Description – Taurus 25W 4000K LED IP65 Bollard
Installation Instructions
General Installation Instructions
These instructions should be read carefully prior to any installation and retained after completion for further reference and
maintenance. Please give these instructions to the building owner/occupier after installation.
Important Safety
1. Before installation, maintenance or lamp replacement, ensure that the mains supply to the luminaire is switched
off and the circuit supply fuses are removed or the circuit breaker is turned off.
2. It is recommended that only a qualified electrical contractor carries out the installation of this luminaire and that
the luminaire is installed in compliance with the current edition of the IEE Wiring Regulations.
3. The person carrying out the installation is to check and verify that the total load on the circuit, including that of this
luminaire does not exceed the rating of the circuit cable, fuse or circuit breaker.
4. Where a luminaire incorporates discharge control gear (inductive load), the circuit capacity and ratings require
careful sizing to avoid nuisance tripping of the protective device used in the installation.
5. Where applicable, careful consideration should be taken during installation to ensure that all fixings and/or
Ratings
1. All luminaires are manufactured & tested in compliance with the requirement contained within BS EN 60598 and are CE marked.
2. All luminaires that are of Class 1 construction and that are marked accordingly, MUST be earthed.
3. All luminaires are designed to operate at 230Volts AC -6%/+10% = 216Volts to 252Volts. Do not operate outside these voltages.
4. All luminaires are only suitable for applications within their rated Ingress Protection limits as stated.
Exclusions to Warranty
Please Note - The limited warranty shall be null and void in the following circumstances:-
Failure by the installer, end user or any third party to exercise caution to protect any covered product or part from outside damage, adverse temperature (normal operating
ambient temperature 0 - 25°C), humidity conditions, fluctuations in the electrical system or physical abuse as well as failure related to workmanship in the installation of
the products or parts.
suspensions are of a suitable size for the luminaire being installed.
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Installation
Disconnect power supply
Select a suitable position to mount the bollard. Avoid locations where the bollard would cause a hazard to pedestrians or motorists. If
located in car park areas, site the bollard a minimum of 450mm back from edge of parking surface to avoid damage from vehicles.
Install the supplied root mounting kit into wet concrete c/w incoming supply cable.
Once the concrete is set, remove the three allen head-securing screws from the bottom and remove the base mounting plate.
Install the base mounting plate onto the 3 bolts and fix into position.
Packing washers may be required to level the base (not supplied).
Alternatively you can use another fixing method such as rawl bolts to a suitable surface.
Place the column onto the base and refit the three allen screws into the base mounting plate.
Remove a further three allen head securing screws from the top of the bollard, and remove the head assembly and gear box.
Release the lid of the gear box and feed in the incoming supply.
Sufficient cable is to be left during installation to allow the luminaire head to be removed for any future maintenance that may be required.
It is the installer’s responsibility to provide adequate electrical connections to maintain the correct IP rating for the installed environment. This
is in accordance to BS EN 7671.
Connect the incoming mains cable to the luminaire.
Connect as follows: LIVE (L) BROWN OR RED
EARTH GREEN / YELLOW
Slide the head assembly into the stem of the bollard and secure. Secure using the three allen head screws.
Restore power supply, switch on and test for satisfactory operation.
NEUTRAL (N) BLUE OR BLACK
Luminaire Code(s) – ATALEDB/1000
IP65
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------Maintenance:
1. This luminaire contains no serviceable parts.
2. If replacing the LED Driver, please ensure the driver is the correct size for the application and the secondary output is 36V constant voltage with a
minimum power rating of 25W per LED.
Blue / Black
Brown / Red
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
www.anselluk.com Issue Date: 20150529
Disposal of Electronic Equipment WEEE Directive 2002/96/EC
This product falls within the scope of the Waste Electrical & Electronic Equipment Directive
(WEEE), which means the product should not be disposed of as normal household waste.
Ensure that this luminaire and lamp is disposed of in accordance with the WEEE Directive.
Contact a local Council Waste Dept. Local Amenity Site, or the DTI for further information.
RoHS - All components and materials used in this product are RoHS 2002/95/EC compliant.