operator Interface are optional components.
The S7999B (or the DSP3944 which is a portable S7999B) or is required conguration of the parameters of the R7910 but is not needed for the operation of the system once congured.
SPECIFICATIONS
1. Electrical Ratings: Operating voltage
• 24VAC (20 to 30 VAC, 60 Hz ±5%)
• 30 amps (Single Heat Exchanger)
• 60 amps (Double Heat Exchanger)
Connected Load for Valve and annunciator functions:
• 24VAC, 60Hz
• 120VAC (+10%/-15%), 60Hz (±5%)
• Model Specic
2. Corrosion:
• R7910A must not be used in a corrosive environment.
3. Operating Temperature: -4°F to 150°F (-20°C to 66°C)
4. Storage/Shipping Temperature: -40°F to 150°F (-40°C to
66°C).
5. Humidity:
• Up to 95% Relative Humidity, noncondensing at 104°F for 14 days. Condensing moisture may cause safety shutdown.
6. Vibration: 0.0 to 0.5g Continuous (V2 level)
7. Enclosure: Nema 1/IP40.
8. Approvals:
Underwriters Laboratories, Inc. (UL): Component Recognized: File No. MP268 (MCCZ)
• R7910 is certied as UL372 Primary Safety Controls.
• The R7910 is certied as UL353 Limit Rated device when using part number 50001464 dual element limit rated NTC
sensors.
CSD-1 Acceptable. Meets CSD-1 section CF-300 requirements as a Primary Safety Control. Meets CSD-1 section CW-400 requirements as a Temperature Operation control. Meets CSD-1 section CW-400 requirements as a Temperature High Limit Control when congured for use with 10 kohm NTC
sensors.
Federal Communications Commission, Part 15, Class B. Emissions.

BURNER CONTROL OPERATION

SAFETY SHUTDOWN OF BURNER CONTROL FUNCTIONS
Safety Shutdown (Lockout) occurs if any of the following occur during the indicated period:
1. INITIATE PERIOD:
a. A/C line power errors occurred. b. Four minute INITIATE period has been exceeded.
2. STANDBY PERIOD:
a. Flame signal is present after 240 seconds. b. Preignition Interlock is open an accumulative time of 30 seconds. c. Interlock Start check feature is enabled and the Interlock String (including Airow Switch) is closed for 120 seconds with the controller closed. (jumpered or welded Interlock). d. Main Valve Terminal is energized. e. Internal system fault occurred.
3. PREPURGE PERIOD:
a. Preignition Interlock opens anytime during PREPURGE period. b. Flame signal is detected for 10 seconds accumulated time during PREPURGE. c. Purge Rate Fan RPM or High Fire Switch fails to close within four minutes and fteen seconds after the ring rate motor is commanded to drive to the high re position at the start of
PREPURGE.
d. Light off Rate Fan RPM or Low Fire Switch fails to close within four minutes and fteen seconds after the ring rate motor is commanded to drive to the low re position at the end of
PREPURGE.
e. Lockout Interlock (if programmed) does not close within 10 seconds. f. Lockout Interlock opens during PREPURGE. g. Pilot Valve terminal is energized. h. Main Valve terminal is energized. i. Internal system fault occurred.
4. PRE-IGNITION TIME
a. Lockout Interlock opens. b. IAS Purge and Ignition enabled and the Interlock opens. c. Preignition Interlock opens. d. Pilot Valve terminal is energized. e. Main Valve terminal is energized.
5. PILOT FLAME ESTABLISHING PERIOD (PFEP):
a. Lockout Interlock opens (if enabled). b. Pilot Valve terminal is not energized. c. No ame is present at the end of the PFEP, or after programmed number of retry attempts. d. Main valve terminal is energized. e. Internal system fault occurred.
46
Page 47
6. MAIN FLAME ESTABLISHING PERIOD (MFEP):
a. Lockout Interlock opens (if enabled). b. Pilot valve terminal is not energized. c. Main valve terminal is not energized. d. No ame present at the end of MFEP. e. Internal system fault occurred.
7. RUN PERIOD:
a. No ame is present, or ame is lost (if enabled-lockout). b. Lockout Interlock opens) if enabled). c. IAS Purge and Ignition enabled and the Interlock opens. d. Pilot terminal energized (if programmed as Interrupted Pilot). e. Main valve terminal is not energized. f. Internal system fault occurred.
8. POSTPURGE PERIOD:
a. Preignition Interlock does not close in ve seconds. b. Pilot Valve terminal is energized. c. Main Valve terminal is energized. d. Internal system fault occurred. e. Flame sensed 240 seconds accumulated time after the RUN period.
SAFETY SHUTDOWN:
1. If the lockout interlocks open or a sensor designated as a
safety limit are read as defective, Control System will lockout and the blower motor will be de-energized.
If these open during the ring period, all fuel valves will be de­energized, the system will complete postpurge, and will lockout indicated by an alarm.
2. If the pilot ame is not detected by the end of the last (3
number recycle attempt), pilot trial for ignition period, the pilot valve, and ignition transformer will be de-energized, the system will complete post purge and will lockout indicated by an alarm.
3. If the main ame is not detected at the end of the last recycle
attempt of the main ame establishing period, all fuel valves will be de-energized, the device will complete postpurge, and will lockout indicated by an alarm.
4. If the ame sensing signal is lost during the run period (if
lockout is selected), all fuel valves will be de-energized within 4 seconds after the loss of the ame signal, the device will complete postpurge, and will lockout indicate by an alarm.
5. Manual reset is required following any safety shutdown.
Manual reset may be accomplished by pressing the push button on the device, pressing the remote reset wired into connector J10, or through an attached display.
Interrupting power to Control System will cause electrical resets, but does not reset a lockout condition.

GENERAL OPERATIONAL SEQUENCE

INITIATE
The R7910 enters the Initiate sequence on Initial Power up or:
• Voltage uctuations vary less than 20VAC or greater than 30VAC.
• Frequency uctuations vary +/-5% (57 to 63 Hz).
• If Demand, LCI, or Stat interrupt (open) during the Prepurge Period.
• After the reset button is pressed or fault is cleared at the displays.
The Initiate sequence also delays the burner motor from being energized and de-energized from an intermittent AC line input or control input. If an AC problem exists for more than 240 seconds a lockout will occur.
HYDRONIC/CENTRAL HEATING
Start-up sequence central heating request (system in standby):
1. Heat request detected (On Setpoint - On Hysteresis).
2. The CH pump is switched on.
3. After a system Safe Start Check, the Blower (fan) is switched
on after a dynamic ILK switch test (if enabled).
4. After the ILK switch is closed and the purge rate proving fan
RPM is achieved (or High Fire Switch is closed) - prepurge time is started.
5. When the purge time is complete, the purge fan RPM is
changed to the Lightoff Rate or if used, the damper motor is driven to the Low Fire Position.
6. As soon as the fan-rpm is equal to the light-off rpm (or the
Low Fire Switch closes), the Trial for Ignition or Pre-Ignition Time is started.
7. Pre-Ignition Time will energize the ignitor and check for
ame.
8. Trial for Ignition. Specics for timings and device actions are
dened by the OEM or installer.
9. The ignition and the gas valve are switched on.
10. The ignition is turned off at the end of the direct burner
ignition period, or for a system that does use a pilot, at the end (or optionally at the middle) of the Pilot Flame Establishing Period (PFEP). For an interrupted pilot system this is followed by a Main Flame Establishing Period (MFEP) where the pilot ignites the main burner. For an intermittent pilot there is no MFEP.
11. The fan is kept at the lightoff rate during the stabilization
timer, if any.
12. Before the release to modulation, the fan is switched to
minimum RPM for the CH Forced Rate and Slow Start Enable, if the water is colder than the threshold.
13. At the end of the CH-heat request the burner is switched off
and the fan stays on until post purge is complete.
14. A new CH-request is blocked for the forced off time set by
the Anti Short Cycle (if enabled).
15. The pump stays on during the pump overrun time (if
enabled).
16. At the end of the pump overrun time the pump will be
switched off.
47
Page 48
DOMESTIC HOT WATER
Start-up sequence DHW-request (system in standby):
1. Heat request detected (either DHW Sensor Only, DHW
Sensor and Remote Command or DHW Switch and Inlet Sensor, whichever applies).
2. The pump is switched on (after the DHW Pump Start Delay).
3. After a system Safe Start Check, the Blower (fan) is switched
on after a dynamic ILK switch test (if enabled).
4. After the ILK switch is closed and the purge rate proving fan
RPM is achieved (or High Fire Switch is closed) - prepurge time is started.
5. When the purge time is complete, the purge fan RPM is
changed to the Lightoff Rate or if used, the damper motor is driven to the Low Fire Position.
6. As soon as the fan-rpm is equal to the light-off rpm (or the
Low Fire Switch closes), the Trial for Ignition or Pre-Ignition Time is started (depending on conguration).
7. Pre-Ignition Time will energize the ignitor and check for
ame.
8. Trial for Ignition. Specics for timings and device actions are
dened by the OEM or installer.
9. The ignition and the gas valve are switched on.
10. The ignition is turned off at the end of the direct burner
ignition period, or for a system that does use a pilot, at the end (or optionally at the middle) of the Pilot Flame Establishing Period (PFEP). For an interrupted pilot system this is followed by a Main Flame Establishing Period (MFEP) where the pilot ignites the main burner. For an intermittent pilot there is no MFEP.
11. The fan is kept at the lightoff rate during the stabilization
timer, if any.
12. Before the release to modulation, the fan is switched to
minimum RPM for the DHW Forced Rate and Slow Start Enable, if the water is colder than the threshold.
13. At the end of the DHW-heat request the burner is switched
off and the fan stays on until post purge is complete.
14. A new DHW-request is blocked for the forced off time set by
the Anti Short Cycle (if enabled).
15. The pump stays on during the pump overrun time (if
enabled).
16. At the end of the pump overrun time the pump will be
switched off.
LEAD LAG
Burner Control System devices contain the ability to be a stand­alone control, operate as a Lead Lag Master control (which also uses the burner control function as one of the slaves), or to operate solely as a slave to the lead lag system.
Control System devices utilize two ModBus™ ports (MB1 and MB2) for communications. One port is designated to support a system S7999B display and the other port supports communications from the LL Master with its slaves.
The Lead Lag master is a software service that is hosted by a Control System. It is not a part of that control, but is an entity that is “above” all of the individual burner controls (including the one that hosts it). The Lead Lag master sees the controls as a set of Modbus devices, each having certain registers, and in this regard it is entirely a communications bus device, talking to the slave buner controls via Modbus.
The LL master uses a few of the host Buner Control's sensors (header temperature and outdoor temperature) and also the STAT electrical inputs in a congurable way, to provide control information.
LEAD LAG (LL) MASTER GENERAL OPERATION
The XP Boiler is a multiple burner application and it works on the basis of the Lead Lag Operation. The XB Boiler is factory congured for Hydronic/Central Heating application, whereas the XW Boiler is factory congured for Domestic Hot Water application. The LL master coordinates the ring of its slave Control Systems. To do this it adds and drops stages to meet changes in load, and it sends ring rate commands to those that are ring.
The LL master turns the rst stage on and eventually turns the last stage off using the same criteria as for any modulation control loop:
When the operating point reaches the Setpoint minus the On hysteresis, then the rst Control System is turned on.
When the operating point reaches the Setpoint plus the Off hysteresis then the last slave Control System (or all slave Control Systems) are turned off.
The LL master PID operates using a percent rate: 0% is a request for no heat at all, and 100% means ring at the maximum modulation rate.
This ring rate is sent to the slaves as a percentage, but this is apportioned to the slave Control Systems according to the rate allocation algorithm selected by the Rate allocation method parameter.
For some algorithms, this rate might be common to all slave Control Systems that are ring. For others it might represent the total system capacity and be allocated proportionally.
For example, if there are 4 slaves and the LL master's percent rate is 30%, then it might satisfy this by ring all four slaves at 30%, or by operating the rst slave at 80% (20% of the system’s capacity) and a second slave at 40% (10% of the system’s capacity).
The LL master may be aware of slave Control System’s minimum ring rate and use this information for some of its algorithms, but when apportioning rate it may also assign rates that are less than this. In fact, the add-stage and drop-stage algorithms may assume this and be dened in terms of theoretical rates that are possibly lower than the actual minimum rate of the Burner Control System. A Control System that is ring and is being commanded to re at less than its minimum modulation rate will operate at its minimum rate: this is a standard behavior for a Buner control system in stand-alone (non-slave) mode. If any slave under LL Master control is in a Run-Limited condition, then for some algorithms the LL master can apportion to that stage the rate that it is actually ring at. Additionally when a slave imposes its own Run-limited rate, this may trigger the LL Master to add a stage, if it needs more capacity, or drop a stage if the run-limiting is providing too much heat (for example if a stage is running at a higher-than commanded rate due to anti­condensation).
By adjusting the parameters in an extreme way it is possible to dene add-stage and drop-stage conditions that overlap or even cross over each other. Certainly it is incorrect to do this, and it would take a very deliberate and non-accidental act to accomplish it. But there are two points in this:
1. LL master does not prevent it, and more important;
2. It will not confuse the LL master because it is implemented
as a state machine that is in only one state at a time;
48
Page 49
For example:
— If its add-stage action has been triggered, it will remain in this condition until either a stage has been added, Or — The criteria for its being in an add-stage condition is no longer met; only then will it take another look around to see what state it should go to next.
DEFINITIONS
Modulating stage: The modulating stage is the Control System
that is receiving varying ring rate requests to track the load.
First stage: This is the Control System that was turned on rst, when no slave Control Systems were ring.
Previous stage: The Control System that was added to those stages that are ring Just prior to the adding of the Control System that is under discussion.
Next stage: The Control System that will or might be added as the next Control System to re.
Last stage: The Control System that is ring and that was added the most recently to the group of slaves that are ring. Typically this is also the modulating stage, however as the load decreases then the last-added stage will be at its minimum rate and the previous stage will be modulating.
Lead boiler: The Lead boiler is the Control System that is the rst stage to re among those stages which are in the equalize runtime (Lead/Lag) group. If a boiler is in the “Use rst” group it may re before the Lead boiler res.
First boiler: A Control System may be assigned to any of three groups: “Use First”, “Equalize Runtime”, or “Use Last”. If one or more Control Systems are in the “Use First” category, then one of these (the one with the lowest sequence number) will always be the rst boiler to re. If there is no Control System in the “Use First” category and one or more are in the “Equalize Runtime” category, then the First boiler is also the Lead boiler.

LOCAL OPERATOR INTERFACE: DISPLAY SYSTEM

FIGURE 49. BURNER CONTROL S7999B DISPLAY SYSTEM
The S7999B is a microprocessor-based touchscreen Operator Interface (OI) display that provide an operator interface for monitoring and conguring parameters in the Burner Control system.
The S7999B can be used to monitor an individual boiler but is primarily used for multiple boiler applications in a lead/lag arrangement. COM 2 port is available for Building Automation applications. The S7999B display is ush mounted into a panel cutout (8-1/8 in. W x 5-7/8 in. H). Wiring connections to the S7999B are through a removable 9-pin wiring header.
FEATURES
Individual boiler status, conguration, history, and
diagnostics.
Allows conguration and monitoring of the Burner Control
Controls burner control sequence, ame signal, diagnostics, historical les, and faults.
S7999B OI Display only:
• Allows switching view between multiple boilers
• Allows viewing Lead-Lag Master
• Ethernet port for downloading software upgrades (when required)
• Real-time data trending analysis and transferring saved trend data to Excel spreadsheet.
• Audible Alarm
• COM 2 Modbus port for Building Automation System applications.
• LED indicators:
• Power
• Network
• COM 2
• COM 1
Model used:
• S7999B1067 has Black Border
49
Page 50
Allows for lead/lag commissioning.
Locates attached boiler(s).
Allows boiler naming.
Color 3.5 in. x 4.625 in. (5.7 in. diagonal) user interface display.
Graphic user interface.
Touch screen.
Communication between the OI Displays and the Burner Control Systems uses Modbus™.
Flush mounting.
Touch screen disable for screen cleaning.
12 VDC power supply (included).
Screen saver.
Contrast control.
Volume control.
SPECIFICATIONS
1. Electrical Ratings:
+12 VDC input, maximum of 500 mA current drain. Included Power Supply for S7999B:
• Inputs: 85 to 264 VAC, 47 to 63 Hz; 120 to 370 VDC.
• Output: 12 VDC; 0 to 2.1 A.
• Power: 25 W.
2. Operating Temperature: 32°F to 122°F (0°C to 50°C)
3. Storage/Shipping Temperature: -40°F to 158°F (-40°C to
70°C).
4. Humidity: 85% maximum relative humidity.
5. Approvals:
FCC Part 15, Class A Digital Device Underwriter’s Laboratories, Inc. (UL) Component Recognized
(for non-continuous operation): File Number MH20613 (MCCZ) Canada: ICES-003

INSTALLATION INSTRUCTIONS (S7999B OI DISPLAY)

MOUNTING THE S7999B OI DISPLAY AND POWER SUPPLY
The OI Display can be mounted on the door panel of an electrical enclosure.
1. Select the location on the door panel to mount the display; note that the device will extend into the enclosure at least one inch past the mounting surface.
2. Provide an opening in the panel door 8-1/8 in. wide by 5-7/8 in. high.
3. Place the OI Display in the opening and use it as a template to mark the location of the four mounting screw holes. Remove the device.
4. Using pilot holes as guides, drill 1/4 in. holes through the door panel.
5. Place the display in the opening, aligning the mounting holes in the device with the drilled holes in the panel.
6. Secure the display to the panel with four #6-32 screws and nuts provided.
7. Select a location inside the enclosure for mounting the power supply.
8. Using the power supply as a template, mark the locations of the two mounting holes in the enclosure.
9. Remove the power supply.
10. Drill 1/4 in. holes through the panel at the marked locations
and secure the power supply with the two #6-32 screws and nuts provided.
11. Remove the 9-pin connector plug from the back of the OI
Display.
12. Wire the connector to the power supply and the RS-485
cables.
13. Ensure the 9-pin connector plug is aligned with the header
pins when inserting the 9-pin connector plug back onto the Display. Secure rmly.
FIGURE 50. S7999B OI DISPLAY CONNECTOR TERMINALS
QUICK SETUP (S7999B OI DISPLAY)
1. Make sure the S7999B 9-pin connector is properly aligned
and pressed rmly in place.
2. Make sure the wires between the 9-pin connector and the
controller are properly wired and secure.
WARNING: Electrical Shock Hazard. Can cause severe injury, death or equipment damage. Line voltage is present at the 120 VAC power supply.
3. Make sure the power supply is connected securely to the
120 VAC power source.
50
Page 51

STARTING UP THE S7999B OI DISPLAY

POWER-UP VALIDATION
The Home page will appear and the “Power” LED will be blinking when the device is properly powered. Select the Setup button to adjust the contrast and sound as desired.
If the screen is dim, check the pin 1 and 2 wiring connections.
Note: An Advanced Startup screen displays for ve seconds after power-up before the Home page displays. This screen allows the user to upgrade the software in the System Display and should normally be bypassed.
Three LEDs exist for I/O trafc: one for the Ethernet network port and two for Modbus™ ports. Modbus Com Port 2 is not active on this device.
1. Make sure the Power and COM1 LEDs are blinking.
2. If the LEDs are not blinking:
• Make sure the proper connections have been made between the Modbus COM1 Port and the rst controller device in the Modbus network.
• Ensure proper wiring of the OI Display 9-pin Header Connections.
3. If connected to a BAS application, COM2 LED will blink
indicating BAS trafc.
HOME PAGE (S7999B OI DISPLAY)
Make sure a screen similar to Figure 51 appears after the OI Display has completely powered up.
On System applications, each Burner Control System is represented on the Home page by an icon and name. Pressing the icon allows the user to zoom in on that boiler and see its specic details. These details are provided on a new page, which can include additional buttons that display additional detail and operation information, which itself leads to other pages. The pages are traversed in a tree structure method, as shown in Figure 53 on Page 52.
The Control System icons will appear in one of four colors indicating the boiler status.
• Blue: Normal operation
• Red: Lockout condition
• Gray: Standby mode (burner switch off)
• Gray and crossed out: communication error (disconnected or powered off)
• Yellow: Preparing for Start-up.
Up to 8 Systems can be displayed on the Home page. The name of each boiler is displayed next to the Control System icon button. When Lead Lag is enabled, the system header temperature and ring rate are displayed for each System. When the burner is in standby or not ring the ring rate is not displayed.
Note: The boiler name may be cut off on the Home page when all icons are present.
The Home page also includes a System Analysis button that allows the user to view status information on a system-wide (that is, multiple boiler) basis. The user can choose which status information to compare from the Burner Controls in the system.
Pressing the Setup button on the Home page displays miscellaneous setup and diagnostic functions. It also contains the setup conguration for BAS applications, under the Advanced Setup button. Pressing the Control System icon opens that control’s status page.
FIGURE 51. S7999B HOME PAGE
(BOILER 1 IN NORMAL OPERATION)

PAGE NAVIGATION

The Burner Control System OI Displays present information and options in a paged manner. Pages are displayed in a tree structure in which the user navigates up and down to arrive at the desired Function (see Figure 53). The page descriptions are provided below so that you can understand the purpose of each and view the selections, parameters, and information that is available or required on each.
COMMON OI DISPLAY PAGE SYMBOLS
Most pages have a Home button in the top-left corner of the screen and a Back button in the top-right corner of the screen. The Home button returns the user to the Home page and terminates any operation in progress. The Back button returns
the user to the previous page.
Two other icons may be noticed near the boiler name.
A bell will be displayed if the system is in Lockout that reset will be required.
A padlock will be shown on screens that require a password to change the parameter. An unlocked padlock indicates the password has been entered to change the parameter.
FIGURE 52. S7999B LEAD LAG HOME PAGE
51
Page 52
FIGURE 53. S7999B DISPLAY PAGE FLOW
52
Page 53
STATUS OR HOME PAGE
A status (summary) page (Figure 54) is displayed when the S7999B display is connected. This status page appears on the S7999B when the Burner control icon is pressed on the “Home” page. The status page displays the current condition of the burner control and displays some of the more important conguration
settings.
The boiler name associated with the burner control is displayed in the title on the status page.
Note: When the burner control has no boiler name dened, Modbus address is used to identify the boiler.
The initial status page displayed contains summary status information as shown in Figure 54. Any status information not applicable for the installation is grayed/blanked out on the screen.
Buttons on this screen include:
• Congure: used to congure the burner control (password protected).
Operation: used to perform daily or frequent functions with the burner control, such as setpoint adjustment, etc.
Diagnostic: used to view burner control diagnostic information.
Details: used to view burner control detail status information.
History: used to view burner control history
Pump: used to expand the pump status information.
Modulation: used to toggle between status displays:
pump, setpoints, and modulation.
CONFIGURE BUTTON
Pressing the Congure button (bottom left) on the Status page opens the Conguration page. The S7999B Conguration page does not have a “Display Setup”
button.
The conguration page allows the user to view and set parameters that dene how the connected R7910A functions in the hydronic heating system. All parameters are factory congured and only a Field Service Agent must perform the conguration settings.
The conguration page contains a menu of parameters grouped into functional areas that the user selects for conguration (see Figure 55).
No specic order for conguration is required. All parameters are enabled for editing, though some may not be applicable (e.g., a conguration parameter may disable a control feature). Selecting a parameter group from the menu displays parameters exclusively applicable for the functional group on the page (see Figure 56). These parameters can be edited, and when the user is nished, control returns back to the conguration menu page.
Each parameter is displayed in its group. If there are more parameters than will t on the screen, a vertical scroll bar allows the user to scroll up and down to view all parameters. The parameter name is displayed on the left and the current setting is displayed in the text box on the right.
FIGURE 54. SUMMARY STATUS PAGE
FIGURE 55. CONFIGURATION MENU PAGE
FIGURE 56. SAMPLE CONFIGURATION PAGE
53
Page 54
CONFIGURATION PASSWORD
Some parameters require a valid conguration password be entered by the user before the parameter can be changed. The password need only be entered once while the user remains on the conguration pages. Leaving the conguration pages ends the scope of the password.
Three levels of access to Burner Control parameters are permitted. Each access level has dened rights when interfacing with conguration and status parameters within the controls.
End user: The end user can read or view the control parameters and be allowed to change some operating parameters, CH setpoint as an example.
Installer: The installer can read all control parameters and change default allowed parameters. This access level is used to customize the control for a particular installation.
OEM: The OEM can read and change all parameters, change sensor limits and burner control safety parameters.
Different passwords exist in the Burner Control for each access level. The end user level requires no password, but the installer and OEM levels have unique passwords dened for them.
The installer and OEM passwords can be changed in the Burner Control after logging in with the current password. When the password is changed, it is saved for all future logins.
Note: For the S7999B System OI display, each boiler in a multi-boiler conguration has its own set of installer and OEM passwords. To avoid user confusion, the passwords should be changed to the same password in each control, but there is no requirement to do so. Make sure to record your password.
The user is notied that a new password is needed to change a parameter (or until a password is entered successfully)—see Figure 57. The user can continue viewing the conguration parameters regardless of whether a password is entered successfully.
The Burner Controls maintain a password time-out that limits the scope of the password entry. Once a password is successfully entered, the control starts an internal timer that expires after 10 minutes of inactivity. After the timer expires, the user is required to re-enter a password before a parameter can be changed.
The user is not required to enter a conguration password for a parameter that has a lower access level than the access level achieved by an earlier password entry for any conguration group (as long as the user stays in the conguration pages). The user only needs to enter a password once until a parameter that has a higher access level is selected.
KEYBOARD
Some pages request user entry of characters. When this type of input is required, a keyboard page appears, as shown in Figure
58. The text box at the top of the screen displays the current (or default) setting of the user input. The user can add to this text, clear it, or change it.
The Shift key on the left side of the screen shifts between upper and lowercase characters. Pressing the Shift key toggles the keyboard from one mode to the other (continuous pressing of the Shift button is not required). The OK button should be pressed when the user is done entering the text input. The Cancel button on the bottom of the screen allows the user to ignore any text changes that have been made and keep the original text value. Pressing the OK or Cancel buttons returns the user to the page displayed prior to the keyboard page.
LOGIN
Pressing the Login button allows entering the password from a keyboard as shown in Figure 58. After the password is entered, the OK button is selected. The Cancel button aborts the password login.
FIGURE 58. DEVICE LOGIN SCREEN
WARNING: Explosion Hazard. Improper conguration can cause
fuel buildup and explosion. Improper user operation may result in property loss, physical injury or death.
Using the OI Displays to change parameters must be attempted by only experienced and/or licensed burner/boiler operators and mechanics.
CHANGE PARAMETER SETTINGS
Change parameter settings by selecting the parameter on the page. A dialog box displays for the parameter with controls allowing the user to change the value (see Figure 59 on Page 55). After changing the setting to a new value, press the OK button. Pressing the Cancel button leaves the parameter unchanged. The changed setting is reected on the screen and sent to the control when the OK button is pressed.
FIGURE 57. LOGIN REQUIRED
54
Page 55
FIGURE 59. EXAMPLE OF CHANGE CONFIGURATION
PARAMETER PAGE
VERIFY
Pressing the Verify button displays safety conguration parameters for an additional verication step to commit the changes.
Safety parameters are grouped into blocks that include only safety parameters, not a mixture of safety data and non-safety data. All parameters within the safety group undergo a verication process. A safety parameter group is identied on the display to indicate when the conguration parameters are safety-related. Each safety parameter group is veried one at a time until all have been veried. See Figure 60.
Note: When the installer proceeds with the safety parameter conguration, the control unlocks the safety parameters in this group and marks them unusable. Failure to complete the entire safety conguration procedure leaves the control in an un­runnable state (lockout 2).
All safety conguration parameters in the group should have the same access level. If this condition isn’t so, the user is asked to enter another password when a higher access level is needed.
Successful login is noted by the lock icon, which changes to “unlocked” on the page. The installer may begin to change safety parameters (or any other parameters) at that time (see Figure 61). If the Burner Control is in an uncongured (or new) state, then this warning doesn’t appear. All parameters that need changes should be changed during the login.
FIGURE 60. SAFETY VERIFICATION
Like operating parameters, safety parameters can be viewed without the need to enter a password.
Safety parameter blocks that have been changed require verication. The verication steps do not have to be completed immediately; the installer can move between and change parameter groups before the verication is done. A Verify button is enabled that allows the installer to conduct verication sessions (the example of the Verify button in Figure 55 is not yet enabled because the installer hasn’t logged in).
FIGURE 61. EDIT SAFETY DATA
If the safety conguration session is terminated after it has started (in the Edit or Verify stages), the Burner Control is left in an uncongured (unrunnable) state.
The installer can terminate the session by pressing the Menu button or by attempting to leave the Verication page with the Home or Back buttons (top-left and -right screen corners, respectively). However, leaving the session at this point leaves the control in an unrunnable state and conrms whether the installer still wants to do so.
The settings of all parameters in each safety block must be veried to save them in the control.
When the installer is done changing safety parameters, pressing the Verify button on the conguration screen begins the Verication process. The settings for all safety parameters in each changed block are presented and Veried by the installer (see Figure 62 on Page 56).
55
Page 56
FIGURE 62. SAFETY PARAMETER CONFIRMATION
Press the Yes button to conrm each safety parameter block. If the No button is selected, the safety parameter block remains unconrmed and the Conguration menu page is displayed. The control remains in an uncongured state in this case.
After all safety parameter blocks have been conrmed, the installer is asked to press and hold the Reset button on the Burner Control to complete the safety verication session (see Figure 63).
FAULT/ALARM HANDLING
Each Burner Control reports to the OI display when a safety lockout or an Alert occurs.
Safety lockouts are indicated on each conguration page as an alarm bell symbol. At the status page (for S7999B), the History button turns red. If the S7999B is displaying the system status icons, the control in alarm will turn red.
The lockout history can be displayed by pressing on the History button. The state information about each lockout is displayed along with the date/time that the lockout occurred (refer to Table
21). Current date/time stamp is a display setup feature.
Note: In the event of a power interruption, the date/time must be reset. The OI Display does NOT have a backup means.
TABLE 21. BURNER CONTROL LOCKOUT HISTORY
DATA COMMENT
Lockout time Set by display
Fault Code Unique code dening which
lockout occurred.
Annunciator rst out First interlock in limit string
results in a shutdown.
Description Fault description
Burner Lockout/Hold Source/reason for lockout/
hold
Burner control state
Sequence time Burner control state timer at
time of fault
Cycle Burner control cycle
Run Hours Burner control hours
I/O All digital I/O status at time of
fault
Annunciator 1-8 states All annunciator I/O status at
time of fault
Fault data Fault dependent data
An alert log can be displayed for each control by pressing the Alert button on the bottom of the history status page. A description of the alert is displayed along with the time when the alert occurred (refer to Table 22).
TABLE 22. BURNER CONTROL ALERT LOG
FIGURE 63. SAFETY PARAMETER RESET
When the Reset button is pressed and held for 3 seconds the conrmed safety parameters are saved in the control. The above Reset dialog box automatically closes when this step is completed.
If this step is not performed, the control remains in a safety lockout state until the installer resolves the unveried safety parameters.
DATA COMMENT
Alert Line Set by display
Alert Code Unique Code dening which
fault occured.
Description Alert description
HISTORY BUTTON
The History button on the Home page serves not only as a button, but also displays Burner Control lockouts, holds, and alerts as they occur. The History button can be selected at any time, regardless of which type of information is displayed, to view history information. Pressing the History button displays a dialog box (see Figure 64 on Page 57) that allows the user to select the type of history to view. The user can also silence an audible alarm generated by the control during a lockout or alert by alarm condition.
56
Page 57
This History dialog box provides an exploded view of the status information displayed in the History button (the font is larger). One of the four buttons (OK, Lockouts, Alerts, or Silence) can be selected. If none of these buttons are selected the dialog box closes after 30 seconds.
FIGURE 64. EXAMPLE OF HYDRONIC HISTORY
Two types of historical data can be displayed on the history page: lockout history and alert log.
The entire 15 fault code history is displayed in a scrollable list with the most recent fault displayed rst followed by the next most recent fault. Summary information is displayed for each fault entry, including the burner cycle count, fault code, and fault number with description. Detailed information for a specic fault entry that also includes burner control sequence state, burner run-time hours, annunciation status, etc., is viewed by selecting (touching the History line) the lockout entry in the list.
Note: The system time can be set in the OI display to ensure that correct timestamps are given to the controls’ lockouts and alerts. Power interruptions will require the time to be reset as the display DOES NOT have a time backup means.
The Clear Lockout button allows the user to acknowledge and clear (reset) the lockout when in lockout state, much the same as pressing the reset button on the front of the Burner Control.
The user can toggle between displaying the controls’ lockout history and alert log by pressing the Alerts or Lockouts button on the bottom of the pages.
FIGURE 66. EXAMPLE OF ALERT SHOWN
To see additional detail about a lockout or alert, touching on the lockout or alert in the list expands the view of that lockout or alert, as shown in Figure 65 and Figure 66.
FIGURE 65. EXAMPLE OF LOCKOUT HISTORY
The date and time that each fault occurred is displayed in the lockout history. The lockout timestamp displays in both the lockout summary and detail information.
The Burner Control does not maintain date or time of day information. The date and time stamp is assigned by the OI display. When the OI display rst obtains the lockout and alert history from the control (during the display data synchronization), no timestamps are assigned since the times that the lockouts occurred are unknown. All new lockouts that occur after the synchronization are assigned timestamps.
FIGURE 67. CONTROL EXPANDED LOCKOUT DETAIL
57
Page 58
FIGURE 68. CONTROL EXPANDED ALERT DETAIL
OPERATION BUTTON
The operation button displays the Burner Control running operation, including setpoint and ring rate values. From this page the user can change setpoints, manually control the boiler’s ring rate, manually turn pumps on, view annunciation information, and switch between hydronic heating loops (Central Heat and Domestic Hot Water), as shown in Figure 69. If a password is required to change any of the settings on this page, the user can press the Login button to enter the password.
Annunciation information is shown in Figure 70 and Figure 71.
FIGURE 70. PROGRAMMABLE ANNUNCIATION
FIGURE 71. FIXED ANNUNCIATION
FIGURE 69. HYDRONIC OPERATION PAGE
58
Page 59
DIAGNOSTICS BUTTON
The Diagnostics button displays analog and digital I/O status of the Burner Control. A snapshot of the diagnostic status is displayed and updated once per second as it changes in the control.
The digital I/O data is displayed as LEDs that are either on (green) or off (red) (See Figure 72). Not all digital I/O can be displayed at the same time on the page, so a horizontal scroll bar is used to move the view left and right to show all digital I/O data.
SYSTEM CONFIGURATION (S7999B OI DISPLAY ONLY)
The OI Display has some functions related to general conguration for the control in the end user installation. Pressing the Display Refresh button invokes a search procedure (see Figure 74). A new R7910A Hydronic Control or R7911 Steam Control is identied by “Unknown” status next to its name in the boiler system list (see Figure 75). “Unknown” indicates that conguration data has not been retrieved from the control yet.
FIGURE 72. DIAGNOSTICS PAGE (DIGITAL I/O)
The control analog I/O can also be viewed on the OI Display. A snapshot of the diagnostic status is displayed and updated as it changes in the control.
The analog I/O data is displayed as bar charts with I/O level represented in the I/O range (see Figure 73) Analog I/O that is not enabled for the installation displays a blank I/O level. Not all analog I/O can be displayed at the same time on the page, so a horizontal scroll bar is used to move the view left and right to show all analog I/O status.
FIGURE 74. SYSTEM REFRESH
FIGURE 75. SYSTEM CONFIGURATION PAGE
The control connected to the Modbus network is indicated to the user after the search procedure has concluded.
Once the control is located it must be synchronized with the OI Display before it can be displayed. New controls are not displayed on the Home page until this synchronization is performed.
FIGURE 73. DIAGNOSTIC PAGE (ANALOG I/O)
59
Page 60
SYSTEM SYNCHRONIZATION (S7999B OI DISPLAY ONLY)
The user can manually synchronize conguration data from the connected controls at any time.
A new control is visible when conguration and status data is gathered from it. This collection procedure takes a few minutes. The control is marked as “Unknown” when no conguration information exists. Normally, control conguration data collection only needs to be performed when the control is initially installed. However, a re synchronization is necessary after the OI Display is reset. See Figure 76.
The user presses the Synchronize button to begin synchronization with the control. See Figure 76.
FIGURE 76. SYSTEM SYNCHRONIZATION
Status of the synchronization is reected in the dialog box. The synchronization can be aborted by selecting the Cancel button.
CONFIGURATION
The Burner Control can be congured from the OI Display. The control conguration is grouped into the functional groups as shown in Table 23.
TABLE 23. FUNCTIONAL CONFIGURATION GROUPS
HYDRONIC CONTROL
System Identication and
Access
CH - Central Heat
Outdoor Reset
DHW - Domestic Hot Water
DHW Storage
DHW Plate
Warm Weather Shutdown
Demand Priority
Modulation Conguration
Pump Conguration
Statistics Conguration
High Limit
Stack Limit
Delta T Limits
T-Rise Limit
Heat Exchanger High Limit
Anti-condensation
Frost Protection Conguration
Annunciation Conguration
Burner Control Interlocks
Burner Control Timings and Rates
Burner Control Ignition
Burner Control Flame Failure
System Conguration
Fan Conguration
Sensor Conguration
Lead Lag Slave Conguration
Lead Lag Master Conguration
Most of this conguration is performed by the Service Agent or at A.O. Smith. Each functional group is displayed on the Conguration menu page.
Parameters in functional groups that are not applicable for the installation can be ignored. In some cases, features in a functional group are disabled by default and are enabled when needed for the installation.
60
Page 61

TROUBLESHOOTING

To support the recommended Troubleshooting, the R7910 has an Alert File. Review the Alert history for possible trends that may have been occurring prior to the actual Lockout. Note Column: H= Hold message; L=Lockout message; H or L= either Hold or Lockout depending on Parameter Conguration.
TABLE 24. TROUBLESHOOTING CODES
CODE DESCRIPTION RECOMMENDED TROUBLESHOOTING OF
NOTE
LOCKOUT CODES
Safety Data Faults
1 Uncongured safety data 1. New Device, complete device conguration and
safety verication.
2. If fault repeats, replace module.
2 Waiting for safety data verication 1. Device in Conguration mode and safety
parameters need verication and a device needs reset to complete verication.
2. Conguration ended without verication, re enter
conguration, verify safety parameters and reset device to complete verication.
3. If fault repeats, replace module.
Internal Operation Errors
3 Internal fault: Hardware fault Internal Fault.
4 Internal fault: Safety Relay key feedback error H
5 Internal fault: Unstable power (DCDC) output H
6 Internal fault: Invalid processor clock H
7 Internal fault: Safety relay drive error H
8 Internal fault: Zero crossing not detected H
9 Internal fault: Flame bias out of range H
10 Internal fault: Invalid Burner control state L
11 Internal fault: Invalid Burner control state ag L
12 Internal fault: Safety relay drive cap short H
13 Internal fault: PII shorted to ILK H or L
14 Internal fault: HFS shorted to LCI H or L
15 Internal fault: Safety relay test failed due to
feedback ON
16 Internal fault: Safety relay test failed due to safety
relay OFF
17 Internal fault: Safety relay test failed due to safety
relay not OFF
18 Internal fault: Safety relay test failed due to
feedback not ON
19 Internal fault: Safety RAM write L
20 Internal fault: Flame ripple and overow H
21 Internal fault: Flame number of sample mismatch H
22 Internal fault: Flame bias out of range H
23 Internal fault: Bias changed since heating cycle
starts
24 Internal fault: Spark voltage stuck low or high H
25 Internal fault: Spark voltage changed too much
during ame sensing time
26 Internal fault: Static ame ripple H
27 Internal fault: Flame rod shorted to ground
detected
28 Internal fault: A/D linearity test fails H
29 Internal fault: Flame bias cannot be set in range H
1. Reset Module.
2. If fault repeats, replace module.
61
L
L
H
L
L
L
L
H
H
H
Page 62
CODE DESCRIPTION RECOMMENDED TROUBLESHOOTING OF
NOTE
LOCKOUT CODES
30 Internal fault: Flame bias shorted to adjacent pin Internal Fault.
31 Internal fault: SLO electronics unknown error H
32 - 46 Internal fault: Safety Key 0 through 14 L
System Errors
47 Flame Rod to ground leakage H
48 Static ame (not ickering) H
49 24 VAC voltage low/high 1. Check the Module and display connections.
50 Modulation fault Internal sub-system fault.
51 Pump fault H
52 Motor tachometer fault H
53 AC inputs phase reversed 1. Check the Module and display connections.
54 Safety GVT model ID does not match application's
model ID
55 Application conguration data block CRC errors Contact the service professional. L
56 - 57 RESERVED
58 Internal fault: HFS shorted to IAS Internal Fault.
59 Internal Fault: Mux pin shorted L
Normal Event Status
60 Internal Fault: HFS shorted to LFS L
61 Anti short cycle Will not be a lockout fault. Hold Only. H
62 Fan speed not proved H
63 LCI OFF 1. Check wiring and correct any faults.
64 PII OFF 1. Check wiring and correct any faults.
65 Interrupted Airow Switch OFF 1. Check wiring and correct any possible shorts.
66 Interrupted Airow Switch ON H or L
1. Reset Module.
2. If fault repeats, replace module.
2. Check the Module power supply and make sure
that both frequency, voltage and VA meet the specications.
1. Review alert messages for possible trends.
2. Correct possible problems.
3. If fault persists, replace module.
2. Check the Module power supply and make
sure that both frequency and voltage meet the specications.
3. On 24 VAC applications, assure that J4-10 and
J8-2 are connected together.
Contact the service professional. L
1. Reset Module.
2. If fault repeats, replace module.
2. Check Interlocks connected to the LCI to assure
proper function.
3. Reset and sequence the module; monitor the LCI status.
4. If code persists, replace the module.
2. Check Preignition Interlock switches to assure
proper functioning.
3. Check the valve operation.
4. Reset and sequence the module; monitor the PII status.
5. If code persists, replace the module.
2. Check airow switches to assure proper
functioning.
3. Check the fan/blower operation.
4. Reset and sequence the module; monitor the
airow status.
5. If code persists, replace the module.
H
H
H
L
L
H
H or L
H or L
62
Page 63
CODE DESCRIPTION RECOMMENDED TROUBLESHOOTING OF
NOTE
LOCKOUT CODES
67 ILK OFF 1. Check wiring and correct any possible shorts.
68 ILK ON H or L
69 Pilot test hold 1. Verify Run/Test is changed to Run.
70 Wait for leakage test completion 1. Internal Fault. Reset Module.
71 - 77 RESERVED
78 Demand Lost in Run 1. Check wiring and correct any possible errors.
79 Outlet high limit 1. Check wiring and correct any possible errors.
80 DHW high limit 1. Check wiring and correct any possible errors.
81 Delta T limit 1. Check Inlet and Outlet sensors and pump circuits
82 Stack limit 1. Check wiring and correct any possible errors.
83 Delta T exchanger/outlet limit Not Applicable. H or L
84 Delta T inlet/exchanger limit Not Applicable. H or L
85 Inlet/outlet inversion limit Not Applicable. H or L
86 Exchanger/outlet inversion limit Not Applicable. H or L
87 Inlet/exchanger inversion limit Not Applicable. H or L
88 Outlet T-rise limit Check for adequate ow. H or L
89 Exchanger T-rise limit Not Applicable. H or L
90 Heat exchanger high limit Not Applicable. H or L
Sensor Faults
91 Inlet sensor fault 1. Check wiring and correct any possible errors.
92 Outlet sensor fault 1. Check wiring and correct any possible errors.
93 DHW sensor fault 1. Check wiring and correct any possible errors.
2. Check Interlock (ILK) switches to assure proper
function.
3. Verify voltage through the interlock string to the
interlock input with a voltmeter.
4. If steps 1-3 are correct and the fault persists,
replace the module.
2. Reset Module.
3. If fault repeats, replace module.
2. If fault repeats, replace module.
2. If previous steps are correct and fault persists,
replace the module.
2. Replace the Outlet high limit.
3. If previous steps are correct and fault persists,
replace the module.
2. Replace the DHW high limit.
3. If previous steps are correct and fault persists,
replace the module.
for proper operation.
2. Recheck the Delta T Limit to conrm proper
setting.
3. If previous steps are correct and fault persists,
replace the module.
2. Replace the Stack high limit.
3. If previous steps are correct and fault persists,
replace the module.
2. Replace the Inlet sensor.
3. If previous steps are correct and fault persists,
replace the module.
2. Replace the Outlet sensor.
3. If previous steps are correct and fault persists,
replace the module.
2. Replace the DHW sensor.
3. If previous steps are correct and fault persists,
replace the module.
H or L
H
H
H
H or L
H or L
H or L
H or L
H
H
H
63
Page 64
CODE DESCRIPTION RECOMMENDED TROUBLESHOOTING OF
LOCKOUT CODES
94 Header sensor fault 1. Check wiring and correct any possible errors.
2. Replace the header sensor.
3. If previous steps are correct and fault persists,
replace the module.
95 Stack sensor fault 1. Check wiring and correct any possible errors.
2. Replace the stack sensor.
3. If previous steps are correct and fault persists,
replace the module.
96 Outdoor sensor fault 1. Check wiring and correct any possible errors.
2. Replace the outdoor sensor.
3. If previous steps are correct and fault persists,
replace the module.
97 Internal Fault: A2D mismatch. Internal Fault.
98 Internal Fault: Exceeded VSNSR voltage L
99 Internal Fault: Exceeded 28V voltage tolerance L
100 Pressure Sensor Fault 1. Verify the Pressure Sensor is a 4-20 ma source.
101-104 RESERVED
Flame Operation Faults
105 Flame detected out of sequence 1. Check that ame is not present in the combustion
106 Flame lost in MFEP 1. Check pilot valve (Main Valve for DSI) wiring and
107 Flame lost early in run L
108 Flame lost in run L
109 Ignition failed L
110 Ignition failure occurred Hold time of recycle and hold option. Will not be a
111 Flame current lower than WEAK threshold Internal hardware test. Not a lockout, H
112 Pilot test ame timeout Interrupted Pilot or DSI application and ame lost
113 Flame circuit timeout Flame sensed during Initiate or off cycle, hold 240
114-121 RESERVED
Rate Proving Faults
122 Lightoff rate proving failed 1. Check wiring and correct any potential wiring
123 Purge rate proving failed L
1. Reset Module.
2. If fault repeats, replace module.
2. Check wiring and correct any possible errors.
3. Test Pressure Sensor for correct operation.
4. Replace the Pressure sensor.
5. If previous steps are correct and fault persists,
replace the module.
chamber. Correct any errors.
2. Make sure that the ame detector is wired to the correct terminal.
3. Make sure the F & G wires are protected from stray noise pickup.
4. Reset and sequence the module, if code reappears, replace the ame detector.
5. Reset and sequence the module, if code reappears, replace the module.
operation - correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, ame
detector, ame detector siting or ame rod
position.
5. If steps 1 through 4 are correct and the fault
persists, replace the module.
lockout fault. Hold Only.
when system in “test” mode.
1. Reset the module to restart.
seconds, if present after 240 seconds, lockout.
errors.
2. Check VFDs ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
NOTE
H
H
H
L
H
H or L
L
H
L
L
L
64
Page 65
CODE DESCRIPTION RECOMMENDED TROUBLESHOOTING OF
NOTE
LOCKOUT CODES
124 High re switch OFF 1. Check wiring and correct any potential wiring
125 High re switch stuck ON H
126 Low re switch OFF 1. Check wiring and correct any potential wiring
127 Low re switch stuck ON H or L
128 Fan speed failed during prepurge 1. Check wiring and correct any potential wiring
129 Fan speed failed during preignition H or L
130 Fan speed failed during ignition H or L
131 Fan movement detected during standby H
132 Fan speed failed during run H
133-135 RESERVED
Start Check Faults
136 Interrupted Airow Switch failed to close 1. Check wiring and correct any possible wiring
137 ILK failed to close 1. Check wiring and correct any possible shorts.
138-142 RESERVED
FAULT CODES 149 THROUGH 165 ARE OEM SPECIFIC FAULT CODES.
143 Internal fault: Flame bias out of range 1 Contact the service professional. L
144 Internal fault: Flame bias out of range 2 Contact the service professional. L
145 Internal fault: Flame bias out of range 3 Contact the service professional. L
146 Internal fault: Flame bias out of range 4 Contact the service professional. L
147 Internal fault: Flame bias out of range 5 Contact the service professional. L
148 Internal fault: Flame bias out of range 6 Contact the service professional. L
149 Flame detected OEM Specic
errors.
2. Check High Fire Switch to assure proper function
(not welded or jumpered).
3. Manually drive the motor to the High Fire position
and adjust the HF switch while in this position and verify voltage through the switch to the HFS input with a voltmeter.
4. If steps 1-3 are correct and the fault persists,
replace the module.
errors.
2. Check Low Fire Switch to assure proper function
(not welded or jumpered).
3. Manually drive the motor to the High Fire position
and adjust the LF switch while in this position and verify voltage through the switch to the LFS input with a voltmeter.
4. If steps 1-3 are correct and the fault persists,
replace the module.
errors.
2. Check VFDs ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.
errors.
2. Check Interrupted Airow switch(es) to assure
proper function.
3. Verify voltage through the airow switch to the
IAS input with a voltmeter.
4. If steps 1-3 are correct and the fault persists,
replace the module.
2. Check Interlock (ILK) switches to assure proper
function.
3. Verify voltage through the interlock string to the
interlock input with a voltmeter.
4. If steps 1-3 are correct and the fault persists,
replace the module.
1. Holds if ame detected during Safe Start check
up to Flame Establishing period.
H
H
H or L
H
H
H or L
65
Page 66
CODE DESCRIPTION RECOMMENDED TROUBLESHOOTING OF
NOTE
LOCKOUT CODES
150 Flame not detected OEM Specic
1. Sequence returns to standby and restarts
sequence at the beginning of Purge after the HF switch opens. If ame detected during Safe Start check up to Flame Establishing period.
151 High re switch ON OEM Specic
1. Check wiring and correct any potential wiring errors.
2. Check High Fire Switch to assure proper function
(not welded or jumpered).
3. Manually drive the motor to the High Fire position and adjust the HF switch while in this position and verify voltage through the switch to the HFS input with a voltmeter.
4. If steps 1-3 are correct and the fault persists, replace the module.
152 Combustion pressure ON OEM Specic
153 Combustion pressure Off H or L
154 Purge Fan switch On OEM Specic
155 Purge Fan switch Off H
156 Combustion pressure and Flame ON OEM Specic
157 Combustion pressure and Flame OFF L
158 Main valve ON OEM Specic
159 Main valve OFF L
160 Ignition ON OEM Specic
161 Ignition OFF L
162 Pilot valve ON OEM Specic
163 Pilot valve OFF L
1. Check wiring and correct any errors.
2. Inspect the Combustion Pressure Switch to make
sure it is working correctly.
3. Reset and sequence the relay module.
4. During STANDBY and PREPURGE, measure
the voltage between Terminal J6-5 and L2 (N). Supply voltage should be present. If not, the lockout switch is defective and needs replacing.
5. If the fault persists, replace the relay module.
1. Purge fan switch is on when it should be off.
1. Check that ame is not present in the combustion
chamber. Correct any errors.
2. Make sure that the ame detector is wired to the correct terminal.
3. Make sure the F & G wires are protected from stray noise pickup.
4. Reset and sequence the module, if code reappears, replace the ame detector.
1. Check Main Valve terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persist,
replace the module.
1. Check Ignition terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persist,
replace the module.
1. Check Pilot Valve terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persist,
replace the module.
H
H or L
H or L
H or L
H or L
L
L
L
66
Page 67
CODE DESCRIPTION RECOMMENDED TROUBLESHOOTING OF
LOCKOUT CODES
164 Block intake ON OEM Specic
165 Block intake OFF L
166-171 RESERVED
Feedback
172 Main relay feedback incorrect Internal Fault.
173 Pilot relay feedback incorrect L
174 Safety relay feedback incorrect L
175 Safety relay open L
176 Main relay ON at safe start check L
177 Pilot relay ON at safe start check L
178 Safety relay ON at safe start check L
179-183 RESERVED
Parameter Faults
184 Invalid BLOWER/HSI output setting 1. Return to Conguration mode and recheck
185 Invalid Delta T limit enable setting L
186 Invalid Delta T limit response setting L
187 Invalid DHW high limit enable setting L
188 Invalid DHW high limit response setting L
189 Invalid Flame sensor type setting L
190 Invalid interrupted air switch enable setting L
191 Invalid interrupted air switch start check enable
setting
192 Invalid igniter on during setting L
193 Invalid ignite failure delay setting L
194 Invalid ignite failure response setting 1. Return to Conguration mode and recheck
195 Invalid ignite failure retries setting L
196 Invalid ignition source setting L
197 Invalid interlock open response setting L
198 Invalid interlock start check setting L
199 Invalid LCI enable setting L
200 Invalid lightoff rate setting L
201 Invalid lightoff rate proving setting L
202 Invalid Main Flame Establishing Period time L
203 Invalid MFEP ame failure response setting L
204 Invalid NTC sensor type setting L
205 Invalid Outlet high limit response setting L
206 Invalid Pilot Flame Establishing Period setting L
207 Invalid PII enable setting L
208 Invalid pilot test hold setting L
209 Invalid Pilot type setting L
210 Invalid Postpurge time setting L
211 Invalid Power up with lockout setting L
1. Check wiring and correct any errors.
2. Inspect the Block Intake Switch to make sure it is
working correctly.
3. Reset and sequence the module.
4. During Standby and Purge, measure the voltage
across the switch. Supply voltage should be present. If not, the Block Intake Switch is defective and needs replacing.
5. If the fault persists, replace the relay module.
1. Reset Module.
2. If fault repeats, replace module.
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
NOTE
L
L
L
L
L
67
Page 68
CODE DESCRIPTION RECOMMENDED TROUBLESHOOTING OF
LOCKOUT CODES
212 Invalid Preignition time setting 1. Return to Conguration mode and recheck
213 Invalid Prepurge rate setting L
214 Invalid Prepurge time setting L
215 Invalid Purge rate proving setting L
216 Invalid Run ame failure response setting L
217 Invalid Run stabilization time setting L
218 Invalid Stack limit enable setting L
219 Invalid Stack limit response setting L
220 Uncongured Delta T limit setpoint setting L
221 Uncongured DHW high limit setpoint setting L
222 Uncongured Outlet high limit setpoint setting L
223 Uncongured Stack limit setpoint setting L
224 Invalid DHW demand source setting L
225 Invalid Flame threshold setting L
226 Invalid Outlet high limit setpoint setting L
227 Invalid DHW high limit setpoint setting L
228 Invalid Stack limit setpoint setting L
229 Invalid Modulation output setting L
230 Invalid CH demand source setting L
231 Invalid Delta T limit delay setting L
232 Invalid Pressure sensor type setting L
233 Invalid IAS closed response setting L
234 Invalid Outlet high limit enable setting Contact the service professional. L
235 Invalid Outlet connector type setting Contact the service professional. L
236 Invalid Inlet connector type setting Contact the service professional. L
237 Invalid DHW connector type setting Contact the service professional. L
238 Invalid Stack connector type setting Contact the service professional. L
239 Invalid S2 (J8-6) connector type setting Contact the service professional. L
240 Invalid S5 (J8-11) connector type setting Contact the service professional. L
241 Exchanger sensor not allowed with stack
connector setting
242 Invalid DHW auto detect conguration Not Applicable. L
243 Invalid UV with spark interference not compatible
with Ignitor on throughout PFEP
244 Internal fault: Safety relay test invalid state Contact the service professional. L
245 Invalid Outlet connector type setting for Trise Contact the service professional. L
246 4-20mA cannot be used for both modulation and
setpoint control
247 Invalid ILK bounce detection enable Not Applicable. L
248 Invalid forced recycle interval Not Applicable. L
249 STAT cannot be demand source when Remote
Stat is enabled
250 Invalid Fan speed error response 1. Check fan cables secured properly. If fault
251-255 RESERVED
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
Not Applicable. L
Contact the service professional. L
Contact the service professional. L
Not Applicable. L
persists contact the service professional.
NOTE
L
L
68
Page 69
TABLE 25. ALERTS
CODE DESCRIPTION
EE Management Faults
0 None (No alert)
1 Alert PCB was restored from factory defaults
2 Safety conguration parameters were restored
from factory defaults
3 Conguration parameters were restored from
factory defaults
4 Invalid Factory Invisibility PCB was detected
5 Invalid Factory Range PCB was detected
6 Invalid range PCB record has been dropped
7 EEPROM lockout history was initialized
8 Switched application annunciation data blocks
9 Switched application conguration data blocks
10 Conguration was restored from factory defaults
11 Backup conguration settings was restored from
active conguration
12 Annunciation conguration was restored from
factory defaults
13 Annunciation conguration was restored from
backup
14 Safety group verication table was restored from
factory defaults
15 Safety group verication table was updated
16 Invalid Parameter PCB was detected
17 Invalid Range PCB was detected
System Parameter Errors
18 Alarm silence time exceeded maximum
19 Invalid safety group verication table was detected
20 Backdoor Password could not be determined
21 Invalid safety group verication table was not
accepted
22 CRC errors were found in application conguration
data blocks
23 Backup Alert PCB was restored from active one
24 RESERVED
25 Lead Lag operation switch was turned OFF
26 Lead Lag operation switch was turned ON
27 Safety processor was reset
28 Application processor was reset
29 Burner switch was turned OFF
30 Burner switch was turned ON
31 Program Module (PM) was inserted into socket
32 Program Module (PM) was removed from socket
33 Alert PCB was congured
34 Parameter PCB was congured
35 Range PCB was congured
36 Program Module (PM) incompatible with product
was inserted into socket
CODE DESCRIPTION
37 Program Module application parameter revision
differs from application processor
38 Program Module safety parameter revision differs
from safety processor
39 PCB incompatible with product contained in
Program Module
40 Parameter PCB in Program Module is too large for
product
41 Range PCB in Program Module was too large for
product
42 Alert PCB in Program Module was too large for
product
43 IAS start check was forced on due to IAS enabled
System Operation Faults
44 Low voltage was detected in safety processor
45 High line frequency occurred
46 Low line frequency occurred
47 Invalid subsystem reset request occurred
48 Write large enumerated Modbus register value
was not allowed
49 Maximum cycle count was reached
50 Maximum hours count was reached
51 Illegal Modbus write was attempted
52 Modbus write attempt was rejected (NOT
ALLOWED)
53 Illegal Modbus read was attempted
54 Safety processor brown-out reset occurred
55 Application processor watchdog reset occurred
56 Application processor brown-out reset occurred
57 Safety processor watchdog reset occurred
58 Alarm was reset by the user at the control
Demand/Rate Command Faults
59 Burner control ring rate was > absolute max rate
60 Burner control ring rate was < absolute min rate
61 Burner control ring rate was invalid, % vs. RPM
62 Burner control was ring with no fan request
63 Burner control rate (nonring) was > absolute max
rate
64 Burner control rate (nonring) was < absolute min
rate
65 Burner control rate (nonring) was absent
66 Burner control rate (nonring) was invalid, %
vs.RPM
67 Fan off cycle rate was invalid, % vs. RPM
68 Setpoint was overridden due to sensor fault
69 Modulation was overridden due to sensor fault
70 No demand source was set due to demand priority
conicts
71-73 RESERVED
69
Page 70
CODE DESCRIPTION
Fan Parameter Errors
74 Periodic Forced Recycle
75 Absolute max fan speed was out of range
76 Absolute min fan speed was out of range
77 Fan gain down was invalid
78 Fan gain up was invalid
79 Fan minimum duty cycle was invalid
80 Fan pulses per revolution was invalid
81 Fan PWM frequency was invalid
82-83 RESERVED
Modulation Parameter Errors
84 Lead Lag CH 4-20 mA water temperature setting
85 No Lead Lag add stage error threshold was
congured
86 No Lead Lag add stage detection time was
congured
87 No Lead Lag drop stage error threshold was
congured
88 No Lead Lag drop stage detection time was
congured
89 RESERVED
90 Modulation output type was invalid
91 Firing rate control parameter was invalid
92 Forced rate was out of range vs. min/max
modulation
93 Forced rate was invalid, % vs. RPM
94 Slow start ramp value was invalid
95 Slow start degrees value was invalid
96 Slow start was ended due to outlet sensor fault
97 Slow start was end due to reference setpoint fault
98 CH max modulation rate was invalid, % vs. RPM
99 CH max modulation rate was > absolute max rate
100 CH modulation range (max minus min) was too
small (< 4% or 40 RPM)
101 DHW max modulation rate was invalid, % vs.RPM
102 DHW max modulation rate was > absolute max
rate
103 DHW modulation range (max minus min) was too
small (< 4% or 40 RPM)
104 Min modulation rate was < absolute min rate
105 Min modulation rate was invalid, % vs. RPM
106 Manual rate was invalid, % vs. RPM
107 Slow start enabled, but forced rate was invalid
108 Analog output hysteresis was invalid
109 Analog modulation output type was invalid
110 IAS open rate differential was invalid
111 IAS open step rate was invalid
112 MIX max modulation rate was invalid, % vs. RPM
113 MIX max modulation rate was >absolute max or <
absolute min rates
CODE DESCRIPTION
114 MIX modulation range (max minus min) was too
small (< 4% or 40 RPM)
Modulation Operation Faults
115 Fan was limited to its minimum duty cycle
116 Manual rate was > CH max modulation rate
117 Manual rate was > DHW max modulation rate
118 Manual rate was < min modulation rate
119 Manual rate in Standby was > absolute max rate
120 Modulation commanded rate was > CH max
modulation rate
121 Modulation commanded rate was > DHW max
modulation rate
122 Modulation commanded rate was < min
modulation rate
123 Modulation rate was limited due to outlet limit
124 Modulation rate was limited due to Delta-T limit
125 Modulation rate was limited due to stack limit
126 Modulation rate was limited due to
anticondensation
127 Fan Speed out of range in RUN
128 Modulation rate was limited due to IAS was open
129 Slow start ramp setting of zero will result in no
modulation rate change
130 No forced rate was congured for slow start ramp
CH parameter Errors
131 CH demand source was invalid
132 CH P-gain was invalid
133 CH I-gain was invalid
134 CH D-gain was invalid
135 CH OFF hysteresis was invalid
136 CH ON hysteresis was invalid
137 CH sensor type was invalid
138 CH hysteresis step time was invalid
139 CH remote control parameter was invalid
140 CH ODR not allowed with remote control
141 Steam P-gain was invalid
142 Steam I-gain was invalid
143 Steam D-gain was invalid
144 Steam OFF hysteresis was invalid
145 Steam ON hysteresis was invalid
CH Operation Faults
146 CH control was suspended due to fault
147 CH header temperature was invalid
148 CH outlet temperature was invalid
149 CH steam pressure was invalid
CH Parameter errors (continued)
150 Steam setpoint source parameter was invalid
151 Minimum water temperature parameter was
greater than setpoint
70
Page 71
CODE DESCRIPTION
152 Minimum water temperature parameter was
greater than time of day setpoint
153 Minimum pressure parameter was greater than
setpoint
154 Minimum pressure parameter was greater than
time of day setpoint
155 CH modulation rate source parameter was invalid
156 Steam modulation rate source parameter was
invalid
DHW Parameter Errors
157 DHW demand source was invalid
158 DHW P-gain was invalid
159 DHW I-gain was invalid
160 DHW D-gain was invalid
161 DHW OFF hysteresis was invalid
162 DHW ON hysteresis was invalid
163 DHW hysteresis step time was invalid
164 DHW sensor type was invalid
165 Inlet sensor type was invalid for DHW
166 Outlet sensor type was invalid for DHW
167 DHW Storage OFF hysteresis was invalid
168 DHW Storage ON hysteresis was invalid
169 DHW modulation sensor type was invalid
170 DHW modulation sensor was not compatible for
AUTO mode
DHW Operation Faults
171 DHW control was suspended due to fault
172 DHW temperature was invalid
173 DHW inlet temperature was invalid
174 DHW outlet temperature was invalid
175 DHW high limit must be disabled for AUTO mode
176 DHW sensor type was not compatible for AUTO
mode
177 DHW priority source setting was invalid
178 DHW priority method setting was invalid
CH Operation Faults (continued)
179 CH S5 (J8 terminal 11) sensor was invalid
180 CH inlet temperature was invalid
181 CH S10 (J10 terminal 7) sensor was invalid
182 Lead Lag CH setpoint source was invalid
Lead Lag Parameter errors
183 Lead Lag P-gain was invalid
184 Lead Lag I-gain was invalid
185 Lead Lag D-gain was invalid
186 Lead Lag OFF hysteresis was invalid
187 Lead Lag ON hysteresis was invalid
188 Lead Lag slave enable was invalid
189 Lead Lag hysteresis step time was invalid
190 No Lead lag Modbus port was assigned
CODE DESCRIPTION
191 Lead Lag base load common setting was invalid
192 Lead Lag DHW demand switch setting was
193 Lead Lag Mix demand switch setting was invalid
194 Lead Lag modulation sensor setting was invalid
195 Lead Lag backup modulation sensor setting was
invalid
196 Lead Lag slave mode setting was invalid
197 Lead Lag rate allocation setting was invalid
198 Lead selection setting was invalid
199 Lag selection setting was invalid
200 Lead Lag slave return setting was invalid
201 Lead Lag add stage method setting was invalid
202 STAT may not be a Lead Lag CH demand source
when Remote Stat is enabled
203 Lead Lag base load rate setting was invalid
Lead Lag Operation Faults
204 Lead Lag master was suspended due to fault
205 Lead Lag slave was suspended due to fault
206 Lead Lag header temperature was invalid
207 Lead Lag was suspended due to no enabled
Program Module installed
208 Lead Lag slave session has timed out
209 Too many Lead Lag slaves were detected
210 Lead Lag slave was discovered
211 Incompatible Lead Lag slave was discovered
212 No base load rate was set for Lead Lag slave
213 Lead Lag slave unable to re before demand to
re delay expired
214 Adding Lead Lag slave aborted due to add
requirement change
215 No Lead Lag slaves available to service demand
216 No Lead Lag active service was set due to
demand priority conicts
217 No Lead Lag add stage method was specied
218 No Lead Lag drop stage method was specied
219 Using backup lead lag header sensor due to
sensor failure
Frost Protection Faults
220 Lead Lag frost protection rate was invalid
221 Lead Lag drop stage method setting was invalid
222 CH frost protection temperature was invalid
223 CH frost protection inlet temperature was invalid
224 DHW frost protection temperature was invalid
225-226 RESERVED
227 DHW priority override time was not derated due to
invalid outdoor temperature
228 Warm weather shutdown was not checked due to
invalid outdoor temperature
229 Lead Lag slave communication timeout
230 RESERVED
71
Page 72
CODE DESCRIPTION
231 Lead Lag CH setpoint was invalid
232 Lead Lag CH time of day setpoint was invalid
233 LL outdoor temperature was invalid
234 Lead Lag ODR time of day setpoint was invalid
235 Lead Lag ODR time of day setpoint exceeded
normal setpoint
236 Lead Lag ODR max outdoor temperature was
invalid
237 Lead Lag ODR min outdoor temperature was
invalid
238 Lead Lag ODR low water temperature was invalid
239 Lead Lag ODR outdoor temperature range was
too small (minimum 12°C / 22°F)
240 Lead Lag ODR water temperature range was too
small (minimum 12°C / 22°F)
241 Lead Lag DHW setpoint was invalid
242 Lead Lag Mix setpoint was invalid
243 Lead Lag CH demand switch was invalid
244 Lead Lag CH setpoint source was invalid
245 RESERVED
246 CH setpoint was invalid
247 CH time of day setpoint was invalid
248 CH outdoor temperature was invalid
249 CH ODR time of day setpoint was invalid
250 CH ODR time of day setpoint exceeds normal
setpoint
251 CH max outdoor setpoint was invalid
252 CH min outdoor setpoint was invalid
253 CH min water setpoint was invalid
254 CH outdoor temperature range was too small
255 CH water temperature range was too small
256 Steam setpoint was invalid
257 Steam time of day setpoint was invalid
258 Steam minimum pressure was invalid
259 CH ODR min water temperature was invalid
260 RESERVED
261 DHW setpoint was invalid
262 DHW time of day setpoint was invalid
263 DHW storage setpoint was invalid
264 STAT may not be a DHW demand source when
Remote Stat is enabled
265-266 RESERVED
267 STAT may not be a CH demand source when
Remote Stat is enabled
268 CH 4mA water temperature setting was invalid
269 CH 20mA water temperature setting was invalid
270 Steam 4mA water temperature setting was invalid
271 Steam 20mA water temperature setting was invalid
272 Abnormal Recycle: Pressure sensor fault
273 Abnormal Recycle: Safety relay drive test failed
CODE DESCRIPTION
274 Abnormal Recycle: Demand off during Pilot Flame
Establishing Period
275 Abnormal Recycle: LCI off during Drive to Purge
Rate
276 Abnormal Recycle: LCI off during Measured Purge
Time
277 Abnormal Recycle: LCI off during Drive to Lightoff
Rate
278 Abnormal Recycle: LCI off during Pre-Ignition test
279 Abnormal Recycle: LCI off during Pre-Ignition time
280 Abnormal Recycle: LCI off during Main Flame
Establishing Period
281 Abnormal Recycle: LCI off during Ignition period
282 Abnormal Recycle: Demand off during Drive to
Purge Rate
283 Abnormal Recycle: Demand off during Measured
Purge Time
284 Abnormal Recycle: Demand off during Drive to
Lightoff Rate
285 Abnormal Recycle: Demand off during Pre-Ignition
test
286 Abnormal Recycle: Demand off during Pre-Ignition
time
287 Abnormal Recycle: Flame was on during Safe
Check
288 Abnormal Recycle: Flame was on during Drive to
Purge Rate
289 Abnormal Recycle: Flame was on during
Measured Purge Time
290 Abnormal Recycle: Flame was on during Drive to
Lightoff Rate
291 Abnormal Recycle: Flame was not on at end of
Ignition period
292 Abnormal Recycle: Flame was lost during Main
Flame Establishing Period
293 Abnormal Recycle: Flame was lost early in Run
294 Abnormal Recycle: Flame was lost during Run
295 Abnormal Recycle: Leakage test failed
296 Abnormal Recycle: Interrupted air ow switch was
off during Drive to Purge Rate
297 Abnormal Recycle: Interrupted air ow switch was
off during Measured Purge Time
298 Abnormal Recycle: Interrupted air ow switch was
off during Drive to Lightoff Rate
299 Abnormal Recycle: Interrupted air ow switch was
off during Pre-Ignition test
300 Abnormal Recycle: Interrupted air ow switch was
off during Pre-Ignition time
301 Abnormal Recycle: Interrupted air ow switch was
off during Main Flame Establishing Period
302 Abnormal Recycle: Ignition failed due to
interrupted air ow switch was off
303 Abnormal Recycle: ILK off during Drive to Purge
Rate
72
Page 73
CODE DESCRIPTION
304 Abnormal Recycle: ILK off during Measured Purge
Time
305 Abnormal Recycle: ILK off during Drive to Lightoff
Rate
306 Abnormal Recycle: ILK off during Pre-Ignition test
307 Abnormal Recycle: ILK off during Pre-Ignition time
308 Abnormal Recycle: ILK off during Main Flame
Establishing Period
309 Abnormal Recycle: ILK off during Ignition period
310 Run was terminated due to ILK was off
311 Run was terminated due to interrupted air ow
switch was off
312 Stuck reset switch
313 Run was terminated due to fan failure
314 Abnormal Recycle: Fan failed during Drive to
Purge Rate
315 Abnormal Recycle: Fan failed during Measured
Purge Time
316 Abnormal Recycle: Fan failed during Drive to
Lightoff Rate
317 Abnormal Recycle: Fan failed during Pre-Ignition
test
318 Abnormal Recycle: Fan failed during Pre-Ignition
time
319 Abnormal Recycle: Fan failed during Ignition
period
320 Abnormal Recycle: Fan failed during Main Flame
Establishing Period
321 Abnormal Recycle: Main Valve off after 10
seconds of RUN
322 Abnormal Recycle: Pilot Valve off after 10 seconds
of RUN
323 Abnormal Recycle: Safety Relay off after 10
seconds of RUN
324 Abnormal Recycle: Hardware ame bias
325 Abnormal Recycle: Hardware static ame
326 Abnormal Recycle: Hardware ame current invalid
327 Abnormal Recycle: Hardware ame rod short
328 Abnormal Recycle: Hardware invalid power
329 Abnormal Recycle: Hardware invalid AC line
330 Abnormal Recycle: Hardware SLO ame ripple
330 Abnormal Recycle: Hardware SLO ame sample
332 Abnormal Recycle: Hardware SLO ame bias
range
333 Abnormal Recycle: Hardware SLO ame bias heat
334 Abnormal Recycle: Hardware SLO spark stuck
335 Abnormal Recycle: Hardware SLO spark changed
336 Abnormal Recycle: Hardware SLO static ame
337 Abnormal Recycle: Hardware SLO rod shorted
338 Abnormal Recycle: Hardware SLO AD linearity
339 Abnormal Recycle: Hardware SLO bias not set
340 Abnormal Recycle: Hardware SLO bias shorted
CODE DESCRIPTION
341 Abnormal Recycle: Hardware SLO electronics
342 Abnormal Recycle: Hardware processor clock
343 Abnormal Recycle: Hardware AC phase
344 Abnormal Recycle: Hardware A2D mismatch
345 Abnormal Recycle: Hardware VSNSR A2D
346 Abnormal Recycle: Hardware 28V A2D
347 Abnormal Recycle: Hardware HFS IAS shorted
348 Abnormal Recycle: Hardware PII INTLK shorted
349 Abnormal Recycle: Hardware HFS LCI shorted
350 Abnormal Recycle: Hardware HFS LFS shorted
351 Abnormal Recycle: Invalid zero crossing
352 Abnormal Recycle: fault stack sensor
353 Abnormal Recycle: stack limit
354 Abnormal Recycle: delta T limit
355 Abnormal Recycle: fault outlet sensor
356 Abnormal Recycle: outlet high limit
357 Abnormal Recycle: fault DHW sensor
358 Abnormal Recycle: DHW high limit
359 Abnormal Recycle: fault inlet sensor
360 Abnormal Recycle: Check Parameters Failed
Internal Errors
361 Internal error: No factory parameters were
detected in control
362 Internal error: PID iteration frequency was invalid
363 Internal error: Demand-Rate interval time was
invalid
364 Internal error: Factory calibration parameter for
modulation was invalid
365 Internal error: CH PID P-scaler was invalid
366 Internal error: CH PID I-scaler was invalid
367 Internal error: CH PID D-scaler was invalid
368 Internal error: DHW PID P-scaler was invalid
369 Internal error: DHW PID I-scaler was invalid
370 Internal error: DHW PID D-scaler was invalid
371 Internal error: Lead Lag master PID P-scaler was
invalid
372 Internal error: Lead Lag master PID I-scaler was
invalid
373 Internal error: Lead Lag master PID D-scaler was
invalid
374 Abnormal Recycle: Hardware ame bias high
375 Abnormal Recycle: Hardware ame bias low
376 Abnormal Recycle: Hardware ame bias delta high
377 Abnormal Recycle: Hardware ame bias delta low
378 Abnormal Recycle: Hardware ame bias dynamic
high
379 Abnormal Recycle: Hardware ame bias dynamic
low
380 Abnormal Recycle: Fan Speed Not Proven
381 Abnormal Recycle: Fan Speed Range Low
73
Page 74
CODE DESCRIPTION
382 Abnormal Recycle: Fan Speed Range High
383-450 RESERVED
Circulator Errors
451 Circulator control was invalid
452 Circulator P-gain was invalid
453 Circulator I-gain was invalid
454 Circulator temperature was invalid
455 Circulator outlet temperature was invalid
456 Circulator inlet temperature was invalid
457 Circulator outdoor temperature was invalid
458 Circulator sensor choice was invalid
459 Circulator PID setpoint was invalid
Debug Faults
460 LCI lost in run
461 Abnormal Recycle: Demand lost in run from
application
462 Abnormal Recycle: Demand lost in run due to high
limit
463 Abnormal Recycle: Demand lost in run due to no
ame
464 LCI lost in Combustion Pressure Establishing
Period
465 LCI lost in Combustion Pressure Stabilization
Period
466 RESERVED
Internal Data Faults
467 Internal error: EEPROM write was attempted
before EEPROM was initialized
468 Internal error: EEPROM cycle count address was
invalid
469 Internal error: EEPROM days count address was
invalid
470 Internal error: EEPROM hours count address was
invalid
471 Internal error: Lockout record EEPROM index was
invalid
472 Internal error: Request to write PM status was
invalid
473 Internal error: PM parameter address was invalid
474 Internal error: PM safety parameter address was
invalid
475 Internal error: Invalid record in lockout history was
removed
476 Internal error: EEPROM write buffer was full
477 Internal error: Data too large was not written to
EEPROM
478 Internal error: Safety key bit 0 was incorrect
479 Internal error: Safety key bit 1 was incorrect
480 Internal error: Safety key bit 2 was incorrect
481 Internal error: Safety key bit 3 was incorrect
CODE DESCRIPTION
482 Internal error: Safety key bit 4 was incorrect
483 Internal error: Safety key bit 5 was incorrect
484 Internal error: Safety key bit 6 was incorrect
485 Internal error: Safety key bit 7 was incorrect
486 Internal error: Safety key bit 8 was incorrect
487 Internal error: Safety key bit 9 was incorrect
488 Internal error: Safety key bit 10 was incorrect
489 Internal error: Safety key bit 11 was incorrect
490 Internal error: Safety key bit 12 was incorrect
491 Internal error: Safety key bit 13 was incorrect
492 Internal error: Safety key bit 14 was incorrect
493 Internal error: Safety key bit 15 was incorrect
494 Internal error: Safety relay timeout
495 Internal error: Safety relay commanded off
496 Internal error: Unknown safety error occurred
497 Internal error: Safety timer was corrupt
498 Internal error: Safety timer was expired
499 Internal error: Safety timings
500 Internal error: Safety shutdown
501 RESERVED
MIX Errors
502 Mix setpoint was invalid
503 Mix time of day setpoint was invalid
504 Mix outdoor temperature was invalid
505 Mix ODR time of day setpoint was invalid
506 Mix ODR time of day setpoint exceeds normal
setpoint
507 Mix ODR max outdoor temperature was invalid
508 Mix ODR min outdoor temperature was invalid
509 Mix ODR low water temperature was invalid
510 Mix ODR outdoor temperature range was invalid
511 Mix ODR water temperature range was invalid
512 Mix demand switch was invalid
513 Mix ON hysteresis was invalid
514 Mix OFF hysteresis was invalid
515 Mix ODR min water temperature was invalid
516 Mix hysteresis step time was invalid
517 Mix P-gain was invalid
518 Mix I-gain was invalid
519 Mix D-gain was invalid
520 Mix control was suspended due to fault
521 Mix S10 (J10-7) temperature was invalid
522 Mix outlet temperature was invalid
523 Mix inlet temperature was invalid
524 Mix S5 (J8-11) temperature was invalid
525 Mix modulation sensor type was invalid
526 Mix ODR min water temperature setpoint was
invalid
74
Page 75
CODE DESCRIPTION
527 Mix circulator sensor was invalid
528 Mix ow control was invalid
529 Mix temperature was invalid
530 Mix sensor was invalid
531 Mix PID setpoint was invalid
532 STAT may not be a Mix demand source when
Remote Stat is enabled
533-539 RESERVED
540 Delta T inlet/outlet enable was invalid
541 Delta T exchanger/outlet enable was invalid
542 Delta T inlet/exchanger enable was invalid
543 Delta T inlet/outlet degrees was out of range
544 Delta T exchanger/outlet degrees was out of range
545 Delta T inlet/exchanger degrees was out of range
546 Delta T response was invalid
547 Delta T inversion limit response was invalid
548 Delta T rate limit enable was invalid
549 Delta T exchanger/outlet wasn't allowed due to
stack limit setting
550 Delta T inlet/outlet limit was exceeded
551 Delta T exchanger/outlet limit was exceeded
552 Delta T inlet/exchanger limit was exceeded
553 Inlet/outlet inversion occurred
554 Exchanger/outlet inversion occurred
555 Inlet/exchanger inversion occurred
556 Delta T exchanger/outlet wasn't allowed due to
stack connector setting
557 Delta T inlet/exchanger wasn't allowed due to
stack limit setting
558 Delta T inlet/exchanger wasn't allowed due to
stack connector setting
559 Delta T delay was not congured for recycle
response
T Rise Errors
560 Outlet T-rise enable was invalid
561 Heat exchanger T-rise enable was invalid
562 T-rise degrees was out of range
563 T-rise response was invalid
564 Outlet T-rise limit was exceeded
565 Heat exchanger T-rise limit was exceeded
566 Heat exchanger T-rise wasn't allowed due to stack
limit setting
567 Heat exchanger T-rise wasn't allowed due to stack
connector setting
568 Outlet T-rise wasn't allowed due to outlet
connector setting
569 T-rise delay was not congured for recycle
response
Heat Exchanger High Limit Errors
570 Heat exchanger high limit setpoint was out of
range
CODE DESCRIPTION
571 Heat exchanger high limit response was invalid
572 Heat exchanger high limit was exceeded
573 Heat exchanger high limit wasn't allowed due to
stack limit setting
574 Heat exchanger high limit wasn't allowed due to
stack connector setting
575 Heat exchanger high limit delay was not
congured for recycle response
Pump Errors
576 CH pump output was invalid
577 DHW pump output was invalid
578 Boiler pump output was invalid
579 Auxiliary pump output was invalid
580 System pump output was invalid
581 Mix pump output was invalid
582-589 RESERVED
DHW Plate Heat Exchanger Errors
590 DHW plate preheat setpoint was invalid
591 DHW plate preheat ON hysteresis was invalid
592 DHW plate preheat OFF hysteresis was invalid
593 Tap detect degrees was out of range
594 Tap detect ON hysteresis was invalid
595 Inlet - DHW tap stop degrees was out of range
596 Outlet - Inlet tap stop degrees was out of range
597 DHW tap detect on threshold was invalid
598 DHW plate preheat detect on threshold was invalid
599 DHW plate preheat detect off threshold was invalid
75
Page 76

MAINTENANCE PROCEDURES

MAINTENANCE SCHEDULES

Yearly procedures for Service Technician:
• Check for reported problems.
• Check the interior; clean and vacuum if needed.
• Clean the condensate trap and ll with fresh water.
• Check for water/gas/ue/ condensate leaks.
• Ensure ue and air lines in good condition and sealed
tight
• Check system water pressure/system piping/expansion
tank
• Check control settings.
• Check spark igniter and ame sensors. Clear and clean any deposits.
• Check wiring and connections.
• Perform start-up checkout and performance verication.
• Flame inspection (stable, uniform)
• Flame signal (at least 10 microamps at high re)
• Clean the heat exchanger if ue temperature is more than 54°F (30°C) above return water temperature.
• Test low water ow conditions.
• Clean the heat exchanger.
• Remove and clean burner using compressed air.
Maintenance by Owner:
Daily:
• Check boiler area .
• Check pressure/temperature gauge.
Monthly:
• Check vent piping.
• Check air intake piping (Direct Vent).
• Check air and vent termination screens.
• Check relief valve.
• Check condensate drain system.
• Check automatic air vents .
Every 6 months:
• Check boiler piping (gas and water) for leaks.
• Check and operate the pressure relief valve.
End of season months:
• Shut the boiler down (unless boiler used for domestic hot water)
Make sure the maintenance of the boiler must be performed to assure maximum boiler efciency and reliability. Failure to service and maintain the boiler and system could result in equipment failure.
Make sure to turn off power to the boiler before any service operation on the boiler except as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock, causing severe personal injury or death.
INSPECT BOILER AREA
1. Verify that boiler area is free of any combustible materials,
gasoline and other ammable vapors and liquids.
2. Verify that air intake area is free of any of the contaminants.
If any of these are present in the boiler intake air vicinity, they must be removed. If they cannot be removed, reinstall the air and vent lines per this manual.
Inspect boiler interior:
1. Remove the front access cover and inspect the interior of
the boiler.
2. Vacuum any sediment from inside the boiler and components.
Remove any obstructions.

GENERAL MAINTENANCE

This is a pre-mix burner system. The ame is not supposed to be directly on the burner. The ame should be just above the burner deck approximately 1/8” and blue in color, see Figure 77.
FIGURE 77. BURNER FLAMES
Visually check ame characteristics through the view port located on the top head of the boiler. Figure 77 shows the normal ame condition.
These boilers are designed to give many years of efcient and satisfactory service when properly operated and maintained. To assure continued good performance, the following recommendations are made.
The area around the unit should be kept clean and free from lint and debris. Sweeping the oor around the boiler should be done carefully. This will reduce the dust and dirt which may enter the burner and heat exchanger, causing improper combustion and
sooting.
MAIN BURNER
Check main burner every three months for proper ame characteristics. The main burner should display the following characteristics:
•Provide complete combustion of gas.
Cause rapid ignition and carry over of ame across entire burner.
Give reasonably quiet operation during initial ignition, operation
and extinction.
Cause no excessive lifting of flame from burner ports.
76
Page 77
If the preceding burner characteristics are not evident, check for accumulation of lint or other foreign material that restricts or blocks the air openings to the burner or boiler. To check burners:
1. Shut off all gas and electricity to unit. Allow unit to cool.
2. Remove main burners from unit.
3. Check that burner ports are free of foreign matter.
4. Clean burner with vacuum cleaner. Do not distort burner
ports.
5. Reinstall burners in unit. Ensure that all the screws on the
burner ange are tightened securely so that the gasket will provide a good seal.
6. Also check for good ow of combustion and ventilating air
to the unit.
After placing the boiler in operation, check the ignition system safety shut-off devices for proper operation. To accomplish this with the main burner operating, close the valve on the manifold. Within four seconds the main burners should extinguish. If this does not occur immediately, discontinue gas supply by closing main manual shut-off and call a qualied serviceman to correct the situation. If the burners extinguish, then light boiler in accordance with lighting and operating instructions.
5. Loosen the seven bolts on the blower adapter at the base
and move the burner ground wire (Green) aside.
6. Lift the blower adapter and remove the manifold assembly
up from the 6 studs located on the cover plate and remove
the burner gasket.
7. Remove any loose foreign material such as dust or lint with a
vacuum. Check all ports for blockage. Dislodge any foreign material causing blockage. Remove any soot or carbon deposits with a rag making sure to remove any lint left on the burner by vacuuming again.
8. Reverse the steps to reassemble the unit.
9. Restore electrical power and gas supply to the boiler.
• Put the boiler back in operation by following the Lighting and Operating instructions in this manual.
• Check for gas leaks and proper boiler and vent
operation.
PRESSURE RELIEF VALVE
The pressure relief valve should be opened at least twice a year to check its working condition. This will aid in assuring proper pressure relief protection. Lift the lever at the top of the valve several times until the valve seats properly and operates freely.
Any safety devices including low water cutoffs used in conjunction with this boiler should receive periodic (every six months) inspection to assure proper operation. A low water cutoff device of the oat type should be ushed every six months. Periodic checks, at least twice a year, should be made for water leaks.
More frequent inspections may be necessary depending on water conditions.
The boiler-mounted gas and electrical controls have been designed to give both dependable service and long life. However, malfunction can occur, as with any piece of equipment. It is therefore recommended that all components be checked periodically by a qualied serviceman for proper operation.

BURNER MAINTENANCE

Qualied service agent should follow this procedure when the boiler’s burner needs cleaning.
1. Turn off the electrical power to the boiler and close the main
manual gas shutoff valve(s). Allow the boiler parts to cool before disassembly.
2. Loosen the ange and separate the gas train from the
manifold assembly.
3. Separate the burner from the blower adapter by rst
removing the four (4) bolts and subsequently, the blower gas kets. The blower should be free to move at this point.
4. For Direct Vent units: It is necessary to loosen and slide
the rubber coupling on the blower adaptor in order to move the blower.
BLOWER COMPARTMENT
The blower compartment should be cleaned annually to remove any dirt and lint that may have accumulated in the compartment or on the blower and motor. Buildups of dirt and lint on the blower and motor can create excessive loads on the motor resulting in higher that normal operating temperatures and possible shortened service life.
AIR FILTER BOX
The air lter box should be cleaned every three months to remove any dust and debris that may have accumulated in the air lter or the lter housing. Buildups of dust on the air lter can block the air intake into the boiler. Air lter can washed and cleaned
with water.
77
Page 78
CONDENSATE REMOVAL SYSTEM
Due to the highly efficient operation of this unit, condensate is formed during operation and must be removed by the conden sate drain systems. Inspect the condensate drains and tubes at least once a month and insure they will allow the free flow of condensate at all times. The system must be inspected more frequently in cold weather if the drain system is located in an area, such as along the floor, where freezing tempera tures are likely to occur. The conden sate drain system must be protected against freezing. Contact a qualified service agent to inspect and correct the condition if freezing of the conden sate lines is a problem.
The transparent drain lines and condensate drain on the bottom of the vent collector should be visually inspected at one month intervals for blockage, particularly in the areas of the loops in the lines which trap a small amount of conden sate, and the exit point of the vent collector drain. Conden sate in portions of the line other than the loop area indicates a blockage in the drain line. Flush the lines with air or water and clear or replace the blocked portions of the line as necessary. Note that areas of the drain line which include a sag or low spot in the line will also form a condensate trap which can be removed by levelling the tube and does not indicate a blocked system.
Inspect the metal vent drain and vent collector drain connectors at six month inter vals. Remove the hoses from the connections, then check with a small wooden dowel or plastic rod passed up through the metal con nection to insure the passage is clear, using caution to not bend or damage the connector. Call a qualied service agent to inspect and correct the problem if any obstructions are found in the connectors. Replace all hoses and clamps immediately after inspec tion and before starting the boiler in accordance with the Lighting and Operating Instructions. Do not operate the boiler unless all condensate drain lines are properly connected and working. When a means to neutralize condensate has been installed you must also follow operating, inspection and maintenance procedures specied by the manufacturer of the product. Inspect the installed device to insure that it does not cause condensate to remain in the boiler or vent for any reason.

VENTING MAINTENANCE

It is recommended that the intake and exhaust piping of the boiler be checked every 6 months for dust, condensate leakage, deterioration and carbon deposits.
1. Turn off the electrical power, and manual gas shut-off. • Allow boiler parts to cool before disassembly.
2. Remove the vent pipe.
• Check parts and chimney for obstructions and clean as
necessary.
3. Remove burner from boiler and other metal parts as required to clean as necessary.
• Refer to parts list for disassembly aid.
4. Clean and reinstall the parts removed in steps 2 and 3.
• Be sure the vent pipe has a minimum upward pitch of 1/4"
per foot (2 cm/m) of length and is sealed as necessary.
5. Restore electrical power and gas supply to boiler.
• Check for gas leaks and proper boiler and vent operation.

HEAT EXCHANGER MAINTENANCE

1. Shut down the boiler:
• Turn Off gas to the boiler.
• Do not drain the boiler unless it will be exposed to freezing temperatures. If using freeze prevention uid in system, do not drain.
2. Ensure the boiler cools down to room temperature.
3. Remove the nuts securing the heat exchanger access cover
to the heat exchanger and set aside.
4. Remove the heat exchanger access cover, burner, and gas
train assembly.
Note: The boiler contains ceramic ber materials. Failure to comply could result in severe personal injury.
5. Remove the condensate hose from the heat exchanger end.
Connect a eld supplied 3/4" diameter hose to a drain pan.
6. Use a vacuum cleaner to remove any deposits/ debris on the
boiler heating surfaces. Do not use any solvent.
7. Brush the heat exchanger while dry using a nylon bristle
brush. Re-vacuum the heat exchanger.
8. Finish cleaning using a clean cloth dampened with warm
water. Rinse out debris with a low pressure water supply.
9. Allow the heat exchanger to dry completely.
10. Remove the rear refractory cover from the back of the
combustion chamber of the heat exchanger and reassemble.
11. Close isolation valves on piping to isolate the boiler from
system. Attach a hose to the boiler drain and ush boiler thoroughly with clean water by using purging valves to allow water to ow through the water make-up line to the boiler.
12. Replace the access cover and restore the boiler for operation.
Qualied service agent should follow this procedure when the boiler’s intake and exhaust piping need cleaning:
78
Page 79

HANDLING CERAMIC FIBER MATERIALS

Removal of combustion chamber lining:
The combustion chamber insulation in this boiler contains ceramic ber material. Ceramic bers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline silica in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this boiler are below the level to convert ceramic bers to cristobalite.
The ceramic ber material used in this boiler is an irritant; hence when handling or replacing the ceramic materials it is advisable that the installer follow these safety guidelines.
1. Avoid breathing dust and contact with skin and eyes.
• Use NIOSH certied dust respirator (N95). This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written. Other types of respirators may be needed depending on the job site conditions. Current NIOSH recommendations can be found on the NIOSH website at http://www.cdc. gov/niosh/homepage.html. NIOSH approved respirators, manufacturers, and phone numbers are also listed on
this website.
• Wear long-sleeved, loose tting clothing, gloves, and eye protection.
2. Apply enough water to the combustion chamber lining to
prevent airborne dust.
3. Remove the combustion chamber lining from the boiler and
place it in a plastic bag for disposal.
4. Wash potentially contaminated clothes separately from
other clothing. Rinse clothes washer thoroughly.
NIOSH stated First Aid:
• Eye: Irrigate immediately.
• Breathing: Fresh air.

REPLACEMENT PARTS

Replacement parts may be ordered through A. O. Smith dealers, authorized servicers or distributors. Refer to the Yellow Pages for where to call or contact (in United States) the A. O. Smith
Water Products Company, 500 Tennessee Waltz Parkway, Ashland City, TN 37015, 1-800-433-2545 or (in Canada) A. O. Smith Enterprises Ltd., 599 Hill Street West, Fergus, ON N1M2X1, 1-888-479-2837. When ordering parts be sure to state
the quantity, part number and description of the item including the complete model and serial number as it appears on the product. Refer to the parts list for more information.
For Technical Assistance call A. O. Smith Technical Information Center at 1-800-527-1953.
79
Page 80

PIPING DIAGRAMS

LOOP TEMPERATURE PROBE
FULL PORT BALL VALVE
LEGEND
TEMPERATURE & PRESSURE
RELIEF VALV E
CHECK VALV E
PRESSURE RELIEF VALV E
TEMPERATURE GAGE
WATER FLOW SWITCH
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
SYSTEM RETURN
FINISHED FLOOR
SECONDARY BOILER PUMP - OPTIONAL
PLACES TEES AS CLOSE TOGETHER AS PRACTICAL
MAKE-UP
WATER
MODEL INLET DIA. OUTLET DIA.
XB-1000 2” 2”
XB-1300 2” 2”
WARNING: THIS DRAWING SHOWS SUGGESTED
XP BOILERS 1000–3400 - ONE BOILER PRIMARY / SECONDARY HYDRONIC
PIPING SYSTEM
PIPING CONFIGURATION AND OTHER DEVICES;
XB-1700 2.5” 2.5”
XB-2000 3” 3”
XB-1600 3” 3”
XB-3400 4” 4”
CHECK WITH LOCAL CODES AND ORDINANCES
FOR ADDITIONAL REQUIREMENTS.
AIR SEPARATOR
SYSTEM SUPPLY
SYSTEM PUMP
EXPANSION
TANK
FIGURE 78. PRIMARY/SECONDARY PIPING SYSTEM
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The boiler is shown with the optional factory installed and sized secondary boiler pump that is available on all XB models.
80
Page 81
FULL PORT BALL VALVE
CHECK VALVE
LEGEND
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
TEMPERATURE GAGE
WATER FLOW SWITCH
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
SYSTEM
RETURN
COLD WATER
SUPPLY
EXPANSION
TANK
MODEL INLET DIA. OUTLET DIA.
XW-1000 2” 2”
HOT WATER
TO FIXTURES
ALTERNATE CONNECTION
STORAGE TANK
AOS
XW-1300 2” 2”
XW-1700 2.5” 2.5”
XW-2000 3” 3”
XW-1600 3” 3”
XW-3400 4” 4”
FIGURE 79. HOT WATER SUPPLY BOILER WITH VERTICAL TANK
XP BOILERS 1000–3400 - ONE BOILER/VERTICAL STORAGE TANK RECOVERY
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
SYSTEM (ONE TEMPERATURE)
FOR ADDITIONAL REQUIREMENTS.
81
FINISHED FLOOR
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. A. O. Smith piping method is based on 50 equivalent feet of piping. Boiler placement shall be as close as practical to the
storage tank. Applications in excess of these recommendations shall require a licensed engineer for design assistance.
Page 82

LIMITED WARRANTY

A. O. Smith Corporation, the warrantor, extends the following LIMITED WARRANTY to the owner of this boiler:
1. If within TEN years after initial installation of the boiler, a heat exchanger or gas burner should prove upon examination by the warrantor to be defective in material or workmanship, the warrantor, at his option will exchange or repair such part or portion. This term is reduced to FIVE years if this boiler is used for water heating purposes other than hydronic space heating.
a. This warranty is extended to the owner for all other parts or portion during the FIRST year following initial installation of this boiler. b. The warranty on the repair or replacement of the part or portion will be limited to the unexpired term of the original warranty.
2. CONDITIONS AND EXCEPTIONS
This warranty should apply only when the boiler is installed in accordance with local plumbing and building codes, ordinances and regulations, the printed
instructions provided with it and good industry practices. In addition, a pressure relief valve, certied by C.S.A. and approved by the American Society of Mechanical Engineers, must have been installed and fresh water used for lling and make-up purposes.
a. This warranty should apply only when the boiler is used: (1) with outlet water temperatures not exceeding the maximum setting of its operative and/or high limit control; (2) at water pressure not exceeding the working pressure shown on the boiler; (3) when lled with boiler water, free to circulate at all times and with the heat exchanger free of damaging scale deposits; (4) in a non-corrosive and non-contaminated atmosphere; (5) in the United States, its territories or possessions, and Canada; (6) at a water velocity ow rate not exceeding or below the boiler’s designed rates; (7) indoor installation only. b. Any accident to the boiler, any misuse, abuse (including freezing) or alteration of it, any operation of it in a modied form, or any attempt to repair leaks
in the heat exchanger will void this warranty.
3. SERVICE AND REPAIR EXPENSE
Under this limited warranty the warrantor will provide only a replacement part. The owner is responsible for all other costs. Such costs may include but are
not limited to:
a. Labor charges for service, removal, repair, or reinstallation of the component part; b. Shipping, delivery, handling, and administrative charges for forwarding the replacement part from the nearest distributor and returning the claimed defec-
tive part to such distributor.
c. All cost necessary or incidental for any material and/or permits required for installation of the replacement.
4. LIMITATIONS ON IMPLIED WARRANTIES
Implied warranties, including any warranty of merchantability imposed on the sale of this boiler under state or provincial law are limited to one (1) year
duration for the boiler or any of its parts. Some states and provinces do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
5. CLAIM PROCEDURE
Any claim under this warranty should be initiated with the dealer who sold the boiler, or with any other dealer handling the warrantor’s products. If this is
not practicable, the owner should contact:
U.S. Customers Canadian Customers A. O. Smith Corporation A. O. Smith Enterprises Ltd. 500 Tennessee Waltz Parkway 599 Hill Street West Ashland City, TN 37015 Fergus, ON N1M 2X1 Telephone: 800-527-1953 Telephone: 1-888-479-2837
a. The warrantor will only honor replacement with identical or similar parts thereof which are manufactured or distributed by the warrantor. b. Dealer replacements are made subject to in-warranty validation by warrantor.
6. DISCLAIMERS
NO OTHER EXPRESS WARRANTY HAS BEEN OR WILL BE MADE ON BEHALF OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY OF
THE BOILER OR THE INSTALLATION, OPERATION, REPAIR OR REPLACEMENT OF THE BOILER. THE WARRANTOR Should NOT BE RESPONSIBLE FOR WATER DAMAGE, LOSS OF USE OF THE UNIT, INCONVENIENCE, LOSS OR DAMAGE TO PERSONAL PROPERTY, OR OTHER CONSEQUENTIAL DAMAGE. THE WARRANTOR Should NOT BE LIABLE BY VIRTUE OF THIS WARRANTY OR OTHERWISE FOR DAMAGE TO ANY PERSONS OR PROPERTY, WHETHER DIRECT OR INDIRECT, AND WHETHER ARISING IN CONTRACT OR TORT.
a. Some states and provinces do not allow the exclusion or limitation of the incidental or consequential damage, so the above limitations or exclusions may
not apply to you.
b. This warranty gives you specic legal rights, and you may also have other rights which vary from state to state or province to province.
Fill in the following for your own reference. Keep it. Registration is not a condition of warranty. The model and serial number are found on the boiler’s rating plate.
Owner______________________________________________________________________________________________________________________________________
Installation Address_________________________________________________________________________________________________________________________
City and State__________________________________________________________________________________ Zip Code __________________________________
Date Installed____________________ Model No. __________________________________________Serial No. ___________________________________________
Dealer’s Name___________________________________________________________________________ Phone No._______________________________________
Dealer’s Address ________________________________________________________________________________________________________________________
______________________________________________________________________________________________________________________________________
FILL IN WARRANTY AND KEEP FOR FUTURE REFERENCE
82
Page 83
Technical Support: 800-527-1953 • Parts: 800-433-2545 • Fax: 800-644-9306
25589 Highway 1, McBee, SC 29101
www.hotwater.com
83
Loading...