Description – Eclipse MultiLED
Installation Instructions
Luminaire Code(s) – AECLED
General Installation Instructions
These instructions should be read carefully prior to any installation and retained after completion for further
reference and maintenance. Please give these instructions to the building owner/occupier after installation.
Important Safety
1. Before installation, maintenance or lamp replacement, ensure that the mains supply to the luminaire is switched off and
the circuit supply fuses are removed or the circuit breaker is turned off.
2. It is recommended that only a qualified electrical contractor carries out the installation of this luminaire and that the
luminaire is installed in compliance with the current edition of the IEE Wiring Regulations.
3. The person carrying out the installation is to check and verify that the total load on the circuit, including that of this
luminaire does not exceed the rating of the circuit cable, fuse or circuit breaker.
4. Where a luminaire incorporates discharge control gear (inductive load), the circuit capacity and ratings require careful
sizing to avoid nuisance tripping of the protective device used in the installation.
5. Where applicable, careful consideration should be taken during installation to ensure that all fixings and/or suspensions
are of a suitable size for the luminaire being installed.
Ratings
1. All luminaires are manufactured & tested in compliance with the requirement contained within BS EN 60598 and are CE marked.
2. All luminaires that are of Class 1 construction and that are marked accordingly, MUST be earthed.
3. All luminaires are designed to operate at 230Volts AC -6%/+10% = 216Volts to 252Volts. Do not operate outside these voltages.
4. All luminaires are only suitable for applications within their rated Ingress Protection limits as stated.
5. Max ambient temperature 25oC
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Installation
Remove the front diffuser from the base of the luminaire.
Select a suitable cable entry point.
Position and fix the base to a suitable solid surface.
Select the power setting you require by adjusting the dip switches on the LED Driver.
Terminate the supply cable into the terminal block mounted in the base, ensuring correct polarity is observed and the luminaire is earthed.
Electrical Connections
IP20
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------ Maintenance:
1. This Luminaire contains no serviceable parts
2. If replacing the LED Driver, please ensure the driver is the correct physical size for the housing and the secondary output / wattage is correct
matching that of the existing LED Driver
Blue / Black
Brown / Red
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------ Ansell Lighting Products, Unit 6B, Stonecross Ind. Park, Yew Tree Way, Warrington, WA3 3JD www.anselluk.com
Connect as follows:-
LIVE (L) BROWN OR RED (switched)
NEUTRAL (N) BLUE OR BLACK
EARTH GREEN / YELLOW
Re-fit the diffuser.