ALCAutomatic Level Control
DLDownlink
EEPROMElectrical erasable programming read only memory
I²C-BusInter Integrated Circuit Bus
LMTLocal Maintenance Terminal
MRMikom Repeater
OMCOperation and Maintenance Center
RFRadio Frequency
RSSIReceive Signal Strength Indication
ULUplink
UPSUninterruptable Power Supply
VSWRVoltage Standing Wave Ratio
M0062A0B.docId.-No. 148964Page 411.12.98
REP1009V1.xx
1 Introduction
This manual describes the functions of the standard software REP1009V1.xx implemented in
band/channel selective Repeaters of the second generation. These Repeaters can be set locally
or remotely. A PCMCIA slot for modem operation is available. The design of the Repeater
comprises a large number of functions which the operator may monitor via terminal emulation
program or the MIKOM OMC software platform. An easy to understand and easy to learn
communication language supports the operator to query status reports from the Repeater or to
change settings.
Your Repeater is equipped with the required software which enables the operator to
communicate with the microprocessor of the control module.
The communication with the microprocessor of the control module is realized with a VT100
compatible dialogue.
The software is accessible in two different ways.
n Locally
n Remotely
Both possibilities are described below.
• The communication can be done locally by connecting a Laptop or a PC with VT100
emulation or a VT100 terminal via the control cable.
Required equipment:- Laptop or PC with terminal program, e.g. PROCOMM
- one serial RS232 cable: SUB-D9 (female) to SUB-D9 (female)
Laptop or PC
with terminal program
figure 1-1 Repeater locally controlled
M0062A0B.docId.-No. 148964Page 511.12.98
REP1009V1.xx
• Furthermore the communication can be realized remotely via modem.
figure 1-2 Repeater remotely controlled
2 Installation
The actual software version is part of the delivery schedule of your Repeater unit and will be
installed in factory.
M0062A0B.docId.-No. 148964Page 611.12.98
REP1009V1.xx
OFF
ON
3 Software download
It might be necessary to download another software version. This can be realized in two
different ways.
n Software download in local mode
n Software download in remote mode
3.1 Download procedure in local mode
Two different download procedures exist in local mode. The software download software or
manually controlled. After a software download previous user settings ( data default values )
might be overwritten. Before you start a software download save the set values for:
n attenuation
n ALC threshold
3.1.1 Download procedure in local mode, software controlled:
Required equipment:- PC with terminal program, e.g. PROCOMM
- one serial RS232 cable: SUB-D9 (female) to SUB-D9 (female)
1. Check the position of DIP-Switch 4 ( position OFF ) on the control module.
DIP-Switch 4
figure 3-1 Position of DIP-Switch 4
1. Switch on Repeater and PC and connect control cable. Wait until the boot process is
finished.
2. Start Repeater software and login by typing ‘User-ID1’ and ‘P-word1’.
3. Type software command:
Syntax:DNLOAD ↵
4. Exit terminal program immediately.
M0062A0B.docId.-No. 148964Page 711.12.98
REP1009V1.xx
OFF
ON
5. To start upload procedure type:
Syntax:upload 1 ↵ or
upload 2 ↵
depending on which serial interface is available ( COM 1 or COM 2 ).
6. The copy procedure is running. You will be asked to continue by pressing any key. Now the
software download is in progress. The download lasts approximately 1 minute.
3.1.2 Download procedure in local mode, manually controlled:
Required equipment:- PC or Laptop
- one serial RS232 cable: SUB-D9 (female) to SUB-D9 (female)
1. Set the DIP-Switch 4 to position ON on the control module.
DIP-Switch 4
figure 3-2 Position of DIP-Switch 4
1. To start upload procedure type:
Syntax:upload 1 ↵ or
upload 2 ↵
depending on which serial interface is available ( COM 1 or COM 2 ).
M0062A0B.docId.-No. 148964Page 811.12.98
REP1009V1.xx
2. The copy procedure is running. You will be asked to continue by pressing any key. Now the
software download is in progress. The download lasts approximately 5 minutes in local
mode.
3. Software boot starts automatically.
4. Don’t forget to switch back the DIP-Switch 4 to position OFF.
M0062A0B.docId.-No. 148964Page 911.12.98
REP1009V1.xx
ON
4 Running the software
4.1 Via PC or Laptop as terminal
The local mode for settings via PC has to be set. Therefore the DIP-Switch 2 has to be at
position OFF.
OFF
figure 4-1 DIP-Switch 2 for local mode
F Note:Only if a Modem M1 is used DIP-Switch 2 has to be set.
A VT100 terminal or a PC with VT100 emulation can be connected to the control module
SM2009 by a standard RS232 cable, if necessary in connection with an adapter 9 to 25.
PC or Laptop - Control Module SM2009
9 contact SUB - D- Connector9 contact SUB - D- Connector
The following communication mode between control module and VT100 is set initially.
M0062A0B.docId.-No. 148964Page 1011.12.98
REP1009V1.xx
.
9600 baud - 8 bit - no parity -1 stopbit
These settings can only be changed after connection of the terminal. If all wanted settings have
been initialized and a modem has to be used it will be recommended to check whether the
settings comply with the capabilities of the modem and the line. Modifications are possible by
software commands.
FNote:Settings on the Repeater can be performed after the following procedure
only.
After connecting the PC to the Repeater, following procedure is necessary to get access to the
program.
1. Step: Type the two keys ( . ) FULLSTOP and (↵) ENTER
You have to type the keys:
↵↵
2. Step: ENTER USER ID
You have to enter:UserID1 ↵
FNote:The input is case sensitive, no blanks. After three mistrial follows
disconnection.
3. Step: ENTER PASSWORD
You have to enter:P-word1 ↵
FNote:The input is case sensitive, no blanks. After three mistrials follows
disconnection.
M0062A0B.docId.-No. 148964Page 1111.12.98
REP1009V1.xx
4.2 Via modem
The Repeater will be delivered with a preset init string. This init string was used for internal
tests. In case no connection can be established check the local conditions and change the init
string if necessary.
Three different modem types are available
• PSTN modem ( DigiTel 34P ), line modem
• Siemens M1 for GSM900, wireless modem
• Motorola for GSM900 or GSM1800, wireless modem
The following list contains the description of the AT commands:
&FSets modem to factory configuration
E0Echo OFF
S0=1Auto answer ON; the GSM module / M1 modem goes off-
S7=60Waiting time for connection after dialing; permissible values
B13Setting to 9600 bps asynchronous mode
\ N6Auto reliable operation
\ N0Standard operation, no error correction
+CBST=7,0,1Set bearer service type to 9600 bps. Non-transparent
X3Not waiting for dial tone; usually used at PABX.
*P1Switch ON phone
&K4Enables XON / XOFF flow control
4.2.1 PSTN modem
hook after the first ringing signal.
are from 0 ... 60.
connection ( uses RLP )
Table 4.2-1 List of AT commands
A Hayes compatible PSTN modem can be connected to the control module SM 2009 by the
control cable, which is subject of the delivery schedule.
The init string for the PSTN modem is:
AT&F X3 E0 S0=2
M0062A0B.docId.-No. 148964Page 1211.12.98
REP1009V1.xx
control module SM2009 - cable connection modem
PCMCIA
figure 4-3 Connection of control module and PSTN modem
The following communication mode between control module and VT100 is initially set for the
use of a Hayes-compatible modem.
9600 baud - 8 bit - no parity -1 stopbit
These settings can only be changed after connection of the terminal. If a different modem has
to be used or if the quality of the line does not allow to use the set parameters, the settings
have to be changed in PC mode. This is the same for all other parameters, which can be set
previously for modem mode by software.
FNote:Settings on the Repeater can be performed after the following procedure
only.
After connection to the Repeater following response appears on screen:
1. Step: ENTER USER ID
Response on the screen:ENTER USER ID:------
You have to enter:UserID1 ↵
FNote:The input is case sensitive, no blanks. After three mistrial follows
disconnection.
2. Step: ENTER PASSWORD
Response on the screen:ENTER PASSWORD:--------
You have to enter:P-word1 ↵
FNote:The input is case sensitive, no blanks. After three mistrials follows
disconnection.
M0062A0B.docId.-No. 148964Page 1311.12.98
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.