TECHNICAL DATA SECTION 2
5
Storage Capacity l 145 295* 368* 282* 245* 245
gal 32 65 81 62 54 54
Recovery thro' 44ºC/80ºF l/h 649 786 1199 1549 1900 1998
gal/h 143 173 264 341 418 440
Recovery thro' 56ºC/100ºF l/h 517 629* 959 1239* 1520* 1598*
gal/h 114 138 212 273 334 352
Recovery thro' 72ºC/130ºF l/h 399 484* 730 953* 1169* 1223*
gal/h 88 106 162 210 257 270
Heat Input Gross kW 42.8 50 80 102 128 139
Btu/h
146,034 170,600 272,960 384,024 436,736 474,268
Heat Input Net kW 39 45 73 93 116 126
Btu/h
133,068 153,540 249,076 317,316 395,792 430,000
Gas NATURAL CAT I2H
Burner Gas Pressure mbar 6.8 6.8 6.8 6.8 6.8 N/A
Pernament Pilot ins wg. 2.73 2.73 2.73 2.73 2.73 N/A
Burner Gas Pressure mbar 10 10 10 10 10
Auto Ignition ins wg. 4 4 4 4 4
Max. Gas Input Pressure mbar 35 35 35 35 35
ins wg. 14 14 14 14 14
Gas Flow Rate m3/h 4.0 4.68 7.44 9.48 11.94 13.14
ft
3
/h 141 164.76 263.58 336.24 421.98 465.06
Gas Connection Rc (in BSP Int) 3/4 3/4 3/4 3/4 3/4 3/4
Flue Gas Temp. ºC 117 140 150 195 185 215
Flue Gas Volume m
3
/h 62 73 116 149 186 202
Gas Injector Orifice Diameter mm 2.69 2.87 3.66 3.45 3.50 N/A
Permanent Pilot in 0.106 0.113 0.144 0.136 0.138 N/A
Gas Injector Orifice Diameter mm 2.40 2.58 3.25 3.18 N/A 3.26
Auto Ignition in 0.094 0.101 0.127 0.125 N/A 0.128
Flue Size (Secondary) mm 150 150 200 200 250 250
in 6 6 8 8 10 10
Cold Water Feed Connection R
(in BSP/Exl) 11/2 11/2 11/2 11/2 11/2 11/2
Hot Water Flow Connection R
(in BSP/Exl) 11/2 11/2 11/2 11/2 11/2 11/2
*Return Connection Rp
(in BSP/Int) 3/4 3/4 3/4 3/4 3/4 3/4
Drain Port Size R (in BSP/Ext) 3/4 3/4 3/4 3/4 3/4 3/4
Max. Working Pressure bar 10.3 10.3 10.3 10.3 10.3 10.3
lbf/in
2
150 150 150 150 150 150
Max. Test Pressure bar 20.6 20.6 20.6 20.6 20.6 20.6
lbf/in
2
300 300 300 300 300 300
Weight Empty kg 190 200 289 257 269 269
lb 419 441 637 566 594 594
Weight Full kg 335 495 656 538 514 514
lb 738 1091 1447 1186 1134 1134
Shipping Weight kg 199 223 316 282 293 293
lb 438 492 697 623 645 645
Shipping Dimensions Depth mm 902 914 914 914 914 914
in 35 1/2 36 36 36 36 36
Shipping Dimensions Width mm 768 762 762 762 762 762
in 30 1/4 30 30 30 30 30
Shipping Dimensions Height mm 1270 1960 2083 1960 1960 1960
in 50 77 82 77 77 77
ANDREWS MODEL NO. 32/143 65/173 81/264 62/341 54/418 54/440
Hi-Flo
RANGE
* If the water heater is to be
used on an unvented system,
the combined temperature/
pressure relief valve must be
fitted directly into the tank.
The secondary return is then
connected to the drain port
via a suitable tee.