Read this manual carefully before first using the water heater. Failure to read
this manual and to follow the instructions in this manual may lead to
accidents, personal injury, and damage to the appliance.
Copyright 2003 A.O. Smith Water Products Company
All rights reserved.
Nothing from this publication may be copied, reproduced and/or published by
means of printing, photocopying or by whatsoever means, without the prior
written approval of A.O. Smith Water Products Company.
A.O. Smith Water Products Company reserves the right to modify specifications
stated in this manual.
Any brand names mentioned in this manual are registered trademarks of their
respective owners.
A.O. Smith Water Products Company accepts no liability for claims from third
parties arising from improper use other than that stated in this manual and in
accordance with the General Conditions registered at the Eindhoven Chamber
of Commerce.
Refer further to the General Conditions. These are available on request, and
without charge.
Although considerable care has been taken to ensure a correct and suitably
comprehensive description of all relevant components, the manual may
nonetheless contain errors and inaccuracies.
Should you detect any errors or inaccuracies in the manual, we would be
grateful to receive notification. This helps us to further improve our
documentation.
More information
If you have any comments or queries concerning any aspect related to the
appliance, then please do not hesitate to contact A.O. Smith Water Products
Company.
A.O. Smith
Postbus 70
5500 AB Veldhoven
The Netherlands
1.1About the applianceThis manual describes how to install, service and use the BFC appliance. The
BFC appliance is a condensing room-sealed water heater with a fan in the air
intake. A concentric chimney connector is fitted standard to the appliance.
Alternatively, the appliance can be connected using a parallel system.
Installation types possible with this appliance are C13, C33, C43, C53 and C63.
The information in this manual is applicable to types: BFC 28, BFC 30, BFC 50
and BFC 60.
The manner of construction and features of the appliance are in conformance
with the European standard for gas-fired storage water heaters for the
production of domestic hot water (ES 89). The appliances are therefore
compliant with the European Directive for Gas Appliances, and have the right to
bear the CE mark.
Warning
0063
Read this manual carefully before starting up the water heater. Failure to
read the manual and to follow the printed instructions may lead to personal
injury and damage to the appliance.
1.2What to do if you
smell gas
1.3RegulationsAs the (end) user, installer or service and maintenance engineer, you must
Warning
Whenever there is a smell of gas:
No naked flames! No smoking!
Avoid causing sparks! Do not use any electrical equipment or switch, i.e. no
telephones, plugs or bells!
Shut off the mains gas supply!
Open windows and doors!
Warn occupants and leave the building!
After leaving the building, alert the gas distribution company or installer.
ensure that the entire installation complies, as a minimum, with the official local:
•building regulations;
•energy supplier’s directives for existing gas installations;
•directives and technical guidelines for natural gas installations;
•safety requirements for low-voltage installations;
•regulations governing the supply of drinking water;
•regulations governing ventilation in buildings;
•regulations governing the supply of air for combustion;
•regulations governing the discharge of products of combustion;
•requirements for installations that consume gas;
•regulations governing indoor waste water disposal;
•regulations imposed by fire service, power companies and municipality;
Release R.1.3 UK9
Page 10
1
Introduction
Furthermore, the installation must comply with the manufacturer’s instructions.
n Remark
Later amendments and/or additions to all regulations, requirements and
guidelines published on or prior to the moment of installing, will apply to the
installation.
1.4Target groupsThe three target groups for this manual are:
•(end) users;
•installers;
•service and maintenance engineers.
Symbols on each page indicate the target groups for whom the information is
intended. See Table 1.1.
Tabl e 1 .1 Target group symbols
SymbolTarget group
(End) user
g
installer
i
Service and maintenance engineer
s
gis
1.5MaintenanceA service should be carried out at least once a year, both on the water side and
on the gas side. Maintenance frequency depends, among other things, on the
water quality, the average burning time per day and the set water temperature.
n Remark
To determine the correct maintenance frequency, it is recommended to
arrange for the service and maintenance engineer to check the appliance on
both the water and gas side, three months after installation. Based on this
check, the best maintenance frequency can be determined.
n Remark
Regular maintenance extends the service life of the appliance.
1.6Forms of notationThe following notation is used in this manual:
n Remark
Important information
cNote
Ignoring this information can lead to the appliance being damaged.
Warning
Failure to carefully read this information may lead to danger of personal
injury, and serious damage to the appliance.
10Instruction Manual BFC
Page 11
gis
Overview of this document
1.7Overview of this
document
Tab le 1. 2 Contents of document
ChapterTarget groupsDescription
2 Functioning of the
appliance
3 Installation
4 Filling and draining
Ta bl e 1. 2 provides an overview of the contents of this document.
This chapter describes how the appliance functions.
gis
This chapter describes the installation activity to be completed
is
before you actually start up the appliance.
This chapter describes how to fill and drain the appliance.
gis
5 The control panel
6 Status of the appliance
7 Starting up and shutting
down
8 Main menu
gis
gis
gis
gis
This chapter describes the general control of the appliance
using the display.
This chapter describes the status (mode or condition) that the
appliance may have, and possible actions to take.
This chapter describes how to start up the appliance, and how
to shut it down for a brief or long period of time. The general
heating cycle of the appliance is also described.
Describes the main menu of the display. This is the actual
menu for the user, however the installer and service and
maintenance engineers will also need to use this menu.
9 Service program
10 Troubleshooting
11 Maintenance frequency
12 Maintenance
13 Warranty (Certificate)
is
gis
gs
s
gis
Describes the service menu. It is mainly intended for the
installer and service and maintenance engineers. End users
may also refer to this chapter for additional information about
the appliance.
This chapter is mainly intended for the installer and the service
and maintenance engineer. It describes appliance errors.
These errors are indicated on the display. A troubleshooting
table of possible causes and solutions is provided. End users
may also refer to this chapter for additional information about
the appliance.
This chapter describes how to determine the optimum
frequency at which to carry out maintenance. Both the end
user and the service and maintenance engineer are
responsible for regular maintenance. They need to reach clear
agreement on this.
n Remark
If the appliance is not regularly maintained, the warranty
will become void.
This chapter sets out the maintenance tasks to be carried out
during a service.
This chapter states the warranty terms and conditions.
Release R.1.3 UK11
Page 12
1
Introduction
gis
12Instruction Manual BFC
Page 13
gis
a
gis
2Functioning of the
appliance
2.1IntroductionTopics covered in this chapter:
•Functional description of the appliance;
•The appliance’s heating cycle;
•Protection for the appliance;
•Safety of the installation.
Introduction
2.2Functional
description of the
appliance
Legend
a plastic top cover
b hot water outlet
c electrical connection block
d ThermoControl
e pressure switch
f control panel
g temperature sensor T
h combustion chamber
i anode
j tank
k heat exchanger
l inspection and cleaning
opening
m temperature sensor T
n cold water inlet
o drain valve
p gas control
q burner
r fan
s air supply hose
t glow igniter
u ionisation rod
v chimney pipe
w siphon
x PU insulation layer
1
2
Figure 2.1 shows a cut-away view of the appliance.
b
c
d
e
f
g
h
i
j
k
l
m
n
o
p
q
r
s
t
u
v
w
x
IMD-0070
Figure 2.1 Cut-away view of the appliance
Release R.1.3 UK13
Page 14
2
Functioning of the appliance
gis
In this appliance the cold water enters the bottom of the tank via the cold water
inlet n. The tap water, heated by the combustion chamber h and heat
exchanger k, leaves the tank through the hot water outlet b. Once the
appliance is completely filled with water, it remains constantly under water
supply pressure. As hot water is drawn from the appliance, cold water is
immediately added.
The air required for combustion is forcibly delivered to the burner q by the
fan r. The gas is fed to the burner q via the gas control p. Thanks to the
modulated supply of gas and air, the optimum gas/air mixture is always
achieved. The special construction of the burner causes the mixture to form a
vortex (the cyclone effect), before it becomes ignited. Because of this vorticity,
ignition at the glow igniter t is improved, and the combustion efficiency is also
optimised. Through the special design of the heat exchanger k, the flue gases
are first led downwards via the combustion chamber, then upwards again via the
heat exchanger, then once more downwards beside the water in the tank. In this
process, the flue gases gradually become cooler. Because the cooled flue
gases flow alongside the cold water below in the tank, they start to condense.
This condensation causes latent heat energy to be released, which is
transferred to the cooler water, and thereby increases the performance of the
unit. The water of condensation yielded by this process is discharged via the
siphon w.
The PU insulation layer x prevents heat loss. The inside of the tank is
enamelled to protect against corrosion. The magnesium anodes i provide
extra protection against corrosion.
For use during maintenance, the appliance has a inspection and cleaning
opening l.
2.3The appliance’s
heating cycle
2.4Protection for the
appliance
The entire appliance is controlled (and monitored) by theThermoControl d. The
temperature sensor T1 g (in the top of the tank j) and the temperature sensor
T2 m (in the bottom of the tank) measure the water temperature. These
temperatures are sent to the ThermoControl. Based on these two observations,
the ThermoControl calculates a net water temperature: T
lies between the temperatures measured at the top and bottom of the tank. As
soon as T
registers a ‘heat demand’. The gas control p is opened, and the gas is mixed
with air. This mixture is ignited by the glow igniter t and the water becomes
heated. As soon as T
ThermoControl stops the heating cycle.
Both when registering and ending the heat demand, the ThermoControl
assumes a certain margin. We refer to this margin as the hysteresis (see
paragraph ’9.2 Setting the hysteresis’).
The ThermoControl monitors the water temperature and ensures safe
combustion. This is achieved by:
•the Water temperature protection;
•the Gas control;
•the Fan;
•the Pressure switch;
•the Ionisation rod.
falls below the set water temperature (T
net
rises above T
net
, the heat demand ends, and the
set
. The value of T
net
), the ThermoControl
set
net
14Instruction Manual BFC
Page 15
gis
2.4.1Water temperature protection
With temperature sensor T1 g and temperature sensor T2 m, the
ThermoControl monitors three temperatures which are important for safety.
Ta bl e 2 .1 explains the functioning of the temperature sensors.
Tab le 2. 1 Temperature protection
ProtectionDescription
Protection for the appliance
Against frost
< 5°C or T2 < 5°C)
(T
1
For maximum water temperature
(T
> 85°C or T2 > 85°C)
1
For extra safety
(T
> 93°C or T2 > 93°C)
1
2.4.2Gas control
2.4.3Fan
The frost protection cuts in. The water is heated to 20°C.
The high-limit safeguard serves to prevent overheating and/or excessive
formation of scale in the appliance. Should the high-limit safeguard be
activated, the heating is halted. This causes the water in the tank to cool down.
Once the water has cooled sufficiently (T1 < 78 °C), the ThermoControl resets
the appliance.
A lockout error of the water heater controller takes place. The controller must
be manually reset before the appliance can resume operation (see paragraph
’6.3 Error conditions’). The reset may only be performed once T
The ThermoControl opens the gas control so that gas can be supplied to the
burner. As a safety measure, the gas control has two valves. Both valves shut
off the gas supply.
Smooth ignition is achieved by opening the gas control with a delay (‘softlite’).
The fan provides an optimum air supply when there is a heat demand. A safety
aspect is that the fan ensures that any gases present in the combustion
chamber get removed, both before and after combustion. We refer to this as
pre- and post-purge.
The fan speed is continuously monitored by the ThermoControl. The
ThermoControl takes control if the speed of rotation varies too much from the
value set.
< 78°C.
1
2.4.4Pressure switch
The pressure switch ensures the discharge of flue gases and the supply of
incoming air during the pre-purge and normal running of the appliance. The
standard position of the pressure switch is open. When sufficient pressure
differential is reached, the pressure switch closes. However, in the event of a
fault, the pressure switch will be tripped open, and the heating cycle will be
interrupted.
Release R.1.3 UK15
Page 16
2
Functioning of the appliance
gis
Table 2.2 shows the trip point per appliance.
Tabl e 2 .2 Pressure switch trip points
AppliancePressure differential [Pa]
ClosingOpening
2.4.5Ionisation rod
2.5Safety of the installation
2.5.1Unvented installation
BFC 28>
BFC 30>
BFC 50>
BFC 60>
635< 605
855< 825
885< 855
1085< 1055
n Remark
The trip point of the pressure switch is not adjustable.
To ensure that no gas will flow when there is no combustion, an ionisation rod
has been fitted. The ThermoControl uses this rod for flame detection, by means
of ionisation detection. The ThermoControl cuts in, the instant it detects that
there is a gas flow but no flame.
In addition to the appliance’s standard safety monitoring, the appliance must
also be protected by an expansion vessel, pressure overflow valve, non-return
valve and a T&P valve.
Use of an expansion vessel, a pressure relief valve and/or a pressure reducing
valve depends on the type of installation: unvented or vented.
With an unvented installation, a pressure relief valve and expansion vessel
prevent excessive pressure in the tank. This prevents damage being caused to
the enamelled coating (in the appliance) or to the tank. A non-return valve
prevents excessive pressure in the water supply system. This valve also
prevents water from flowing backwards from the tank into the cold water supply
system. The pressure reducing valve protects the installation against an
excessively high water supply pressure (> 8 bar). These components are fitted
to the cold water pipe. See paragraph ’3.6.1 Cold water side’.
2.5.2Vented installation
With a vented installation, excess pressure is taken up by the open water
reservoir. The level of the water reservoir determines the maximum working
pressure in the tank, which may not exceed 8 bar. The installation must also be
fitted with an overflow from the hot water pipe, which discharges into the water
reservoir. See paragraph ’3.6.2 Hot water side’.
2.5.3T&P valve
A T&P valve is only mandatory in an ‘unvented’ installation. However,
A.O. Smith also recommends the use of a T&P valve in ‘vented’ installations.
A T&P valve monitors the pressure in the tank, and the water temperature at the
top of the tank. If the pressure in the tank becomes excessive (>10 bar) or the
water temperature is too high (>97°C), the valve will open. The hot water will
immediately flow out of the tank. Because the appliance is under water supply
pressure, cold water will automatically flow into the tank. The valve remains
open until the unsafe situation has been averted. A connecting point for a T&P
valve is standard on the appliance. See paragraph ’3.6.2 Hot water side’.
16Instruction Manual BFC
Page 17
Introduction
is
is
3Installation
Warning
The installation should be carried out by an approved installer in compliance
with the general and local regulations imposed by the gas, water and power
supply companies and the fire service.
The appliance may only be installed in a room which complies with the
requirements stated in national and local ventilation regulations.
Refer also to paragraph ’1.3 Regulations’.
3.1IntroductionThis chapter describes the installation activities to be carried out before the
appliance may be started up, namely:
•Packaging;
•Environmental conditions;
•Technical specifications;
•Water connections, Unvented;
•Water connections, Vented;
•Gas connection;
•Air supply and flue gas discharge;
•Electrical connection;
•Checking the supply pressure and burner pressure;
•Conversion to a different gas category.
n Remark
Starting up the appliance is described in chapter ’7 Starting up and shutting
down’.
3.2PackagingTo avoid damaging the appliance, remove the packaging carefully. We
recommend unpacking the appliance at or near its intended location.
cNote
The appliance may only be manoeuvred in an upright position. Take care
that the appliance is not damaged after unpacking.
3.3Environmental
conditions
The BFC appliance is a room-sealed appliance. Installation types possible with
this appliance are C13, C33, C43, C53 and C63. This makes it possible to install
the appliance in either a closed or an open boiler room.
Release R.1.3 UK17
Page 18
3
Installation
is
3.3.1Humidity and ambient temperature
The boiler room must be frost-free, or be protected against frost. Table 3.1
shows the environmental conditions that must be adhered to, for correct
functioning of the electronics present in the appliance to be guaranteed.
Table 3 . 1 Humidity and ambient temperature specifications
Humidity and ambient temperature
Humiditymax. 93% RH at +25°C
Ambient temperatureFunctional: 0 ≤ t ≤ 60°C
3.3.2Maximum floor loading
In connection with the appliance’s weight, take account of the maximum floor
loading, see Tab le 3 .2 .
Table 3 . 2 Weight specifications related to maximum floor loading
Weight of the appliance filled with water
BFC 28392 kg
BFC 30, BFC 50, BFC 60593 kg
3.3.3Water composition
The appliance is intended for heating drinking water. The drinking water must
comply with the regulations governing drinking water for human consumption.
Table 3.3 shows these requirements.
Table 3 . 3 Water specifications
Water composition
Hardness
(alkaline earth ions)
Conductivity> 125 µS/cm
Acidity (pH value)7.0 < pH value < 9.5
n Remark
If the water specifications deviate from those stated in Ta bl e 3 .3 , then the
tank protection cannot be guaranteed.
See also chapter ’13 Warranty (Certificate)’.
3.3.4Working clearances
For access to the appliance it is recommended that the following clearances
are observed (see Figure 3.2):
•AA: around the appliance’s control column and cleaning openings: 100 cm.
•BB: around the appliance itself: 50 cm.
•Above the appliance (room to replace the anodes):
-100 cm if using fixed anodes, or
-50 cm if using flexible anodes.
> 1.00 mmol/l:
•German hardness >5.6° dH
•French hardness > 10.0° fH
•British hardness > 7.0° eH
18Instruction Manual BFC
Page 19
is
a
Environmental conditions
If the available clearance is less than 100 cm, flexible magnesium anodes
may be ordered from A.O. Smith, the installer / supplier.
n Remark
When installing the appliance, be aware that any leakage from the tank and/
or connections can cause damage to the immediate environment or floors
below the level of the boiler room. If this is the case, then the appliance
should be installed above a wastewater drain or in a suitable metal leak tray.
The leak tray must have an appropriate wastewater drain and must be at
least 5cm deep with a length and width at least 5cm greater than the
diameter of the appliance.
Figure 3.1 Working clearances
IMD-0073
Release R.1.3 UK19
Page 20
3
Installation
is
3.4Technical
specifications
The appliance is supplied without accessories. Check the dimensions and other
specifications for the accessories to be used, based on Figure 3.2 and
Table 3.6.
IMD-0073
Figure 3.2 Plan and elevation of the appliance
20Instruction Manual BFC
Page 21
is
Tab l e 3.4 Dimensions
Technical specifications
Dime
nsion
A Total height (mm)1370190019001900
DDiameter of the appliance (mm)705705705705
GDiameter of air supply/flue gas discharge (mm)80/125100/150100/150100/150
KHeight of the gas connection (mm)1270181018101810
MHeight of cold water supply connection (mm)160160160160
NHeight of hot water outlet connection (mm)1405192019201920
PHeight of cleaning and inspection opening (mm) 200200200200
RHeight of drain valve (mm)75757575
SHeight of T&P valve (mm)890141514151415
WHeight of condensation drainage (mm)110110110110
XHeight of air supply connection (mm)1205173017301730
Fan rotational speed at ignitionr. p.m.4500450045004500
Working speed of fanrpm4980540060006660
Diameter of air restrictormm23.023.028.029.0
(mm)
o
Cminutes23352420
95 x 70
Release R.1.3 UK21
Page 22
3
Installation
is
Tabl e 3 .5 General and electrical data
DESCRIPTIONUnitBFC 28 BFC 30BFC 50BFC 60
Electrical power consumptionW175
Supply voltageVAC230 (-15% +10%)
Mains frequencyHz50 (±1 Hz)
22Instruction Manual BFC
Page 23
is
Tab l e 3.6 Gas data
Installation diagram
Gas category dataII
Data for natural gas 2H: G20-20 mbar
Orifice diametermm4.905.107.007.10
Nominal load (upper value)kW32.134.552.663.2
Nominal capacitykW30.332.848.659.6
Supply pressurembar20202020
Burner pressurembar8.58.58.511.5
Gas consumption
Data for LP gas 3+
General
Orifice diametermm2.502.603.403.80
Restrictor diametermmn.a.n.a.n.a.n.a.
G30-30 mbar (butane)
Nominal load (upper value)kW30.732.850.659.4
Supply pressurembar37373737
Burner pressure
Gas consumption
(1)
(2)
(1)
UnitBFC 28BFC 30BFC 50BFC 60
2H3+
m3/h3.13.35.06.0
mbar37373737
kg/h2.22.43.74.3
G31-37 mbar (butane)
Nominal load (upper value)kW29.030.950.359.1
Supply pressurembar37373737
Burner pressure
Gas consumption
(1) Based on 1013.25 mbar and 15oC.
(2) If using a flat sealing plate instead of a burner pressure regulator, it is assumed that the burner pressure is equal to the supply pressure.
In practice however, the burner pressure will be lower.
3.5Installation diagram
(2)
(1)
Figure 3.3 shows the water and gas connection diagrams for unvented and
vented installations. The following paragraphs, describing the connections in
detail, make reference to these diagrams
mbar37373737
kg/h2.12.23.64.2
Release R.1.3 UK23
Page 24
3
Installation
is
Legend
a pressure-reducing valve
(mandatory)
b expansion vessel (mandatory)
c T&P valve (mandatory)
d stop valve (recommended)
e non-return valve (mandatory)
f circulation pump (optional)
g drain valve
h gas valve (mandatory)
i stop valve (mandatory)
j temperature gauge (optional)
k condensation drainage
(mandatory)
l hot water draw-off points
m pressure relief valve
(mandatory)
n water cistern
o float valve
p 3-way venting valve
(recommended)
q overflow pipe
a cold water supply
b hot water outlet
c circulation pipe
d gas supply
e flue gas discharge and air
supply
UNVENTED
d
h
VENTED
d
b
l
i
j
T
e
E
N
T
T
E
E
S
R
E
R
c
d
f
e
d
c
b
a
a
m
ei
k
g
po
IMD-0139
a
q
l
b
i
T
j
e
c
n
h
i
c
a
c
d
efd
k
g
IMD-0138
Figure 3.3 Installation diagrams
24Instruction Manual BFC
Page 25
is
3.6Water connections,
Unvented
3.6.1Cold water side
3.6.2Hot water side
Water connections, Unvented
See a in Figure 3.3.
1. Fit an approved stop valve i on the cold water side as required by
regulations.
Refer also to paragraph ’1.3 Regulations’.
2. The maximum working pressure of the appliance is 8 bar. Because the
pressure in the water pipe at times can exceed 8 bar, you must fit an
approved pressure-reducing valve a.
3. Fit a non-return valve e and an expansion vessel b.
4. Fit a pressure relief valve m and connect the overflow side to an open
wastewater pipe.
See b in Figure 3.3.
n Remark
Insulating long hot water pipes prevents unnecessary energy loss.
1. Optional: fit a temperature gauge j to be able to check the temperature of
the tap water.
2. Fit the T&P valve c.
3. Fit a stop valve i in the hot water outlet pipe, for use when servicing.
3.6.3Circulation pipe
See c in Figure 3.3.
If an immediate flow of hot water is required at draw-off points, a circulation
pump can be installed. This improves comfort and reduces water wastage.
1. Fit a circulation pump f of the correct capacity for the length and resistance
of the circulation system.
2. Fit a non-return valvee behind the circulation pump to guarantee the
direction of circulation.
3. Fit two stop valves d for service purposes.
4. Connect the circulation pipe to the cold water supply pipe.
3.6.4Condensation drainage
1. Fit a sloping wastewater pipe to the siphon k for condensation drainage and
connect this to the wastewater discharge in the boiler room.
cNote
All piping behind the siphon must be condensation-resistant.
Release R.1.3 UK25
Page 26
3
3.7Water connections,
Vented
3.7.1Cold water side
3.7.2Hot water side
Installation
is
See a in Figure 3.3.
1. Fit an approved stop valve i on the cold water side between the water
cistern n and the appliance, as required by regulations. Refer also to
paragraph ’1.3 Regulations’.
See b in Figure 3.3.
n Remark
Insulating long hot water pipes prevents unnecessary energy loss.
1. Fit the T&P valve c.
2. Optional: fit a temperature gauge j to be able to check the temperature of
the tap water.
3. Fit a stop valve i in the hot water outlet pipe, for use when servicing.
4. If a circulation pipe is to be fitted, then refer to paragraph 3.7.3.
3.8Gas connection
3.7.3Circulation pipe
See c in Figure 3.3.
If an immediate flow of hot water is required at draw-off points, a circulation
pump can be installed. This improves comfort and reduces water wastage.
1. Fit a circulation pump f of the correct capacity for the length and resistance
of the circulation system.
2. Fit a non-return valvee behind the circulation pump to guarantee the
direction of circulation.
3. Fit two stop valves d for service purposes.
4. Connect the circulation pipe to the cold water supply pipe.
3.7.4Condensation drainage
See paragraph ’3.6.4 Condensation drainage’.
Warning
Gas installation may only be carried out by an authorised installer in
compliance with the general regulations imposed by the gas company.
Refer also to paragraph ’1.3 Regulations’.
cNote
Make sure that the diameter and length of the gas supply pipe are large
enough to supply sufficient capacity to the appliance.
See d in Figure 3.3.
1. Fit a gas valve h in the gas supply pipe.
2. Blow the gas pipe through before use, to be sure it is clean.
3. Close the gas valve.
26Instruction Manual BFC
Page 27
is
3.9Air supply and flue
gas discharge
Air supply and flue gas discharge
4. Fit the gas supply pipe to the gas control.
Warning
Check for leaks after fitting.
Warning
The installation should be carried out by an authorised installer, in
compliance with the general and local regulations imposed by gas, water
supply and power supply companies and the fire service. Refer also to
paragraph ’1.3 Regulations’.
Depending on the approved installation types, there are several alternatives
for connecting the air supply and flue gas discharge. The BFC appliances are
approved for installation types C13, C33, C43, C53 and C63.
The most common installation types are:
•C13: Concentric wall flue terminal and
•C33: Concentric roof flue terminal.
This manual describes these installation types. If an explanation of other types
of installation is required, please contact A.O. Smith.
cNote
A.O. Smith prescribes the use of a roof or wall-mounted terminal,
exclusively of a type approved for the appliance. See paragraph
Pipe material, flue gas dischargeThick-walled aluminium with lip ring seal
Pipe material, air intakeThin-walled galvanised sheet steel
Pipe diameterConcentric
•BFC 28: Ø 80/125 mm.
•BFC 30, 50 and 60: Ø 100/150 mm.
1. The M2000 MDV SE model is a special version of the Mugro 3000 series. No other wall flue terminal may be used, as the
BFC-appliance is approved exclusively for this model of wall flue terminal. You can order the wall flue terminal from A.O. Smith or your
trade supplier, by specifying model: M2000 MDV SE.
28Instruction Manual BFC
(1)
Page 29
is
3.9.2Concentric roof flue terminal
A.O. Smith Water Products Company prescribes the roof flue terminal
(installation type C33) as specified in Ta b le 3 .9 .
Tabl e 3.9 Concentric roof flue terminal specifications
SpecificationDescription
Manufacturer Muelink & Grol
ModelM2000 DDV SEC HR
Air supply and flue gas discharge
(1)
Pipe material, flue gas
discharge
Pipe material, air intakeThin-walled galvanised sheet steel
Pipe diameterConcentric
1. The model M2000 DDV SEC HR is a special version of the Mugro 3000 series. No other
roof flue terminal may be used, as the BFC- appliance is approved exclusively for this
model of roof flue terminal. You can order the roof flue terminal from A.O. Smith or your
trade supplier, by specifying model: M2000 DDV SEC HR.
Thick-walled lip ring seal
•BFC 28: 80/125 mm.
•BFC 30, 50 and 60: Ø 100/150 mm.
IMD-0004
Figure 3.5 Roof flue terminal
Release R.1.3 UK29
Page 30
3
3.10 Electrical
connection
Installation
is
Warning
The installation should be carried out by an approved installer in compliance
with the general and local regulations imposed by the gas, water and power
supply companies and the fire service.
Refer also to paragraph ’1.3 Regulations’.
3.10.1Introduction
Topics covered in this paragraph:
•3.10.2 Preparation;
•3.10.3 Mains voltage;
Optionally, it is possible to connect an isolating transformer, a continuous pump,
a program-controlled pump, a “Tank ON” and an “Alarm OFF” to the appliance.
For these options, see:
•3.10.4 Isolating Transformer;
•3.10.5 Continuous pump;
•3.10.6 program-controlled pump;
•3.10.7 Extra ON mode switch (“Tank ON”);
•3.10.8 Connecting extra error signal (“Alarm OUT”).
n Remark
The optional components are not included in the rating for electrical power
consumption (see tables in paragraph 3.4).
3.10.2Preparation
cNote
The appliance is phase-sensitive. It is absolutely essential to connect the
phase (L) from the mains to the phase of the appliance, and the neutral (N)
of the mains to the neutral of the appliance.
There should also be no potential difference present between neutral (N)
and earth (
applied in the supply circuit. See ’3.10.4 Isolating Transformer’.
Figure 3.6 shows a view of the electrical connection block. Ta b le 3 .1 0 shows the
associated connections.
Table 3 . 1 0 Electrical connection block
Unu
Tank onContinuous
sed
X1X
1-456789101112131415161718192021222324
pump
LNNL
A
2
Regulated
pump
A). If this is the case, then an isolating transformer must be
Alarm OffIsolating transformerMains power
primarysecondary
X1X
A
2
A
NL
A
NL
A
NL
A
30Instruction Manual BFC
Page 31
is
Electrical connection
1
2
1
3
Figure 3.6 Connection block (connections 1 through 24 explained in
Ta bl e 3 .1 0)
In preparation you should first remove the two plastic covers and the
protective cap of the electrical section. The plastic covers are attached to the
appliance by 4 screws and Velcro fastenings. The covers are also joined to
each other with Velcro fastenings.
1. Unscrew the screws of the plastic covers.
2. Carefully remove the black plastic covers from the appliance.
The electrical section is now visible.
3. Undo the 2 screws 1 from the electrical section and remove the protective
cap 2 from the electrical section.
The connection block 3 is now visible.
1
24
IMD-0077
n Remark
Refer to ’A.2 Electrical diagram BFC’ for the connection of electrical
components.
3.10.3Mains voltage
The appliance is supplied without a power cord and main switch.
n Remark
In order to receive electrical power, the appliance has to be connected to the
mains voltage by means of a permanent electrical connection. A twoterminal main switch with a contact gap of at least 3 mm must be fitted
between this fixed connection and the appliance. The power cord must have
cores of at least 3 x 1.0 mm2.
1. Connect phase (L), neutral (N) and earth (
22 through 24 of the connector block as indicated in Table 3.10.
2. Fit the power cord in the pull relief.
3. If you do not need to make any more connections:
-Fit the cap on the electrical connection block.
-Fit the plastic covers onto the appliance.
Release R.1.3 UK31
A) of the power cord to terminals
Page 32
3
Installation
4. Connect the power cord to the main switch.
Warning
Leave the appliance disconnected until you are ready to start it up.
5. If you do not need to make any more connections:
-Fit the cap on the electrical connection block.
-Fit the plastic covers onto the appliance.
3.10.4Isolating Transformer
An isolating transformer should be used if there is a case of “floating neutral”.
1. Refer to fitting instructions provided with the isolating transformer
2. Connect phase (L), neutral (N) and earth (
terminals 16 through 21 of the connector block as indicated in Table 3.10.
3. Fit the cables in the pull relief.
4. If you do not need to make any more connections:
-Fit the cap on the electrical connection block.
-Fit the plastic covers onto the appliance.
5. Connect the power cord to the main switch.
is
(1)
A) of the power cables to
.
3.10.5Continuous pump
The continuous pump will start up as soon as mains power is connected to the
appliance.
1. Connect phase (L), neutral (N) and earth (
indicated in Ta bl e 3 .1 0 .
2. Fit the cable in the pull relief.
3. If you do not need to make any more connections:
-Fit the cap on the electrical connection block.
-Fit the plastic covers onto the appliance.
3.10.6program-controlled pump
Switching on of the program-controlled pump is determined by settings of the
ThermoControl.
1. Connect phase (L), neutral (N) and earth (
indicated in Ta bl e 3 .1 0 .
2. Fit the cable in the pull relief.
3. If you do not need to make any more connections:
-Fit the cap on the electrical connection block.
-Fit the plastic covers onto the appliance.
3.10.7Extra ON mode switch (“Tank ON”)
Tank ON is a facility for connecting an external ON/OFF switch. In the OFF
position, the programmed operating mode is active. In the ON position, the
programmed operating mode is overruled, and the “ON mode” is active.
1. Connect cables (X
2. Fit the cable in the pull relief.
and X2) to terminals 5 and 6 as indicated in Ta b le 3 .1 0.
1
A) to terminals 7, 8 and 9 as
A to terminals 10, 11 and 12 as
1. Contact A.O. Smith for details of the correct isolating transformer.
32Instruction Manual BFC
Page 33
is
3.10.8Connecting extra error signal (“Alarm OUT”)
3.11 Checking the supply
pressure and burner
pressure
Checking the supply pressure and burner pressure
3. If you do not need to make any more connections:
-Fit the cap on the electrical connection block.
-Fit the plastic covers onto the appliance.
Alarm OUT is a potential free terminal that is switched when an error is
detected. This can be used to signal errors, for example by turning on a lamp.
A 230 V circuit can be directly powered. For other voltages, a specific relay
prescribed by A.O. Smith is required.
1. Connect the phase cables (X
in Table 3.10. If required, connect earth (A) to terminal 15.
2. Fit the cable in the pull relief.
3. If you do not need to make any more connections:
-Fit the cap on the electrical connection block.
-Fit the plastic covers onto the appliance.
and X2) to terminals 13 and 14 as indicated
1
cNote
Before you start up the appliance and/or begin to check the supply
pressure and burner pressure, you must first fill the appliance. Please
refer to paragraph ’4.2 Filling the appliance’ for filling instructions.
cNote
Before starting-up for the first time, and following conversion, you
must always check the supply pressure and burner pressure. If
necessary, adjust these to be certain of optimum performance of the
appliance.
cNote
The easiest way to check the gas pressures is by using two pressure
gauges. This procedure assumes that these two gauges are available.
To check the supply pressure and burner pressure, proceed as follows:
1. Disconnect the appliance from the mains. See paragraph ’7.3.2 Disconnect
the appliance from the mains’.
2. Undo the screws of the plastic covers.
3. Carefully remove the black plastic covers from the appliance.
The electrical section is now visible.
4. There are 2 test nipples on the gas control (Figure 3.13) for measuring the
supply pressure @ and the burner pressure # respectively.
Sealing screws are located inside the test nipples. Loosen both sealing
screws by a few turns. Do not loosen them completely; this makes them
difficult to tighten again.
5. Connect a pressure gauge to the lower pressure test nipple #.
6. Open the gas supply and vent the gas supply line via the upper nipple @.
7. Connect a pressure gauge to the upper test nipple as soon as gas starts to
flow from this nipple.
8. Switch on the power to the appliance using the mains switch on the
appliance.
Release R.1.3 UK33
Page 34
3
I
0
Figure 3.7 ThermoControl
INTERNAL CHECK
Figure 3.8 Internal check
MENU
»OFF
^ ON
È WEEK PROGRAM
Figure 3.9 Main menu
»START OPERATION
^ CHANGE SETPOINT
È Tset=65ÉC
Figure 3.10 Starting up
Installation
is
9. Turn the ThermoControl ON by setting the 0/I switch to position I.
The display will now show
will then go to the main menu.
10. Activate the “ON mode” by going through the following steps:
-Press once on the blue arrow (L) to bring the pointer (
press E. The display as shown in Figure 3.10 appears.
-Confirm with E the option
The appliance is now in “ON mode” and will ignite.
11. Once the display shows the text
before reading the dynamic pressures (the fan needs this time to run up to
full rotational speed).
12. Use the pressure gauge to read the supply pressure at the test nipple #.
Depending on the gas, refer to Ta b le 3 .6 .
n Remark
Consult the mains gas supply company if the supply pressure is not correct.
INTERNAL CHECK for about 10 seconds, and
») to ON and
START OPERATION.
RUNNING you must wait about 1 minute
n Remark
If the burner pressure is not correct and the appliance is fitted with a flat
sealing plate, you will not be able to adjust the pressure. In this case, consult
your installer or supplier.
If the appliance is fitted with a burner pressure regulator, then the pressure
can be adjusted by following steps 13 through 17.
13. Remove the cap 8 from the burner pressure regulator 7.
14. Adjust the burner pressure by turning the adjusting screw 9, depending on
the correction required:
15. Cover the opening of the adjusting screw and check the burner pressure
against the target value from Ta bl e 3. 6.
16. If the pressure reading is not correct, repeat steps 14 and 15 until the correct
pressure is attained.
34Instruction Manual BFC
Page 35
is
MENU
»OFF
^ ON
È WEEK PROGRAM
Figure 3.11 Main menu
Conversion to a different gas category
17. Activate the “OFF mode” of the ThermoControl:
-If the
-Use H and L to position the cursor (») beside OFF
-Confirm with E.
18. Wait until the fan has stopped. and turn the ThermoControl off.
MENU is not displayed:
press B.
cNote
Failure to wait until the fan stops can cause damage to the appliance.
19. Shut off the gas supply.
20. Disconnect the two pressure gauges and re-tighten the sealing screws in the
test nipples.
21. Replace the plastic covers.
n Remark
Before starting-up the appliance, take time to fill in the warranty card
supplied with the appliance. This enables us to guarantee the quality of our
systems, and to further enhance our warranty procedure.
3.12 Conversion to a
different gas
category
Please return this card as soon as possible. Your customer will then receive
a warranty certificate with our warranty conditions.
cNote
The conversion may only by carried out by an authorised installer.
If the appliance must operate on a family of gas (LP gas or natural gas) other
than the category of gas for which the appliance has been set up at the
factory, the appliance will have be adapted using a special conversion kit.
cNote
After conversion, check the supply pressure and the burner pressure.
1. Disconnect the appliance from the mains. See paragraph ’7.3.2 Disconnect
the appliance from the mains’.
2. Shut off the gas supply.
3. Undo the screws of the plastic covers.
4. Carefully remove the black plastic covers from the appliance.
5. Loosen the 2 screws of the electrical section, and remove the protective cap
from the electrical section Figure 3.6).
6. Detach the connector 1 that connects the cabling of the glow igniter and the
ionisation rod to the controller.
7. Detach the three-part gas coupling 2 adjacent to the burner.
-Detach the air supply hose 3.
-Detach the detach the pressure switch hose 4.
Release R.1.3 UK35
Page 36
3
Legend
a connector
b gas coupling
c air supply hose
d pressure switch hose
e distribution plate
f orifice
Installation
8. Remove the burner as complete assembly.
a
c
d
is
e
b
5
Figure 3.12 Orifice assembly
9. Place and fit the burner with parts from the conversion kit.
n Remark
The burner for LP gases can be recognised by the letter ‘P’ which is stamped
into the metal of the gas/air distribution plate 5.
10.Select and fit the correct orifice from the conversion kit, based on Table 3.6.
The injector diameter is stamped into each injector 6
11. Check whether there is a burner pressure regulator 7 fitted to the gas
control, or simply a flat sealing plate!.
36Instruction Manual BFC
Page 37
is
Legend
g burner pressure regulator
h burner pressure control cap
i burner pressure control
adjusting screw
j connector
k flat sealing plate
l supply pressure test nipple
M burner pressure test nipple
Conversion to a different gas category
k
l
m
j
Figure 3.13 Conversion of gas control
n Remark
12.If the flat sealing plate or burner pressure regulator need to be replaced:
13.Refit the connector 1 of the glow igniter and ionisation rod to the controller.
14.Re-fit the three-part gas coupling b.
cNote
15.Check the burner and supply pressure (see paragraph 3.11).
g
i
In the event the supply pressure for a gas category is the same as the burner
pressure (see the gas tables in paragraph 3.4) then the gas control must be
fitted with a flat sealing plate with cork gasket. A burner pressure that
deviates in comparison to the supply pressure requires the use of a burner
pressure regulator with rubber gasket. Each conversion kit contains all the
necessary components.
-Unscrew the connector j from the gas control.
-If necessary, remove the flat sealing plate ! or burner pressure
regulator 7.
-If necessary, fit the flat sealing plate or burner pressure regulator
supplied with the conversion kit.
-Refit the connector to the gas control.
h
IMD-0079
16.Replace the plastic cover.
17.Remove the sticker showing the new gas category from the conversion kit,
and attach it below the appliance’s rating plate. This clearly indicates that the
appliance may no longer be run on the gas for which it was originally
supplied.
18.Start the appliance (see paragraph 7.2).
Release R.1.3 UK37
Page 38
3
Installation
is
38Instruction Manual BFC
Page 39
gis
gis
4Filling and draining
4.1IntroductionTopics covered in this chapter:
•Filling the appliance.
•Draining the appliance.
The components referred to in these paragraphs are illustrated in Figure 4.1.
4.2Filling the appliance
4.2.1Filling unvented installations
To fill the appliance, proceed as follows.
1. Open the stop valve i in the hot water pipe and, if present, the stop valves
d for the circulation pump.
2. Shut drain valve g.
3. Open the nearest hot water draw-off point l.
4. Open the supply valve i on the cold water side a so that cold water flows
into the appliance.
5. Completely fill the appliance (when cold water flows at normal pressure from
the nearest hot water draw-off point, the appliance is full).
6. Bleed the entire installation of air, for example by opening all hot water drawoff points.
7. The appliance is now under water supply pressure. There should be no
water coming out of the overflow valve m nor the T&P valvec. If this does
happen, the cause might be:
-The water supply pressure is greater than the specified 8 bar.
Rectify this by fitting a pressure-reducing valve a.
-The overflow valve in the protected cold supply setup is defective or
incorrectly fitted.
Introduction
4.2.2Filling vented installations
To fill the appliance, proceed as follows.
1. Open the stop valve i in the hot water pipe and, if present, the stop valves
d for the circulation pump.
2. Shut drain valve g.
3. Open the nearest hot water draw-off point l.
4. Open the supply valve i on the cold water side a so that cold water flows
into the appliance.
5. Completely fill the appliance (when cold water flows at normal pressure from
the nearest hot water draw-off point, the appliance is full).
6. Bleed the entire installation of air, for example by opening all hot water drawoff points.
7. The appliance is now under water supply pressure. There should be no
water coming out of the T&P valve c. If this does happen, the T&P valve
might be defective or incorrectly fitted.
Release R.1.3 UK39
Page 40
4
Filling and draining
gis
Legend
a pressure-reducing valve
(mandatory)
b expansion vessel (mandatory)
c T&P valve (mandatory)
d stop valve (recommended)
e non-return valve (mandatory)
f circulation pump (optional)
g drain valve
h gas valve (mandatory)
i stop valve (mandatory)
j temperature gauge (optional)
k condensation drainage
(mandatory)
l hot water draw-off points
m pressure relief valve
(mandatory)
n water cistern
o float valve
p 3-way venting valve
(recommended)
q overflow pipe
a cold water supply
b hot water outlet
c circulation pipe
d gas supply
e flue gas discharge and air
supply
UNVENTED
j
d
h
VENTED
d
l
b
i
T
e
E
N
T
T
E
E
S
R
E
R
c
d
f
e
d
c
b
a
ei
m
a
kg
p
q
o
IMD-0139
a
l
b
i
T
c
n
j
e
h
i
c
a
c
d
efd
k
g
IMD-0138
Figure 4.1 Installation diagrams
40Instruction Manual BFC
Page 41
gis
4.3Draining the
appliance
MENU
»OFF
^ ON
È WEEK PROGRAM
Figure 4.2 Main menu
I
0
Figure 4.3 ThermoControl
4.3.1Draining unvented installations
Some service activities require the appliance to be drained. The procedure is as
follows:
1. Activate the MENU with B.
2. Use H and L to place the cursor beside
3. Confirm
4. Wait until the fan has stopped. The
OFF with E.
cNote
Failure to wait until the fan stops can cause damage to the appliance.
5. Turn the appliance OFF (position 0) using the ON/OFF switch on the
control panel. See Figure 4.3.
6. Disconnect the appliance by putting the mains switch between the appliance
and the mains power supply to position 0.
7. Shut off the gas supply h.
8. Close the stop valve i in the hot water pipe.
9. Close the supply valve of the cold water supply a.
10. Open the drain valve g.
11. Bleed the appliance (or installation) so that it drains completely empty.
Draining the appliance
OFF. See Figure 4.2.
S icon is then dimmed.
4.3.2Draining vented installations
Some service activities require the appliance to be drained. The procedure is as
follows:
1. Activate the
2. Use H and L to place the cursor beside
3. Confirm
4. Wait until the fan has stopped. The
MENU with B.
OFF with E.
cNote
Failure to wait until the fan stops can cause damage to the appliance.
5. Turn the appliance OFF (position 0) using the ON/OFF switch on the
control panel. See Figure 4.3.
6. Disconnect the appliance by putting the mains switch between the appliance
and the mains power supply to position 0.
7. Shut off the gas supply h.
8. Close the stop valve i in the hot water pipe.
9. Close the stop valve between the water cistern and the cold water inlet.
10. Open the drain valve g.
11. Bleed the appliance (or installation) so that it drains completely empty.
OFF. See Figure 4.2.
S icon is then dimmed.
Release R.1.3 UK41
Page 42
4
Filling and draining
gis
42Instruction Manual BFC
Page 43
Introduction
gis
gis
5The control panel
5.1IntroductionTopics covered in this chapter:
•5.2 Operating;
•5.3 Explanation of the icons;
•5.4 ON/OFF switch of ThermoControl;
•5.5 Navigation buttons;
•5.6 PC connection..
5.2OperatingFigure 5.1 shows the ThermoControl. The control panel is completely menu-
driven. It comprises:
•a 4-line display with 20 characters per line;
•6 push buttons for operating the appliance (below the display);
•6 graphical symbols (above the display);
•a connector for a service PC;
•an ON/OFF switch.
The push buttons are divided into three groups:
•Navigation buttons:
-Buttons UP H, and DOWN L;
-Enter: E;
-Reset button: R
•The main menu: B (see chapter ’8 Main menu’);
•the service program: S (see chapter ’9 Service program’, this chapter is
specifically intended for the service and maintenance engineer and
installer).
MENU
»OFF
^ ON
» WEEK PROGRAM
I
0
Figure 5.1 ThermoControl
^»START OPERATION
È CHANGE SETPOINT
Tset=70ÉC
Figure 5.2 The display
Release R.1.3 UK43
In this manual, the display of the ThermoControl is shown as in Figure 5.2, both
with and without icons.
Page 44
5
The control panel
gis
5.3Explanation of the
icons
5.4ON/OFF switch of
ThermoControl
INTERNAL CHECK
Table 5.1 gives an explanation of the icons.
Tabl e 5 .1 Icons and their meaning
IconNameExplanation
W
S
D
O
G
V
The ON/OFF switch of the ThermoControl switches the appliance ON and OFF.
Note that in the OFF position the appliance remains electrically live, in order for
the continuous pump to stay running.
After switching on, the text
10 seconds. The main menu then appears (see chapter ’8 Main menu’). If no
selection is made in the main menu, the appliance automatically switches to
OFF mode. See paragraph ’6.2 Operating modes’.
Heat demandHeat demand detected
PurgePre- and post-purge using fan
Pressure switchPressure switch is closed
Glow(Pre)glow
Gas controlGas control open / ignition
Flame detectionAppliance running
INTERNAL CHECK appears on the display for about
n Remark
Figure 5.3 Internal check
5.5Navigation buttonsThe use of these buttons is explained with the help of Figure 5.4. This figure
MENU
OFF
^»ON
È WEEK PROGRAM
EXTRA PERIOD
SETTINGS
Figure 5.4 Navigation buttons
To electrically disconnect the appliance, you must use the main switch
between the appliance and the mains power supply.
shows the main menu. See also chapter’8 Main menu’.
The navigation buttons are:
•Buttons UP H and DOWN L;
•Enter: E;
•Reset button: R
The arrows
and L to scroll.
The cursor » points to the option to be activated. In the display as shown in
Figure 5.4 you can scroll through the main menu.
The main menu consists of:
SETTINGS. The options EXTRA PERIOD and SETTINGS only become visible
after scrolling downwards.
The selected option is confirmed using E.
With the R button, you go back one page in a menu, and all options
selected in the current menu are lost.
^ and È indicate that you can scroll up and/or down. Use buttons H
OFF, ON, WEEK PROGRAM, EXTRA PERIOD and
n Remark
The R button is also used to reset the appliance following an error.
5.6PC connection.The PC connection is exclusively intended for technicians from A.O. Smith who
can read the status and history of the appliance. These details can be important
for troubleshooting and/or responding to complaints.
44Instruction Manual BFC
Page 45
Introduction
gis
gis
6Status of the
appliance
6.1IntroductionTopics covered in this chapter:
•6.2 Operating modes;
•6.3 Error conditions;
•6.4 Service condition.
6.2Operating modesWhen running, the appliance has four basic operating modes, namely:
OFF
OFF
13:45 Thursday6ÉC
FROST PROTECTION
ACTIVATED
Figure 6.1 Frost protection
ON
13:45 Thursday67ÉC
Tset 75ÉC
Figure 6.2 ON
EXTRA
12:30 Thursday76ÉC
TH 12:45 Tset 75ÉC
PERIOD ACTIVATED
Figure 6.3 Extra period
In this mode, the frost protection is activated. Figure 6.1 shows the display
with the following information:
-line one: the text OFF;
-line two: the time, the day and alternately T
2.3;
-lines three and four: the text FROST PROTECTION ACTIVATED.
ON
In this mode the appliance continuously fulfils the demand for hot water.
Figure 6.2 shows the display with the following information:
-line one: the text ON;
-line two: the time, the day and alternately T
2.3;
-line three: the programmed water temperature T
-line four: is empty when the appliance is idle, or depending on the
heating cycle, a text such as
heating cycle’.
EXTRA
In this mode, one extra period is programmed and activated. In this mode,
OFF or PROG position is temporarily overruled to fulfil a single period of
the
heat demand. Once the period has passed, the appliance automatically
returns to the previous operating mode. Figure 6.3 shows the display with
the following information:
-line one: the text EXTRA;
-line two: the time, the day and alternately T
2.3;
-line three: the switch-on time, and the related water temperature
setting;
-line four: the text PERIOD ACTIVATED.
PROG
In this mode a preset week program is active, and the appliance responds
continually to heat demand within the time periods set in the week program.
There are two distinct situations possible in this mode:
HEAT DEMAND. See ’7.4 The appliance’s
and T
1
and T
1
and T
1
. See paragraph
net
. See paragraph
net
;
set
. See paragraph
net
Release R.1.3 UK45
Page 46
6
Status of the appliance
gis
PROG
10:00 Monday76ÉC
MO 11:15 Tset 75ÉC
Figure 6.4 week program
active, current time within
programmed period
PROG
12:00 Monday76ÉC
MO 11:15
PERIOD ACTIVATED
Figure 6.5 week program
active, current time outside
programmed period
1) The current time falls within a set time period of the week program.
Figure 6.4 shows the display in this situation:
-line one: the text PROG;
-line two: the time, the day and alternately T
2.3;
-line three: the next scheduled switch-off time and the water
temperature T
-line four: is empty, or depending on the heating cycle, a text such as
HEAT DEMAND. See paragraph ’7.4 The appliance’s heating cycle’
2) The current time falls outside a set time period of the week program.
Figure 6.5 shows the display in this situation:
-line one: the text
-line two: the time, the day and alternately T
2.3;
-line three: the next scheduled switch-on time;
-line four: the text
In all modes, the temperature may at any moment drop below the desired
temperature. The appliance then enters a heating cycle. This heating cycle is
the same for all basic operating modes. See paragraph ’7.4 The appliance’s
heating cycle’.
of the active period;
set
PROG;
PERIOD ACTIVATED.
and T
1
and T
1
. See paragraph
net
. See paragraph
net
n Remark
Setting and programming of the basic operating modes are described in
chapter ’8 Main menu’.
6.3Error conditions
S04: SENSOR ERROR
CHECK
SENSOR OR DUMMY
Figure 6.6 Example of an error
message
Figure 6.6 shows an example of an error condition. If the appliance enters this
condition, the display will show the following information:
•line one: error code comprising a letter and two digits, followed by the error
description;
•lines two through four: alternately, a brief explanation of the error, and a brief
action to resolve the error.
cNote
The displayed action to resolve the error may only be performed by a
service- and maintenance engineer.
There are various types of errors:
•LOCK OUT ERRORS
When the cause is no longer present, these errors require a reset with the
R button, before the appliance can resume running.
•BLOCKING ERRORS
These errors disappear automatically once the cause of the error has been
removed, after which the appliance resumes by itself.
The display does not show what type of error has been detected. For a detailed
overview of error conditions, please refer to chapter ’10 Troubleshooting’.
If, as end-user, you find the appliance in an error condition, you may attempt to
re-start the appliance by pressing the R button once.
However, should the error return or become persistent, you should contact your
service and maintenance engineer.
46Instruction Manual BFC
Page 47
gis
6.4Service condition
!!!WARNING!!!
Service condition
Figure 6.7 shows the message SERVICE REQUIRED. Should this message
appear, then the appliance is in need of a service and maintenance inspection.
In that case, contact your service and maintenance engineer.
MAX. BURNINGHOURS:
SERVICE REQUIRED
Figure 6.7 Service required
n Remark
The message SERVICE REQUIRED is based on the number of burning
hours and the preset service interval. Should the service interval have been
incorrectly selected, contact the service and maintenance engineer for
instructions on how to adjust this. See chapter ’11 Maintenance frequency’.
Release R.1.3 UK47
Page 48
6
Status of the appliance
gis
48Instruction Manual BFC
Page 49
gis
gis
7Starting up and
shutting down
7.1IntroductionTopics covered in this chapter:
•Starting up.
•Shutting down.
7.2Starting upStart-up the appliance as follows:
1. Fill the appliance. See chapter ’4 Filling and draining’
2. Open the gas valve (see ’Figure 4.1 Installation diagrams’).
3. Switch on the power to the appliance using the mains switch between the
appliance and the power supply.
4. Turn the ThermoControl ON by setting ON/OFF switch to position I.
Introduction
I
0
Figure 7.1 ThermoControl
INTERNAL CHECK
Figure 7.2 Internal check
MENU
»
OFF
^ ON
È WEEK PROGRAM
Figure 7.3 Main menu
»START OPERATION
^ CHANGE SETPOINT
È Tset=65ÉC
Figure 7.4 Starting up
The display will now show INTERNAL CHECK for about 10 seconds, then
go to the main menu.
5. Activate the “ON mode” by going through the following steps:
-Press once on the DOWN button (L) to position the cursor (») beside
ON, then press E. The display shown in figure Figure 7.4 will
appear.
-Confirm with E the option START OPERATION.
The appliance will now enter “ON mode”. If there is a heat demand, the
appliance will run through a heating cycle. See paragraph ’7.4 The
appliance’s heating cycle’.
If the heating cycle is not run, then there is no current heat demand;
should this happen, then T
described in paragraph ’8.4 Setting the water temperature’
will probably need to be set. This is
set
7.3Shutting downYou can:
•Shut the appliance down for a brief period (“OFF mode”).
•Disconnect the appliance from the mains.
Release R.1.3 UK49
Page 50
7
OFF
13:45 Thursday6ÉC
FROST PROTECTION
ACTIVATED
Figure 7.5 Frost protection
Starting up and shutting down
gis
•Shut the appliance down for a longer period.
7.3.1Shut the appliance down for a brief period (“OFF mode”)
To shut the appliance down for a brief period, you must activate the frost
protection.
With the frost protection you can prevent water freezing in the appliance.
Activate the frost protection as follows:
1. Press button B to select the main menu.
2. Using H and L position the cursor (») beside OFF.
Confirm with E.
The frost protection cuts in if the water temperature drops below 5°C. The text
FROST will then appear on line one of the display The appliance will heat the
water to 20°C (T
n Remark
These values of 5°C and 20°C cannot be adjusted.
7.3.2Disconnect the appliance from the mains
The appliance should only be disconnected from mains power in the correct
way. The correct procedure is as follows:
) before dropping back to OFF mode.
set
MENU
»OFF
^ ON
È WEEK PROGRAM
Figure 7.6 Main menu
I
0
Figure 7.7 ThermoControl
1. Activate the MENU with B.
2. Use H and L to position the cursor beside OFF. See Figure 7.6.
3. Confirm OFF with E.
4. Wait until the fan has stopped. The
S icon is then dimmed.
cNote
Failure to wait until the fan stops can cause damage to the appliance.
5. Turn the appliance OFF (position 0) using the ON/OFF switch on the
control panel. See Figure 7.7.
6. Disconnect the appliance by putting the mains switch between the appliance
and the mains power supply to position 0.
7.3.3Shut the appliance down for a longer period
Drain the appliance, if you are shutting it down for a longer period of time.
Proceed as follows:
1. Disconnect the appliance from the mains as described in paragraph 7.3.2.
2. Shut off the gas supply.
3. Close the stop valve in the hot water pipe.
4. Open the drain valve.
5. Bleed the appliance (or installation) so that it drains completely empty.
50Instruction Manual BFC
Page 51
gis
The appliance’s heating cycle
7.4The appliance’s
heating cycle
ON
Ê
13:45 Thursday63ÉC
Tset 65ÉC
HEAT DEMAND
The appliance’s heating cycle is activated as soon as the measured water
temperature (T
depends on the currently selected appliance operating mode. For example, if
the appliance is in the “OFF mode” (frost protection), then this value is 5°C. If
the appliance is in the “ON mode”, then this threshold value is selectable, for
example, 65°C.
The heating cycle runs in turn through the following states:
1. HEAT DEMAND;
2. PRE-PURGE;
3. PRESSURE SWITCH;
4. PRE-GLOW;
5. IGNITION;
6. RUNNING;
7. POST-PURGE.
The complete cycle is explained in the example set out below assuming the
appliance is operating in mode ON.
) falls below the threshold value (T
net
). This threshold value
set
n Remark
The same heating cycle applies to the other operating modes.
Once the appliance starts, it will run through 8 steps:
1. The water temperature drops below the set temperature of (for example)
65°C. The ThermoControl detects a heat demand and starts the heating
cycle.
-The
-The message HEAT DEMAND appears.
W icon is activated.
Figure 7.8 Frost protection cuts
in
ON
13:45 Thursday63ÉC
Tset 65ÉC
PRE PURGE
Figure 7.9 Pre-purge
ON
Ê Ê
13:45 Thursday63ÉC
Tset 65ÉC
PRESSURE SWITCH
Figure 7.10 Pressure switch
ON Ê
13:45 Thursday63ÉC
Tset 65ÉC
GLOW PLUG
Figure 7.11 Pre-glow
Ê Ê
Ê
Ê
2. Following the heat demand, the fan is powered up and the pre-purge begins.
This lasts about 15 seconds. During this phase, any residual gases are
removed.
-The
-The message PRE PURGE appears.
3. During the pre-purge, the pressure switch closes.
-The
-The message PRESSURE SWITCH appears.
4. After some time, the pre-purge ceases and the ThermoControl reduces the
speed of the fan to the rotational speed for ignition. This is followed by the
pre-glow of the glow igniter.
-The S and D icons are dimmed.
-The
S icon is activated.
D icon is activated.
O icon is activated.
Release R.1.3 UK51
Page 52
7
Starting up and shutting down
gis
ON Ê Ê
13:45 Thursday63ÉC
Tset 65ÉC
IGNITION
Figure 7.12 Ignition
ON Ê Ê Ê
13:45 Thursday63ÉC
Tset 65ÉC
RUNNING
Figure 7.13 Running
ON Ê Ê
13:45 Thursday65ÉC
Tset 65ÉC
POST PURGE
Figure 7.14 Post-purge
ON
14:05 Thursday65ÉC
Ê
5. After a number of seconds pre-glow, the gas control is opened and ignition
takes place.
-The
-The message IGNITION appears.
6. After ignition, the flame is detected and the appliance will be running. This
means that actual heating has started. The rotation speed of the fan then
Ê
increases to the normal running speed, and the pressure switch will close:
-The
-The
-The message RUNNING appears.
7. Once the water is up to temperature, the heat demand drops off, and the
post-purge starts. This lasts about 25 seconds.
-The W, G and V icons are dimmed.
-The
-The message POST PURGE appears.
8. Following the post-purge, the fan stops and the pressure switch opens:
-The D and S icons are dimmed.
-The message POST PURGE disappears.
At the first subsequent heat demand, the heating cycle will resume from step 1.
G icon is activated.
O icon is dimmed.
V and D icons are activated.
S icon is activated.
Figure 7.15 Running
52Instruction Manual BFC
Page 53
gis
gis
8Main menu
8.1Introduction
MENU
»OFF
^ ON
È WEEK PROGRAM
EXTRA PERIOD
SETTINGS
Figure 8.1 Main menu
Introduction
The MENU is reached by pressing button B of theThermoControl. The options
are:
OFF
•
Select this option if you wish to shut the appliance down for a brief period,
but do not wish to drain it. In this mode, the frost protection is active. This
prevents water from freezing in the appliance. See paragraph ’7.3 Shutting
down’.
ON
•
In this mode, the appliance continually responds to the hot water demand.
See paragraph ’8.3 Switching into “ON mode”’.
WEEK PROGRAM
•
Select this option to allow the appliance to respond to heat demand only
during pre-programmed periods. Outside those periods, only frost
protection is active. See paragraph ’8.5 Week programme’.
EXTRA PERIOD
•
Select this option to override the OFF mode or PROG mode so that a single
temporary period of heat demand will be fulfilled. See paragraph ’8.6 Extra
period’.
SETTINGS
•
Select this option in order to set the language and the time. You can also
use this option to display the regulation interval (temperature), and the
ignition and running speeds of the fan. See paragraph ’8.7 Settings’.
n Remark
If you fail to make any selection with the main menu open, then after 30
seconds, the appliance will automatically return to the mode it was
previously in.
Topics covered in this chapter:
•Setting the water temperature
•Week programme
•Extra period
•Settings
8.2Notational
convention for
menu-related
instructions
Release R.1.3 UK53
The MENU (B) of the ThermoControl is divided into sub-menus. For example,
SETTINGS is one of the functions reached from the main menu. The menu
SETTINGS is itself divided into sub-menus. For example, LANGUAGE is a sub-
menu of SETTINGS. So, for example, to select menu LANGUAGE, this manual
employs the following convention:
•B: SETTINGS | LANGUAGE
Confirm with E.
Page 54
8
Main menu
gis
This means:
Activate the main menu with B.
1. B:
SETTINGS: Using button H and/or L go to SETTINGS and press E.
2.
LANGUAGE: Using button H and/or L go to LANGUAGE.
3.
4. Confirm with E: After pressing E, the sub-menu LANGUAGE is
activated.
This notation is also used for more than 2 sub-menus.
8.3Switching into “ON
mode”
8.4Setting the water
temperature
8.4.1Setting the water temperature via SETPOINT MENU
START OPERATION
^»CHANGE SETPOINT
È Tset=65ÉC
Figure 8.2 Setting SETPOINT
SETPOINT
» 65ÉC
Figure 8.3 Adjusting water
temperature
You can switch the appliance into “ON mode” from any operational mode, as
follows:
•B: ON | START OPERATION
Confirm with E.
n Remark
Starting up and shutting down the entire appliance is described in chapter 7.
The water temperature can be set to any value between 40°C and 80°C.
Set the water temperature via:
ON | CHANGE SETPOINT
1. B:
Confirm with E.
2. Use:
-H to increase the value;
-L to decrease the value.
-Confirm with E. After confirming, the appliance enters “ON
mode”.
n Remark
If the temperature setting is higher than the current water temperature, it is
possible that the appliance does not immediately start heating. To prevent
excessively frequent switching on and off, there is a heating margin. This
margin is set standard to 2°C. The appliance starts heating when the water
temperature is 2°C colder than the SETPOINT and continues heating until
the water is 2°C hotter than the SETPOINT.
We refer to this margin as the hysteresis. The service and maintenance
engineer can adjust this value (see paragraph 9.2).
8.4.2Setting water temperature during ON mode
ON
13:45 Thursday65ÉC
Tset=65ÉC
Figure 8.4 ON mode: the
appliance is on
54Instruction Manual BFC
The water temperature can also be directly adjusted when the appliance is in
“ON mode”. Simply use:
•H to increase the value;
•L to decrease the value.
•t6Confirm with E.
Page 55
gis
8.5Week programme
8.5.1Introduction
PROG
07:55 Monday64ÉC
MO 08:00 Tset 75ÉC
PROGRAM ACTIVATED
Figure 8.5 week program active
Week programme
Using the week program, you can set the water temperature for the days and
times you wish.
If the appliance is running under a week program, then this is indicated on the
display by the text
the time of day, the day of the week and the temperature. The third line shows
the next switching time of the week program and the programmed temperature.
The fourth line shows the text
The appliance’s default week program switches the appliance on every day at
00:00 hours and off at 23:59 hours. The water temperature setting is standard
65°C.
If you wish, you can change every setting in the standard week program of the
appliance.
If, while the week program is running, the water temperature becomes too low,
then the appliance will run through the heating cycle (see ’7.4 The appliance’s
heating cycle’), then return to the week program.
The following topics are covered in this paragraph:
•8.5.2 Starting up and shutting down the week program
•8.5.3 Changing the appliance’s standard week program
•8.5.4 Adding times to a week program
•8.5.5 Deleting times from a week program
PROG on the first line (see Figure 8.5). The second line shows
PROGRAM ACTIVATED.
8.5.2Starting up and shutting down the week program
The week program can be started up from any other operating mode, as follows:
•B:
WEEK PROGRAM | START OPERATION
Confirm with E.
A week program can be shut down simply by activating a different operating
mode, for example “ON mode”.
8.5.3Changing the appliance’s standard week program
n Remark
First fill-in the desired week program on the program card supplied. See
appendix ’A.3 Week program card’.
A week program is made up of a number of programmable periods in which you
can have the appliance switch on and off. A period consists of:
•switch-on time: day of the week, and time in hours and minutes;
•switch-off time: in hours and minutes;
•the water temperature setting;
•on/off setting for a program-controlled pump.
n Remark
The switch-off time must always be followed by a switch-off time on the
same day of the week. A maximum of three periods may be programmed
per day. You can program a maximum of 21 periods per week.
WEEK PROGRAM
START OPERATION
^»PROGRAM OVERVIEW
È
Figure 8.6 Week programme
Bring up the menu for the week program via:
WEEK PROGRAM | PROGRAM OVERVIEW.
1. B:
Confirm with E.
Release R.1.3 UK55
Page 56
8
Main menu
gis
DAY TIME Tset
ON »SU 00:00 65ÉC P
OFF SU 23:59
ON MO 00:00 65ÉC P
OFF MO 23:59
ON TU 00:00 65ÉC P
OFF TU 23:59
ON WE 00:00 65ÉC P
OFF WE 23:59
ON TH 00:00 65ÉC P
OFF TH 23:59
ON FR 00:00 65ÉC P
OFF FR 23:59
ON SA 00:00 65ÉC P
OFF SA 23:59
INSERT
DELETE
START OPERATION
Figure 8.7 Standard week
program
ON »SU 00:00
OFF SU 23:59
Tset 65ÉC
PUMP ONSAVE
Figure 8.8 Week programme
ON SU»08:00
OFF SU 08:00
Tset 65ÉC
PUMP ONSAVE
Figure 8.9 Setting switch-on
hours in week program
ON SU 08»15
OFF SU 08:15
Tset 65ÉC
PUMP ONSAVE
Figure 8.10 Setting switch-on
minutes in week program
ON SU 08:15
OFF SU»08:15
Tset 65ÉC
PUMP ONSAVE
Figure 8.11 Setting switch-off
hours in week program
The display now shows the menu for the week program, see Figure 8.7. With
the default setting, the program switches on and off every day at 00:00 and
23:59 hours respectively, the water temperature is 65ºc and the pump is
switched on (
Example
As an example, we will set the switch-on time for Sunday to 08:15 hours, and
the matching switch-off time to 12:45 hours. The water temperature will be set
to 75ºC and the pump will run continuously.
The following settings are entered one by one via the menu: the switch-on time,
the switch-off time, the desired water temperature, and the state of the programcontrolled pump.
Setting the switch-on time
2. Bring the cursor to
Figure 8.8 will appear. The day indicated by the » will blink.
3. Use H and L to select the day desired. In the example, this is
Confirm with E.
The cursor moves to the hour digits, which will blink. See Figure 8.9.
4. Use H and L to select the hour. In the example this is
Confirm with E.
The cursor moves to the minute digits, which will blink. See Figure 8.10.
P).
SU and press E. The sub-menu shown in
SU (Sunday).
08.
n Remark
Because the switch-off time can never be earlier than the switch-on time, the
switch-off time setting is automatically adjusted with the switch-on time.
5. Use H and L to select the minutes. In the example this is
Confirm with E.
The cursor moves to the switch-off hour digits, which will blink. See
Figure 8.11.
Setting switch-off time
6. Use H and L to select the hour. In the example this is
Confirm with E.
15.
12.
56Instruction Manual BFC
Page 57
gis
Week programme
ON SU 08:15
OFF SU 12»15
Tset 65ÉC
PUMP ONSAVE
Figure 8.12 Setting switch-off
minutes in week program
ON SU 08:15
OFF SU 12:45
Tset»65ÉC
PUMP ONSAVE
Figure 8.13 Setting water
temperature in week program
ON SU 08:15
OFF SU 12:45
Tset 75ÉC
PUMP ONSAVE
Figure 8.14 Setting the pump in
week program
ON SU 08:15
OFF SU 12:45
Tset 75ÉC
PUMP ON»SAVE
Figure 8.15 Save week
program
DAY TIME Tset
ON »SU 08:15 75ÉC P
OFF SU 12:45
ON MO 00:00 65ÉC P
OFF MO 23:59
ON TU 00:00 65ÉC P
OFF TU 23:59
The cursor moves to the minute digits, which will blink. See Figure 8.12.
7. Use H and L to select the minutes. In the example this is
45.
Confirm with E.
The cursor moves to the water temperature. See Figure 8.13.
Setting the water temperature
8. Use H and L to select the water temperature. In the example this is 75ÉC.
Confirm with E.
The cursor moves to
PUMP ON . See Figure 8.14.
Setting program-controlled pump
9. If required, a pump can be controlled during the period. Use H and L to
PUMP ON . The pump ensures a regular circulation of hot water in
select
the hot water pipes. You can skip this step if you there is no pump in your
hot water circuit.
Confirm with E.
The cursor moves to SAVE. See Figure 8.15.
10. Confirm with E.
The display shown in Figure 8.16 appears.
11. If you wish, use L to scroll to another day, and change more switch-on and
switch-off times. Simply repeat steps 3 through 10.
12. After changing all desired switch-on and switch off times, you can start
running the week program:
-Scroll with L to
START OPERATION.
Confirm with E.
Figure 8.16 Add week program
8.5.4Adding times to a week program
WEEK PROGRAM
START OPERATION
^»PROGRAM OVERVIEW
È
Figure 8.17 Inserting a week
program
The menu to INSERT switch-on and switch-off times into a week program is
reached via:
WEEK PROGRAM | PROGRAM OVERVIEW.
1. B:
Confirm with E.
Release R.1.3 UK57
Page 58
8
Main menu
gis
DAY TIME Tset
»SU 08:15 75ÉC P
OFF SU 12:45
ON MO 00:00 65ÉC P
....................
....................
OFF SA 23:59
INSERT
DELETE
START OPERATION
Figure 8.18 Week programme
ON »SU 08:15
OFF SU 12:45
Tset 65ÉC
PUMP ONSAVE
Figure 8.19 Adding a period
DAY TIME Tset
ON »SU 18:00 75ÉC P
OFF SU 22:00
ON MO 00:00 65ÉC P
OFF MO 23:59
....................
....................
OFF SA 23:59
INSERT
DELETE
START OPERATION
Figure 8.20 Period added
The display shows the menu for the week program, see Figure 8.18. The
cursor points to the active period.
2. Scroll L to
Confirm with E.
The sub-menu for adding a period will appear. See Figure 8.19.
Example
As an example, we will program an extra period in which the switch-on time is
set to 18:00 hours, and the matching switch-off time to 22:00 hours. The water
temperature will be set to 75ºC and the pump will run continuously.
3. Repeat steps 3 through 10 of paragraph 8.5.3. After the option
display as shown in Figure 8.20 appears; i.e. with the cursor beside the
period we have just added.
4. To activate the week program with the new period added, scroll down with
L to
INSERT.
SAVE the
START OPERATION and confirm with E.
8.5.5Deleting times from a week program
DAY TIME Tset
ON »SU 08:15 75ÉC P
OFF SU 12:45
ON SU 18:00 75ÉC P
OFF SU 22:00
....................
....................
OFF SA 23:59
INSERT
DELETE
START OPERATION
Figure 8.21 A program
MENU
OFF
^»ON
È WEEK PROGRAM
Figure 8.22 Week programme
All switch-on/off times are shown sequentially in the display. Assume that the
switch-on/off times for the appliance are programmed as in Figure 8.21.
To delete a period, proceed as follows:
WEEK PROGRAM.
1. B:
Confirm with E.
58Instruction Manual BFC
Page 59
gis
Week programme
WEEK PROGRAM
START OPERATION
^»PROGRAM OVERVIEW
È
Figure 8.23 week program
options
DAY TIME Tset
ON !SU 08:15 75ÉC P
OFF SU 12:45
ON SU 18:00 75ÉC P
OFF SU 22:00
....................
....................
OFF SA 23:59
INSERT
DELETE
START OPERATION
Figure 8.24 A program
DAY TIME Tset
ON !SU 18:00 75ÉC P
OFF SU 22:00
ON MO 00:00 65ÉC P
OFF MO 23:59
....................
....................
OFF SA 23:59
INSERT
DELETE
START OPERATION
Figure 8.25 Select
DAY TIME Tset
ON ! DELETE
OFFBLOCK?
ON MO 00:00 65ÉC P
Figure 8.26 Confirm deletion of
block from week program
DAY TIME Tset
ON SU 08:15 75ÉC P
OFF SU 12:45
ON MO 00:00 65ÉC P
OFF MO 23:59
....................
....................
OFF SA 23:59
INSERT
DELETE
START OPERATION
Figure 8.27 Period deleted
2. Scroll with L to PROGRAM OVERVIEW.
Confirm with E.
The display will show the week program sub-menu, see Figure 8.21.
3. Scroll with L to
DELETE.
Confirm with E.
4. The display will change as shown in Figure 8.24. To warn you that you are
now working in the delete sub-menu, the cursor is replaced with an
exclamation mark (
!) and the period settings will blink (illustrated in the
figure by underlining).
5. Scroll with L to the day to be deleted. For example, the second period of SU
(Sunday). See Figure 8.25.
Confirm with E.
6. The lines showing switch-on/off times are replaced by the text
DELETE BLOCK?. See Figure 8.26.
Confirm with E
(or use R to cancel deletion)
The switching period has been deleted. You will return now to the week
program menu. The cursor is beside the first programmed period. See
Figure 8.27.
7. Scroll with L to
START OPERATION.
Confirm with E.
The week program is active.
Release R.1.3 UK59
Page 60
8
8.6Extra period
8.6.1Introduction
EXTRA
10:00 Monday76ÉC
MO 11:15 Tset 75ÉC
PERIOD ACTIVATED
Figure 8.28 Extra period active
8.6.2Programming an extra period
MENU
ON
^ WEEK PROGRAM
ȻEXTRA PERIOD
Figure 8.29 Extra period
ON SU»08:00
OFF SU 08:00
Tset 65ÉC
PUMP ONSTART
Figure 8.30 Setting switch-on
hour for extra period
ON SU 08»15
OFF SU 08:15
Tset 65ÉC
PUMP ONSTART
Figure 8.31 Setting the switchon minutes for extra period
ON SU 08:15
OFF SU»08:15
Tset 65ÉC
PUMP ONSTART
Figure 8.32 Setting switch-off
hour for extra period
ON SU 08:15
OFF SU 12»15
Tset 65ÉC
PUMP ONSTART
Main menu
gis
Use an extra period when you either want to have the appliance switch on and
off for a certain period, either without modifying the active week program, or
without taking the appliance out of OFF mode (frost protection active).
If the appliance is running under an ‘extra period’, then this is indicated in the
display with the text EXTRA. See Figure 8.28.
If the water temperature becomes too low during the extra period (see
’8.6.2 Programming an extra period’), the appliance will run through the heating
cycle (see ’7.4 The appliance’s heating cycle’), then fall back into the extra
period.
The same settings can be made for an extra period as for a week program
period. See paragraph ’8.5.3 Changing the appliance’s standard week
program’.
Bring up the menu for entering an extra period via:
EXTRA PERIOD
1. B:
Confirm with E.
The display show the settings for the extra period. See Figure 8.30.
Setting the switch-on time
2. Use H and L to select the day desired. In the example this is SU.
Confirm with E.
The cursor moves to the hour digits, which will blink. See Figure 8.30.
3. Use H and L to set the switch-on hour to the desired value. In the example
08.
this is
Confirm with E.
The cursor moves to the minute digits, which will blink. See Figure 8.31.
n Remark
Because the switch-off time can never be earlier than the switch-on time, the
switch-off time setting is automatically adjusted with the switch-on time.
4. Use H and L to select the minutes. In the example this is
Confirm with E.
The cursor moves to the hour digits of the switch-off period. See Figure 8.32.
Setting switch-off time
5. Use H and L to select the hour. In the example this is 12.
Confirm with E.
The cursor moves to the minute digits, which will blink. See Figure 8.33.
6. Use H and L to select the minutes. In the example this is
Confirm with E.
15.
45.
Figure 8.33 Setting the switchoff minutes for extra period
60Instruction Manual BFC
Page 61
gis
Settings
ON SU 08:15
OFF SU 12:45
Tset»65ÉC
PUMP ONSAVE
Figure 8.34 Setting water
temperature for extra period
ON SU 08:15
OFF SU 12:45
Tset 75ÉC
PUMP»ONSTART
Figure 8.35 Pump setting for
extra period
ON ZO 08:15
OFF ZO 12:45
Tset 75ÉC
PUMP ON»START
Figure 8.36 Saving extra period
8.7Settings
The cursor moves to the water temperature. See Figure 8.34.
Setting the water temperature
7. Use H and L to select the water temperature. In the example this is 75.
Confirm with E.
The cursor moves to
PUMP ON. See Figure 8.35.
Setting program-controlled pump
8. If required, a pump can be controlled during the period. Use H and L to
PUMP ON. The pump ensures a regular circulation of hot water in the
select
hot water pipes. You can skip this step if you there is no pump in your hot
water circuit.
Confirm with E.
The cursor moves to
START. See Figure 8.36.
9. Confirm with E.
The extra period has been programmed.
n Remark
Once the extra period has completed running, the controller returns to the
mode ON, OFF or WEEK PROGRAM. The following week, the extra period
will NOT be automatically switched on.
MENU
WEEK PROGRAM
^ EXTRA PERIOD
ȻSETTINGS
Figure 8.37 Settings
SETTINGS
»LANGUAGE
^ DAY/TIME
È SPECIFICATIONS
8.7.1Introduction
Using the option SETTINGS you can adjust certain settings, and display certain
appliance specifications. See Table 8.1.
Tab le 8.1 Adjustable settings and displayable appliance specifications
Adjustable settings! Menu language
Displayable appliance
specifications
This category is only relevant to
the installer and/or service and
maintenance engineer.
8.7.2Setting menu language
Bring up the menu for selecting the language via:
SETTINGS.
1. B:
Confirm with E.
The display shows the menu for settings. See Figure 8.38.
2. The cursor is positioned beside LANGUAGE
Confirm with E.
The display shows the language selection menu. See Figure 8.39.
! Current day of week, and time
! Regulation interval (water
temperature).
! Ignition speed of fan.
! Running speed of fan.
Figure 8.38 Language
Release R.1.3 UK61
Page 62
8
Main menu
gis
LANGUAGE
ENGLISH
^ NEDERLANDS
ȻDEUTSCH
FRANCAIS
ITALIANO
Figure 8.39 Language selection
8.7.3Setting day and time
MENU
WEEK PROGRAM
^ EXTRA PERIOD
ȻSETTINGS
Figure 8.40 Settings
SETTINGS
LANGUAGE
^»DAY/TIME
È SPECIFICATIONS
Figure 8.41 Day and time
DAY
»Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saterday
Figure 8.42 Setting the day
TIME
»00:00
3. Scroll with L to the desired language.
Confirm with E.
The language is set.
Bring up the menu for entering the day and time via:
SETTINGS.
1. B:
Confirm with E.
The display shows the menu for settings. See Figure 8.38.
2. Scroll with H and L to DAY/TIME
Confirm with E.
The display shows the sub-menu for selecting the day of the week. See
Figure 8.42.
3. The cursor is positioned beside Sunday.
Scroll with H and L to the desired day.
Confirm with E.
The day of the week has been set. The display shows the sub-menu for
adjusting the time. See Figure 8.43.
4. The cursor moves to the hour digits, which will blink.
Scroll with H and L to the current hour, for example 15.
Confirm with E.
Figure 8.43 Setting the hour
TIME
Figure 8.44 Setting the minutes
TIME
Figure 8.45 Setting the minutes
15»00
15»45
5. The cursor moves to the minute digits, which will blink.
Scroll with H and L to the next minute in time, for example 45.
Confirm the minute setting with E.
The current time has been set.
n Remark
The appliance takes no account of daylight saving.
8.7.4Displaying appliance specifications
n Remark
This category is only relevant to the installer and/or service and
maintenance engineer.
62Instruction Manual BFC
Page 63
gis
Settings
Ta bl e 8 .2 shows the standard appliance specifications.
Tab le 8.2 Appliance specifications
MENU
WEEK PROGRAM
^ EXTRA PERIOD
ȻSETTINGS
Figure 8.46 Main menu
SETTINGS
LANGUAGE
^ DAY/TIME
ȻSPECIFICATIONS
Figure 8.47 Settings
SPECIFICATIONS
»REGULATION INTERVAL
^ IGNITION SPEED
È WORKING SPEED
ApplianceIgnition speed
of fan
Running speed
of fan
Regulation
interval
BFC 284500 rpm4980 rpm40-80 °C
BFC 304500 rpm5400 rpm40-80 °C
BFC 504500 rpm6000 rpm40-80 °C
BFC 604500 rpm6660 rpm40-80 °C
Bring up the menu to display the appliance specifications via:
1. B: SETTINGS.
Confirm with E.
2. Scroll with L to SPECIFICATIONS
Confirm with E.
The display shows the sub-menu for displaying appliance specifications.
See Figure 8.48.
3. Scroll with L to the section to be displayed, for example
REGULATION INTERVAL.
The relevant display specification appears, see Figure 8.49.
Figure 8.48 Appliance
specifications
REGULATION INTERVAL
40_80ÉC
Figure 8.49 Regulation interval
Release R.1.3 UK63
Page 64
8
Main menu
gis
64Instruction Manual BFC
Page 65
is
is
9Service program
9.1Introduction
SERVICE MENU
»HYSTERESE
^ HISTORIE OF ERRORS
È APPLIANCE HISTORY
SELECT APPLIANCE
PUMP RELAY
SERVICE INTERVAL
CONTRAST DISPLAY
TIME BACKLIGHT
SCROLLSPEED
Figure 9.1 Service program
Introduction
The service program is used by the installer or service and maintenance
engineer for:
•Setting the hysteresis;
•Displaying the error history;
•Displaying the appliance history;
•Display the selected appliance;
•Setting the pump on/off;
•Setting the service interval;
•Setting the display contrast;
•Setting the backlight time;
•Setting the display scroll speed.
These sub-menus are briefly described in the following paragraphs. If you are
not familiar in general with how to use the displays and menus, first read chapter
’5 The control panel’.
9.2Setting the
hysteresis
HYSTERESE UP»3ÉC
Figure 9.2 Heating cycle upper
limit
9.3Displaying the error
history
n Remark
The notation convention for the service menu is identical to that described
in paragraph ’8.2 Notational convention for menu-related instructions’. The
difference is, you use S to bring up the service program, instead of B
which brings up the main menu.
If the preset temperature (SETPOINT) is higher than the current water
temperature, then the appliance might not immediately start the heating cycle
(see chapter ’7.4 The appliance’s heating cycle’). To prevent excessively
frequent switching on and off, a there is a heating margin. We refer to this
margin as the hysteresis. The standard setting for this margin is 2°C. The
heating cycle starts if the water temperature drops to 2°C below the SETPOINT
and ends when the water reaches 2°C above the SETPOINT.
Set the hysteresis via:
•S:
Set the hysteresis via
•S:
Display the error history via:
•S:
The controller will display an overview of ‘Blocking errors’ and ‘Lock out errors’.
In both cases, note that the ThermoControl reserves 15 lines for the last 15 error
messages. If there are less than 15 error messages, then an ellipsis (...) is
displayed. The display first shows the ‘Blocking errors’. When E is
pressed, the ‘Lock out Errors’ are then displayed.
HYSTERESE UP
Figure 9.2 shows an example.
HYSTERESE DOWN
HISTORIE OF ERRORS
Release R.1.3 UK65
Page 66
9
Service program
is
HISTORIE OF ERRORS(B)
S04 SENSOR ERROR
F06 IONIZATION
È CO2 50 HZ ERROR
Figure 9.3 Blocking errors
HISTORIE OF ERRORS(L)
F02: FAN
F07: FLAME ERROR
È ...
Figure 9.4 Lock out errors
9.4Displaying the
appliance history
APPLIANCE HISTORY
BURNINGHOURS 000410
^IGNITIONS001000
ÈFLAME ERRORS 000021
Figure 9.3 shows an example of ‘Blocking errors’. In this case, the text
HISTORIE OF ERRORS is followed by (B).
Figure 9.4 shows an example of the ‘Lock out errors’. In this case, the text
HISTORIE OF ERRORS is followed by (L).
n Remark
For an overview of all errors and the possible causes, please refer to chapter
’10 Troubleshooting’.
The appliance history sub-menu is used to display the burning hours, the
number of ignitions, the number of flame errors, and the number of ignition
errors.
Bring up the menu for displaying the appliance history via:
•S:
Bring up the menu for displaying the appliance selection via:
•S:
APPLIANCE HISTORY
Figure 9.5 shows an example.
SELECT APPLIANCE
The appliance selection has been correctly preset in the factory.
Figure 9.6 shows the relevant display.
Figure 9.6 Select appliance
9.6Setting the pump
on/off
PUMP RELAY
»ON
OFF
Figure 9.7 Pump relay
9.7Setting the service
interval
If a program-controlled pump is installed (Installation, see paragraph 3.10.6)
then this can be turned ON or OFF via:
•S:
If the mode
mode WEEK PROGRAM or EXTRA PERIOD has priority over the ON/OFF
selection for the pump relay in the service menu.
Example
One of the week program periods is currently active. The pump relay setting is
OFF within this period. If the pump relay is set ON in the service menu, the pump
will nonetheless remain OFF. The pump will only switch ON once the week
program period has ended.
To aid servicing, the ThermoControl has a service interval which defines the
frequency of maintenance by the service and maintenance engineer based on
the number of burning hours. Refer also to paragraph 11.2 .
PUMP RELAY
The standard setting for the pump relay is OFF.
Figure 9.7 shows the related display.
WEEK PROGRAM or EXTRA PERIOD is active, then the setting for
66Instruction Manual BFC
Page 67
is
SERVICE INTERVAL
» 500
^ 1000 BURNING HOURS
È 1500
Figure 9.8 Service interval
Setting the display contrast
The service interval is based on the number of burning hours. This can be set
to 500, 1000 and 1500 hours. The standard setting for number of hours is 500.
Once the preset number of hours is reached, a message to this effect will
appear. See paragraph ’6.4 Service condition’.
Adjust the service interval via:
•S:
Refer also to paragraph ’11.2 Determining service interval’.
SERVICE INTERVAL
Figure 9.8 shows the related display.
9.8Setting the display
contrast
CONTRAST DISPLAY
» 95 %
Figure 9.9 Display contrast
9.9Setting the backlight
time
TIME BACKLIGHT
» 255 sec
Figure 9.10 Backlight time
9.10 Setting the display
scroll speed
SCROLLSPEED
» 10
Adjust the display contrast via:
•S:
Adjust the backlight time (the time that the display backlight stays lit after the last
button is pressed) via:
•S: TIME BACKLIGHT
Adjust the display scroll speed via:
•S: SCROLLSPEED
CONTRAST DISPLAY
The standard setting is 100%. The range is from 0 through 100%.
Figure 9.9 shows the related display.
The standard value is 255 sec. The range is from 0 through 255 seconds.
Figure 9.10 shows the related display.
The standard setting is 10. The range is from 0 through 100. Setting the
value too high or low will make scrolling difficult.
Figure 9.11 shows the related display.
Figure 9.11 Scroll speed
Release R.1.3 UK67
Page 68
9
Service program
is
68Instruction Manual BFC
Page 69
gis
10Troubleshooting
10.1 IntroductionA distinction is made between:
•General errors
General errors are not reported on the display. General errors are:
-Gas smell
-Display does not light up
-Insufficient or no hot water.
-Water leakage
-Explosive ignition
Table 10.1 gives a troubleshooting overview for general errors.
•Displayed errors
S02: SENSOR ERROR
TOP TANK
SENSOR 1
NOT CONNECTED
Figure 10.1 Possible error
Errors are reported on the display, as follows:
-Line 1: An error code and its short description. The code is made up
of a letter and two digits.
-Lines 2, 3 and 4: a long description, and a recommended action,
alternating every 2 seconds. See Figure 10.1 and Figure 10.2.
S02: SENSOR ERROR
TOP TANK
CHECK TOP TANK
SENSOR
Figure 10.2 Action
The displayed errors are divided into two groups:
There are various types of errors:
-LOCK OUT ERRORS
When the cause is no longer present, these errors require a reset with
the R button, before the appliance can resume running.
-BLOCKING ERRORS
These errors disappear automatically once the cause of the error has
been removed, after which the appliance resumes by itself.
Table 10.2 gives a troubleshooting overview for the errors that appear on the
display.
n Remark
Footnotes referred to from within any table are shown at the bottom of the
last page of that table.
Release R.1.3 UK69
Page 70
is
Immediately contact your installer or local gas company.
n Remark
Warning
Immediately close the main gas valve.
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
10.2 Troubleshooting table for general errors
SymptomCauseSolutionRemark
Table 10.1 General errors (Sheet 1 of 3)
Gas smellGas leak
Warning
Do not operate any switches.
Warning
No naked flames.
Warning
Ventilate the boiler room.
Release R.1.3 UK70
Page 71
is
If the error cannot be rectified, contact your installer.
See appendix ’A.2 Electrical diagram BFC’.
(position I).
block.
Check that the condensation water discharge is working properly.
Rectify if necessary.
1. Check whether the mains switch is ON.
2. Check that there is power to the mains switch.
3. Check whether the ON/OFF switch of the ThermoControl is ON
4. Check whether there is power to the electrical connection
5. The voltage measured must be 230 VAC (-15%, +10%).
No electric power
present
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
SymptomCauseSolutionRemark
Table 10.1 General errors (Sheet 2 of 3)
Display is offAppliance is turned off. Start-up the appliance. See ’7.2 Starting up’
Tighten the threaded connection. If the leak persists, consult your installer.
Defective fuse(s)Replace fuse(s)To replace the fuses you must contact your installer.
Water leakageLeakage from one of
the water connections
(threaded).
Trace the leak.
Condensation water
leakage
Leakage from another
nearby water
appliance or pipe
Consult the supplier and/or manufacturer.
segment.
Leakage from the
appliance’s tank.
Release R.1.3 UK71
Page 72
is
If ignition is not improved, consult your installer.
Set the correct supply pressure and/or burner pressure, see
’3.11 Checking the supply pressure and burner pressure’.
If the error cannot be rectified, contact your installer.
See appendix ’A.2 Electrical diagram BFC’.
(position I).
block.
1. Check whether the mains switch is ON.
2. Check that there is power to the mains switch.
3. Check whether the ON/OFF switch of the ThermoControl is ON
4. Check whether there is power to the electrical connection
If there continues to be insufficient or no hot water, consult your
installer.
Reduce hot water consumption and give the appliance time to heat
up.
5. The voltage measured must be 230 VAC (-15%, +10%).
Put the controller in ON mode, see ’8.3 Switching into “ON mode”’.
) to a higher value, see ’8.4 Setting the water
set
Set temperature (T
temperature’.
) is
set
Hot water supply is
used up.
Appliance is turned off. Start-up the appliance. See ’7.2 Starting up’
No electric power
pressure and/or burner
pressure.
Contaminated burnerClean the burner. See ’12.4.2 Cleaning the burner’
Contaminated orifice.Clean the orifice. See ’12.4.3 Cleaning the orifice’
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
SymptomCauseSolutionRemark
Table 10.1 General errors (Sheet 3 of 3)
Explosive ignitionIncorrect supply
Insufficient or no hot
present.
water.
The controller is in
Temperature (T
OFF mode.
set too low.
10.3 Troubleshooting table for displayed errors
Release R.1.3 UK72
Page 73
is
Replace the sensor.To replace the necessary parts, you must contact your installer.
Connect the sensor lead to JP3.See appendix ’A.2 Electrical diagram BFC’.
Damaged wiring or
Sensor is not
(correctly) connected.
2
defective sensor.
Connect the sensor lead to JP5.See appendix ’A.2 Electrical diagram BFC’.
Sensor is not
(correctly) connected.
to JP4.See appendix ’A.2 Electrical diagram BFC’.
(2)
.To replace the necessary parts, you must contact your installer.
1
Replace sensor T
Damaged wiring or
defective sensor.
.
1
(1)
.To replace the necessary parts, you must contact your installer.
1
Replace sensor T
Connect the sensor lead to JP5.See appendix ’A.2 Electrical diagram BFC’.
Damaged wiring or
Sensor is not
(correctly) connected.
defective sensor.
.
1
(1)
Connect the dummy sensor lead
Dummy is not
(correctly) connected.
to JP4.See appendix ’A.2 Electrical diagram BFC’.
(3)
Connect the dummy sensor lead
Defective dummy.Replace the dummy sensor.To replace the necessary parts, you must contact your installer.
Dummy is not
(correctly) connected.
Defective dummy.Replace the dummy sensor.To replace the necessary parts, you must contact your installer.
.To replace the necessary parts, you must contact your installer.
2
Replace sensor T
Short circuit in the
sensor circuit.
at the
2
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
Code + DescriptionPossible causeSolutionRemark
S01 (blocking error)
Open circuit from
Table 10.2 Displayed errors (Sheet 1 of 10)
temperature sensor T
at bottom of tank.
S02 (blocking error)
Open circuit from
sensor 1 of
temperature sensor T
at the top of the tank
S03 (blocking error)
Open circuit from
sensor 2 of
temperature sensor T
S04 (blocking error)
Open circuit from
dummy 1.
S05 (blocking error)
Open circuit from
dummy 2.
S11 (blocking error)
Short circuit from the
at the top of the tank
temp. sensor T
bottom of the tank.
Release R.1.3 UK73
Page 74
is
.To replace the necessary parts, you must contact your installer.
1
Replace sensor T
Short circuit in the
sensor circuit
.To replace the dummy sensor you must contact your installer.
(2)
.To replace the necessary parts, you must contact your installer.
1
1
Replace the dummy sensor
Short circuit in dummy
circuit
Replace sensor T
Short circuit in the
sensor circuit
1
.To replace the dummy sensor you must contact your installer.
(2)
Replace the dummy sensor
Short circuit in dummy
circuit
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
Table 10.2 Displayed errors (Sheet 2 of 10)
S12 (blocking error)
Short circuit from
Code + DescriptionPossible causeSolutionRemark
sensor 1 of
S13 (blocking error)
Short circuit from
sensor 2 of
temperature sensor T
S14 (blocking error)
Short circuit from
dummy 1
S15 (blocking error)
Short in circuit of
temperature sensor T
at the top of the tank
at the top of the tank
dummy 2.
Release R.1.3 UK74
Page 75
is
To have the wiring replaced and a new fan fitted, you must contact
If errors become persistent, contact your installer.
See appendix ’A.2 Electrical diagram BFC’.
your installer.
circuit.
1. Disconnect the lead at the ionisation rod.
2. Ignite the appliance 3 times, with an interrupted ionisation
Connect the phase and the neutral correctly. The appliance is
phase-sensitive. See ’3.10 Electrical connection’.
Condensation on the
Phase and neutral
swapped in error.
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
Code + DescriptionPossible causeSolutionRemark
F01 (blocking error)
Defect in power supply
Table 10.2 Displayed errors (Sheet 3 of 10)
circuit.
3. Reconnect the ionisation lead to the ionisation rod.
ionisation rod.
4. Ignite the appliance again
condensation to evaporate.
5. The repeated ignition attempts will have caused the
Floating neutral.Install an isolating transformer. See ’3.10.4 Isolating Transformer’. Contact your installer to have an isolating transformer installed.
replaced.
2. If any wires are damaged, the wiring harness must be
3. Reset the water heater controller.
1. Check whether the fan is contaminated.
2. Check that the rotor can rotate freely.
3. Reset the water heater controller.
1. Check the supply voltage. This must be 230 VAC (+10% -15%).
2. Reset the water heater controller.
Damaged wiring.1. Check the wiring between the fan and the controller.
F02 (lock out error)
Fan fails to run at
correct speed.
Contaminated or
blocked fan.
Because of a voltage
drop in the mains
power, the fan will not
run at the correct
speed.
Release R.1.3 UK75
Page 76
is
If the error cannot be resolved or is persistent, contact your
installer.
To replace the necessary parts, you must contact your installer.
appliance specifications’.
hose between fan and burner are correctly fitted. Refit these if
necessary.
hose between fan and burner for cracks. If necessary, replace
the hoses.
controller.
1. Check the wiring between the pressure switch and the
2. If necessary, replace the wiring.
Damaged wiring /
Open circuit
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
Table 10.2 Displayed errors (Sheet 4 of 10)
F03 (lock out error)
The pressure switch
Code + DescriptionPossible causeSolutionRemark
fails to work correctly.
2. Check that the hoses on the pressure switch and the air supply
1. Check the running speed of the fan. See ’8.7.4 Displaying
Pressure switch not
closing.
3. Check the hoses on the pressure switch and the air supply
Ta bl e 3 .7 .
4. Check whether the flue gas discharge is compliant with
blockage that may be present.
Remove any blockage that may be present.
See Ta bl e 1 2. 1. If there is insufficient pressure differential,
clean the heat exchanger. If the pressure differential is
acceptable, check that the pressure switch is closing, using a
multimeter.
5. Check for blockage in the flue gas discharge. Remove any
6. Check for blockage in the condensation water discharge.
7. Measure the pressure differential across the pressure switch.
Release R.1.3 UK76
Page 77
is
To repair the gas supply, contact your installer.
control.
2. Check supply pressure to the gas control.
how to bleed air from the gas line, and measure the supply
pressure and burner pressure.
To replace the necessary parts, you must contact your installer.
3. If necessary, repair the gas supply.
2. Check that the gas valve(s) open and shut correctly.
If the error persists, contact your installer.
To replace the necessary parts, you must contact your installer.
between 2 and 5 Ω.
3. If necessary, replace the gas control.
1. Check that the glow igniter is correctly connected (JP2).
2. Check the wiring of the glow igniter.
3. Measure the resistance across the glow igniter. This must lie
µA.
4. Check that the glow igniter lights up during ignition.
5. If necessary, replace the glow igniter.
1. Check that the ionisation rod is correctly connected (JP2).
2. Check the wiring of the ionisation rod.
3. Measure the ionisation current. This must be a minimum of 1.5
4. If necessary, replace the wiring.
(+10% -15%).
No gas.1. Open the main gas valve and/or the gas valve before the gas
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
Table 10.2 Displayed errors (Sheet 5 of 10)
F04 (lock out error)
Three unsuccessful
Code + DescriptionPossible causeSolutionRemark
ignition attempts.
Air in the gas pipes.Bleed the air out of the gas pipe.See ’3.11 Checking the supply pressure and burner pressure’ for
No burner pressure.1. Check the burner pressure at the gas control.
Defect in the glow
igniter circuit.
Defect in the ionisation
circuit.
Supply voltage too low Check the supply voltage to the appliance. This must be 230 VAC
Release R.1.3 UK77
Page 78
is
If the error cannot be resolved or is persistent, contact your
installer.
If the error persists, contact your installer.
To replace the necessary parts, you must contact your installer.
If the error cannot be resolved or is persistent, contact your
installer.
To replace the necessary parts, you must contact your installer.
If the error cannot be resolved or is persistent, contact your
installer.
To replace the necessary parts, you must contact your installer.
2. If necessary, install the correct roof or wall terminal.
Recirculating flue
have been signalled.
area.
3. Check that the roof or wall terminal discharges into a permitted
gases.
Check the wiring of the ionisation rod. If necessary, replace the
wiring.
Damaged cable in
contact with metal
F06 (lock out error)
Short circuit between
’3.9 Air supply and flue gas discharge’.
1. Check that the correct roof or wall terminal has been fitted. See
Incorrect roof or wall
terminal.
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
Code + DescriptionPossible causeSolutionRemark
F05 (lock out error)
Table 10.2 Displayed errors (Sheet 6 of 10)
Too many flame errors
intact, in the vicinity of the air distribution plate of the burner.
1. Check whether the ceramic part of the ionisation rod is still
2. If this is not the case, the ionisation rod must be replaced.
surface.
Ceramic part of the
ionisation rod is
broken/cracked.
ionisation rod and
earth
gas valves have closed.
Defective gas valves.1. Check whether there is still burner pressure present, after the
F07 (lock out error)
A flame has been
have closed.
2. Check whether a flame is still present, after the gas valves
3. If this is the case, then the gas control must be replaced.
detected after the gas
valve was closed.
1. Reset ThermoControl.
Flame detection
before gas valve
F08 (lock out error)
2. If the error appears again, replace ThermoControl.
opened.
Error message from
safety relay.
Release R.1.3 UK78
Page 79
is
If the error cannot be resolved or is persistent, contact your
installer.
If the error cannot be resolved or is persistent, contact your
installer.
To replace the necessary parts, you must contact your installer.
1. Check that the circulation pump (if present) is working.
.
2. Check the position of the temperature sensor T
1
3. Reset the water heater controller.
C. If this is the
o
Error “F09” remains active in the event that the water
temperature during a reset was higher than 78
n Remark
case, first draw water off by opening the nearest hot water tap,
appliance specifications’.
hose between fan and burner are correctly fitted. Refit these if
necessary.
air supply hose between fan and burner. If necessary, replace
the hoses.
so that cold water can flow in.
2. Check that the hoses on the pressure switch and the air supply
1. Check the running speed of the fan. See ’8.7.4 Displaying
3. Check for cracks in the hoses on the pressure switch and the
Ta bl e 3 .8 .
4. Check whether the flue gas discharge is compliant with
blockage that may be present.
Remove any blockage that may be present.
Ta bl e 1 2. 1. If there is insufficient pressure differential, clean the
heat exchanger. If the pressure differential is acceptable, check
that the pressure switch is closing, using a multimeter.
5. Check for blockage in the flue gas discharge. Remove any
6. Check for blockage in the condensation water discharge.
7. Measure the pressure differential across the pressure switch.
8.
Temperature at the top
of the tank exceeds
93°C.
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
Table 10.2 Displayed errors (Sheet 7 of 10)
F09 (lock out error)
Water temperature
Code + DescriptionPossible causeSolutionRemark
protection.
Pressure switch not
closing.
F10 (lock out error)
Restriction on number
of ignition attempts
based on pressure
switch state changes.
Release R.1.3 UK79
Page 80
is
Defective gas valves.See F07.
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
Table 10.2 Displayed errors (Sheet 8 of 10)
F11 (lock out error)
Flame detection with
Code + DescriptionPossible causeSolutionRemark
closed gas valve.
Release R.1.3 UK80
Page 81
is
To replace the necessary parts, you must contact your installer.
table 3.8. If this is not the case, contact your installer.
ThermoControl.
1. Reset the ThermoControl.
2. Check that the frequency of the mains power complies with
3. If the frequency is correct but the error persists, replace the
Incorrect reference
voltage from the AD
converter.
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
Table 10.2 Displayed errors (Sheet 9 of 10)
C02 (lock out error)
Error message from
Code + DescriptionPossible causeSolutionRemark
the water heater
controller.
EEPROM read error.
50 Hz error.
Internal error message
from the water heater
controller.
Internal
communication error
Gas valve relay error.
Safety relay error.
Internal error message
from the water heater
controller.
Ignition relay error.
RAM error.
EEPROM error.
EEPROM contents do
not match the software
version.
Processor software
error.
Release R.1.3 UK81
Page 82
is
If the error does not disappear, you must contact your installer.
To replace the necessary parts, you must contact your installer.
To obtain a selection resistor, you must contact your installer.
To replace the necessary parts, you must contact your installer.
To replace the dummy sensor you must contact your installer.
resistor.
’9.5 Display the selected appliance’.
3. If incorrect appliance selected, select the correct one.
None. This is a temporary message that may appear from time to
The temperature of the
E01 (blocking error)
time, but will disappear automatically.
water at the top of the
tank is > 85°C.
The temperature
protection at the top of
the tank has been
activated.
Wait for the error to disappear (maximum 1 hour). If the error does
not disappear, the water heater controller must be replaced.
1. Check whether the correct appliance has been selected. See
2. If the correct appliance is selected, fit the correct selection
Too many resets in too
short a period.
Incorrect appliance
selection /
Incorrect selection
resistor.
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
Table 10.2 Displayed errors (Sheet 10 of 10)
C03 (blocking error)
Reset error.
C04 (blocking error)
Appliance selection
Code + DescriptionPossible causeSolutionRemark
error.
1. Check sensor position and wiring.
The temperature
E03 (blocking error)
the error persists.
2. Reset the ThermoControl if necessary. Replace the sensor if
differential between
the two temperature
at the top of
1
Error in temperature
sensor T
sensors in the tank is >
the tank.
10°C over a period of
60 seconds or longer.
if the error persists.
1. Check wiring from dummy 1 and dummy 2.
2. Reset ThermoControl if necessary. Replace the dummy sensor
10°C
The two dummy
sensors detect a
differential of >
.
(2)
E04 (blocking error)
Error in the dummy
sensor
contains 2 NTCs for the high-limit thermostat and safety thermostat protection.
1
over a period of 60
seconds or longer.
is a ‘2 in 1’ sensor, T
1
2. The dummy sensor consists of dummy sensor 1 and dummy sensor 2
3. The dummy sensor consists of dummy sensor 1 and dummy sensor 2
1. Temperature sensor T
Release R.1.3 UK82
Page 83
Introduction
gs
gs
11Maintenance
frequency
11.1 IntroductionA service should be carried out at least once a year, both on the water side and
on the gas side. Maintenance frequency depends, among other things, on the
water quality, the average burning time per day and the set water temperature.
n Remark
Regular maintenance extends the service life of the appliance.
n Remark
To determine the correct maintenance frequency, it is recommended to
arrange for the service and maintenance engineer to check the appliance on
both the water and gas side, three months after installation. Based on this
check, the best maintenance frequency can be determined.
11.2 Determining service
interval
!!!WARNING!!!
MAX. BURNINGHOURS:
SERVICE REQUIRED
Figure 11.1 Service required
To aid servicing, the ThermoControl has a service interval which defines the
frequency of maintenance by the service and maintenance engineer based on
the number of burning hours.
The service interval can be set to: 500, 1000 or 1500 burning hours. The
standard setting is 500 burning hours.
Example
In the first three months, the appliance has burnt 300 hours. During
maintenance, it is evident that one service per year will be sufficient. So after
one year, some 1200 burning hours will have elapsed. The first value below
1200 hours that can be selected is 1000 burning hours.
In this case, the service and maintenance engineer sets the interval to 1000.
Example
In the first three months, the appliance has burnt 300 hours. During
maintenance, it is evident (perhaps due to the water quality) that service will be
required at least once every 6 months. So after six months, some 600 burning
hours will have elapsed. The first value below 600 hours that can be selected is
500 burning hours.
In this case, the service and maintenance engineer sets the interval to 500.
Once the set number of burning hours has elapsed, the message
SERVICE REQUIRED will appear on the display. See Figure 11.1. Once the
message appears. contact should be made with the service and maintenance
engineer.
Release R.1.3 UK83
Page 84
11
Maintenance frequency
gs
84Instruction Manual BFC
Page 85
s
s
12Maintenance
12.1 Introduction
Introduction
cNote
Maintenance may only by carried out by an approved service and
maintenance engineer.
At each service, the appliance undergoes maintenance both on the water side
and on the gas side. The maintenance should be carried out in the following
order.
1. Preparation for maintenance;
2. Water-side maintenance;
3. Gas-side maintenance;
4. Finalising maintenance.
12.2 Preparation for
maintenance
MENU
»OFF
^ ON
È WEEK PROGRAM
Figure 12.1 Main menu
n Remark
Before ordering spare parts, take a moment to write down the appliance type
and model, and the full serial number of the appliance. Only by ordering with
this information can you be sure to receive the correct spare parts. These
details can be found on the rating plate.
To test whether all components are still working properly, you should complete
the following steps:
1. Activate the MENU with B.
2. Use H and L to position the cursor beside OFF. See Figure 12.1.
3. Confirm OFF with E.
4. Wait until the fan has stopped. The
S icon is then dimmed.
cNote
Failure to wait until the fan stops can cause damage to the appliance.
5. Turn the appliance OFF (position 0) using the ON/OFF switch on the
control panel. See Figure 12.2.
6. Turn the ThermoControl ON by putting the ON/OFF switch to position I.
I
0
Figure 12.2 ThermoControl
Release R.1.3 UK85
Page 86
12
Maintenance
s
INTERNAL CHECK
Figure 12.3 Internal check
MENU
»OFF
^ ON
È WEEK PROGRAM
Figure 12.4 Main menu
»START OPERATION
^ CHANGE SETPOINT
È
Tset=65ÉC
Figure 12.5 Starting up
The display will now show INTERNAL CHECK for about 10 seconds, and
will then go to the main menu.
7. Activate the “ON mode” by going through the following steps:
-Press once on the DOWN button (L) to position the cursor beside ON,
then press E. The display shown in Figure 12.5 appears.
-Confirm with E the option START OPERATION.
8. If there is no heat demand, increase T
water temperature’ (take note of the original setting) and draw off some
water to create a heat demand.
9. Check whether the heating cycle runs correctly. See paragraph ’7.4 The
appliance’s heating cycle’.
10. If you adjusted T
’8.4 Setting the water temperature’.
11. Remove the plastic cover on the top side of the appliance.
12. Check the supply and burner pressures and adjust these, where necessary.
See paragraph ’3.11 Checking the supply pressure and burner pressure’.
13. Check that all components of the flue gas system are properly attached.
14. Check the pressure differential across the orifice plate of the pressure
switch. See Table 12.1. If the pressure differential is too low, then the heat
exchanger should be cleaned. See paragraph ’12.5 Finalising
maintenance’.
Table 12.1 Pressure switch differential
, return the setting to the original value. See paragraph
set
. See paragraph ’8.4 Setting the
set
ApplianceObserved pressure differential across the pressure switch
(Pa)
BFC 28>
BFC 30>
BFC 50>
BFC 60>
15. Test the operation of the overflow valve of the cold supply setup. The water
should spurt out.
16. Test the overflow operation of the T&P valve. The water should spurt out.
17. Check the wastewater pipes of the overflow valves and remove any lime
buildup that may be present.
18. Drain the appliance. See paragraph ’4.3 Draining the appliance’.
635
885
885
1085
86Instruction Manual BFC
Page 87
s
12.3 Water-side maintenance
12.3.1Introduction
12.3.2Checking the anodes
12.3.3Descaling and cleaning the tank
1. Remove the cover plate 1 on the outer jacket. See Figure 12.6.
1
IMD-0080
Figure 12.6 Cleaning opening
Water-side maintenance
The following steps should be carried out on the water side:
1. Checking the anodes.
2. Descaling and cleaning the tank.
3. Cleaning condensation water discharge.
Timely replacement of the anodes extends the service life of the appliance. The
appliance’s anodes must be replaced as soon as they are 60% or more used up
(take this into consideration when determining the maintenance frequency).
1. Loosen the anodes using suitable tools.
2. Check the anodes, and if necessary, replace them.
Scale and lime buildup prevent effective conduction of the heat to the water.
Periodic descaling prevents buildup of these deposits. This increases the
service life of the appliance, and also improves the heating process. Take the
rate of scale formation into account when deciding on maintenance frequency.
2. Undo the bolts.
3. Remove the cover and the gasket.
4. Inspect the tank and remove any contamination.
(1)
5. Remove the scale using Borcoil
6. Close the cleaning opening.
Use a new rubber gasket for this.
.
12.3.4Cleaning condensation water discharge
12.4 Gas-side maintenance
12.4.1Introduction
12.4.2Cleaning the burner
It is essential to clean the condensation water discharge and siphon, to prevent
blockages.
The following steps should be carried out on the gas side:
1. Cleaning the burner.
2. Cleaning the orifice.
3. Finalising maintenance.
1. Detach the burner.
2. Remove all contamination present on the burner.
3. Fit the burner.
1. A.O. Smith recommends the use of Borcoil, as the composition of this material is known to us.
Borcoil can be ordered from A.O. Smith.
Release R.1.3 UK87
Page 88
12
Maintenance
s
12.4.3Cleaning the orifice
1. Detach the orifice.
2. Remove all contamination present in the orifice.
3. Fit the orifice.
12.4.4Cleaning heat exchanger
1. Detach the burner.
2. Clean the combustion chamber of the heat exchanger using a vacuum
cleaner and a soft brush.
3. Detach the flue gas discharge.
4. Clean the end of the heat exchanger using tap water.
5. Fit the burner.
6. Fit the flue gas discharge.
n Remark
Check the pressure differential again after cleaning. If the pressure
differential is too low following cleaning, please contact the supplier of the
appliance.
12.5 Finalising maintenance
To finalise the maintenance carry out the following steps:
1. Fill the appliance. See paragraph ’4.2 Filling the appliance’.
2. Re-start the appliance. See ’7.2 Starting up’.
3. Remove the
pressing R once, followed by E once.
SERVICE REQUIRED message. Do this by:
88Instruction Manual BFC
Page 89
General warranty
gis
gis
13Warranty (Certificate)
To register your warranty, you should complete and return the enclosed
warranty card after which a warranty certificate will be sent to you. This
certificate gives the owner of a water heater supplied by A.O. Smith Water
Products Company B.V. of Veldhoven, The Netherlands (hereinafter
“A.O. Smith”) the right to the warranty set out below, defining commitments of
A.O. Smith to the owner.
13.1 General warrantyIf within one year of the original installation date of a water heater supplied by
A.O. Smith, following verification, and at the sole option of A.O. Smith, a part or
component, (with exclusion of the tank) proves to be defective or does not
function correctly due to manufacturing and/or material defects, A.O. Smith
shall replace or repair this part or component.
13.2 Tank warrantyIf within 3 years of the original installation date of a water heater supplied by
A.O. Smith, following inspection, and at the sole option of A.O. Smith, the glasslined steel tank proves to be leaking due to rust or corrosion occurring on the
water side, A.O. Smith shall provide an entirely new water heater of equivalent
size and quality. The warranty period given on the replacement water heater
shall be equal to the remaining warranty period of the original water heater that
was supplied. Notwithstanding that stated earlier in this article, in the event that
unfiltered or softened water is used, or allowed to stand in the water heater, the
warranty shall be reduced to one year from the original installation date.
13.3 Installation and
conditions of use
The warranty set out in article 1 and 2 will apply solely under the following
conditions:
a. the water heater is installed under strict adherence to the installation
instructions of A.O. Smith applying to the specific model, and the relevant
local authority installation and building codes, rules and regulations in force;
b. the water heater remains installed at the original site of installation;
c. the appliance is exclusively used with drinking water, which at all times can
freely circulate (a separately installed heat exchanger is mandatory for
heating salt water or corrosive water);
d. the tank is safeguarded against harmful scaling and lime buildup by means
of periodic maintenance;
e. the water temperatures in the heater do not exceed the maximum setting of
the thermostats, which form a part of the water heater;
f. the water pressure and/or heat load do not exceed the maximum values
stated on the water heater rating plate;
g. the water heater is installed in a non-corrosive atmosphere or environment;
h. the water heater is connected to a cold water supply arrangement, which is:
approved by the relevant authority; with sufficient capacity for this purpose;
supplying a pressure no greater than the working pressure stated on the
water heater; and where applicable, fitted with a temperature and pressure
relief valve compliant with the installation instructions of A.O. Smith
pertaining to the specific model of water heater, and under adherence to the
relevant local authority installation and building codes, rules and regulations
in force;
i. the anodes are replaced and renewed no later than when 60% used up.
13.4 ExclusionsThe warranty set out in article 1 and 2 will not apply, in the event of:
a. damage to the water heater caused by an external factor;
Release R.1.3 UK89
Page 90
13
Warranty (Certificate)
gis
b. misuse, neglect (including frost damage), modification, incorrect and/or
unauthorised use of the water heater and any attempt to repair leaks;
c. contaminants or other substances having been allowed to enter the tank;
d. the conductivity of the water being less than 125 µS/cm and/or the hardness
(alkaline-earth ions) of the water being less than 1.00 mmol/lit
(seeTa bl e 3 .3 );
e. unfiltered, recirculated water flowing through or being stored in the water
heater;
f. any attempts at repair to a defective water heater other than by an approved
service engineer.
13.5 Scope of the
warranty
13.6 ClaimsA claim on grounds of the specified warranty must be submitted to the dealer
13.7 Limitation of liability
A.O. Smith
The obligations of A.O. Smith pursuant to the specified warranty do not extend
beyond free delivery from the Veldhoven warehouse of the replacement parts or
components or water heater. Shipping, labour, installation and any other costs
associated with the replacement will not be accepted by A.O. Smith.
from whom the water heater was purchased, or to another authorised dealer for
the products of A.O. Smith Water Products Company. Inspection of the water
heater as referred to in articles 1 and 2 shall take place in one of the laboratories
of A.O. Smith.
A.O. Smith grants no other warranty or guarantee over its water heaters nor the
(parts or components of) water heaters supplied for replacement, other than the
warranty expressly set out in this Certificate.
A.O. Smith is not liable for damage to persons or property caused by (parts or
components, or the glass-lined steel tank of) a (replacement) water heater that
it has supplied under the terms of this warranty, nor on any other grounds.
90Instruction Manual BFC
Page 91
is
AAppendices
A.1IntroductionThis appendix contains:
•The Electrical diagram BFC.
•A Week program card.
Release R.1.3 UK91
Page 92
A
A.2Electrical diagram
BFC
Appendices
is
= brown
= brown
%
%
= blue
&
= yellow/green
'
= black
(
= white (flat ca-
#
= grey/beige
$
TERMINAL STRIP CONNECTIONS:
A Earth
N Neutral
L1Phase input of controller
L2Phase input of isolating transformer (primary side)
L3Phase output of isolating transformer (secondary side)
L4Phase input of program-controlled pump
L5Phase input of continuous pump
COMPONENTS:
A Controller
B Ionisation rod
C Glow igniter
D Gas control
E Burner earth connection
FExtra ON mode switch
G Continuous pump
H Program-controlled pump
JExtra error signal
K Isolating transformer
LDouble-pole mains switch
M ON/OFF switch control
N Display/Flat cable
OFan
P Temperature sensor (T2 - bottom of tank)
Q Dummy
R Temperature sensor (T1 - top of tank)
S Selection resistor
TPressure switch
CONTROLLER CONNECTIONS:
J1 Connector for display to controller
J2 Connector for power supply to controller
J19 Connector for extra error signal
J20 Connector for gas control
J21 Connector for program-controlled pump
J24 Connector for fan
JP2 Connector for ionisation rod and glow igniter
JP3 Connector for temperature sensor T2
JP4 Connector for dummy
JP5 Connector for temperature sensor T1
JP6 Connector for selection resistor and pressure switch
JP8 Connector for extra ON mode switch
F1 Fuse
F2 Fuse
Figure A.1 Electrical diagram BFC
92Instruction Manual BFC
Page 93
ON
.... °CON / OFF
.... °CON / OFF
.... °CON / OFF
.... °CON / OFF
.... °CON / OFF
.... °CON / OFF
.... °CON / OFF
.... °CON / OFF
.... °CON / OFF
.... °CON / OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
A.3Week program card
.... °CON / OFF12.
.... °CON / OFF13.
.... °CON / OFF14.
.... °CON / OFF15.
.... °CON / OFF16.
.... °CON / OFF17.
.... °CON / OFF18.
.... °CON / OFF19.
.... °CON / OFF20.
.... °CON / OFF21.
.... °CON / OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFFOFF
OFFOFF
OFFOFF
OFFOFF
OFFOFF
OFFOFF
OFFOFF
OFFOFF
OFFOFF
PeriodDAYTIMETs etPumpPeriodDAYTIMETs etPump
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
You can fill-in the week program card, cut it out and keep it near the appliance.