Section 1 - Field Wireable Connector
Technical Bulletin
HH Pressure Transmitter
Quick Start Installation Guide
1. Insert cable through Pressing Screw, Compression Ring, Seal Grommet, and Sleeve as shown below.
2. Strip back 1-1/4” of outer sheathing, cut off any excess wires, shield and ground. Strip off 1/4” insulation from remaining two wires. It is not necessary or recommended
Shown With
Cap Removed
TP-
TP+
ZERO
SPAN
CABLE REQUIREMENTS
2 conductor, stranded, 18-24 AWG,
shielded with ground.
To install connector, simply line up key, press
into receptacle, and hand-tighten the
*Receptacle pins should be coated with USDA approved dielectric grease to Minimize possibility of corrosion.
TP-
TP+
Retaining Ring
Pin 2 - Black
(-PWR)
ZERO
SPAN
3. Orient Connector end so that center pin connecting screw is horizontal facing right (see detail).
Sleeve
Connector End
Pin 1 - Red
(+PWR 9-30 VDC)
DETAIL
*Dielectric Grease
P/N: 5662400000
4. Wire LOOP+ (red) wire to top-right terminal, and LOOP- (black) wire to top-left terminal. No connection is made to the center and bottom terminals.
5. Screw on the Sleeve. Hand-tighten only.
Compression
Ring
Seal
Grommet
-2 included choose one to accommodate cable OD
Pressing Screw
6. Press the Seal Grommet into the Sleeve and hand-tighten the Pressing Screw against the compression ring.
7. Use a wrench to tighten the Pressing Screw another 3/4 turn. Do not over-tighten!
Molded Cord Set
Loop+ (red) wire
Loop- (black) wire
P/N: 42117K0025 42117K0050 42117K0100
Shield (bare) wire
Note: Green and White not used
Field Wireable Connector
P/N: 42119B0000 (without cable)
Loop+ (red) wire
Loop- (black) wire
Shield (clear or bare) wire
Available upgrade kit # 56642A0001 includes: (1) 42119B0000 Connector (1) 56623A0002 Receptacle (1) 5662400000 Dielectric grease
Section 2 - Specifications
Excitation: 10-40 VDC (Absolute), 24 VDC Nominal regulated or
unregulated
Output: 4-20 mA DC, 2 wire with non-interrupting circuit verification test points Loop Resistance: 0-700 ohms at 24 VDC Wiring Connection: 5 pin M12 Quick Disconnect Receptacle Recommended Cable: 18-24 AWG, foil shielded, and PVC coated. (4-8mm
(0.16-0.31”) cable sheath OD)
Accuracy: ± 0.5% of full scale Repeatability: ± 0.3% of full scale Hysteresis: ± 0.10% of full scale Linearity: ±0.10% of full scale Stability: ±0.30% of calibrated range/6 months Storage Temperature: -40°C to 65°C (-40°F to 149°F) Process Temperature Limits: -1°C to 149°C (30°F to 300°F) (Horizontal mount recommended over 135°C (275°F)) Ambient Temperature Limits: -18°C to 49°C (0°F to 120°F) Effect of Temperature Change: ± 0.1 psig/5.5°C (10°F) typical Over-Range Rating: Minimum of 2 times base range
Response Time: 200 uSec Wetted Parts: 316L stainless steel (Ra max. = 25 microinches, 0.6 microns) Housing Material: 304 stainless steel Span Adjustment: ± 50% of range, except 15 psi ±10% Zero Adjustment: 10% Mounting: Direct connection Standards: Designed and manufactured to sound engineering practices in accordance with Article 3.3 of the PED 97/23/EC
NEMA 4X IP66/67
CSA B51-03 3-A CE (pending) Warranty: 1 year
Rev. 1.1 Doc 1164 Page 1
Page 2
Anderson electronic sensors require very little maintenance. We suggest that the sensor be inspected at 6 month intervals to ensure that it is not being
Sensor Range
Sensor Reads at Atmospheric Zero
Sensor Range
Sensor Reads at Atmospheric Zero
0-psig - Positive Pressure 4.00 mA 0-Bar - Positive Pressure4.00 mA 30" Hg - 15 psig 11.92 mA -1 Bar - 1 Bar 12 mA 30" Hg - 35 psig 8.72 mA -1 Bar - 2.5 Bar 8.57 mA 30" Hg - 85 psig 6.36 mA -1 Bar - 6 Bar 6.29 mA 30" Hg - 185 psig 5.18 mA -1 Bar - 13 Bar 5.14 mA
Section 3 - Installation / Calibration Verification
physically abused, moisture is not entering the housing, and that the wiring is sound.
If you feel that the output of the HH transmitter is not correct, calibration of the unit may be required.
Equipment required: Pressure source Accurate reference gauge DC Milliamp Meter (accurate to .01 mA) Small straight blade screwdriver Calculator
Calibration - Transmitter Adjustments to the transmitter are made via the "ZERO" and "SPAN" potentiometers. These two adjustments are non-interactive, meaning changing the zero will not change the span. As general maintenance to the unit, a zero check is recommended at approximately 6 month intervals. If your unit is calibrated at a compound range, you will not see 4.00 mA at atmospheric zero. As reference, you may use the following chart to determine if your unit may require calibration (most common ranges are shown).
The output of a properly calibrated transmitter may be calculated by using the following formula:
NOTE: For pressure transmitters with compound ranges, the ranges must first be converted to all one type unit of measure. For example, a 30" Hg/0/35 psig unit may be considered to have a range of -14.7 psig-0-35 psig and a span of 49.7 psig (2.036" Hg = 1 psi). Be careful not to lose the (-) sign while performing the calculation of the proper reading.
mA Output [ 16x [ ]]+4
NOTE: The transmitter should be wired in a complete loop at this point, or on a test bench. Although no interaction between zero and span occurs, when making adjustments you should be as close to the top and bottom transmitter range as possible. This will ensure the best possible linearity in the final signal output.
1. Expose the transmitter to a known zero reference point. If transmitter range starts at atmospheric zero, zero adjust at atmospheric zero. If transmitter is a compound range, you should be as close to sensor zero as possible . You must calculate the expected mA signal (use formula above).
2. Remove cap from transmitter.
3. With your meter set to DC mA, connect the RED (Meter +) lead to the (TP +) terminal. Connect the BLACK (Meter - ) lead to the (TP -) terminal.
4. Adjust the transmitter ZERO potentiometer as shown, until you either see 4.00 mA if you are at atmospheric zero, or your expected mA signal for a compound range.
5. Expose the transmitter to a know pressure at the top end of the range. Standard ranges may be turned down to a maximum of 50%.
6. Adjust the transmitter SPAN potentiometer, until you see 20 mA output.
Span Adjustment Screw
(Known Value - Low End of Range)
Transmitter Span
SPAN
TP+
2.42
2.31
Rev. 1.1 Doc 1164 Page 2
Zero Adjustment Screw
ZERO
TP-
2.87
1-1/2” TRI-CLAMP