Description – Delta 14W LED IP65 Bulkhead
® Installation Instructions
General Installation Instructions
These instructions should be read carefully prior to any installation and retained after completion for further
reference and maintenance. Please give these instructions to the building owner/occupier after installation.
Important Safety
1. Before installation, maintenance or lamp replacement, ensure that the mains supply to the luminaire is switched
off and the circuit supply fuses are removed or the circuit breaker is turned off.
2. It is recommended that only a qualified electrical contractor carries out the installation of this luminaire and that
the luminaire is installed in compliance with the current edition of the IEE Wiring Regulations.
3. The person carrying out the installation is to check and verify that the total load on the circuit, including that of this
luminaire does not exceed the rating of the circuit cable, fuse or circuit breaker.
4. Where a luminaire incorporates discharge control gear (inductive load), the circuit capacity and ratings require
careful sizing to avoid nuisance tripping of the protective device used in the installation.
5. Where applicable, careful consideration should be taken during installation to ensure that all fixings and/or
Ratings
1. All luminaires are manufactured & tested in compliance with the requirement contained within BS EN 60598 and are CE marked.
2. All luminaires that are of Class 1 construction and that are marked accordingly, MUST be earthed.
3. All luminaires are designed to operate at 230Volts AC -6%/+10% = 216Volts to 252Volts. Do not operate outside these voltages.
4. All luminaires are only suitable for applications within their rated Ingress Protection limits as stated.
Exclusions to Warranty
Please Note - The limited warranty shall be null and void in the following circumstances:-
Failure by the installer, end user or any third party to exercise caution to protect any covered product or part from outside damage,
adverse temperature (normal operating ambient temperature -10 - 40°C), humidity conditions, fluctuations in the electrical system or
physical abuse as well as failure related to workmanship in the installation of the products or parts.
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Installation
suspensions are of a suitable size for the luminaire being installed.
Remove the diffuser from the base by releasing the four captive retaining screws. Unscrew the two retaining screws and
hinge the gear tray.
Select a suitable cable entry point, and carefully remove the appropriate knock-out(s) (20mm North, South, East and West
conduit entry points and Beza mountings at centre of the base).
Position and fix the base to a suitable solid surface using screws supplied, sealant should be applied around the screw
heads to reduce water ingress if the luminaire is to be mounted externally (Luminaires should not be installed where the
illuminated surface is within 0.5m from th e front of the fitting). NOTE: If mounting on a BESA conduit box, a suitable
gasket (rubber) should be used.
Secure supply cable into the luminaire through previously selected entry ensuring that a cable gland, grommet or sealing
compound is used to maintain the IP rating of the luminaire.
Terminate the cable into the terminals ensuring correct polarity is observed.
Re-attach the gear tray back into position.
Re-fit the diffuser, taking care to ensure it is properly seated on the gasket seal. Do not over-tighten the screws. An
effective weatherproof seal can be provided with moderate tightening of screws. Fix front bezel.
Restore power supply, switch on and test for satisfactory operation.
Luminaire Code(s) – ADLED2/
IP65
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------Maintenance:
If replacing the LED Driver, please ensure the driver matches the specification of the model installed.
1.
Blue / Black
Brown / Red
Disposal of Electronic Equipment WEEE Directive 2002/96/EC
This product falls within the scope of the Waste Electrical & Electronic Equipment Directive
(WEEE), which means the product should not be disposed of as normal household waste.
Ensure that this luminaire and lamp is disposed of in accordance with the WEEE Directive.
Contact a local Council Waste Dept. Local Amenity Site, or the Environment Agency for
further information. RoHS - All components and materials used in this product are RoHS
2002/95/EC com
liant.
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------Ansell Lighting Products, Unit 6B, Stonecross Ind. Park, Yew Tree Way, Warrington, WA3 3JD
www.anselluk.com